This guide describes placement and fixing of KITOZER online double-conversion UPS cabinets. UPS units must be installed in a clean, cool, and ventilated room with ambient temperature between 20 and 25 C. Keep 1000 mm clearance at the front for service and 600 mm at the rear for cable entry. Check floor loading against the nameplate weight, because a loaded UPS battery cabinet can exceed 800 kg per square meter. Bolt the cabinet to the concrete floor with M12 expansion anchors, and use a spirit level to shim the unit until it is perfectly level. Never install a UPS in a location exposed to direct sunlight or moisture.
Clearances
Front 1000 mm, rear 600 mm, ambient 20 to 25 C. KITOZER 20 kVA UPS from $4,800.