KITOZER Precision AC Humidifier Cleaning FAQ

This FAQ describes cleaning of the steam humidifier cylinder in KITOZER precision air conditioners. Over months of operation, calcium and magnesium scale builds up on the heating electrodes, reducing steam output and tripping the low-humidity alarm. Every six months, technicians should drain the cylinder, flush it with descaling solution, and inspect electrode consumption. When electrodes are eroded below 60 percent of original length, replace the complete cylinder. Always use demineralized or softened water to extend cylinder life. After reassembly, run a manual humidification test for 30 minutes and verify steam generation on the sight glass.