KITOZER Battery FAQ: Replacement Criteria

Replace the entire battery string when any of the following occurs: measured capacity falls below 80 percent of rated Ah after a full discharge test; internal resistance rises more than 20 percent above the factory baseline; any case shows swelling, leakage, or cracked valve; or float voltage spread across cells exceeds 0.2V after a successful equalize. KITOZER never recommends replacing only the weakest cell in an aged string, because new cells in series with old cells carry disproportionate charge and fail within months. Always source batteries of the same manufacturer, model, Ah rating, and production batch when replacing. Label the new install date on every battery and reset the IR baseline so future trending is accurate.

Table of Contents

Triggers

Below 80 percent capacity, 20 percent IR rise, swollen case, 0.2V spread. KITOZER packs from $55/pc.

Price

From $55/pc. Contact +86 13922289957 for replacement battery.

Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com