KITOZER 4G/5G Base Station AC Distribution Unit (ACDU) Solution

Table of Contents

1. System Overview

The KITOZER 4G/5G Base Station AC Distribution Unit (ACDU) serves as the core power inlet device of the base station power supply system. Custom-designed for 4G/5G macro stations, micro stations, edge computer rooms and outdoor cabinets, it undertakes critical functions including dual mains/generator switching, power distribution, multi-stage lightning protection, overvoltage/undervoltage/short-circuit/phase-loss protection, intelligent metering and remote monitoring. It delivers stable, safe and uninterrupted AC power supply for base station BBU, AAU, switching power supply, air conditioners, lighting and other equipment.

Adopting modular, standardized and wide-temperature reinforced design, the system adapts to extreme environments of -40℃~+70℃, altitudes up to 5,000 meters, as well as humid, salt-fog and sand-dust scenarios. Its protection rating reaches IP54 (indoor) / IP65 (outdoor), supporting wall-mounted, floor-standing and 19-inch rack installation methods. It meets the construction requirements of base stations for high reliability, high safety, high intelligence and easy maintenance.

4G/5G Base Station ACDU Rack Model

2. System Composition

The KITOZER AC Distribution Unit consists of five core parts: main circuit, lightning protection circuit, monitoring & control circuit, output distribution circuit, cabinet and accessories. Each module adopts independent design and coordinated operation to ensure full-link power supply safety and controllability.

  1. Main Circuit: Equipped with isolating switches for dual mains/generator input, ATS automatic transfer switch (transfer time ≤100ms), main circuit breaker and busbar copper bar (tinned T2 red copper), realizing power access and reliable switching.
  2. Lightning Protection Circuit: Integrated with Class C (8/20μs, 40kA) + Class D (8/20μs, 20kA) multi-stage surge protection devices (SPD), complete with lightning strike counter and failure alarm, complying with GB 50689 Code for Design of Lightning Protection and Earthing Engineering of Telecommunication Bureau (Station).
  3. Monitoring & Control Circuit: Configured with intelligent electricity meter (Modbus RTU supported), voltage/current/frequency sampling module, phase-loss/overvoltage-undervoltage/leakage detection unit, audible-visual alarm and RS485 communication interface, realizing four remote functions: remote measurement, remote signaling, remote control and remote regulation.
  4. Output Distribution Circuit: Multiple independent circuit breakers (1P/3P, optional 6~63A) provide separate protection and power supply for loads such as switching power supply, air conditioner, lighting and monitoring, with reserved expansion circuits.
  5. Cabinet & Accessories: Cold-rolled steel cabinet (electrostatic plastic spraying for anti-corrosion and rust prevention), PE/N separated earthing copper bar, cable gland, cooling fan, temperature & humidity sensor, door lock and misoperation prevention mechanism.

3. System Classification

ACDU Communication Interface Side

Classified by four dimensions including installation scenario, power rating, functional configuration and phase number, covering all scenario demands of 4G/5G base stations.

3.1 Classification by Installation Scenario

  • Indoor Type (ACDU-I): Applied to base station computer rooms and integrated cabinets, 19-inch rack/wall-mounted, IP54 protection, operating temperature -10℃~+50℃.
  • Outdoor Type (ACDU-O): Used for outdoor macro stations and tower base cabinets, floor-standing/wall-mounted, IP65 protection, wide temperature range -40℃~+70℃, anti-condensation and anti-salt-fog.
  • Micro Station Type (ACDU-M): Suitable for 5G pico stations, pole-mounted stations and integrated cabinets, compact wall-mounted design, IP55 protection, power ≤30kVA.

3.2 Classification by Rated Power / Current

  • Economical Type (Low Power): 3~10kVA (10~32A), single mains input, basic lightning protection + manual switching, applicable to suburban/rural micro stations.
  • Standard Type (Medium Power): 10~30kVA (40~63A), dual mains + generator interface, automatic switching + intelligent metering + multi-stage lightning protection, for urban macro stations.
  • Enhanced Type (High Power): 30~60kVA (80~125A), dual mains + dual generator interfaces, redundant switching + precise monitoring + remote operation & maintenance, for high-density 5G base stations / edge computer rooms.

3.3 Classification by Functional Configuration

ACDU Production Workshop

  • Basic Version: Manual switching + basic lightning protection + shunt power distribution, without intelligent monitoring, for low-cost scenarios.
  • Standard Version: Automatic switching + multi-stage lightning protection + intelligent electricity meter + local alarm, Modbus communication supported, mainstream configuration.
  • Intelligent Version: Redundant automatic switching + SPD failure monitoring + remote monitoring (APP/cloud platform) + energy consumption statistics + fault early warning, adapted to smart 5G base stations.

3.4 Classification by Phase Number

  • Single-Phase Type (220V): For micro stations and small cabinets, power ≤10kVA.
  • Three-Phase Type (380V): For macro stations and high-power loads, power ≥10kVA, three-phase four-wire system for balanced power supply.

4. System Schematic Principle

The following is the standard schematic diagram of KITOZER 4G/5G Base Station ACDU (three-phase dual input + generator + intelligent monitoring), clearly showing power flow, protection logic and monitoring links.

Principle Description

  1. Input Side: Three-way input including Mains 1 (L1/L2/L3/N/PE), Mains 2 (L1/L2/L3/N/PE) and generator (emergency interface), connected to ATS automatic transfer module via isolating switch to realize seamless switching logic: Mains 1 priority → Mains 2 backup → generator emergency (≤100ms switching).
  2. Lightning Protection Side: Class C SPD (phase-to-ground) + Class D SPD (neutral-to-ground) are connected in parallel on the input busbar to rapidly discharge surge current during lightning strikes and protect downstream equipment; SPD is equipped with failure contacts to trigger alarms upon fault.
  3. Power Distribution Side: After the main circuit breaker, the busbar is divided into multiple independent output circuits (switching power supply, air conditioner, lighting, monitoring, reserved), each equipped with miniature circuit breaker (MCB) for overload/short-circuit protection.
  4. Monitoring Side: Intelligent electricity meter collects total incoming voltage, current, frequency, power and electric energy; current sampling data of each circuit is uploaded to the monitoring module; phase-loss/overvoltage-undervoltage/leakage signals are transmitted to the alarm unit for local audible-visual alarm and remote upload to cloud platform.
  5. Earthing Side: PE busbar is reliably connected to cabinet shell, SPD earthing terminal and equipment protective earth, with earthing resistance ≤4Ω; N busbar and PE busbar are strictly separated to avoid stray current.

On-site Installation & Wiring of Outdoor ACDU

5. System Configuration List (3 Tiers: Low / Medium / High, Brand: KITOZER)

5.1 Low-End Configuration List (Economical Type, 3~10kVA, Single/Three-Phase, Basic Version)

表格

No.Product NameModel SpecificationTechnical ParametersQtyUnitBrandRemarks
1Low-End AC Distribution UnitKITOZER-ACDU-L1Rated voltage: 220V/380V; Rated current:10~32A; Input: single mains; Switching: manual; Lightning protection: Class C (40kA); Protection: IP54; Mounting: wall/19-inch rack; Temp: -10℃~+50℃1SetKITOZERIndoor micro station / suburban station
2Isolating SwitchKITOZER-DS-32ARated current:32A; Poles:1P/3P; Breaking capacity:6kA; Mechanical life:≥10,000 times1PcsKITOZERMain input switch
3Main MCBKITOZER-MCB-32A/1PRated current:32A; Poles:1P; Tripping characteristic: Type C; Breaking capacity:6kA1PcsKITOZERMain circuit protection
4Branch MCBKITOZER-MCB-16A/1PRated current:16A; Poles:1P; Tripping characteristic: Type C; Breaking capacity:6kA4PcsKITOZER2×switch power supply, 1×air conditioner, 1×lighting
5Class C SPDKITOZER-SPD-C40Discharge capacity:40kA (8/20μs); Voltage protection level:≤1.5kV; Response time:≤25ns; Failure alarm: dry contact1PcsKITOZERPhase lightning protection
6SPD Circuit BreakerKITOZER-MCB-10A/1PRated current:10A; Protect SPD, cut off upon fault1PcsKITOZERFront-end protection for SPD
7Earthing Copper BarKITOZER-PE-400Material: tinned T2 red copper; Size:400×40×5mm; Bolt holes:M6×81StripKITOZERProtective earth convergence
8CabinetKITOZER-CAB-L1Material:1.2mm cold-rolled steel; Protection:IP54; Size:600×400×200mm; Color: light gray1SetKITOZERWall-mounted
9Cable GlandKITOZER-PG-16Spec:PG16; Adapted cable:6~12mm; Waterproof & dustproof4PcsKITOZERInlet/outlet cable sealing
10Terminal BlockKITOZER-TB-2.5Rated current:20A; Wiring spec:0.5~2.5mm²; Flame retardant: UL94 V020PcsKITOZERInternal wiring

5.2 Medium-End Configuration List (Standard Type, 10~30kVA, Three-Phase, Standard Version)

表格

No.Product NameModel SpecificationTechnical ParametersQtyUnitBrandRemarks
1Medium-End AC Distribution UnitKITOZER-ACDU-M1Rated voltage:380V±15%; Rated current:40~63A; Input: dual mains + generator; Switching: ATS automatic (≤100ms); Lightning protection: Class C+D; Protection:IP54; Mounting: wall/floor; Temp:-20℃~+60℃; Smart meter: Modbus RTU1SetKITOZERUrban macro station / indoor computer room
2Dual ATS Automatic Transfer SwitchKITOZER-ATS-63A/3PRated current:63A; Poles:3P+N; Transfer time:≤100ms; Mechanical interlock; Voltage range:120~290VAC; Service life:≥5,000 times1PcsKITOZERAutomatic switching for dual mains
3Generator Emergency InterfaceKITOZER-GEN-63ARated current:63A; Industrial waterproof plug; Mechanical interlock; Anti-misplug1PcsKITOZEREmergency generator access
4Main MCBKITOZER-MCB-63A/3PRated current:63A; Poles:3P+N; Tripping characteristic: Type C; Breaking capacity:10kA1PcsKITOZERMain circuit protection
53P Branch MCBKITOZER-MCB-32A/3PRated current:32A; Poles:3P; Tripping characteristic: Type C; Breaking capacity:10kA3PcsKITOZER2×switch power supply, 1×air conditioner
61P Branch MCBKITOZER-MCB-16A/1PRated current:16A; Poles:1P; Tripping characteristic: Type C; Breaking capacity:6kA4PcsKITOZER1×lighting,1×monitoring,2×reserved
7Class C SPDKITOZER-SPD-C60Discharge capacity:60kA (8/20μs); Voltage protection level:≤1.2kV; Response time:≤25ns; Failure alarm: dry contact3PcsKITOZERL1/L2/L3 phase lightning protection
8Class D SPDKITOZER-SPD-D20Discharge capacity:20kA (8/20μs); Voltage protection level:≤0.8kV; Response time:≤25ns; Failure alarm: dry contact1PcsKITOZERNeutral wire lightning protection
9Three-Phase Smart MeterKITOZER-METER-3PMeasuring items: three-phase voltage/current/frequency/power/electric energy; Accuracy:0.5S class; Interface:RS485 (Modbus RTU); LCD display; Temp:-20℃~+60℃1PcsKITOZEREnergy metering & monitoring
10Phase-Loss & Overvoltage-Undervoltage ProtectorKITOZER-PROT-3PDetection: phase loss/phase error/overvoltage (≥420V)/undervoltage (≤320V); Action time:≤3s; Output: dry contact alarm1PcsKITOZERThree-phase power anomaly protection
11Audible-Visual AlarmKITOZER-ALARM-220VOperating voltage:AC220V; Volume:≥85dB; Luminance:≥500cd; Triggered by SPD failure/phase loss/overvoltage-undervoltage1PcsKITOZERLocal fault alarm
12SPD Circuit BreakerKITOZER-MCB-16A/1PRated current:16A; Protect SPD, cut off upon fault4PcsKITOZERFront-end protection for SPD
13Earthing Copper BarKITOZER-PE-600Material: tinned T2 red copper; Size:600×40×5mm; Bolt holes:M8×121StripKITOZERProtective earth convergence
14Neutral Copper BarKITOZER-N-600Material: tinned T2 red copper; Size:600×40×5mm; Bolt holes:M8×121StripKITOZERNeutral wire convergence
15CabinetKITOZER-CAB-M1Material:1.5mm cold-rolled steel; Protection:IP54; Size:800×600×250mm; Color: light gray; 2 cooling fans1SetKITOZERWall/floor-mounted
16Cooling FanKITOZER-FAN-220VOperating voltage:AC220V; Air volume:120m³/h; Noise:≤45dB; Temperature-controlled startup:≥40℃2PcsKITOZERCabinet heat dissipation
17Cable GlandKITOZER-PG-21Spec:PG21; Adapted cable:10~16mm; Waterproof & dustproof6PcsKITOZERInlet/outlet cable sealing
18Terminal BlockKITOZER-TB-4.0Rated current:32A; Wiring spec:1.0~4.0mm²; Flame retardant: UL94 V030PcsKITOZERInternal wiring

5.3 High-End Configuration List (Enhanced Type, 30~60kVA, Three-Phase, Intelligent Version)

表格

No.Product NameModel SpecificationTechnical ParametersQtyUnitBrandRemarks
1High-End AC Distribution UnitKITOZER-ACDU-H1Rated voltage:380V±20%; Rated current:80~125A; Input: dual mains + dual generator interfaces; Switching: redundant ATS automatic (≤80ms); Lightning protection: Class C+D + SPD failure monitoring; Protection:IP65; Mounting: floor; Temp:-40℃~+70℃; Intelligent monitoring: cloud platform + APP; Energy statistics + fault early warning1SetKITOZERHigh-density 5G base station / edge computer room / outdoor macro station
2Redundant Dual ATS Transfer SwitchKITOZER-ATS-125A/3PRated current:125A; Poles:3P+N; Transfer time:≤80ms; Dual-coil redundancy; Mechanical + electronic interlock; Voltage range:100~300VAC; Service life:≥10,000 times; Communication interface equipped1PcsKITOZERRedundant switching for dual mains
3Dual Generator Emergency InterfaceKITOZER-GEN-125ARated current:125A; 2×industrial waterproof plugs; Mechanical interlock; Anti-misplug with status monitoring2PcsKITOZERDual generator redundant access
4Molded Case Main Circuit BreakerKITOZER-MCCB-125A/3PRated current:125A; Poles:3P+N; Tripping characteristic: Type C; Breaking capacity:25kA; Thermal-magnetic protection1PcsKITOZERMain circuit protection
53P Branch MCBKITOZER-MCB-63A/3PRated current:63A; Poles:3P; Tripping characteristic: Type C; Breaking capacity:10kA4PcsKITOZER3×switch power supply,1×air conditioner
61P Branch MCBKITOZER-MCB-32A/1PRated current:32A; Poles:1P; Tripping characteristic: Type C; Breaking capacity:10kA6PcsKITOZER2×lighting,2×monitoring,2×reserved
7Class C SPDKITOZER-SPD-C80Discharge capacity:80kA (8/20μs); Voltage protection level:≤1.0kV; Response time:≤20ns; Failure alarm: dry contact + RS485; Lightning counter3PcsKITOZERL1/L2/L3 phase lightning protection
8Class D SPDKITOZER-SPD-D40Discharge capacity:40kA (8/20μs); Voltage protection level:≤0.6kV; Response time:≤20ns; Failure alarm: dry contact + RS485; Lightning counter1PcsKITOZERNeutral wire lightning protection
9SPD Monitoring ModuleKITOZER-SPD-MONMonitoring items: SPD failure, leakage current, lightning strike count; Interface:RS485; Accuracy:±5%; Temp:-40℃~+70℃1PcsKITOZERIntelligent monitoring for lightning protection system
10Multifunctional Smart MeterKITOZER-METER-3P-HMeasuring items: three-phase voltage/current/frequency/power/electric energy/harmonics/power factor; Accuracy:0.2S class; Interface:RS485 + Ethernet; Touch LCD screen; Temp:-40℃~+70℃; Cloud upload supported1PcsKITOZERHigh-precision energy metering & monitoring
11Integrated Power ProtectorKITOZER-PROT-3P-HDetection: phase loss/phase error/overvoltage/undervoltage/leakage/three-phase unbalance; Action time:≤1s; Output: dry contact + RS485 alarm with fault recording1PcsKITOZERFull-range power anomaly protection
12Intelligent Supervisory Control UnitKITOZER-SCU-ACFunctions: data collection, alarm processing, remote control, energy statistics, fault early warning; Interface:RS485 + Ethernet + 4G; Protocol: Modbus/TCP; APP/cloud platform compatible; Temp:-40℃~+70℃1PcsKITOZERCore unit for system intelligent monitoring
13Intelligent Audible-Visual AlarmKITOZER-ALARM-H-220VOperating voltage:AC220V; Volume:≥90dB; Luminance:≥800cd; Graded fault alarm, remote alarm silencing supported1PcsKITOZERLocal intelligent alarm
14SPD Circuit BreakerKITOZER-MCB-20A/1PRated current:20A; Protect SPD, cut off upon fault4PcsKITOZERFront-end protection for SPD
15Earthing Copper BarKITOZER-PE-800Material: tinned T2 red copper; Size:800×50×6mm; Bolt holes:M10×151StripKITOZERProtective earth convergence
16Neutral Copper BarKITOZER-N-800Material: tinned T2 red copper; Size:800×50×6mm; Bolt holes:M10×151StripKITOZERNeutral wire convergence
17Outdoor CabinetKITOZER-CAB-H1Material:2.0mm 304 stainless steel; Protection:IP65; Size:1000×800×350mm; Color: industrial gray; 4 cooling fans; Temperature & humidity control; Anti-condensation heating1SetKITOZERFloor-standing outdoor cabinet
18Industrial Cooling FanKITOZER-FAN-H-220VOperating voltage:AC220V; Air volume:180m³/h; Noise:≤40dB; Temperature-controlled speed regulation; IP55 protection4PcsKITOZERHigh-efficiency cabinet heat dissipation
19Temperature & Humidity SensorKITOZER-TH-SENMeasuring range: temp -40℃~+70℃, humidity 0~100% RH; Accuracy: temp ±0.5℃, humidity ±3% RH; Interface:RS485; Waterproof & dustproof1PcsKITOZERCabinet environmental monitoring
20Cable GlandKITOZER-PG-29Spec:PG29; Adapted cable:16~22mm; Waterproof, dustproof & anti-corrosion8PcsKITOZERInlet/outlet cable sealing
21Terminal BlockKITOZER-TB-6.0Rated current:40A; Wiring spec:1.5~6.0mm²; Flame retardant: UL94 V0; Anti-corrosion40PcsKITOZERInternal wiring

6. Full Product Technical Specifications

Internal Wiring Layout of ACDU

6.1 KITOZER-ACDU-L1 (Low-End AC Distribution Unit)

  • Rated operating voltage: 220V (single-phase) / 380V (three-phase) ±15%
  • Rated frequency: 50Hz±2Hz
  • Rated input current: optional 10A/16A/32A
  • Input mode: single mains supply
  • Switching mode: manual isolating switch
  • Lightning protection: Class C SPD (40kA, 8/20μs)
  • Branch configuration: 1P/3P main breaker + 4 independent 1P output circuits
  • Protection rating: IP54 (indoor)
  • Operating temperature: -10℃~+50℃
  • Relative humidity: ≤95% (non-condensing)
  • Insulation resistance: ≥2MΩ (DC1000V)
  • Earthing resistance: ≤4Ω

6.2 KITOZER-ACDU-M1 (Medium-End AC Distribution Unit)

Medium-End ACDU Installed in Tower Cabinet

  • Rated operating voltage: 380V±15% (three-phase four-wire)
  • Rated frequency: 50Hz±2Hz
  • Rated input current: optional 40A/63A
  • Input mode: dual mains + 1 generator emergency interface
  • Switching mode: ATS automatic transfer (transfer time ≤100ms), mechanical interlock
  • Lightning protection: Class C (60kA) + Class D (20kA) multi-stage SPD with failure alarm
  • Branch configuration: 3P+N main breaker + 7 output circuits (3×3P + 4×1P)
  • Monitoring functions: 0.5S class smart meter (Modbus RTU), phase-loss/overvoltage-undervoltage protection, local audible-visual alarm
  • Protection rating: IP54 (indoor/outdoor general)
  • Operating temperature: -20℃~+60℃
  • Relative humidity: ≤95% (non-condensing)
  • Insulation resistance: ≥2MΩ (DC1000V)
  • Earthing resistance: ≤4Ω
  • Communication interface: RS485 (Modbus RTU)

6.3 KITOZER-ACDU-H1 (High-End AC Distribution Unit)

Remote Cloud Monitoring Platform

  • Rated operating voltage: 380V±20% (three-phase four-wire)
  • Rated frequency: 50Hz±2Hz
  • Rated input current: optional 80A/100A/125A
  • Input mode: dual mains + 2 redundant generator interfaces
  • Switching mode: redundant ATS automatic transfer (transfer time ≤80ms), mechanical + electronic dual interlock
  • Lightning protection: Class C (80kA) + Class D (40kA) + SPD failure monitoring + lightning strike counter
  • Branch configuration: 3P+N molded case main breaker + 10 output circuits (4×3P + 6×1P)
  • Monitoring functions: 0.2S class multifunctional smart meter (harmonic monitoring), integrated power protection (phase loss/phase error/overvoltage/undervoltage/leakage/unbalance), intelligent supervisory control unit (4G/Ethernet, cloud platform + APP), graded fault alarm & recording
  • Protection rating: IP65 (outdoor exclusive, anti-salt-fog & anti-condensation)
  • Operating temperature: -40℃~+70℃ wide temperature range
  • Relative humidity: ≤95% (non-condensing)
  • Insulation resistance: ≥5MΩ (DC1000V)
  • Earthing resistance: ≤4Ω
  • Communication interface: RS485 + Ethernet + 4G (Modbus/TCP)
  • Altitude adaptation: 0~5,000m, no capacity derating at high altitude

6.4 General Technical Specifications of Core Supporting Products

Internal Complete Wiring of Standard ACDU

  1. ATS Automatic Transfer Switch: Mechanical life ≥5,000 times (medium-end) / ≥10,000 times (high-end); transfer time ≤100ms (medium-end) / ≤80ms (high-end); breaking capacity ≥10kA
  2. SPD Surge Protection Device: Response time ≤25ns (low/medium-end) / ≤20ns (high-end); voltage protection level ≤1.5kV (Class C low-end) / ≤1.2kV (Class C medium-end) / ≤1.0kV (Class C high-end)
  3. Smart Electricity Meter: Accuracy 0.5S class (medium-end) / 0.2S class (high-end); measuring precision ±0.5% (medium-end) / ±0.2% (high-end); Modbus RTU supported (medium-end) / Modbus TCP supported (high-end)
  4. Cabinet: Material: cold-rolled steel (low/medium-end, 1.2~1.5mm) / 304 stainless steel (high-end, 2.0mm); protection IP54 (low/medium-end) / IP65 (high-end); anti-corrosion grade C3 (low/medium-end) / C5-M (high-end, salt-fog environment)

7. Full Product Application Scope

The full range of KITOZER 4G/5G Base Station ACDU covers five core sectors: communications, electric power, energy, transportation and industry, adapting to strict power supply demands of multiple scenarios.

7.1 Communication Base Station Scenarios (Core Application)

  • 4G Macro Station: Urban/suburban standard base stations, medium-end ACDU-M1 as mainstream, providing stable three-phase power supply
  • 5G Macro Station: High-density AAU/BBU base stations, high-end ACDU-H1 preferred, wide temperature & intelligent monitoring adapting to high power consumption of 5G
  • 5G Micro/Pico Station: Pole-mounted/wall-mounted stations & integrated cabinets, low-end ACDU-L1 with compact size and low cost
  • Base Station Edge Computer Room: Centralized BBU deployment computer rooms, high-end ACDU-H1 with redundant power supply & precise monitoring to guarantee stable core equipment operation
  • Outdoor Base Station / Tower Cabinet: Mountain, desert and coastal outdoor scenarios, high-end IP65 ACDU-H1 with anti-salt-fog, anti-condensation and wide temperature design

7.2 Electric Power & Energy Scenarios

Internal Layout of Industrial ACDU

  • PV/Wind Power Base Station: New energy supporting base stations, medium/high-end ACDU adapting to voltage fluctuation of PV inverters and lightning-prone wild environments
  • Substation Communication Computer Room: Power system communication equipment power supply, medium-end ACDU-M1 with dual mains transfer and high insulation design resisting strong electromagnetic interference of power systems

7.3 Transportation Scenarios

  • High-Speed Rail / Tunnel Base Station: Communication base stations along high-speed railways and inside tunnels, medium/high-end ACDU with seismic design adapting to large temperature difference and high humidity in tunnels
  • Expressway Base Station: Roadside 5G base stations, high-end IP65 ACDU-H1 with anti-dust & anti-salt-fog features for long-term unattended outdoor operation

7.4 Industrial Scenarios

  • Industry 4.0 Base Station: Factory 5G industrial base stations, medium-end ACDU-M1 with anti-electromagnetic interference and separate circuit protection adapting to diversified industrial loads
  • Mine / Oilfield Base Station: Remote communication base stations in mines and oilfields, high-end ACDU-H1 with wide temperature, high protection grade and remote monitoring for unattended extreme environments

7.5 Other Scenarios

  • Smart City Surveillance Base Station: Urban security & smart light pole supporting base stations, low/medium-end ACDU with compact size and low cost for distributed deployment
  • Emergency Communication Vehicle: Power distribution matching emergency communication vehicles, medium-end ACDU-M1 with vehicle-mounted seismic design and quick interface for emergency scenarios

8. Core Advantages of Full Product Line

KITOZER full-series 4G/5G Base Station ACDU features six core strengths: high reliability, high safety, high intelligence, easy maintenance, flexible customization and factory after-sales guarantee, covering all dimensions of function, technology and service.

8.1 Functional Advantages (All Series)

  1. High-Reliability Power Supply: Three-tier power supply architecture (dual mains + generator), ATS automatic transfer within 100ms to realize millisecond-level uninterrupted power supply and avoid base station service interruption
  2. Multi-Stage Lightning Protection: Class C + Class D multi-stage SPD with maximum discharge capacity up to 80kA, SPD failure alarm & lightning strike counter to completely solve base station damage caused by lightning strikes
  3. Full-Link Protection: Seven-fold protection against overcurrent, short circuit, phase loss, phase error, overvoltage, undervoltage, leakage and three-phase unbalance; faults isolated automatically to protect downstream equipment
  4. Wide Temperature Environment Adaptation: -40℃~+70℃ wide temperature design, no capacity derating at altitude up to 5,000 meters, suitable for deserts, coastal areas, mountainous regions and other extreme environments
  5. Flexible Circuit Configuration: Up to 10 independent output circuits adapting to multi-load power supply of switching power supply, air conditioner, lighting and monitoring; reserved expansion circuits for future capacity expansion

8.2 Technical Parameter Advantages (All Series)

  1. Domestic Core Devices: Self-developed power management chip + high-quality domestic circuit breakers/contactors/SPD, 95% localization rate, 35% cost reduction and 50% shorter delivery cycle
  2. High Insulation & Anti-Corrosion: Insulation resistance ≥2MΩ (low-end) / ≥5MΩ (high-end); cabinet anti-corrosion grade C3 (low/medium-end) / C5-M (high-end), adapting to high humidity and salt-fog environments
  3. High-Precision Monitoring: Smart meter accuracy up to 0.2S class (high-end), voltage/current measuring precision ±0.2% with harmonic monitoring to accurately track energy consumption data
  4. Long Service Life Design: ATS mechanical life ≥5,000 times (medium-end) / ≥10,000 times (high-end); auxiliary contact life of contactor ≥10⁶ times; all series devices guaranteed for at least 1 year

8.3 Customization Capability

  1. Customizable configurations: Support customization of input voltage (220V/380V), rated current (10~125A), circuit quantity and communication interface (RS485/Ethernet/4G) to meet different base station load demands
  2. Structural customization: Wall-mounted, floor-standing and 19-inch rack mounting available; customizable cabinet size, color and protection grade (IP54/IP65); outdoor cabinets support integrated anti-condensation heating and heat dissipation design
  3. Functional customization: Customizable energy consumption statistics, fault early warning, remote control and APP/cloud platform docking; compatible with existing operator monitoring systems (Huawei FSU, ZTE OMC, etc.)
  4. OEM/ODM Service: Support OEM & ODM processing, providing complete technical drawings, production standards and testing solutions with brand protection for clients

8.4 Confidentiality & Stock Delivery Guarantee

  1. Strict non-disclosure agreement: Sign NDA to strictly protect client customized schemes, technical parameters and project information; self-developed core technology with zero risk of technical leakage
  2. Fast delivery with sufficient stock: Standard products in stock all year round; delivery cycle ≤3 days for low/medium-end products, ≤7 days for high-end products, ≤15 days for customized products to support rapid base station deployment
  3. Global supply chain: Global high-quality supply chain for core components, bulk procurement to cut costs while ensuring stable supply and avoiding project delays due to stock shortage

8.5 Service Advantages

  1. Full life-cycle service: One-stop solution covering scheme design, product selection, installation & commissioning, operation & maintenance training and emergency troubleshooting to solve all base station power distribution problems
  2. 7×24-hour technical support: Professional technical team on standby 24/7, providing remote guidance via phone/WeChat for fault diagnosis; on-site service within 4 hours for domestic emergency faults
  3. Free technical training: Free training for client operation & maintenance staff covering product principles, operation procedures, fault handling and daily maintenance to enable independent client operation
  4. On-time after-sales response & full lifecycle maintenance support

9. Bid Winning Control Parameters for Full Product Line (* Marked as Key Bid Control Items)

9.1 General Bid Control Parameters (Applicable to All Series)

  1. Brand: KITOZER (genuine factory product, authorization certificate provided)
  2. Rated operating voltage: 220V/380V±15% (low/medium-end) / 380V±20% (high-end)
  3. Rated frequency: 50Hz±2Hz
  4. Lightning protection: Built-in multi-stage SPD (Class C ≥40kA + Class D ≥20kA) with failure alarm function
  5. Protection grade: IP54 (indoor type) / IP65 (outdoor type)
  6. Operating temperature: -10℃~+50℃ (low-end) / -20℃~+60℃ (medium-end) / -40℃~+70℃ (high-end)
  7. Insulation resistance: ≥2MΩ (DC1000V)
  8. Earthing resistance: ≤4Ω
  9. Communication interface: RS485 (Modbus RTU) supported; high-end model additionally supports Ethernet + 4G
  10. Warranty period: ≥1 year for all series, ≥2 years for core components

9.2 Bid Control Parameters for Low-End Model (KITOZER-ACDU-L1)

  1. Rated input current: optional 10A/16A/32A
  2. Input mode: single mains supply
  3. Switching mode: manual isolating switch
  4. Circuit configuration: ≥4 independent output circuits
  5. Cabinet material: cold-rolled steel ≥1.2mm with electrostatic plastic spraying anti-corrosion treatment

9.3 Bid Control Parameters for Medium-End Model (KITOZER-ACDU-M1)

  1. Rated input current: optional 40A/63A
  2. Input mode: dual mains + 1 generator emergency interface
  3. Switching mode: ATS automatic transfer with transfer time ≤100ms and mechanical interlock
  4. Smart electricity meter: accuracy ≥0.5S class, supporting three-phase voltage/current/energy metering
  5. Protection functions: phase-loss/overvoltage-undervoltage/short-circuit/overload protection with automatic fault alarm
  6. Cabinet material: cold-rolled steel ≥1.5mm with electrostatic plastic spraying anti-corrosion, equipped with cooling fans

9.4 Bid Control Parameters for High-End Model (KITOZER-ACDU-H1)

  1. Rated input current: optional 80A/100A/125A
  2. Input mode: dual mains + 2 redundant generator interfaces
  3. Switching mode: redundant ATS automatic transfer with transfer time ≤80ms and mechanical + electronic dual interlock
  4. Smart electricity meter: accuracy ≥0.2S class, supporting harmonic and three-phase unbalance monitoring
  5. Protection functions: seven-fold protection against phase loss/phase error/overvoltage/undervoltage/leakage/short-circuit/overload/three-phase unbalance
  6. SPD monitoring: built-in SPD failure monitoring module supporting leakage current detection and lightning strike count statistics
  7. Monitoring functions: built-in intelligent supervisory control unit supporting 4G/Ethernet communication, cloud platform + APP remote operation & maintenance
  8. Cabinet material: ≥2.0mm 304 stainless steel, IP65 protection grade, anti-salt-fog & anti-condensation for wide temperature adaptation
  9. Altitude adaptation: stable operation without capacity derating at altitude 0~5,000m

10. Complete Product Solutions

10.1 4G/5G Macro Station AC Power Distribution Solution (Mainly Medium-End, Optional High-End)

  • Solution Architecture: Dual mains (main/backup) → ATS automatic transfer → Class C + D lightning protection → main circuit breaker → multi-circuit separate protection (2×switch power supply, 1×air conditioner, 1×lighting, 1×monitoring, 2×reserved) → load equipment
  • Core Equipment: KITOZER-ACDU-M1 (medium-end), built-in 63A ATS, C60+D20 SPD, 0.5S class smart meter, phase-loss & overvoltage-undervoltage protector
  • Solution Advantages: Seamless transfer between dual mains to avoid base station service interruption caused by single mains failure; multi-stage lightning protection adapting to urban lightning-prone environments; intelligent metering for real-time energy consumption monitoring to reduce operating costs; wall-mounted design saving computer room space
  • Applicable Scenarios: Urban/suburban 4G/5G macro stations with load power 10~30kVA, operating temperature -20℃~+60℃

10.2 5G Micro/Pico Station AC Power Distribution Solution (Low-End Model)

  • Solution Architecture: Single mains → manual isolating switch → Class C lightning protection → main circuit breaker → 4-circuit separate protection (2×switch power supply, 1×air conditioner, 1×lighting) → load equipment
  • Core Equipment: KITOZER-ACDU-L1 (low-end), built-in 32A isolating switch, C40 SPD, basic power distribution circuits
  • Solution Advantages: Compact size (600×400×200mm) adapting to narrow space of pole/wall-mounted stations; low-cost deployment meeting basic power supply demands of micro stations; IP54 protection for simple outdoor environments
  • Applicable Scenarios: 5G pico stations, pole-mounted stations and integrated cabinets with load power 3~10kVA, operating temperature -10℃~+50℃

10.3 Outdoor 5G Macro Station / Mountain Base Station AC Power Distribution Solution (High-End Model)

  • Solution Architecture: Dual mains (main/backup) + dual redundant generators → redundant ATS automatic transfer → Class C + D lightning protection + SPD monitoring → molded case main circuit breaker → 10-circuit separate protection → load equipment; supporting temperature & humidity monitoring, anti-condensation heating, intelligent heat dissipation and 4G remote monitoring
  • Core Equipment: KITOZER-ACDU-H1 (high-end), built-in 125A redundant ATS, C80+D40 SPD + SPD monitoring, 0.2S class multifunctional meter, integrated power protector, intelligent supervisory control unit
  • Solution Advantages: Redundant power supply architecture with dual mains + dual generators to completely eliminate power supply interruption; -40℃~+70℃ wide temperature adapting to extreme temperature in mountains/deserts; IP65 anti-salt-fog & anti-condensation protection for coastal/high-humidity environments; 4G remote monitoring realizing unattended operation with real-time status tracking & fault early warning
  • Applicable Scenarios: Outdoor 5G macro stations in mountains, deserts and coastal areas with load power 30~60kVA, operating temperature -40℃~+70℃, altitude 0~5,000m

10.4 Base Station Edge Computer Room AC Power Distribution Solution (High-End Model)

  • Solution Architecture: Dual mains (main/backup) → redundant ATS automatic transfer → Class C + D lightning protection → molded case main circuit breaker → multi-circuit separate protection (multiple BBU, 2×air conditioner, 2×lighting, 2×monitoring, 2×reserved) → load equipment; supporting precise energy consumption monitoring, harmonic control and remote operation & maintenance platform
  • Core Equipment: KITOZER-ACDU-H1 (high-end), built-in 125A redundant ATS, C80+D40 SPD, 0.2S class multifunctional meter (harmonic monitoring), Ethernet-connected intelligent supervisory control unit
  • Solution Advantages: High-power redundant power supply meeting high power consumption demand of centralized BBU deployment; harmonic monitoring & control to guarantee power supply quality of computer room equipment; remote operation & maintenance platform for centralized management of power distribution equipment across multiple computer rooms to cut operation costs
  • Applicable Scenarios: 5G BBU edge computer rooms and small data centers with load power 30~60kVA requiring 24/7 uninterrupted power supply

11. Product Application Cases

11.1 China Mobile 5G Macro Station Power Distribution Project (2024-2025)

  • Project Location: 1,200 urban 5G macro stations in Guangdong, Zhejiang and Jiangsu provinces
  • Project Demand: Dual mains power supply, lightning protection, intelligent metering, wall-mounted installation adapting to high power consumption of 5G AAU
  • Selected Product: KITOZER-ACDU-M1 (medium-end, 63A three-phase)
  • Project Outcome: Post-deployment base station power supply reliability reached 99.999%, zero lightning strike damage accidents; intelligent metering realized accurate energy consumption statistics with average monthly power saving of 150 kWh per station; remote monitoring reduced on-site maintenance frequency by 60% and cut operating costs by 35%
  • Client Comment: KITOZER products feature strong stability and excellent lightning protection performance with convenient intelligent monitoring, fully meeting high-reliability power supply demands of 5G base stations for long-term cooperation

11.2 China Telecom Mountain Outdoor 5G Macro Station Power Distribution Project (2023-2024)

  • Project Location: 350 outdoor 5G macro stations in mountainous Yunnan and Guizhou provinces
  • Project Demand: Wide temperature range (-40℃~+70℃), IP65 protection, anti-condensation, dual mains + generator redundancy, 4G remote monitoring adapting to extreme mountain environments
  • Selected Product: KITOZER-ACDU-H1 (high-end, 100A three-phase)
  • Project Outcome: Products operated stably under -35℃ low temperature, +65℃ high temperature and 95% high humidity without shutdown faults; IP65 protection effectively resisted rainwater, dust and salt-fog erosion; 4G remote monitoring realized unattended operation with fault response time shortened to within 1 hour and maintenance efficiency improved by 80%
  • Client Comment: KITOZER high-end model perfectly adapts to extreme mountain environments, solving maintenance difficulties of outdoor base stations with wide temperature, high protection and remote monitoring functions, making it the preferred power distribution equipment for mountain 5G base stations

11.3 China Unicom 5G Micro Station Power Distribution Project (2024)

  • Project Location: 800 smart city 5G micro stations in Beijing and Shanghai
  • Project Demand: Compact size, low cost, wall-mounted installation, basic lightning protection adapting to narrow space of smart light poles and wall surfaces
  • Selected Product: KITOZER-ACDU-L1 (low-end, 32A single-phase)
  • Project Outcome: Compact products enable rapid installation matching smart light pole deployment; basic lightning protection effectively avoids urban lightning strike damage; low-cost deployment meets mass construction demands of micro stations with project delivery cycle shortened by 50%
  • Client Comment: KITOZER low-end model delivers high cost performance, easy installation and stable performance, perfectly matching low-cost and rapid deployment demands of 5G micro stations

11.4 Provincial Tower Company Base Station Edge Computer Room Power Distribution Project (2023)

  • Project Location: Base station edge computer rooms covering 12 prefecture-level cities in one province
  • Project Demand: High-power redundant power supply, precise energy consumption monitoring, harmonic control, centralized remote operation & maintenance to meet high-reliability power supply demands of centralized BBU deployment
  • Selected Product: KITOZER-ACDU-H1 (high-end, 125A three-phase)
  • Project Outcome: Redundant power supply architecture achieved zero power supply interruption to guarantee 24/7 stable operation of BBU equipment; 0.2S high-precision meter accurately tracked energy consumption and harmonics to provide data support for computer room energy-saving transformation; remote operation & maintenance platform centralized management of 12 computer rooms reducing maintenance staff by 70% and greatly improving management efficiency
  • Client Comment: KITOZER high-end model features powerful functions, stable performance and convenient operation & maintenance, providing highly reliable and intelligent power distribution solutions for base station edge computer rooms

12. Common Product Faults & Maintenance Specifications

12.1 Common Faults & Troubleshooting

表格

Fault PhenomenonPossible CausesSolutions
Phase-loss alarm1. Three-phase input phase loss; 2. Rectifier module failure; 3. Blown AC input fuse1. Inspect three-phase mains voltage and repair broken lines; 2. Troubleshoot and replace faulty rectifier module; 3. Replace fuse with matching specification
MCB tripping (main/branch)1. Short circuit of load or cable; 2. Mismatched MCB capacity; 3. Overloaded load1. Disconnect loads immediately, locate and repair short-circuit point; 2. Replace MCB with matched capacity; 3. Reduce loads to avoid overload operation
SPD failure alarm1. Aging & damaged SPD; 2. Excessive SPD leakage current; 3. Tripped SPD circuit breaker1. Replace with same-spec Class C/D SPD; 2. Inspect SPD earthing connection and fasten terminals; 3. Close SPD circuit breaker and investigate tripping cause
Overvoltage/undervoltage alarm1. Mains voltage fluctuation beyond rated range; 2. Faulty voltage sampling module; 3. Unbalanced three-phase voltage1. Alarm clears automatically after mains voltage recovers to normal range; 2. Replace voltage sampling module; 3. Adjust three-phase loads to balance voltage
ATS transfer failure1. Faulty ATS control power supply; 2. Stuck mechanical interlock; 3. Abnormal input voltage1. Inspect ATS 220V control power supply and repair supply lines; 2. Power off, clean mechanical interlock components and apply lubricant; 3. Troubleshoot abnormal input voltage and restore normal power supply
Remote communication interruption1. Disconnected communication line (RS485/Ethernet); 2. Faulty monitoring module; 3. Weak 4G signal1. Inspect communication line connection, fasten terminals or replace network cable; 2. Restart or replace monitoring module; 3. Adjust 4G antenna position to enhance signal strength

12.2 Daily Maintenance Specifications

12.2.1 Daily Inspection (Remote, Intelligent Version Only)

  • Check system operating status via cloud platform/APP: voltage, current, frequency, temperature, humidity and alarm information, confirm no abnormal alarms
  • Monitor load current of each circuit to avoid overload operation; track SPD leakage current data for early warning of SPD aging

12.2.2 Weekly On-Site Inspection (All Series)

  1. Visual Inspection: Check cabinet shell for deformation, corrosion and damage; intact door lock and non-aging sealing strip; no damage, aging or loosening of inlet/outlet cables
  2. Indicator Light Inspection: Check indicator status of ATS, SPD, electricity meter and monitoring module; steady green light for normal operation, flashing red light for alarm
  3. Terminal Inspection: Power off and fasten all wiring terminals (copper bar, MCB, SPD, electricity meter) to avoid heating caused by loose connections; inspect terminals for oxidation and ablation marks
  4. Heat Dissipation Inspection: Clean dust screen of cooling fan (low/medium-end); check fan operation for abnormal noise; inspect heating & heat dissipation modules of high-end outdoor cabinets

12.2.3 Monthly Maintenance (On-Site, All Series)

  1. Insulation Test: Measure system insulation resistance with megohmmeter after power off (≥2MΩ); locate and repair cable insulation damage if index fails to meet standard
  2. Earthing Test: Measure cabinet earthing resistance (≤4Ω); re-lay earthing electrode and fasten terminals for poor earthing
  3. SPD Inspection: Check SPD shell for damage and ablation, record lightning strike counter readings; replace SPD immediately upon failure
  4. MCB & Contactor Inspection: Switch MCB on/off 3~5 times to ensure smooth operation without jamming or abnormal noise; inspect contactor contacts for ablation and reliable action

12.2.4 Quarterly Maintenance (On-Site, Medium & High-End Models)

  1. Smart Meter Calibration: Calibrate on-board smart meter with standard meter to guarantee metering accuracy (error ≤±0.5%)
  2. Monitoring Module Test: Verify remote communication, alarm upload and remote control functions; upgrade monitoring module firmware to latest version
  3. Lightning Protection System Test: Test SPD discharge capacity and voltage protection level with lightning protection tester; replace SPD if parameters fail to meet standards

12.2.5 Annual Maintenance (On-Site, All Series)

  1. Complete Disassembly Inspection: Disassemble cabinet to clean internal dust and debris; inspect copper bar for oxidation and deformation, insulating parts for aging and damage
  2. Core Component Replacement: Replace severely aged SPD, contactors and fans; inspect ATS mechanical parts and replace worn accessories
  3. Full System Function Test: Simulate mains interruption, phase loss, overvoltage/undervoltage and lightning strikes to test normal transfer, protection and alarm functions
  4. Maintenance Record Filing: Sort and archive full-year inspection, maintenance and fault handling records; formulate maintenance plan for the next year

13. Factory Strength & After-Sales Service

13.1 Factory Strength

  1. Production Base: KITOZER owns two production bases in Guangzhou, Guangdong and Wenzhou, Zhejiang, covering total area of 20,000㎡ with 12 standardized workshops and 8 fully automatic production lines, annual output reaching 100,000 sets of AC distribution units
  2. R&D Team: Over 50 core R&D personnel including 5 PhD holders and 20 master’s degree holders, focusing on communication power supply and power distribution equipment R&D, holding over 30 invention patents and 50 utility model patents with 95% self-developed domestic power management chip localization rate
  3. Production Technology: Adopt fully automatic sheet metal processing, electrostatic plastic spraying, SMT chip mounting and wave soldering processes; core components sourced from top domestic & international brands (Schneider, Chint, Delixi, domestic chip manufacturers); every unit undergoes 72-hour aging test and 100% function test before delivery under ISO9001 quality management system certification to guarantee stable product quality
  4. Supply Chain Guarantee: Global high-quality supply chain system with bulk procurement of core components and sufficient inventory; standard products delivered within 3 days, customized products within 15 days to support rapid base station deployment
  5. Qualification Certifications: Products pass MIIT Network Access Certification, CE, RoHS, ISO9001 Quality System Certification, ISO14001 Environmental System Certification, complying with communication industry standard YD/T 2164-2010 AC Distribution Units for Telecommunications Equipment

13.2 After-Sales Service

  1. Warranty Commitment: All series guaranteed for 1 year, core components (ATS, SPD, smart meter) guaranteed for 2 years; free repair, component replacement or whole machine replacement for non-human quality defects within warranty period
  2. 7×24-Hour Technical Support: Professional technical team on standby 24/7 providing remote technical support via phone, WeChat and email for consultation and fault diagnosis
  3. Rapid On-Site Service: 30 domestic service outlets covering all provinces and cities nationwide; emergency on-site service within 4 hours (first-tier cities), 8 hours (second-tier cities) and 24 hours (remote areas) to resolve on-site faults timely
  4. Free Technical Training: Free training for client operation & maintenance staff covering product principles, operation procedures, fault handling and daily maintenance via online live broadcast or on-site offline training to build independent client operation capacity
  5. Lifelong Maintenance Service: Lifelong maintenance available after warranty expiration, only charging component cost fees; regular client follow-up to track product operating status and provide maintenance suggestions for extended service life
  6. Customized Service: Provide customized scheme design, product selection, installation & commissioning and operation & maintenance hosting services according to project demands for one-stop power distribution solutions

14. Conclusion

The full range of KITOZER 4G/5G Base Station AC Distribution Units features core strengths of high reliability, high safety, high intelligence, easy maintenance and flexible customization, deeply adapting to strict power supply demands of all 4G/5G base station scenarios. It delivers comprehensive customized AC power distribution solutions covering suburban micro stations, urban macro stations, indoor computer rooms and extreme outdoor environments.

Adopting self-developed core technology and global high-quality supply chain with full-process quality control, every unit maintains stable and reliable performance. The comprehensive after-sales service system with 7×24-hour technical support and rapid on-site service safeguards long-term stable operation of base stations.

In the future, KITOZER will continue deepening the communication power distribution sector, increase R&D investment, continuously optimize product performance and intelligence level, launch more innovative products adapting to 5G-A and 6G eras, boost high-quality development of the communication industry and provide more superior and reliable power distribution guarantee for global 4G/5G base station construction.

15. Search Keywords, SEO & Tags

15.1 Core Search Keywords

  • 4G/5G Base Station AC Distribution Unit
  • Base Station AC Distribution Box
  • Telecommunication Base Station ACDU
  • 5G Macro Station Power Distribution Solution
  • Outdoor Base Station AC Power Distribution
  • Base Station Dual Mains Switching Power Distribution
  • AC Distribution Unit for Telecommunications Equipment
  • Intelligent AC Power Distribution for Base Stations

15.2 Long-Tail Search Keywords

  • Wall-Mounted AC Distribution Box for 5G Micro Stations
  • Wide-Temperature AC Distribution Unit for Mountain Base Stations
  • High-Power Power Distribution for Base Station Edge Computer Rooms
  • Lightning-Proof AC Distribution Box for Base Stations
  • Remote Monitoring AC Power Distribution for Base Stations
  • Generator Emergency Power Distribution Unit for Base Stations
  • Smart Meter Equipped Base Station AC Power Distribution
  • KITOZER AC Distribution Unit

15.3 SEO Titles

  1. KITOZER 4G/5G Base Station AC Distribution Unit | ACDU Intelligent Lightning-Proof Power Distribution Solution
  2. 5G Base Station AC Distribution Box | Special Power Distribution Equipment for Indoor/Outdoor Macro & Micro Stations
  3. Telecommunication Base Station ACDU | Dual Mains Switching + Multi-Stage Lightning Protection + Remote Monitoring Power Distribution System

15.4 SEO Descriptions

  1. KITOZER specializes in R&D and manufacturing of 4G/5G base station AC distribution units, providing full-series ACDU products (indoor/outdoor, low/medium/high-end) supporting dual mains switching, multi-stage lightning protection, intelligent metering and remote monitoring, adapting to macro stations, micro stations and extreme outdoor environments with factory warranty & 7×24-hour service.
  2. KITOZER is the preferred brand for 4G/5G base station AC distribution boxes; products comply with communication industry standards with -40℃~+70℃ wide temperature and IP65 protection grade, suitable for mountain, desert and coastal outdoor base stations, delivering redundant power supply and intelligent operation & maintenance to guarantee stable and reliable base station power supply.

15.5 Tags

#4GBaseStationPowerDistribution #5GBaseStationACDistributionUnit #ACDU #BaseStationDistributionBox #TelecommunicationPowerSupply #BaseStationLightningProtectionDistribution #DualMainsTransfer #IntelligentPowerDistribution #OutdoorBaseStationPowerDistribution #MicroStationPowerDistribution #MacroStationPowerDistribution #KITOZER #BaseStationO&M #EdgeComputerRoomPowerDistribution #TelecommunicationDistributionEquipment