KITOZER Cabinet Guide: Grounding and Cable Management

Every cabinet must have a dedicated grounding conductor bonded to the data center grounding busbar. KITOZER recommends a 16 mm2 green-yellow copper braid from the cabinet grounding stud to the nearest grounding bar, with torque to the lug spec. Use separate cables for power and data: route AC power on the left vertical manager, data cables on the right vertical manager, with a minimum 150 mm separation to prevent EMI. Horizontal cable arms should support the bundle weight so patch cords do not strain the RJ45 jacks. Label both ends of every cable at install time, because tracing an unlabeled bundle after the fact is a major labor cost. Blank off unused rack units with brush panels to preserve hot and cold aisle separation.

Table of Contents

Method

16 mm2 braid, power left data right, 150 mm separation, label both ends, blank panels. KITOZER cable manager from $85.