Equalized charging applies a controlled overcharge to break up lead sulfate crystals and rebalance cell voltages across a long battery string. KITOZER recommends an equalize cycle once every 6 months for strings older than 2 years, or whenever cell spread exceeds 0.1V. Set the charger to 2.30V to 2.35V per cell for 12 to 24 hours while monitoring each cell voltage. Stop the equalize early if any cell exceeds 2.40V or vents gas heavily. VRLA batteries tolerate equalize only within manufacturer limits; sealed AGM units usually require no equalize at all, and forcing one can dry out the electrolyte permanently. Confirm the battery type before starting.

Table of Contents

Procedure

2.30 to 2.35V per cell, 12 to 24 hours, monitor cells. KITOZER battery service from $220.

Price

From $220. Contact +86 13922289957 for equalize service.

Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com