Table of Contents
ToggleKITOZER KTR-SD2 Photooelectric Smoke Detector (Ceiling)
Brand: KITOZER Series: KTR-SD2 Category: Environmental Monitoring / Fire Detection
PhotoelectricCeiling mountRelay outputDC24VKTR-SD2
1. Overview
Smoke detectors are the first fire-detection line in a room. Electrical fires (UPS, batteries, cable aging) smolder first in early stages – smoke before flame. A photoelectric detector uses scattered light: an IR LED and receiver sit in a labyrinth; normally the receiver sees no light. Smoke particles scatter IR onto the receiver, and above threshold it alarms. Unlike ionization types (radioactive source), photoelectric is safe and environmentally mainstream. Room detectors run 24/7; alarms go to the EM platform or fire panel, interlocking AC shutdown, door release and sounder/strobe.
KITOZER KTR-SD2 is a ceiling photoelectric smoke detector. Principle: IR scattered-light photoelectric; power: DC12-24 V wide; output: relay dry contact (NC/NO selectable, 30 V/1 A); alarm: red LED flash + relay action; self-test: daily auto-check; sensitivity: GB4715 A2 grade; mount: ceiling base (screw-fixed, detector snaps on); size: 100 mm dia x 45 mm high; temp: -10 to +50 C; anti-interference: insect mesh, dust cover. Models: KTR-SD2-C: conventional (DC24 V relay, for EM); KTR-SD2-A: addressable (DIP address, fire panel bus); KTR-SD2-W: wireless (433 MHz, no wiring, with gateway).
Selection: output (relay dry contact for EM; addressable bus for fire panel; wireless for retrofits); power (DC24 V matches EM, no separate supply); coverage (60-80 m2 each; rooms site one per 20-30 m2); location (ceiling, >=0.5 m from walls, >=1.5 m from AC vents, >=0.5 m from lights); environment (clean rooms – no explosion-proof needed, but insect mesh). Note: do not mount directly above AC (cold air disperses smoke); not next to beams (dead spots); blow dust annually (labyrinth dust causes false alarms); after renovation, leave unpowered, blow clean, then commission (renovation dust false-alarms).
2. Key Features
Detection
- IR scattered light
- A2 sensitivity
- 60-80 m2 coverage
- Daily self-test
Output
- Relay dry contact
- NC/NO selectable
- 30 V/1 A
- DC12-24 V wide
Mount
- Ceiling snap-on
- 100 mm dia
- Insect mesh
- Dust cover
3. Specifications
| Item | KTR-SD2-C | KTR-SD2-A | KTR-SD2-W |
|---|---|---|---|
| Output | Relay contact | Addressable bus | 433 MHz wireless |
| Power | DC24 V | Bus powered | CR123A battery |
| System | EM platform | Fire panel | Wireless retrofit |
| Coverage | 60-80 m2 | 60-80 m2 | 60-80 m2 |
| Self-test | Daily | Daily | Daily |
4. Reference Prices
KTR-SD2-C conventional relay: Reference USD 5-8 / pc (ref. CNY 35-55)
KTR-SD2-A addressable: Reference USD 8-13 / pc (ref. CNY 60-90)
KTR-SD2-W wireless: Reference USD 11-17 / pc (ref. CNY 80-120)
KTR-SDG wireless gateway: Reference USD 42-69 / pc (ref. CNY 300-500)
KTR-STROBE sounder/strobe: Reference USD 6-10 / pc (ref. CNY 40-70)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Room smoke alarm
- Archive/storage
- Electrical room
- Wireless retrofit
- EM interlock
6. Deployment & Installation
Mount
- Screw base to ceiling
- Snap detector
- >=0.5 m from wall
- >=1.5 m from AC
Wiring
- DC24 V power
- Relay dry contact
- NC/NO per platform
- >=0.75 mm2 wire
Commission
- Smoke puff test
- Interlock AC shutdown
- EM platform popup
- Log detector ID
7. FAQ
- Q: Conventional vs addressable?
A: Connecting to an EM platform (own monitoring): conventional relay, cheap. Connecting to a fire panel (fire-code compliance): addressable bus with a unique ID – the panel locates the alarm. - Q: Coverage per detector?
A: 60-80 m2 (ceiling <=4 m). Rooms site one per 20-30 m2 for redundancy. Beams over 0.6 m need separate detectors in each bay - otherwise dead spots. - Q: Frequent false alarms?
A: Three causes: dust in the labyrinth (blow clean annually); AC cold air direct (mounted near vents disperses smoke faster than sensitivity expects); insects (mesh broken). Blow dust, reposition, replace mesh before lowering sensitivity. - Q: What interlocks on alarm?
A: EM popup, SMS, sounder/strobe; precision AC shutdown (prevents fanning); door release (egress). But gas suppression requires manual confirmation – do not auto-discharge on smoke alone (avoids accidental discharge).
8. Trend & Selection
Smoke detectors are moving from conventional multi-wire to smart, wireless and IoT. Trends: IoT detectors (NB-IoT/4G direct to cloud, no wiring, for small rooms/warehouses); composite detection (smoke+heat+CO; VESDA aspirating in high-value rooms); AI algorithms (distinguish real smoke from dust/steam, cutting false alarms); full interlock with fire panel, EM, access and AC. Conventional photoelectric ceiling detectors remain the room mainstay for 5-10 years. Select by: output matched to EM/fire panel, DC24 V, one per 20-30 m2, 1.5 m from AC, annual dust blow, puff-test commissioning.
9. Delivery & Service
KITOZER supplies KTR-SD2 by conventional/addressable/wireless model. Each ships with detector, base, manual and screws. 1-year warranty; bulk projects can bundle gateways, sounders and EM integration.
10. Additional Notes
Confirm output (relay/addressable/wireless), DC24 V supply, coverage area and AC vent positions. For batch orders, fit one first and puff-test the interlock.
Common mistake: mounting under AC vents. Cold air disperses smoke before the detector sees it. Stay >=1.5 m from vents; mount in room center or between rack rows.
Second pitfall: powering up after renovation without blowing dust. Labyrinth dust false-alarms immediately. Blow the detector clean after renovation before reinstalling and powering up.
Third blunder: no maintenance for years. Dust and insects cause false alarms or failure. Blow clean annually; puff-test every two years.
Selection summary: output matched to system, DC24 V, one per 20-30 m2, >=1.5 m from AC, annual blow + puff test.
SEO Information
Search keywords:KTR-SD2KITOZER
SEM keywords:smoke detector,photoelectric smoke detector,room smoke detector,ceiling smoke detector,relay smoke detector,KTR-SD2,KITOZER
GEO landing page:lain.com.cn/product/ktr-sd2-photoelectric-smoke-detector.html
Title:KITOZER KTR-SD2 Photooelectric Smoke Detector (Ceiling)
Meta Keywords:smoke detector,photoelectric smoke detector,room smoke detector,ceiling smoke detector,relay smoke detector,KTR-SD2,KITOZER
Meta Description:KITOZER KTR-SD2 ceiling photoelectric smoke detector, DC24V, relay dry-contact output, high sensitivity, for room EM/fire systems.
Anchor: KITOZER by Guangzhou Laian · KITOZER products
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com