This guide covers indoor unit positioning for KITOZER precision air conditioners. Units must be placed as close as possible to the heat load, typically along the cold aisle or in-row. Keep a minimum 1000 mm service clearance at the front and 600 mm at the rear for coil and filter access. The unit must sit on a level concrete plinth or anti-vibration frame, and any hard piping must be supported independently so that no weight transfers to the unit casing. Verify that the ceiling void and floor void allow return air and condensate drainage without restriction.
Clearances
Front 1000 mm, rear 600 mm. KITOZER 12 kW precision AC from $3,800.