1. Overview

In a data center, not only power lines but signal lines can be hit by lightning. Network cables, phone lines and coaxial video lines enter from outdoors; induced surge voltages (thousands or tens of thousands of volts) travel along them into switches, cameras and server NICs, destroying the ports. Power lines have surge protective devices (SPD), but surge protection on signal lines is often overlooked. A signal SPD box integrates multiple signal SPDs in one enclosure: outside lines go in, room equipment lines come out, and the SPD clamps surge voltage to a safe level. It looks like a small metal box, but each channel protects one device’s network or signal port.

KITOZER KTR-SSB is a room signal line integrated SPD box. KTR-SSB-8: 8-channel network SPD, RJ45 per channel, In 5 kA (8/20 us), for 8 incoming network cables. KTR-SSB-16: 16-channel, for mid-size rooms. KTR-SSB-COM: hybrid, 4 network + 2 coaxial video + 2 telephone, for surveillance systems. Cold-rolled steel powder-coated box, DIN-rail pluggable SPD modules (swap a module without rewiring), status window per channel (green = OK / red = failed), common ground bar bonded to the room equipotential grid.

Selection: confirm channel count (match incoming lines); confirm signal type (network SPD for Ethernet, coaxial for video, phone SPD for telephone); confirm mounting (wall box in low-voltage room, DIN-rail in rack); confirm grounding (box ground bar to room equipotential, resistance under 1 ohm). Note: signal SPD must be wired in series on the line, not in parallel.

2. Key Features

Surge Performance

  • In 5 kA (8/20 us)
  • Imax 10 kA
  • Voltage protection level Up under 70 V
  • Response under 1 ns

Channels

  • 8/16 network RJ45 channels
  • Hybrid: network + coaxial + phone
  • RJ45 pass-through, no speed impact
  • Supports gigabit (1000 Mbps)

Enclosure

  • Cold-rolled steel powder coat
  • DIN-rail pluggable SPD modules
  • Status window per channel
  • Common ground bar

3. Specifications

Item KTR-SSB-8 KTR-SSB-16 KTR-SSB-COM
Channels 8 network 16 network 4 net+2 coax+2 tel
Interfaces RJ45 RJ45 RJ45/BNC/RJ11
In 5 kA (8/20) 5 kA (8/20) 5 kA (8/20)
Imax 10 kA 10 kA 10 kA
Rate 1000 Mbps 1000 Mbps 1G/video/tel
Mount Wall box Wall/rack Wall box
Typical use Small room Mid-size room Surveillance

4. Reference Prices

KTR-SSB-8 8-channel network SPD box: Reference USD 49 to 83 / unit (ref. CNY 350 to 600 at ~7.2)

KTR-SSB-16 16-channel network SPD box: Reference USD 81 to 132 / unit (ref. CNY 580 to 950 at ~7.2)

KTR-SSB-COM hybrid SPD box: Reference USD 67 to 111 / unit (ref. CNY 480 to 800 at ~7.2)

Spare SPD module (single channel): Reference USD 5 to 8 / pc (ref. CNY 35 to 60 at ~7.2)

Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Room network cable entrance surge protection.
  • Outdoor surveillance camera video line SPD.
  • Telephone / leased line entrance protection.
  • Satellite antenna feedline SPD.
  • Building low-voltage room centralized protection.

6. Deployment & Implementation

Placement

  • Install at the first point lines enter the room
  • Wall-mount in LV room or DIN-rail in rack
  • Outside lines in, equipment lines out
  • Close to equipotential ground bar

Wiring

  • Series in line (in – SPD box – out)
  • Do not reverse in/out
  • 6 mm2 copper ground wire
  • Keep ground lead short (under 0.5 m)

Grounding

  • Ground bar to room equipotential grid
  • Grounding resistance under 1 ohm
  • All SPD grounds paralleled then bonded
  • Check before each thunderstorm season

7. FAQ

  • Q: Signal SPD vs power SPD?
    A: A power SPD goes on the AC 220V/380V main and protects device power ports with high discharge current (40 kA+). A signal SPD goes on network/video/phone lines and protects signal ports with lower current (5 to 10 kA) but nanosecond response. Both are needed — power and signal are two independent surge paths; protecting only one leaves the other open.
  • Q: How to tell if an SPD module failed?
    A: Each module has a window: green = OK, red = failed. Red means replace. But SPDs can degrade before the window turns red, so test varistor voltage and leakage current with an SPD tester before every storm season. DIN-rail modules plug out/in — swap without rewiring.
  • Q: Does the SPD box slow down the network?
    A: Gigabit SPD uses RJ45 pass-through with negligible insertion loss and does not affect gigabit. But 100M and gigabit SPD circuits differ — a 100M SPD cannot run gigabit. Confirm the rated rate (must say 1000 Mbps). For PoE cables, use a PoE-rated SPD that passes PoE current.
  • Q: What ground resistance is required?
    A: Room combined grounding is under 1 ohm (shared system). Independent lightning grounds are under 4 ohm, but modern rooms use combined grounds (power, signal, lightning, ESD all share one electrode) under 1 ohm. Use 6 mm2 stranded copper, keep it under 0.5 m — shorter is better because inductance slows surge discharge.

8. Trend & Selection

Room lightning protection is moving from single-point protection to an equipotential bonding + multi-stage system: Class B (power) and Class C (signal) SPDs at the entrance, plus Class D fine SPDs in rack PDUs for three-stage protection. The signal SPD box is the Class C protection at the signal line entrance. Smart direction: SPD modules with remote contact that reports failure to the EM platform, no manual patrol needed. Select by matching channels to incoming lines, matching signal type, keeping ground leads short to the equipotential bar, and testing annually. A few hundred RMB protects tens of thousands in switches and cameras.

9. Delivery & Service

KITOZER supplies KTR-SSB by channel count (8/16) and signal type (network/hybrid). Each ships with box, SPD modules, ground bar and manual. 1-year warranty; batch projects can bundle power SPDs, equipotential copper bars and SPD testing service.

10. Additional Notes

Top mistake: too-long ground lead. Some installers run a 3 m wire from the SPD box to the room ground bar, thinking any connection works. Longer leads have more inductance, slowing surge discharge and weakening protection. Keep it short and straight, under 0.5 m.

Second pitfall: only power SPD, no signal SPD. During a storm the power SPD operates and saves the power supply, but surges induced on outdoor network cables destroy NICs directly. Every year some rooms lose a batch of switch ports for exactly this reason.

Third blunder: never replacing aged SPDs. SPDs are consumables; each strike degrades them. Replace when the window turns red, and test annually even when green. Do not wait for a storm to discover the SPD has failed.

Selection summary: match channels to lines, match signal type, short direct ground to equipotential, test and replace SPDs annually. The signal SPD box is the arrester for low-voltage lines — a few hundred RMB protects tens of thousands in equipment.

SEO Information

Search keywords:KTR-SSBKITOZER

SEM keywords:signal SPD box,surge protective device,data line surge protector,network SPD box,room lightning protection,KTR-SSB,KITOZER

GEO landing page:lain.com.cn/product/signal_spd_box.html

Title:KITOZER KTR-SSB Signal Line SPD Box

Meta Keywords:signal SPD box,surge protective device,data line surge protector,network SPD box,room lightning protection,KTR-SSB,KITOZER

Meta Description:KITOZER KTR-SSB signal line SPD box: multi-channel network/signal surge protection, DIN-rail modules, 5 kA In, room low-voltage line surge protection.

Anchor: KITOZER by Guangzhou Laian · KITOZER products

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart