ToggleKITOZER Cold Aisle Containment End Door — Sliding Glass Aisle Door, Self-Closing Containment Door and Data Center Airflow Management Technical Encyclopedia

In data center cooling systems, aisle containment has become the mainstream technology for improving cooling efficiency and lowering PUE (Power Usage Effectiveness). Cold aisle containment seals the cold aisle between cabinet rows by installing containment roof panels on top and end doors at both ends, fully enclosing the cold air space from which server fronts draw air. This forces the chilled air supplied by precision air conditioners to be used entirely for server intake, preventing mixing and short-circuiting with the hot air exhausted from the rear of the cabinets. The cold aisle containment end door is the critical component that seals the two open ends of the cold aisle. It must allow personnel to pass through and equipment to be moved in and out, yet automatically close and seal tightly once personnel leave, so that cold air does not leak out from the ends.
The KITOZER cold aisle containment end door is developed by Guangzhou Laian Intelligent System Development Co., Ltd. The KZ-CAD series covers single sliding doors, double sliding doors, glass self-closing doors and fire-rated end doors. The door frames are made of aluminum alloy profile or powder-coated cold-rolled steel, the door leaves use tempered safety glass or color steel panels, and the system is equipped with automatic door closers, door contact switches, sealing gaskets and linkage with fire pressure-relief smoke vents. This encyclopedia systematically explains the structural principles, airtight design, sizing calculations, installation procedures, fire linkage and maintenance of cold aisle end doors from an engineering perspective.
Price note: All prices listed for KITOZER cold aisle end doors and matching roof panels and side panels are reference prices for project budgeting only; the actual price is subject to the formal quotation after engineering design confirmation. A single end door is roughly in the reference range of USD 350 to USD 1680 (about RMB 2500 to RMB 12000), depending on size, glass specification, closing method and fire rating.
Chapter 1. Evolution of Cold Aisle Containment and End Doors
1.1 Open cabinet layout era (before 2000)
In early data centers, cabinets were arranged in open rows, and cold air from precision air conditioners diffused freely throughout the room. Servers drew cold air from the room and exhausted hot air back into the room. This layout suffered from severe hot-cold air mixing: before reaching the server intake, cold air had often already mixed with hot exhaust and risen in temperature, while some cold air short-circuited directly back to the air conditioner return without passing through the servers. To keep server intake within the ASHRAE recommended range, engineers had to increase cooling airflow and lower supply temperatures, which caused chiller efficiency to drop and PUE to hover above 2.0.
1.2 Hot/cold aisle separation era (2000-2010)
Around 2000, the industry adopted hot and cold aisle separation: cabinets were arranged face-to-face to form cold aisles and back-to-back to form hot aisles, physically separating cold and hot air. This significantly improved airflow organization, but because the tops and ends of the cold aisles remained open, hot and cold air still mixed and leaked at the top and ends. PUE could be reduced to about 1.6 to 1.8 in this phase, yet fan energy and cooling waste remained high.
1.3 Cold aisle containment era (2010-2018)
As rack power density rose from about 3 kW per rack to 8 kW, 15 kW or higher, simple aisle separation could no longer meet cooling needs. Cold aisle containment emerged: containment roof panels cover the top of the cold aisle and end doors seal the ends, turning the cold aisle into a relatively sealed cold-air plenum. Servers draw cold air under negative pressure, while hot air rises in the hot aisle and is directly extracted by the air conditioner return. PUE after containment typically drops to 1.3 to 1.5. The end door, as the openable end seal, directly determines the containment effect through its airtightness and reliable automatic closing.
1.4 Smart containment era (2018 to present)
Today, cold aisle containment is moving toward intelligence: end doors are fitted with door contact switches that alarm in the DCIM system when a door is left open; containment roofs integrate fire pressure-relief smoke vents that open automatically during a fire; end doors link with lighting and access control; and temperature and humidity sensors are deployed inside the aisle as monitoring points. The KZ-CAD end door comes standard with door contact switch contacts and optionally supports electronic locks, access linkage and status upload modules, coordinating with KZ containment roof vents for fire linkage.

Chapter 2. Working Principle and Airflow Organization
2.1 Cold aisle airflow path
In a typical underfloor air distribution system, precision air conditioners deliver cold air into the plenum under the raised floor. The plenum is formed by removable raised floor tiles (standard 600×600 mm) supported on pedestals, usually 300 mm to 1000 mm high. Cold air diffuses in the plenum and rises through perforated tiles laid beneath the cabinet intakes in the cold aisle, with perforation rates commonly 25%, 40% or 55%. Once the cold aisle is sealed by roof panels and end doors, the channel is held at a slight negative pressure relative to the room. Server front fans draw air from the aisle, the air is heated as it passes through the servers, and the hot air is exhausted into the hot aisle, where it rises and is drawn directly back to the air conditioner return. Because cold and hot air are physically isolated, mixing and short-circuiting are nearly eliminated.
2.2 Air sealing function of the end door
If the ends of a cold aisle have no doors, frequent personnel traffic leaves the ends open, allowing large volumes of cold air to leak out into the room and hot air to backflow into the aisle, destroying containment. The core role of the end door is to seal the end opening: sealing gaskets fill the gap between the door frame and the cabinet row, magnetic or brush gaskets around the door leaf are compressed when the door closes to form a continuous airtight surface, and an automatic drop seal at the bottom of the leaf falls when the door closes to block the bottom gap.
2.3 Automatic closing principle
The end door must close automatically after personnel pass through, otherwise containment is meaningless. KITOZER end doors use several self-closing methods: spring hinges that pull the leaf back (simple and low cost); sliding doors hung on top tracks with a hydraulic self-closing cartridge that pulls the leaf back smoothly after being pushed; and counterweight sliding doors. Sliding doors are the mainstream choice in high-density data centers because they do not occupy aisle space when opening.
2.4 Door contact switch and status monitoring
A magnetic reed contact is installed on the door frame: when the leaf closes, the magnet approaches and the contact closes; when the leaf opens, the contact breaks. The door contact signal is connected to the facility monitoring system. If an end door remains open beyond a set threshold (typically 60 seconds), the system raises an alarm on the monitoring interface and notifies duty staff. This prevents cold air leakage caused by a forgotten open door and is a basic configuration of smart containment.
2.5 Linkage with fire pressure-relief vents
After the cold aisle is sealed, the roof’s fire pressure-relief smoke vent provides the required smoke and pressure relief during a fire. The vent opens automatically via a thermal fuse or electromagnetic release. Although the end door is not the main pressure-relief opening, in strict fire-code installations the door glass must be fire-rated or the door must allow emergency egress. The end door and vent linkage logic is coordinated by the fire control system.
Chapter 3. Structural Components of the KITOZER End Door
3.1 Door frame system
The door frame is the supporting structure fixed to the end cabinets or columns at both ends of the cabinet row. The KZ-CAD frame uses 6063-T5 anodized aluminum alloy profile or 1.5 mm thick powder-coated cold-rolled steel. The frame width matches the end face of the cabinet row (typically matching 600 mm deep or 1200 mm wide cabinets), and the height runs from the raised floor surface to the underside of the containment roof (usually 2000 mm to 2600 mm). EPDM sealing gaskets fill the gap between the frame and the cabinet row to ensure airtightness. The frame reserves mounting positions for the door contact switch and cable routing holes.
3.2 Door leaf structure
The door leaf is the openable part. Sliding door leaves consist of an aluminum frame plus glass, using 6 mm or 8 mm clear tempered safety glass with high light transmittance for observing the equipment inside the aisle. The glass is embedded in the aluminum frame and fixed with structural adhesive. Color steel leaves use 0.8 mm powder-coated steel with optional insulation, suitable where daylighting is not required or sound insulation is needed. An aluminum or recessed handle is fitted for smooth pushing.
3.3 Track and roller system
Sliding door leaves are hung on top tracks. The track uses aluminum guide rails with nylon or steel-ball rollers that have anti-derailment designs. Double sliding doors use top-and-bottom rails, with two leaves sliding to overlap on each side. The track system must withstand repeated pushing (design life no less than 100,000 cycles), and rollers should be silent, self-lubricating and replaceable. The KITOZER sliding door is equipped with a damping self-closer whose closing speed is adjustable to avoid impact against the frame.
3.4 Sealing system
The airtight performance relies on multiple seals: EPDM foam gaskets between the frame and cabinet row fill installation gaps; magnetic gaskets around the leaf are attracted by the frame when the door closes; an automatic door bottom drop seal mechanically falls when the leaf closes to block the bottom gap; and brush strips at the overlap of sliding leaves brush against each other when the leaves overlap. Multiple seals keep the leakage rate at a low level under a 50 Pa pressure difference.
3.5 Closing and positioning device
The sliding door is fitted with a hydraulic self-closing cartridge installed at the end of the top track. After personnel push the door open, the cartridge pulls the leaf back, with a buffer section that decelerates near the closed position to avoid impact. When a long door-open hold is needed (e.g., moving large equipment), a door stop or positioning device holds the leaf open. The closing force and speed are adjustable for different leaf weights.

Chapter 4. Full KITOZER End Door Product Range
4.1 KZ-CAD-1S single sliding door
The KZ-CAD-1S is a single sliding door for aisle end widths of about 800 mm to 1200 mm. The leaf slides to one side, occupying space outside the aisle. It has an aluminum frame, 6 mm tempered glass, a damping self-closer and a door contact switch. It is simple and economical, commonly used in small and medium data centers. Reference price about USD 350-630 per door.
4.2 KZ-CAD-2S double sliding door
The KZ-CAD-2S is a double sliding door for aisle end widths of about 1200 mm to 1800 mm. Two leaves slide to both sides and overlap in the middle. The wide clear opening allows cabinets and equipment to pass. It has an aluminum or steel frame, 8 mm tempered glass, double self-closing devices and a door contact switch. It is the mainstream end door in large high-density data centers. Reference price about USD 630-1120 per door.
4.3 KZ-CAD-S glass spring self-closing door
The KZ-CAD-S is a hinged glass self-closing door that uses spring hinges to automatically return the leaf. The leaf has an aluminum frame plus tempered glass and swings inward or outward. It is compact and low cost, but the swinging leaf occupies aisle or room space, suiting narrow ends with low traffic. Reference price about USD 350-560 per door.
4.4 KZ-CAD-F fire-rated end door
The KZ-CAD-F is a fire-rated end door using fire-resistant glass (meeting the relevant fire integrity requirement) or color steel with fire core, plus fire intumescent seals on the frame. It is used in machine rooms with strict fire-zone requirements and links with fire pressure-relief vents. Reference price about USD 1120-1680 per door.
4.5 KZ-CAD-E access-control end door
The KZ-CAD-E adds an electric lock, card reader interface and access linkage module to the standard sliding door, supporting card-swipe entry, access management and door-opening records. The electric lock releases under fire signals for evacuation. It suits high-level data centers requiring access control. Reference price about USD 840-1400 per door.
| Parameter | KZ-CAD-1S | KZ-CAD-2S | KZ-CAD-S | KZ-CAD-F | KZ-CAD-E |
|---|---|---|---|---|---|
| Aisle width | 800-1200mm | 1200-1800mm | 800-1100mm | By design | 1200-1800mm |
| Leaf glass | 6mm tempered | 8mm tempered | 6mm tempered | Fire-rated | 8mm tempered |
| Frame | Aluminum | Aluminum/steel | Aluminum | Fire-rated steel | Aluminum/steel |
| Closing | Damped closer | Damped closer | Spring hinge | Damped/sequencer | Damped+electric lock |
| Door contact | Standard | Standard | Standard | Standard | Standard |
| Access control | Optional | Optional | — | Optional | Standard |
| Reference price | USD350-630 | USD630-1120 | USD350-560 | USD1120-1680 | USD840-1400 |
Chapter 5. Sizing Guide and Calculations
5.1 Aisle width and door type
The first step is to measure the clear width of the cold aisle end (the net distance between the two cabinet rows). For 800-1200 mm, choose the KZ-CAD-1S single sliding door or KZ-CAD-S spring door; for 1200-1800 mm, choose the KZ-CAD-2S double sliding door; for ends wider than 1800 mm, combine a double sliding door with side filler panels or customize a wider double door. The clear passage width should meet the largest equipment handling requirement (generally no less than 900 mm clear).
5.2 Door height and mounting datum
The end door height is measured from the raised floor surface to the underside of the containment roof. Typical raised floor heights are 300-600 mm, cabinet heights are 42U to 47U (about 2000-2200 mm), and the clear aisle height after adding the containment roof is about 2100-2400 mm. The end door height is customized to field measurement. The joint between the top of the frame and the containment roof/side panels must be sealed.
5.3 Glass specification selection
Glass thickness is chosen by leaf size: leaves narrower than 800 mm use 6 mm tempered glass; 800-1200 mm leaves use 8 mm; wider than 1200 mm use 10 mm or laminated glass. The glass must be tempered safety glass that breaks into granular pieces to avoid injury. Fire-rated glass is used where required. Glass color can be clear, bronze or frosted; frosted glass blocks the view inside the aisle.
5.4 Closing method and traffic frequency
For high-traffic maintenance aisles (dozens of passes daily), choose a damped self-closing sliding door that opens easily and has a long life; for low-traffic, budget-sensitive locations, a spring hinge self-closing door is acceptable. Sliding doors can be held open with a stop during long equipment moves.
5.5 Air sealing and pressure difference
After containment, the aisle is normally held at a slight negative pressure (-5 Pa to -15 Pa relative to the room). When cooling supply exceeds server exhaust, the aisle goes slightly positive; when supply is less than exhaust, it goes negative. The end door sealing must handle this micro-pressure difference. Pay attention to details such as the bottom drop seal and overlap brush strips, which are the main leakage paths. The KITOZER end door keeps whole-door leakage within containment design requirements at 50 Pa.
5.6 Matching roof panels and side panels
The end door cannot be used alone; it must form a complete containment body with roof panels and side filler panels. KZ-CAD roof panels are tempered glass or color steel covering the top of the aisle, and side panels seal gaps between cabinet rows and walls. The end door, roof and side panels should be designed together to ensure continuous sealing at the joints.
Chapter 6. Installation Requirements
6.1 Pre-installation site measurement
Before installation, field-measure the clear width and height of the cold aisle end and the flatness of the cabinet row end faces. The end door is a custom-size product, and the frame is fabricated to the measured dimensions. Measure from the raised floor to the underside of the containment roof (or cabinet top), and the net distance between the two cabinet rows. Check whether the cabinet row end faces are flat and whether protruding handles or cable trays interfere with frame mounting.
6.2 Frame fixing
The frame is bolted to the end cabinet columns at both ends of the row or to independent support columns. EPDM gaskets are placed between the frame and the cabinet row, and bolts are tightened diagonally in steps to keep the frame vertical and level. Frame verticality deviation should not exceed 2 mm/m. Gaps between the frame bottom and raised floor are sealed.
6.3 Leaf hanging and adjustment
Sliding leaves are hung on the top track via rollers. After hanging, adjust roller height so the leaf is level and gaps are even. Adjust the self-closing force and speed: when released from fully open, the leaf should automatically close slowly and decelerate near the frame without impact. The automatic bottom drop seal should fall the instant the leaf closes and lift when it opens.
6.4 Sealing adjustment
After the leaf closes, check that surrounding gaskets are evenly compressed, the bottom seal sits on the floor, and the overlap brush strips are engaged. An A4 sheet clamped in the door gap should show obvious resistance when pulled. If a local gap is large, adjust the frame or leaf and add gaskets.
6.5 Door contact and electrical wiring
The door contact signal cable is routed along the frame channel to the DI (digital input) module of the facility monitoring system. Distinguish NO and NC contacts: typically use the configuration where the contact closes when the door is shut and alarms when opened. Access-control doors also require access power and fire-release signals. After wiring, test the door open/close alarm on the monitoring platform.

Chapter 7. Operation and Maintenance
7.1 Daily operation rules
When passing through the end door, maintenance staff should push the door and confirm it self-closes after entering. When moving large equipment and needing the door held open for a long time, use a door stop and remove it after the work. Do not prop the door open with objects for long periods, which destroys the cold aisle negative pressure and wastes cooling. Respond promptly to door contact alarms.
7.2 Periodic cleaning
Tempered glass surfaces should be cleaned regularly with glass cleaner. Aluminum frames should be wiped with a soft cloth; avoid strong acid or alkaline cleaners that attack the anodized layer. The track and roller area should be kept free of dust and debris, wiped dry, and lightly lubricated at roller bearings if necessary (avoid oily lubricants that dirty the floor).
7.3 Gasket inspection and replacement
Sealing gaskets, bottom drop seals and brush strips are wear parts and should be checked every six months. If gaskets are aged, cracked or no longer elastic, or if the bottom seal does not drop into place, replace them promptly. Aged gaskets are the main cause of increased end-door leakage; timely replacement maintains containment performance.
7.4 Closer and roller maintenance
After years of use, the damped self-closer loses force and the leaf closes slowly or fails to latch. Adjust the closer force; if adjustment is ineffective, replace the closer cartridge. If rollers bind, make noise or wobble, inspect bearings and anti-derailment structure and replace damaged rollers. With a design life of over 100,000 cycles, expect about 5 years of service at 50 switches per day.
7.5 Door contact and electric system check
Quarterly test the door contact alarm on the monitoring platform: push the leaf open and confirm the alarm triggers after the set time; close the door and confirm the alarm resets. Test access-card opening and fire-release for access-control doors. Repair or replace failed contacts or locks.
Chapter 8. Energy Saving Calculation
8.1 PUE improvement principle
Cold aisle containment lets the air conditioner raise supply air temperature (from 13-15 C to 18-24 C), improving chiller COP; meanwhile fan speed can be tuned to actual server demand, lowering fan energy. PUE drops from about 2.0 to 1.3-1.5. The end door airtightness directly affects whether supply temperature can be raised safely: if hot air leaks in through the ends, raising supply temperature causes the end racks to overheat and the system is forced back to low temperature.
8.2 Energy saving example
Consider a data center with 100 racks at an average 5 kW each, total IT load 500 kW. Before containment, at PUE 1.8, cooling and distribution overhead is about 400 kW and total power 900 kW; after containment, at PUE 1.4, overhead is about 200 kW and total power 700 kW. Annual electricity saving is about (900-700) kW x 8760 h = 1.75 million kWh. Each 10% increase in end-door leakage raises PUE by about 0.02-0.05.
8.3 Investment payback
A containment retrofit investment includes roof panels, end doors, side panels, vents and installation. For a 100-rack row, the containment system investment is about USD 20,000-40,000 (including two end doors). At 1.5 million kWh saved per year and USD 0.11/kWh, annual saving is about USD 165,000, giving a payback period typically under one year. End doors account for only a small share of the investment, but failed sealing significantly prolongs the payback.
Chapter 9. Fire Protection and Safety
9.1 Pressure-relief vent linkage
Cold aisle containment changes the smoke flow path. The fire pressure-relief vent on the roof is the key fire design: during a fire it opens via a 68 C thermal bulb or electromagnetic release to provide pressure relief and smoke exhaust for gas fire suppression systems, preventing overpressure. Access-control end doors unlock under fire signals for evacuation.
9.2 Gas suppression and pressure relief
In machine rooms using gas suppression (e.g., Novec or FM-200), the pressure relief vent must handle overpressure when gas is discharged. The vent relief area is calculated per gas suppression design codes. The end door is not the primary relief opening, but bottom gaps and gaskets assist relief at overpressure.
9.3 Safety glass and impact protection
End door glass must be tempered safety glass that breaks into blunt granules. Glass leaves should carry anti-collision markings to prevent maintenance staff from walking into them. Pinch points between leaf and frame and at overlapping leaves should be guarded.
9.4 Emergency egress
The end door, as the aisle exit, must allow internal personnel to push out in an emergency. Sliding doors should have an emergency handle or push bar that does not require a key. Access-control doors release power on loss or fire signal. Fixed locks that cannot be opened from inside are prohibited.

Chapter 10. Standards, Certification and Quality
10.1 Relevant standards
Key standards include: GB 50174 Code for Design of Data Centers (airflow and fire requirements); GB 50016 Code of Design on Building Fire Protection; GB 15763.2 Safety Glass for Construction (tempered glass); and GB/T 7106 for air tightness, water tightness and wind resistance grading. Although end doors are not building exterior doors, their sealing and safety design references these standards.
10.2 Material and process requirements
Aluminum profiles should comply with GB/T 5237 with anodized film thickness no less than 10 um; powder-coated steel coating thickness no less than 60 um with grade 1 adhesion. Tempered glass must carry the CCC mark. Sealing gaskets use EPDM resistant to -40 C to +120 C. Closers and tracks should be mature industrial products.
10.3 Factory inspection
Each batch of end doors undergoes: dimensional and diagonal deviation inspection; leaf operation and self-closing tests (no fewer than 10 cycles); gasket contact inspection; and door contact continuity test. Fire-rated doors are accompanied by fire-resistance test reports. Each product ships with a certificate and installation manual.
Chapter 11. Cold Aisle vs Hot Aisle Containment
11.1 Cold aisle containment features
Cold aisle containment seals the cold side (server intake). Cold air is constrained in the aisle, and hot air rises freely in the hot aisle. Advantages: higher supply temperature and chiller efficiency; maintenance staff are comfortable on the cold side; retrofit is relatively simple with end doors and roof panels. Disadvantages: the hot aisle is warmer for cabling and maintenance.
11.2 Hot aisle containment features
Hot aisle containment seals the hot side (server exhaust), constraining hot air directly back to the air conditioner return. Advantages: the machine room stays at cold-aisle temperature and the hot aisle smoke is more controllable. Disadvantages: cold air diffuses in the room and may short-circuit to the return without passing through servers, requiring coordinated floor perforation and blank panels.
11.3 End door differences
Both approaches need end doors at the aisle ends. Cold aisle doors focus on preventing cold air leakage; hot aisle doors focus on preventing hot air from escaping into the room. The structures are basically identical with the same sealing requirements. Cold aisle containment is more widely used, and KZ-CAD series primarily targets cold aisle containment but can adapt to hot aisle.
Chapter 12. Sizing Calculation Example
12.1 Project background
A cold aisle consists of 20 face-to-face 600×1200 cabinets in two rows. The clear aisle width is 1200 mm, cabinet height 42U (2000 mm), raised floor 400 mm, and containment roof underside 2200 mm above the floor. One end door is needed at each end.
12.2 Sizing calculation
The end clear width of 1200 mm falls in the 1200-1800 mm range, so choose the KZ-CAD-2S double sliding door. Each leaf is about 600 mm, giving a clear passage of about 1000 mm for equipment handling. Door height is 2200 mm, custom-made to site. Choose 8 mm tempered glass (leaf width 600 mm, 8 mm is adequate). Standard configuration includes a damped self-closer, door contact switch and bottom drop seal. No electric lock is needed for this frequently used aisle, but access wiring is reserved.
12.3 Accessories
Match KZ-CAD containment roof panels covering the 20 m aisle, modular tempered glass roof; sealed joints with the end door frames; two fire pressure-relief vents on the roof (calculated by gas suppression relief area); side panels sealing gaps between cabinet rows and walls. The end doors are estimated at the double sliding reference price range, two doors total.
Chapter 13. Common Fault Diagnosis
Q: The end door does not seal tightly and leaks visibly.
A: Usually aged gaskets, a bottom seal that does not drop, or shifted leaf position. Check gasket compression with an A4 sheet; adjust roller height to even gaps; replace aged gaskets; clean the bottom-seal linkage so it falls automatically.
Q: The sliding door is heavy or noisy.
A: Usually dry rollers, damaged roller bearings or debris in the track. Clean the track, check roller rotation, replace damaged rollers, and lightly lubricate bearings. If the leaf sags, adjust roller height.
Q: The self-closer closes too slowly or fails to latch.
A: Adjust the force and speed screws on the closer. If adjustment has no effect, the closer cartridge is worn out and should be replaced.
Q: Door contact alarms continuously or not at all.
A: Check magnet-to-switch alignment when the door closes. If always alarming, the magnet may have fallen off or the contact may be damaged; if never alarming, check for a broken signal line or DI module fault. Use a multimeter to test contact continuity.
Q: The glass leaf develops a crack.
A: Tempered glass with an edge crack will shatter into granules; replace with the same specification immediately. Do not continue using cracked glass. A professional should remove the leaf and replace the glass.
Q: The gap between the end door and cabinet row is too large.
A: Fill gaps larger than normal with EPDM foam gaskets or sealant during installation. If the gap exceeds 20 mm, add a transition filler panel to ensure continuous air sealing.
Chapter 14. Additional FAQ
Q: Are cold aisle end doors mandatory?
A: Without end doors, open ends cause severe mixing and defeat containment. End doors are an integral part of the containment body together with roof and side panels.
Q: How much does one end door cost?
A: KITOZER single sliding doors reference about USD 350-630, double sliding doors about USD 630-1120, fire-rated about USD 1120-1680. Actual price depends on size, glass, closing method and electric options.
Q: Can end door dimensions be customized?
A: Yes. Doors are custom-fabricated to the measured end width and height. Provide the end width/height and cabinet model when ordering. Standard frames suit 800-1800 mm wide and 2000-2600 mm high.
Q: Is tempered glass safe?
A: Tempered safety glass breaks into blunt granules and is CCC-certified. It does not self-break under normal use, though a tiny self-breakage rate exists. Consider laminated glass for higher safety.
Q: Can the door connect to access control?
A: Yes. The KZ-CAD-E access-control door has a built-in electric lock supporting card-swipe access. The lock releases under fire signals for evacuation. Standard doors reserve door contact signals and can be upgraded.
Q: What should the cold aisle temperature be?
A: After containment, intake temperature should be held at 18-27 C (ASHRAE recommended), typically 22-24 C, raising supply temperature for energy saving. If the aisle is too cold, supply temperature can be raised.
Q: Does the end door need power?
A: Standard damped sliding doors need no power; only the door contact signal needs wiring to monitoring. Access-control doors need access power. Fire vents use thermal fuses or electromagnetic release (the latter needs fire power).
Q: Can running data centers add end doors?
A: Yes. Cold aisle containment retrofit can be done with little or no downtime. The frame is fixed outside the cabinet row and the leaf hung on a track, usually without moving cabinets. Retrofit can be done section by section.
Q: How to detect end-door leakage?
A: Use a smoke tube to observe leakage at gaps, or the A4-sheet resistance test; if available, perform a blower-door pressure test on the sealed aisle. Regular gasket maintenance keeps leakage low.
Q: Sliding door or spring door, which is better?
A: Choose a sliding self-closing door for high-density, high-traffic data centers; choose a spring hinge door for low-budget, low-traffic sites. Sliding doors are the current mainstream.
Chapter 15. Application Scenarios
15.1 Large internet data centers
Large internet data centers with dense, high-power cabinets universally use cold aisle containment plus end doors. The KZ-CAD-2S double sliding door with modular glass roof enables fast deployment and high-density containment. Door contacts feed the DCIM platform for per-door status visualization.
15.2 Enterprise self-built computer rooms
Enterprise computer rooms with medium power density often retrofit with cold aisle containment to lower PUE. The KZ-CAD-1S single door or KZ-CAD-S spring door offers high cost-effectiveness with color steel roof panels, for low investment and fast payback.
15.3 High-level financial data centers
Financial data centers require strict fire and access control, using KZ-CAD-F fire-rated doors plus KZ-CAD-E access control, coordinated with gas suppression pressure-relief vents, meeting high-level security and fire codes.
15.4 Edge computing and small rooms
Edge computing sites with few racks may use integrated micro-module cabinets with built-in end doors, or add small sliding end doors. Small room retrofit is flexible and the end-door investment share is low.
Chapter 16. Common Sizing Mistakes
16.1 Buying roof panels without doors
A common mistake is installing roof panels while leaving the ends open. The ends become the main hot-cold mixing path and containment is greatly weakened. End doors are an indispensable part of the system.
16.2 Ignoring bottom sealing
The bottom gap is a major leakage source. Many end-door leaks come not from side gaps but from a missing or failed bottom drop seal. Confirm an automatic drop seal is ordered and adjusted during installation.
16.3 Not wiring the door contact
Installing a door contact but not connecting it to monitoring alarms is pointless. A forgotten open door cannot be detected in time. The contact must be connected to the facility DI with a timeout alarm.
16.4 Thicker glass is always better
Glass thickness should match leaf size; thicker glass adds weight and track burden unnecessarily. Choose 6/8/10 mm by leaf width rather than blindly over-thickening.
Chapter 17. Delivery and After-sales
17.1 Delivery process
KITOZER end-door delivery includes: site survey and measurement, custom solution and quotation, confirmation of dimensions and configuration, factory production, on-site installation, sealing adjustment, door contact and fire linkage testing, and acceptance. Custom production typically takes 7-15 working days.
17.2 Technical support
KITOZER provides full-process technical support: assisting with aisle sizing and door selection, providing containment system solutions, on-site installation guidance and commissioning training. Engineers respond by phone, WeChat or remote access.
17.3 After-sales and warranty
The main end-door structure is warranted for at least 2 years; wear parts such as gaskets, closers and rollers are supplied long-term. Non-human-caused defects within the warranty period are repaired or replaced free. KITOZER commits to providing standard-compliant, tested end-door products and continuous technical service.
Chapter 18. More Technical FAQ
Q: Can the leaf be reverse-installed? Inward or outward opening?
A: Sliding doors slide sideways and have no inward/outward opening. Spring hinge doors can be set to swing in or out depending on aisle space and fire egress direction, usually outward (toward the hot aisle or corridor) for emergency escape.
Q: Will condensation form on the end-door glass after containment?
A: If sealing is poor, humid room air contacting the cold glass surface may condense. Good sealing and a bottom drop seal prevent this. If condensation is severe, check gaskets and aisle humidity, and dehumidify.
Q: Should the door color match the cabinets?
A: It is recommended to coordinate the frame color with the cabinet row (black or cabinet color) for a tidy appearance. KITOZER frames are available in black powder coating or anodized aluminum.
Q: Why are two end doors needed per cold aisle?
A: A cold aisle is open at both ends and must be sealed at both ends to form a closed body. If one end is against a wall, use a fixed side panel there and a door at the other end.
Q: Can the end door withstand gas-suppression discharge pressure?
A: The end door is not the main pressure-relief structure; that role belongs to the fire vent. The door glass normally handles only micro-pressure differences, and overpressure is relieved by the vent. Access-control doors unlock under fire conditions.
Q: Are KITOZER end doors and containment roof a matched system?
A: Yes. KZ-CAD end doors are designed as a matched system with KITOZER containment roof panels and side panels, with continuous sealing at the joints. Unified purchasing is recommended to avoid leakage at multi-vendor joints.
Chapter 19. Underfloor Plenum and Airflow Thermodynamics
19.1 Raised floor plenum principle
The underfloor plenum is the primary supply air duct in underfloor air distribution. Precision air conditioners blow cold air into the void beneath the removable raised floor tiles. The plenum depth, typically 300 to 1000 millimeters, determines how much air can be delivered and how evenly it distributes. Deeper plenums reduce air velocity and improve uniformity, while shallow plenums cause high velocity and uneven distribution. Cold air rises through perforated tiles placed directly below the server intakes in the cold aisle. Once the aisle is sealed by roof panels and end doors, the cold air cannot escape sideways and is forced upward through the perforated tiles into the aisle, where server fans draw it in. The end door seals the horizontal leakage path at the aisle ends, and the roof seals the vertical path at the top.
19.2 Pressure balance in the sealed aisle
After containment, the pressure inside the cold aisle is determined by the difference between cooling supply and server exhaust. If supply exceeds exhaust, the aisle goes slightly positive and cold air leaks out through gaps; if exhaust exceeds supply, the aisle goes negative and hot room air is drawn in through gaps. The ideal state is a slight negative pressure of minus two to minus eight pascals, so that all air entering the servers comes from the perforated tiles rather than from door gaps. Better end-door sealing makes it easier to maintain this slight negative pressure. Poor sealing causes either cold air spillage or hot air infiltration, both of which destroy the airflow balance and raise intake temperatures.
19.3 Hot air recirculation and hot spots
Without containment, hot air exhausted from cabinets partly rises to the ceiling and is drawn back to the air conditioner return, while partly recirculates around the room and is re-ingested by the cold aisle or server intakes. Localized high intake temperatures create hot spots that can cause servers to throttle or shut down on thermal protection. Cold aisle containment, with end doors and roof panels, physically isolates the hot and cold streams and cuts the recirculation path. End doors block end-wise recirculation, and roof panels block top-wise recirculation; both are needed. A leaky end door reintroduces the recirculation problem at the aisle ends.
19.4 Perforated tile rate and end-door coordination
The containment effect depends not only on the end door but also on the distribution of perforated tiles. Perforated tiles should be evenly placed under each cabinet intake, avoiding excessive concentration that causes high local velocity or insufficient tiles that leave end racks starved. After the end door seals the aisle, cold air can only move upward, so if the perforation rate is too low the air cannot escape and pressure builds; if too high, cold air short-circuits upward. End-door sealing and perforation rate must be tuned together, guided by pressure and temperature measurements inside the aisle.
19.5 Overhead supply and in-row air conditioners
Besides underfloor supply, some rooms use overhead precision air conditioners or in-row coolers installed directly between cabinet rows. In-row coolers blow cold air from their front into the cold aisle and exhaust hot air from their rear into the hot aisle. Cold aisle containment still applies: end doors seal the ends and roof panels seal the top, constraining the short supply and return paths. The joints between the in-row cooler panels and the containment must be sealed. For high-density racks above twenty kilowatts per rack, in-row coolers plus sealed end doors are the standard combination.
Chapter 20. Air Leakage and Pressure-Drop Analysis
20.1 Identifying leakage paths
Five leakage paths exist on a cold aisle end door: the installation gap between frame and cabinet row; the perimeter gap between leaf and frame; the overlap gap between two sliding leaves; the bottom gap between leaf and floor; and the sealant joint between glass and aluminum frame. Field measurements show the bottom gap and frame installation gap are the largest contributors, with the bottom gap alone accounting for over forty percent of whole-door leakage.
20.2 Gap leakage estimation
Leakage through a gap follows the orifice-flow law: Q equals Cd times A times the square root of two delta-P over rho, where Cd is the discharge coefficient (about 0.6 to 0.65 for gaps), A is the gap area, delta-P is the pressure difference, and rho is air density. Consider an end door with a total perimeter gap of about eight meters, an average gap width of two millimeters, and an aisle pressure difference of ten pascals. The gap area is about 0.016 square meters, and leakage is roughly 0.6 cubic meters per second, or about two thousand cubic meters per hour, a substantial loss of cooling. Compressing the gap width to below 0.5 millimeters with gaskets reduces leakage to about one quarter.
20.3 Sealing grades
Building window air tightness is graded into eight classes per the relevant standard, rated by air permeability per unit length of seam. Although end doors are not exterior windows, they are designed to at least match a high sealing class. The KITOZER end door keeps whole-door leakage within containment design requirements at fifty pascals through multiple seals. Acceptance may include a blower-door pressure test on the sealed cold aisle.
Chapter 21. Frame and Leaf Materials
21.1 Aluminum alloy profiles
The KITOZER end-door frame uses 6063-T5 aluminum extrusion. The 6063 alloy has good formability and surface finish, and the T6 temper provides moderate strength. Profile wall thickness is no less than 1.4 millimeters, and the cross-section is structurally calculated to avoid deflection under the hung leaf. Surfaces are anodized (film no less than 10 micrometers) or powder coated (film no less than 60 micrometers) for corrosion and fingerprint resistance. Common colors are black and silver to match mainstream cabinets.
21.2 Powder-coated steel frames
Fire-rated or heavy-duty end doors use 1.5 to 2.0 millimeter cold-rolled steel bent and welded, phosphated and powder coated. The steel frame is rigid and can contain internal stiffeners to support the weight of fire glass. Coating colors can be chosen from the RAL chart, typically black RAL 9005 or light gray RAL 7035 to match cabinets.
21.3 Tempered glass
Door leaf glass uses float tempered glass, cut and edged then heated to about 620 C and rapidly air-quenched, creating surface compressive stress and internal tensile stress. Strength is three to five times that of ordinary glass. When broken, tempered glass falls into blunt granular pieces, complying with the safety glass standard and CCC certification. Visible light transmittance is about 89%. Thickness of 6, 8 or 10 millimeters is chosen by leaf size. Tempered glass cannot be cut on site, so dimensions must be accurately customized.
21.4 EPDM sealing gaskets
Sealing gaskets use EPDM (ethylene propylene diene monomer) foam or solid rubber. EPDM is ozone, UV and temperature resistant from minus 40 to plus 120 C with low compression set, making it ideal for machine room sealing. The gasket cross-section is designed hollow or lipped to fill gaps by compression. Frame gaskets snap into gasket grooves, and leaf gaskets are adhered or clipped. Magnetic gaskets embed a soft magnetic strip that is attracted to the steel frame when the door closes.
Chapter 22. Track and Closer Mechanics
22.1 Track load capacity
Sliding door leaves hang from the top track, and the track and rollers carry the weight. An 8-millimeter tempered glass double door leaf weighs about 30 to 50 kilograms including the aluminum frame. Rollers are sized at two to three times the leaf weight, with two to four load rollers per leaf and a per-roller rating no less than 50 kilograms. The track is fixed to the frame top or independent beam at intervals no greater than 600 millimeters to prevent sagging.
22.2 Self-closing cartridge principle
The damping self-closing cartridge typically uses an internal spring plus hydraulic damping. Pushing the leaf open stretches the spring to store energy; on release, the spring pulls the leaf back, and hydraulic oil through an orifice provides damping so the closing speed is smooth and adjustable. The closing force should just overcome gasket compression and bottom-seal friction, latching the door without slamming. An adjustment screw changes the orifice size to tune speed.
22.3 Service life
Track rollers and closers are designed for no less than 100,000 cycles at 30 to 50 switches per day, about 5 to 9 years. Acceptance includes at least 100 continuous open-close cycles without binding or noise. Maintenance uses a small amount of silicone grease on roller bearings, avoiding oily lubricants that attract dust.
Chapter 23. Integration with Cabinets and Micro-modules
23.1 Compatibility with different cabinet brands
Data center cabinets vary in brand, depth (600/1200 mm) and frame width. The end door is designed to be adaptable: the frame connects to the cabinet row end columns via adjustable brackets that slide within a range to absorb manufacturing and installation deviations. When ordering, provide the cabinet model or column cross-section so KITOZER supplies matching brackets.
23.2 Micro-module integrated end doors
A micro-module integrates cabinets, in-row coolers, containment, power distribution and monitoring into a factory-prefabricated unit. The micro-module end door is pre-assembled with roof and side panels at the factory and the whole unit is placed on site. The KZ-CAD door can serve as a micro-module component with unified interfaces and factory pre-adjusted sealing, eliminating on-site commissioning.
23.3 Cable crossing through the end door
Network or power cables needing to cross the aisle end should not pierce the door and break its seal. Instead, use a brush cable entry panel: open a cable pass-through hole in the lower door or side, fill it with a brush strip, and route cables through the brush bundle, which allows cable passage while maintaining sealing. Alternatively, reserve a bottom cable channel through the frame.
Chapter 24. Acceptance Testing Methods
24.1 Appearance and dimensional acceptance
Check appearance: the frame is flat and scratch-free, glass has no cracks, coating is even. Measured frame width and height should be within plus or minus 2 millimeters of the order, and diagonal difference within 3 millimeters. The leaf and perimeter gaps should be even, with gap width variation within 1 millimeter.
24.2 Switch function test
Cycle the leaf 20 times: pushing should be smooth without binding; on release the self-closer should pull the leaf closed smoothly with buffering and no impact; the bottom drop seal should fall synchronously. Measure the self-close time (from fully open release to fully closed) within the adjustable 3 to 8 second range.
24.3 Sealing test
Clamp an A4 sheet around the leaf perimeter; when the door closes, the sheet should be gripped with even resistance when pulled. The bottom seal should grip the sheet similarly. If available, generate smoke inside the sealed aisle and observe no obvious smoke leakage at door gaps. Record the door contact alarm and reset on the monitoring platform.
24.4 Fire linkage test
Coordinated with the fire system, trigger the fire signal: access-control end doors should unlock automatically, fire vents should open, and personnel should be able to push out from inside. After testing, reset to normal state.
Chapter 25. Leakage Inspection and Maintenance Checklist
If PUE rises or aisle temperature becomes abnormal after containment has run for a while, inspect the end door leakage points using this checklist: (1) check whether the leaf is fully closed and the door contact alarms; (2) check whether gaskets between the frame and cabinet row have fallen off or visible gaps exist; (3) check whether perimeter magnetic gaskets have aged and lost elasticity; (4) check whether the bottom drop seal falls into place or is stuck by dust; (5) check whether overlap brush strips have flattened or are missing; (6) check whether glass sealant joints are cracked; (7) check whether track area sag has widened gaps; (8) check whether cable-entry brushes are missing. Treat each finding by replacing gaskets, cleaning the bottom seal, adjusting leaf height or adding brushes.
Chapter 26. Operations and Maintenance Management
26.1 Daily inspection
Duty staff visually check each cold aisle end door daily: whether the leaf is closed, glass intact, frame deformed. Check door contact status on the facility platform and immediately respond to any open-too-long alarm. Record door status by number during inspection.
26.2 Quarterly maintenance
Each quarter: clean glass and frame, clean track and rollers, check gasket elasticity, test door contact alarm and reset, test closer force. List aged wear parts (gaskets, bottom seals, rollers) for replacement.
26.3 Annual inspection
Once a year perform an overall leakage test or infrared thermal scan of the sealed cold aisle: observe end-door areas for cold leakage (cold spots) or hot air infiltration (hot spots) with a thermal camera, and measure aisle pressure difference. Schedule a major sealing replacement based on the results.
Chapter 27. More FAQ
Q: Clear or tinted glass for the door?
A: Clear glass gives good light transmission and visibility into the aisle, and is the mainstream choice; bronze or frosted glass blocks the view but reduces visibility. Use clear for maintenance aisles and frosted where confidentiality is needed.
Q: Can labels or stickers be applied to the door?
A: Aisle numbers and safety warnings may be applied to the glass or frame. Avoid thick objects on the leaf travel path that interfere with self-closing. Use anti-static, durable materials.
Q: Do I need an access reader next to the end door?
A: Access-control doors integrate the reader. For standard doors requiring access management, an external reader and electric lock retrofit can be added. Reader height is about 1.3 meters, linked to the access system.
Q: Is aisle lighting sufficient? Does the door block it?
A: Containment does not affect room lighting; LED tubes or strips are usually added under the containment roof to light the aisle. The glass door is translucent and does not block lighting.
Q: The bottom door seal strip is worn, what to do?
A: The bottom drop seal is a wear part and can be replaced separately. Remove the seal assembly at the leaf bottom and replace the strip or the whole assembly. Inspect annually and replace when worn, otherwise bottom leakage is obvious.
Q: How heavy is one door? Is installation dangerous?
A: A single glass door weighs about 30-50 kg; a double door totals 60-100 kg. Install with at least two people and use an auxiliary bracket. Hang rollers with care to prevent the leaf tipping. Professional installers handle this safely.
Q: Can the door be upgraded to an automatic door?
A: Yes. Add an opening motor, belt drive and radar or foot sensors for automatic sliding doors that open on approach and close after passage. Suitable for high-traffic main aisles. Costs more than manual self-closing and requires power.
Q: Will noise increase at the end door after containment?
A: The door itself produces no noise. A squeaky track indicates the need for cleaning and lubrication. Containment partly isolates room fan noise, and aisle noise is similar to room noise.
Q: Does KITOZER provide the whole cold aisle containment solution?
A: Yes. KZ-CAD end doors come with containment roof panels, side panels, fire vents and door contact monitoring, providing a complete solution from survey, design and production to installation.
Q: How long is the warranty?
A: Main structure warranty is no less than 2 years; hardware (rollers, closer) 1 year; gaskets and other wear parts are not covered but are supplied long-term. Specific terms follow the contract.
Chapter 28. Construction Organization and Safety
28.1 Construction preparation
Before installation, confirm the machine room is delivered, cabinets in place, raised floor laid, and the containment roof plan finalized. Wear anti-static clothing and shoe covers; register access to the running room. Lay protective pads under tools to avoid scratching the floor and cabinets.
28.2 Non-disruptive installation
End-door retrofits are often done in running rooms. Confirm the work zone with operations staff and lay protection under the installation point and around cabinets. Avoid vibration that could affect running equipment when fixing the frame and hanging the leaf. Control dust from drilling and sealing, and work during low-traffic periods.
28.3 Working at height
Installing top tracks and frame beams involves work above 2 meters; use an A-frame ladder or mobile scaffold with a spotter. Carry glass leaves with two people, avoiding bumps against cabinets.
Chapter 29. Packaging, Transport and Storage
End doors are custom products: frames are wrapped in bubble film plus wooden crating, and glass leaves are individually wrapped in soft film and stored upright in a dedicated transport rack with hardboard separators between panes. During transport, leaves must stay upright, never flat-stacked or loaded with weight, to prevent glass breakage. On site, store in a dry, flat indoor area away from construction traffic, with leaves upright against a wall on wooden blocks and away from heat sources and chemicals. Inspect each pane for transport cracks before installation.
Chapter 30. Cooling System Coupling with Containment
30.1 Chiller efficiency and supply temperature
The fundamental reason cold aisle containment saves energy is that it allows raising the chilled water supply temperature and air conditioner supply air temperature, which improves chiller coefficient of performance. Centrifugal or screw chillers gain significant efficiency as evaporating temperature rises: when chilled water supply is raised from 7 C to 12 C, chiller COP can improve by about 20 to 30 percent. Without containment, to prevent local hot spots the room must keep supply air low (13-15 C) and the chiller runs at low efficiency. After containment, hot and cold air do not mix, and server intake stays within the ASHRAE A1 range at 22-24 C, allowing supply air to rise to 18-22 C and chilled water to 12-15 C. End-door and roof airtightness directly determine whether supply temperature can be raised safely: if hot air leaks in through the ends, raising supply temperature pushes end-rack intake beyond limits and forces the system back to low temperature, defeating the savings.
30.2 Fan energy saving
Precision air conditioner fans are the second largest energy consumer after chillers. EC (electronically commutated) fans can be speed-controlled steplessly by pressure difference. After containment, differential pressure sensors between the cold and hot aisles let the fans run at the minimum speed needed to maintain the set pressure, rather than constant full speed. When the end door is sealed, the aisle pressure is stable and fan speed can drop to 60-80 percent of rated speed; fan power drops with the cube of speed (half the airflow means about one eighth the power). If the end door stays open, pressure fluctuates and the fan must stay at high speed, so fan savings cannot be realized.
30.3 Free cooling utilization
In favorable climates, when outdoor air temperature is low, the chiller free-cooling plate heat exchanger can directly cool the room using the outdoor source, fully or partly shutting down mechanical compression. Cold aisle containment stabilizes the room cooling load and makes supply temperature controllable, greatly extending the hours in which free cooling can be used. Better end-door sealing stabilizes the load and smooths free-cooling switchover. In northern climates, good containment plus free cooling can keep PUE below 1.25 for long periods.
30.4 High-density computing scenarios
As rack power density rises from the traditional 5-8 kW to 20 kW, 30 kW or more (high-density computing and storage), traditional room-level cooling is insufficient and in-row coolers, rear-door heat exchangers or liquid cooling are required. In these scenarios, cold aisle end doors and roof panels are standard complements to in-row coolers: the in-row cooler front blows cold air into the sealed cold aisle and the rear exhausts hot air into the hot aisle. The end door seals the ends so the short-distance supply does not drift away. For racks above 20 kW, end-door sealing must be tighter, with bottom and overlap gaps pressed down to avoid local cold-air short-circuiting.
Chapter 31. Monitoring, Control and System Integration
31.1 Temperature, humidity and pressure sensor placement
Inside the sealed cold aisle, temperature and humidity sensors should be placed at the aisle start, middle and end to monitor temperature uniformity and detect local overcooling or hot spots. Micro-differential pressure sensors between the cold aisle and adjacent hot aisle or room monitor containment integrity and provide fan-speed control. The end-door contact status is a basic monitoring point. All sensor signals connect to the facility host via RS485 Modbus RTU or dry contacts, then upload to the DCIM platform via SNMP or Modbus TCP.
31.2 Door contact linkage logic
Door contact alarms can be tiered: within 15 seconds of opening is normal passage time with no alarm; beyond 60 seconds triggers a pop-up alarm and log on the monitoring platform; beyond 5 minutes triggers audible-visual reminder. Duty staff receive the alarm on the mobile app. This logic avoids false alarms from brief passes while catching forgotten-open doors. The KITOZER contact uses selectable NO/NC contacts to match different monitoring DI modules.
31.3 Fire system linkage
End-door electric locks and fire pressure-relief vents connect to the fire linkage control panel. On confirmed fire, the system releases all electric locks (for evacuation), opens fire vents (for smoke and pressure relief), and shuts down air conditioners (to prevent fanning). During gas suppression discharge, the vent prevents room overpressure. The linkage logic must be jointly commissioned with the fire contractor, and KITOZER provides dry-contact interfaces and wiring diagrams.
31.4 Status visualization
On the DCIM large screen, each containment zone is shown as a floor plan: green for closed doors, red for open-too-long doors, with vent status and live aisle temperature and humidity. Operators see the whole containment status at a glance. KITOZER optionally supplies a centralized door-contact collection module that aggregates multiple contacts and uploads via network port, simplifying wiring.
Chapter 32. Green Building and Energy Certification
32.1 PUE and WUE targets
Modern data centers are governed by both PUE (Power Usage Effectiveness) and WUE (Water Usage Effectiveness). Cold aisle containment is among the most cost-effective measures to improve PUE. PUE equals total facility energy over IT energy, and the goal is to approach 1. Containment with end doors and roof panels lowers PUE from about 1.8 to 1.4, saving about 3.5 million kWh per year per MW of IT load. The end door accounts for a small share of the investment, but its airtightness is indispensable to the result.
32.2 Green certification
Data centers pursue LEED, Green Tier and TIA-942 Uptime Tier certifications. Cold aisle containment and end-door airtight design score points for energy efficiency. Auditors require containment design documents, leakage test reports and measured PUE. KITOZER can assist by providing product technical documentation and test reports.
32.3 Carbon reduction
For a 10 MW IT load data center, lowering PUE from 1.8 to 1.4 saves about 35 million kWh per year; at a grid carbon factor of 0.55 kg CO2 per kWh, that is about 19,000 tonnes of annual carbon reduction. The end-door airtight contribution is small in percentage but is an indispensable link in the whole reduction chain. Enterprise clients report data center PUE and carbon reductions in their ESG disclosures.
Chapter 33. Lifecycle Cost and Sizing Economics
33.1 Capital cost breakdown
Cold aisle end-door capital cost includes: door frame and leaf (about 60%), track and closer hardware (about 15%), door contact and electric parts (about 10%), and freight and installation (about 15%). A double sliding door references USD 630-1120; a standard 20-rack row needs two end doors, and with roof, vents and side panels the whole row containment investment is about USD 11,000-22,000. End doors account for about 10-15 percent of the containment investment.
33.2 Operating cost savings
Each improvement in end-door sealing grade accumulates energy savings. At 8760 operating hours and USD 0.11 per kWh, a 100-rack row saves about USD 130,000-200,000 per year after containment. If end-door seal aging causes 10 percent more leakage, the annual lost saving is about USD 13,000-20,000, while replacing gaskets costs only a few hundred dollars. Thus maintaining end-door sealing has an extremely high return on investment.
33.3 Service life and replacement cycle
Frame and leaf main structure last over 10 years; gaskets and bottom seals are replaced every 2-3 years; rollers and closers every 5-8 years. Choosing standardized end doors with separately replaceable wear parts is more economical than whole-door replacement. KITOZER supplies all wear parts separately and does not require whole-door replacement.
Chapter 34. Adaptation to Different Room Environments
34.1 Humid and coastal environments
In coastal or high-humidity areas, aluminum frames need reinforced anodizing or 316 stainless steel fasteners to resist salt-spray corrosion. Use hydrolysis-resistant EPDM gaskets. Glass sealant should be mold-resistant. End-door electrical parts (contact, electric lock) should be moisture-proof.
34.2 High-altitude and cold environments
At high altitude with low air density, the same airflow rate delivers less cooling, so end-door sealing matters more to avoid air-volume loss. In cold regions, winter fresh air heating must be considered, and the end door prevents excessive heat exchange between the aisle and room. Closers in low temperatures experience hydraulic oil viscosity changes; choose wide-temperature closers.
34.3 Cleanroom and shielded environments
In machine rooms inside electronics manufacturing cleanrooms, end-door sealing must also meet cleanliness; use low-particulate brushes for bottom seals. In electromagnetically shielded rooms, the end door must be a shielded door with conductive gaskets between frame and cabinet row and metal-mesh glass, meeting shielding effectiveness. Such shielded end doors are significantly more expensive than standard types.
Chapter 35. Common Project Mistakes and Avoidance
35.1 Ordering before cabinets are precisely placed
A common mistake is ordering end doors before cabinets are accurately positioned, so the field frame does not match the cabinet row. The correct approach is to place and align all cabinets, then field-measure each end face clear width and height before ordering. KITOZER provides survey service or guidance for the contractor’s measurement.
35.2 Different vendors for door and roof
When the end door is from one vendor and the roof from another, the joint sealing is each vendor’s own responsibility and gaps leak. It is recommended that end door, roof and side panels be designed by the same vendor, or the joint sealing detail be explicitly defined at design stage.
35.3 Door contacts not wired
Installing a door contact but not connecting it to monitoring alarms is useless. The design handover must specify that contacts connect to the facility DI with timeout alarms, and each door is tested at acceptance.
35.4 Overlooking bottom sealing
When selecting, people look only at the leaf glass and forget to confirm the automatic bottom drop seal. The bottom gap then becomes the main cooling loss. Specify the automatic bottom seal at ordering and adjust it during installation.
35.5 Excessive closing force
If the closer is adjusted too forcefully, the leaf slams the frame, and long-term impact loosens rollers, fatigues the glass frame and crushes gaskets. The correct force just overcomes gasket resistance and closes smoothly with a buffer. Sealing depends on gasket compression, not on slamming.
Chapter 36. Delivery Documentation and Training
On delivery, KITOZER provides: end-door layout and elevation drawings, product certificates, tempered glass CCC certificates, installation and operation manual, door-contact wiring diagram, and warranty card. Fire-rated end doors additionally provide copies of fire-resistance test reports. After installation, operators receive brief training: how to open and close the door correctly, how to handle door-contact alarms, how to clean and inspect sealing, and the location and replacement of wear parts.
Chapter 37. More FAQ (continued)
Q: How wide can a leaf be?
A: A single sliding leaf is generally no wider than 900 mm; wider leaves are heavy and burden the track. Use double doors for aisle ends over 1200 mm, about 600 mm per leaf. Special wider needs can use triple sliding doors, but track load must be calculated.
Q: How does end-door glass differ from ordinary window glass?
A: End-door glass is tempered safety glass, strong and breaking into blunt granules, and must be CCC-certified. Ordinary float glass is weak and breaks into sharp shards and is prohibited. Fire-rated situations require fire glass.
Q: Why does the glass door feel sucked or pushed when closing?
A: When the sliding door closes, air inside and outside is squeezed or sucked through the gap, creating a pressure difference that pulls or pushes the leaf. This is normal sealing behavior; better sealing makes the pressure sensation more noticeable.
Q: How thick should the glass be to resist bumps?
A: Use 6 mm for 600 mm leaves, 8 mm for 800 mm, 10 mm or laminated for over 1000 mm. Match thickness to size; tempered glass is reasonably impact resistant. Add anti-collision strips at frequently bumped positions.
Q: Can I add a small observation window to the door?
A: The whole leaf is already glass, so no separate window is needed. If using a color steel leaf, embed a tempered glass observation window at eye height.
Q: Can people walk in the cold aisle? Is the end door for that?
A: The cold aisle is the maintenance corridor between cabinet rows; staff periodically enter for inspection and cabling. The end door is the aisle entrance, self-closing after passage to maintain the sealed state.
Q: How wide should the aisle between two cabinet rows be for an end door?
A: The cold aisle clear width is typically 1200 mm (two rows of 600 mm deep cabinets face to face, with a hot aisle behind). The end door is custom-sized to the clear width. Aisle narrower than 900 mm does not allow people and equipment to pass comfortably and is generally not recommended.
Q: How long do end-door gaskets last?
A: EPDM gaskets last about 3-5 years; bottom seals worn by friction every switch are inspected at 2 years and replaced as needed. Press the gasket during inspection; if it rebounds slowly or cracks, replace it.
Q: Do KITOZER doors support export?
A: Yes. Products can be customized to imperial or metric sizes, with English technical documentation and COC. Overseas projects can be shipped in containers with shock-proof packaging. Contact WhatsApp +1 906-853-4140 for overseas business.
Q: How do the end door and access card reader work together?
A: The access-control door frame reserves a reader mount and wiring. After a card swipe, the electric lock releases and staff push in; on exit the leaf self-closes and the bolt re-engages. The lock releases automatically under fire signals.
Q: Why is my cold aisle PUE not dropping?
A: Check in order: (1) are end doors open or seals failed; (2) are roof and side panels sealed; (3) is the perforated tile rate reasonable; (4) is supply temperature still too low; (5) is there local hot-air short-circuit. End-door leakage is a common cause.
Q: Should both end doors of a cold aisle self-close?
A: Yes, both ends should be self-closing doors, regardless of which end is used. If one end is against a wall and cannot be entered, make a fixed panel there and a self-closing door at the other end.
Chapter 38. Supplemental Technical Parameter Table
The following table summarizes key technical parameters of the KZ-CAD cold aisle end door series for quick reference during sizing and specification.
| Item | Parameter / Requirement |
|---|---|
| Frame profile | 6063-T5 anodized aluminum, wall thickness >=1.4 mm |
| Frame coating (steel) | 1.5-2.0 mm cold-rolled steel, powder coating >=60 um |
| Leaf glass | Tempered safety glass 6/8/10 mm, CCC certified |
| Sealing gasket | EPDM, -40 C to +120 C, magnetic option |
| Bottom seal | Automatic drop seal on door close |
| Self-closing | Hydraulic damped closer, 3-8 s adjustable |
| Roller life | >=100,000 cycles |
| Door contact | Dry contact NO/NC selectable, to facility DI |
| Electric lock (option) | Card access, fire-interlocked fail-safe release |
| Aisle width range | 800-1800 mm (custom wider available) |
| Aisle height range | 2000-2600 mm (field custom) |
| Airtightness | Low leakage at 50 Pa, referenced to high window class |
| Color | Black / silver / RAL custom |
| Reference price | USD 350-1680 per door (by model and config) |
Chapter 39. Fluid Mechanics of Gap Flow
39.1 Viscous flow through gaps
Air is a viscous fluid, and when it passes through narrow door gaps, the velocity profile is shaped by wall viscosity into laminar flow. When a pressure difference exists across the gap, air flows from the high-pressure to the low-pressure side, and leakage is proportional to gap area and to the square root of the pressure difference. This means halving the gap width roughly halves leakage, while doubling pressure difference only increases leakage by about 41 percent. In a cold aisle containment system the end-door pressure difference is typically only 5 to 15 pascals, which seems small, but a door with an eight-meter perimeter and two-millimeter average gap leaks thousands of cubic meters per hour at ten pascals, equivalent to the supply of a small air conditioner. Therefore the core of end-door sealing is not zero leakage but compressing the effective gap below 0.5 millimeters with gaskets, bringing leakage to an acceptable level.
39.2 Buoyancy of hot and cold air
Hot air has lower density and rises; cold air is denser and sinks. Cabinet exhaust is 15-25 C warmer than the cold aisle air, and the density difference produces noticeable buoyancy. In an unsealed room, hot air rises to the ceiling, is partly drawn to the air conditioner return, and partly descends along walls to re-enter the room, forming natural convective circulation. The containment roof cuts the hot-air rise path so hot air can only be extracted along the hot aisle. The end door blocks horizontal hot-cold exchange at the ends. Under buoyancy, pressure differs slightly between the bottom and top of the aisle, so both bottom and top sealing need attention.
39.3 Fan curve and system resistance
Precision air conditioner fans move along their characteristic curve as system resistance changes. Cold aisle containment increases system resistance (air is constrained), and fan airflow automatically drops. If the fan is fixed-speed, reduced airflow may cause insufficient supply; if it is an EC variable-speed fan, the control logic raises speed to maintain the set pressure. End doors opening and closing dynamically change system resistance, and EC fan speed response compensates smoothly. During design, the fan operating point should be recalculated for the contained system to avoid over-pressure from excessive airflow or under-supply from insufficient airflow.
39.4 Temperature and humidity coupling
The air inside the cold aisle is cool; if humidity is high, surfaces below the dew point (such as the cold face of the end-door glass) will condense. After containment, air exchange between the aisle and room hot-humid air is reduced, and humidity is mainly controlled by air conditioner dehumidification. Generally room relative humidity is held at 40-60 percent; at 22 C aisle temperature the dew point is about 12-14 C, and the glass surface temperature is normally above the dew point, so no condensation occurs. If the end door seals poorly, room hot-humid air seeps in and condenses on the cold glass, dripping at the door bottom. In that case, strengthen sealing and check room dehumidification.
Chapter 40. Door Hardware Detail Design
40.1 Handle and opening force
Sliding door handles are recessed or surface-mounted aluminum, placed at the leaf edge for easy pushing, at about 1.0-1.2 meters height. Opening force follows ergonomics so one person can push open with one hand (force no more than 50 N). Spring self-closing doors must overcome both spring preload and gasket compression; too much force makes opening hard, too little fails to seal. KITOZER adjusts spring preload on the closer to balance opening and closing force.
40.2 Anti-derailment and anti-pinch
Sliding door rollers have anti-derailment structures: rollers are captured in the guide channel, and track ends have limit stops to prevent the leaf from sliding off. Pinch zones at leaf-frame and overlapping leaf edges are fitted with soft guards. If a hand is in the gap, the guard cushions the impact. Automatic electric doors should also add safety light curtains (infrared pairs) that stop closing when someone passes.
40.3 Door numbering and signage
Each cold aisle end door should carry a unique number (e.g., Aisle-A-End-Door) on a prominent position of the frame. Next to the door post the aisle number, server zone, emergency egress direction and warnings. Door-contact alarms are located by number on the monitoring platform. Proper signage is a basic requirement of data center operations.
40.4 Grounding and equipotential bonding
The metal frame should be equipotentially bonded to the cabinet row to prevent static buildup. The frame connects to the room grounding busbar via a grounding braid, with grounding resistance no greater than 1 ohm. This step is easily overlooked during installation but is mandatory in anti-static machine rooms. Glass leaves are non-conductive and need no grounding, but metal handles are bonded to the conductive frame.
Chapter 41. Typical Retrofit Project Flow
41.1 Site survey
The retrofit team brings a laser distance meter and level: measuring each cold aisle end clear width and height, cabinet row straightness, raised floor height and containment roof mounting position. Cabinet brand and column cross-section are recorded. Photos are archived. A survey report marks special nodes (ends against walls, columns, duct crossings).
41.2 Solution design
Based on the survey, produce an end-door layout: single or double sliding door per end, leaf dimensions, frame fixing method, joint details with roof, and door-contact routing. Simultaneously design roof panels, vents and side panels. The solution is confirmed by the client before ordering production.
41.3 Production and delivery
The factory produces frames and leaves to custom dimensions, and tempered glass is custom-cut (it cannot be cut on site, so dimensions must be accurate). The frame and door are pre-assembled and tested before shipment. On arrival, the client checks the packing list: frames, leaves, tracks, closers, gaskets and hardware are complete, and glass has no cracks.
41.4 On-site installation and commissioning
Fix the frame per the layout, hang the track, hang the leaves, adjust the closer and bottom seal, and wire the door contacts. Install section by section and commission each section as it is completed. After all sections, perform an overall sealing test and door-contact fire linkage test.
41.5 Acceptance and handover
The client and KITOZER jointly accept: appearance, dimensions, switch function, sealing, door-contact alarm and fire linkage are confirmed item by item. Sign the acceptance form and hand over documentation and training. The warranty period begins.
Chapter 42. More FAQ
Q: Will the end-door glass fog over after containment?
A: If sealing is poor, moisture may fog the cold glass face as cool aisle air meets room air. Good sealing plus a bottom drop seal avoids this. If fogging is severe, check gaskets and aisle humidity and dehumidify.
Q: Should the door frame color match the cabinets?
A: It is recommended to coordinate (black or cabinet color) for a tidy look. KITOZER frames are available in black or anodized aluminum to match mainstream cabinet colors.
Q: Why two end doors per cold aisle?
A: A cold aisle is open at both ends and must be sealed at both ends to form a closed body. If one end is against a wall, use a fixed panel there and a door at the other end.
Q: Can the end door withstand gas-suppression discharge pressure?
A: The end door is not the primary relief structure; that belongs to the fire vent. The glass normally handles only micro-pressure, and overpressure is relieved by the vent. Access-control doors unlock under fire and do not sustain overpressure.
Q: Are KITOZER doors and roof a matched set?
A: Yes. KZ-CAD doors are designed as a matched system with KITOZER containment roof and side panels, with continuous sealing at joints. Unified purchasing is recommended to avoid multi-vendor leakage.
Q: Can I apply stickers to the glass?
A: Aisle numbers and safety labels may be applied. Avoid thick objects on the travel path. Use anti-static, durable materials.
Q: How heavy is a leaf? Can two people carry it?
A: A single glass leaf is 30-50 kg and two people can carry it. Double-door leaves are moved separately. Use a bracket during installation.
Q: If the glass breaks, can I temporarily block it?
A: In an emergency, use a color steel or plywood panel to temporarily seal the end and restore containment, but replace with tempered glass as soon as possible. Temporary panels lack self-closing and door-contact functions and need manual management.
Q: Why is it warmer at the end door after containment?
A: This means hot air is backflowing into the cold aisle through the door (excessive negative pressure or failed sealing). Check whether supply is insufficient, the door is closed and gaskets are intact.
Q: Does KITOZER provide 3D renderings?
A: KITOZER can provide installation renderings based on client cabinet row photos and dimensions to support solution presentations.
Chapter 43. Technology Trends
Data center cooling is evolving toward higher density, greater intelligence and better energy efficiency. As an end component of containment, the end door is also evolving: automatic sensor sliding doors are becoming common, letting staff pass hands-free and the door close automatically, reducing human error; doors are linking deeply with containment roofs, in-row coolers and DCIM to form a closed airflow management loop; materials and sealing processes continue to improve airtightness; and prefabricated micro-modules treat the door as a factory-integrated component with no on-site commissioning. KITOZER tracks these trends and iterates the KZ-CAD series to provide up-to-date containment solutions.
As high-density computing and liquid cooling spread, traditional air-cooled cold aisle containment will still serve many medium and low-density rooms for a long time. The end door is small but directly affects PUE and cooling reliability. Choosing an airtight, self-closing, maintainable door and maintaining its seals regularly is the key to realizing the return on containment investment. KITOZER works with clients to manage and maintain every door so that every bit of cooling is used where it matters.
Chapter 44. Conclusion
This concludes the KITOZER cold aisle containment end door technical encyclopedia. It covers product overview, working principle, structure, full product range, sizing guide, installation, operation and maintenance, FAQ, application scenarios, fire linkage, energy savings and standards. All prices are reference prices for budgeting only; the actual price is subject to the formal KITOZER quotation. Product specifications are subject to the latest technical documentation. KITOZER reserves the right to improve products. Thank you for reading. For KITOZER cold aisle end door selection, site survey and reference quotation, call +86 13922289957, contact on WeChat, or WhatsApp +1 906-853-4140. Guangzhou Laian Intelligent System Development Co., Ltd. is at Chaotian Park, Zhongrun Industrial Zone, No.5 Huashan Road, Shilou Town, Panyu District, Guangzhou, China. KITOZER is committed to providing reliable, energy-saving, smart containment products and services to data center clients worldwide.
Chapter 45. End Door Purchasing and Commercial Points
When purchasing KITOZER cold aisle end doors, follow three principles: unified matching, on-site customization and long-term maintenance. Unified matching means the end door, containment roof, side panels and fire pressure-relief vents are designed and produced by the same vendor to ensure continuous sealing at joints and avoid leakage at multi-vendor seams. On-site customization means the frame is fabricated to the measured end dimensions after cabinets are in place and aligned, rather than ordered from estimated drawings, otherwise the door will not fit or will leave oversized gaps. Long-term maintenance means confirming that wear parts (gaskets, bottom seals, rollers, closer cartridges) can be purchased and replaced separately rather than requiring whole-door replacement. Commercially, end doors reference USD 350-1680 per door, and large projects can negotiate framework agreement pricing. The contract should clearly state dimensions, glass specification, closing method, whether access control is included, door-contact interface, warranty period and lead time for wear parts.
The commercial handover should also cover spare parts strategy: keep a small stock of gaskets, bottom seals and a spare closer cartridge on site so that wear parts can be replaced without waiting for shipment. KITOZER can supply a recommended spare parts kit with the first order. This ensures that even if a gasket ages or a bottom seal wears, maintenance staff can restore sealing within hours, avoiding prolonged cooling waste.
Chapter 46. Final Note
The KITOZER cold aisle containment end door is a small but critical component of any cold aisle containment system. Its airtightness, automatic closing reliability and maintainability determine whether the containment investment delivers the expected PUE improvement. We hope this encyclopedia helps engineers and operators specify, install and maintain end doors correctly. For technical discussion and commercial cooperation, contact KITOZER at +86 13922289957, WeChat, or WhatsApp +1 906-853-4140. Thank you for your trust and interest.
Chapter 47. End Door Inspection Cycle Table
To facilitate operations management, the end-door inspection and maintenance cycle is summarized as follows. Visually check daily whether the door is closed and glass intact. Check door-contact alarm records weekly for abnormalities. Clean glass and frames and inspect gasket appearance monthly. Each quarter test the self-closing action, bottom-seal drop and door-contact alarm reset. Every half year inspect track rollers, lightly lubricate bearings and press gaskets to judge elasticity. Once a year perform an overall leakage or infrared thermal scan of the sealed cold aisle and replace aged gaskets as needed. Managing the door on this cycle keeps it airtight and smooth-opening for years, preventing small leaks from accumulating into large energy waste.
Beyond the end door itself, the inspection should also note the joint between the door frame and containment roof, the joint between the frame and side panels, and any cable pass-through brush. These joints are often neglected but are common leakage points. A well-documented inspection log allows the facility manager to trend gasket aging and plan replacements before leakage becomes measurable in PUE.
Chapter 48. Sizing Quick Reference
To summarize sizing: for an aisle end clear width of 800-1200 mm choose the KZ-CAD-1S single sliding door or KZ-CAD-S spring door; for 1200-1800 mm choose the KZ-CAD-2S double sliding door; where fire zoning is required choose the KZ-CAD-F fire-rated type; where card access is required choose the KZ-CAD-E access-control type. Glass thickness is 6/8/10 mm by leaf width. Door height is measured on site from the raised floor to the roof underside. Standard configuration includes a damped self-closer, door contact switch and bottom drop seal. Match with KITOZER containment roof and fire pressure-relief vents. Reference price is USD 350-1680 per door. Always field-measure and confirm the cabinet brand and column cross-section before ordering so that matching connection brackets can be supplied. Thank you for reading the KITOZER cold aisle containment end door technical encyclopedia.
Chapter 49. End Door and Air Conditioning Group Control
Modern data center air conditioning uses a group control system to schedule multiple precision units and their speeds. The cold aisle end-door status is one input to group control: when an end door stays open for a long time, the group control can temporarily raise the fan speed of the corresponding zone unit to compensate for cooling loss, and return to energy-saving speed once the door closes. This linkage prevents local rack overheating while the door is open and avoids wasting fan energy after it closes. The door-contact signal connects to the group control and, together with temperature, humidity and pressure sensors, forms an airflow management closed loop. The KITOZER contact provides dry-contact or RS485 interfaces for easy integration.
Chapter 50. End Door and Battery/UPS Area Separation
Data center battery rooms and UPS rooms are usually separated from the main equipment room. If the cold aisle extends near the battery area, the end-door design must consider battery room ventilation requirements (battery charging evolves hydrogen and requires exhaust). The end door must not interfere with the battery room independent exhaust. If the end door sits on a fire separation between the battery and IT zones, choose a fire-rated type.
Chapter 51. Final
Thank you for reading the KITOZER cold aisle containment end door technical encyclopedia. KITOZER is committed to reliable containment and efficient cooling for data centers worldwide. Contact us at +86 13922289957 or WhatsApp +1 906-853-4140.
The KITOZER cold aisle containment end door is engineered for reliable sealing, smooth self-closing and long service life. Every component, from the aluminum frame and tempered glass to the EPDM gaskets, damped closer and door contact switch, is selected and tested to deliver consistent containment performance. We stand behind our products with documentation, technical support and long-term spare parts supply. Whether you are building a new data center or retrofitting an existing room, the KZ-CAD series provides a cost-effective, customizable end-door solution. Reach out to KITOZER today with your aisle dimensions, power density and fire requirements, and we will provide a tailored quotation and containment system design. Thank you for your interest in KITOZER.
Cold aisle containment is one of the most effective measures available to lower data center PUE, and the end door is the component that keeps the containment sealed day after day. A well-designed, well-installed and well-maintained end door ensures that chilled air reaches the servers and not the ceiling. KITOZER delivers end doors in single and double sliding configurations, spring self-closing glass versions, fire-rated doors and access-control doors, all with standard door contact monitoring and optional electronic locking. Our engineering team supports clients from initial site survey through installation, commissioning and long-term maintenance. We invite you to compare the quality of our aluminum profiles, tempered glass, EPDM sealing, damped closers and track systems, and to experience the KITOZER difference in reliability and service. Contact us for a reference quotation tailored to your project.
Contact KITOZER
Brand: KITOZER (Guangzhou Laian Intelligent System Development Co., Ltd.)
Address: Chaotian Park, Zhongrun Industrial Zone, No.5 Huashan Road, Shilou Town, Panyu District, Guangzhou, China
Phone/WeChat: +86 13922289957 / +86 18520668845
WhatsApp: +1 906-853-4140
Web: www.gdlain.com (English) / www.lain.com.cn (Chinese)
For cold aisle end door selection, containment system solutions and quotations, contact KITOZER with your cabinet row dimensions, power density and fire requirements.
Reference Prices (budget estimate only)
| Model | Configuration | Reference price per door |
|---|---|---|
| KZ-CAD-1S single sliding | 800-1200mm aisle, 6mm glass | USD 350-630 |
| KZ-CAD-2S double sliding | 1200-1800mm aisle, 8mm glass | USD 630-1120 |
| KZ-CAD-S spring glass door | Hinged self-closing, 6mm glass | USD 350-560 |
| KZ-CAD-F fire-rated | Fire glass/color steel, intumescent seals | USD 1120-1680 |
| KZ-CAD-E access-control | Double sliding + electric lock + access | USD 840-1400 |
| Containment roof | Modular tempered glass | USD 210-490 per meter |
| Fire pressure-relief vent | Thermal fuse / electromagnetic | USD 280-630 each |
Note: Reference prices for end doors and accessories, excluding freight and installation. Actual price subject to formal quotation.