This guide describes outdoor condenser fixing for KITOZER precision air conditioners. Outdoor units must be installed on a concrete curb or steel frame with anti-vibration pads, keeping the condenser at least 200 mm above roof level to avoid water pooling. Maintain 1500 mm clearance above the unit and 1000 mm on the sides for airflow, and never install two condensers facing each other without a plenum wall. Anchor bolts must be sized for local wind load. After installation, confirm the fan rotates freely and that discharge air is not re-circulated into the condenser intake.
Clearances
Above 1500 mm, sides 1000 mm. Anti vibration pads from $12 each.