Table of Contents
ToggleKITOZER KTR-EEV2 Electronic Expansion Valve for Precision AC
Brand: KITOZER Series: KTR-EEV2 Category: Data Center Engineering / Refrigeration Control
EEVStepper motorSuperheat controlR410A/R32KTR-EEV2
1. Overview
The electronic expansion valve (EEV) is the throttling element in a vapor-compression cycle. High-pressure liquid leaving the condenser is suddenly depressurized across the valve into a low-pressure, low-temperature liquid-vapor mix before entering the evaporator. A traditional thermal expansion valve (TXV) senses superheat via a bulb and acts mechanically – slow, coarse. An EEV drives the needle directly with a stepper motor; the controller recalculates opening from superheat (outlet temp minus saturation temp at measured pressure) in real time, holding superheat at 1.8-3 K and lifting evaporator utilization from 70% to over 90%. Precision AC runs year-round with fluctuating load; the EEV modulates cooling capacity from 10% to 100%, part-load EER beating TXV units.
KITOZER KTR-EEV2 is an EEV for precision AC. Build: forged brass body, stainless needle with refrigerant-resistant seals; drive: 2-phase stepper, 2000 pulses closed-to-open, coil DC12V/DC24V; ports: flange or threaded, pipe ODs 12/16/22 mm; refrigerants: R22/R407C/R410A/R32; pressure: high side 4.5 MPa, low side 3.5 MPa; superheat: built-in PID, 1.0-8 K adjustable, default 2.5 K. Models: KTR-EEV2-14: ~14 kW (5-10 kW AC); KTR-EEV2-22: ~22 kW (10-20 kW AC); KTR-EEV2-30: ~30 kW (20-30 kW AC).
Selection: capacity (valve must exceed compressor rating by 1.2x); refrigerant (R410A high-pressure needs a rated body); pipe size (match evaporator liquid line); controller (EEV needs a dedicated driver, never connect to 220 V directly); orientation (vertical body, coil on top, arrow toward evaporator). Note: EEV is precision gear – pressure-test, leak-check and vacuum before commissioning; never hot-plug the coil; do not alter the default superheat – a commissioning engineer retunes it from evaporator outlet temp and suction pressure.
2. Key Features
Control
- 2000-step stroke
- 1.8-3 K superheat
- Real-time PID
- High part-load EER
Body
- Forged brass
- Stainless needle
- Refrigerant seals
- R410A/R32 ready
Drive
- 2-phase stepper
- DC12/24 V coil
- Flange/threaded
- Vertical mount
3. Specifications
| Item | KTR-EEV2-14 | KTR-EEV2-22 | KTR-EEV2-30 |
|---|---|---|---|
| Capacity | ~14 kW | ~22 kW | ~30 kW |
| Pipe OD | 12 mm | 16 mm | 22 mm |
| Steps | 2000 | 2000 | 2000 |
| Superheat | 1.0-8 K | 1.0-8 K | 1.0-8 K |
| Refrigerant | R410A/R32 | R410A/R32 | R410A/R32 |
4. Reference Prices
KTR-EEV2-14 14 kW valve: Reference USD 53-72 / pc (ref. CNY 380-520)
KTR-EEV2-22 22 kW valve: Reference USD 72-100 / pc (ref. CNY 520-720)
KTR-EEV2-30 30 kW valve: Reference USD 100-136 / pc (ref. CNY 720-980)
KTR-EEV2-COIL driver coil: Reference USD 11-17 / pc (ref. CNY 80-120)
KTR-EEV2-CTRL superheat board: Reference USD 83-125 / pc (ref. CNY 600-900)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Precision AC throttling
- DX/chiller retrofits
- Lab precision AC
- Industrial chillers
- Heat-pump water heaters
6. Deployment & Installation
Install
- Vertical body
- Coil up
- Arrow to evaporator
- Service clearance
Piping
- Flare/flange joints
- Nitrogen-purge brazing
- Pressure test 4.5 MPa
- Vacuum to 50 Pa
Commission
- Wire DC24 V driver
- Set refrigerant
- Default 2.5 K SH
- Tune on suction temp
7. FAQ
- Q: Can an EEV swap in directly for a TXV?
A: Mounting is similar, but no. A TXV is self-contained; an EEV needs a driver board, suction-temp and pressure sensors, and EEV firmware in the controller. Converting a TXV unit means adding all of that – it is not a bolt-on swap. - Q: What superheat setpoint?
A: 2.5 K default for DX evaporators. Too low (<1 K) floods the compressor with liquid and causes slugging; too high (>6 K) dries the evaporator and wastes capacity. Aim for outlet temp 1.8-3 K above saturation. - Q: Coil burned out?
A: The coil is a universal DC12/24 V two-wire part – unplug and replace, body untouched. Usual causes: wrong voltage (DC24 coil on AC220) or a shorted driver. Measure driver output before fitting a new coil. - Q: How to size capacity?
A: Pick valve at 1.1-1.3x compressor rating. A 14 kW valve suits a 10-12 kW compressor. Too small: fully open still under-throttles at high load; too large: it dithers in tiny steps at low load and goes non-linear.
8. Trend & Selection
EEVs are becoming standard on medium/large refrigeration units, displacing TXVs. Trends: wider capacity range (1 kW residential to 50 kW commercial); communication – driver boards join RS485/Modbus so DCIM sees valve opening, superheat and differential pressure remotely; and VFD-compressor pairing – variable-speed compressor plus variable valve opening gives 5-100% capacity turndown and part-load EER 30% above fixed-speed units. Precision AC is moving from fixed-speed+capillary/TXV to VFD+EEV. Select by: 1.2x compressor capacity, refrigerant-pressure rated, matched driver board, 2.5 K default superheat tuned by a commissioning engineer.
9. Delivery & Service
KITOZER supplies KTR-EEV2 valve body, matching coil and driver board by model. Each ships with body, coil and manual; bulk orders can bundle driver boards and sensors. 1-year warranty; commissioning support available for projects.
10. Additional Notes
Match compressor capacity, refrigerant (R410A/R32 high-pressure) and pipe OD to site piping; mount body vertically with coil on top; feed driver board with DC24 V without reversing. For batch orders, bench-test a sample for superheat tuning.
Common mistake: hot-plugging the coil. Arcing under load burns the driver output MOSFET. Power off and wait 30 s for capacitor bleed before swapping a coil.
Second pitfall: brazing without nitrogen. Oxide scale forms inside the tube, rides the refrigerant to the valve seat, and jams the needle. Purge with nitrogen throughout brazing and flush lines.
Third blunder: fiddling with superheat. Setting 0.5 K chasing cooling floods the compressor with liquid; slugging destroys valves within months. Leave tuning to an engineer per standard.
Selection summary: valve capacity = compressor x1.2, R410A/R32 pressure-rated, vertical body with coil up, DC24 V driver, 2.5 K superheat tuned by engineer.
SEO Information
Search keywords:KTR-EEV2KITOZER
SEM keywords:electronic expansion valve,EEV,precision AC expansion valve,stepper valve,superheat control,KTR-EEV2,KITOZER
GEO landing page:lain.com.cn/product/ktr-eev2-electronic-expansion-valve.html
Title:KITOZER KTR-EEV2 Electronic Expansion Valve for Precision AC
Meta Keywords:electronic expansion valve,EEV,precision AC expansion valve,stepper valve,superheat control,KTR-EEV2,KITOZER
Meta Description:KITOZER KTR-EEV2 electronic expansion valve, stepper-driven, 2000-step stroke, adjustable superheat 1.8-3K, for R410A/R32 precision AC.
Anchor: KITOZER by Guangzhou Laian · KITOZER products
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com