Table of Contents
Toggle1 System Overview
The KITOZER open water-cooled integrated cabinet is a new-generation liquid cooling heat dissipation infrastructure developed to meet the demands of high-density computing power scenarios, renovation and upgrading of traditional computer rooms, and low-carbon data center construction. It is a highly integrated cabinet product integrating cabinet body, open water-cooling circulation system, power distribution system, intelligent monitoring system and safety protection system, fully complying with national and industrial standards including YD/T 6049-2024 Technical Requirements and Test Methods for Cold Plate Liquid-Cooled Whole Rack Servers and T/CAICI 131-25 Technical Specification for Liquid Cooling System Engineering.
KITOZER Open Water-Cooled Integrated Cabinet Cluster
The core feature of the open water-cooling circulation system lies in an open section where the primary circulation loop directly contacts the atmosphere. Evaporative heat dissipation is realized via the open cooling tower, delivering core advantages including high heat exchange efficiency, low initial investment cost, strong cold storage and peak shaving capacity, and high utilization rate of natural cold sources. It is especially suitable for data center construction and renovation projects in water-rich and humid regions.
All core components of the full product line are domestically produced with independent R&D and manufacturing by KITOZER. We provide full-chain services covering standardized products, customized development, OEM/ODM processing, and military-grade confidential production, fully meeting differentiated liquid cooling heat dissipation demands across all industries, scales and grades.
2 System Composition
The KITOZER open water-cooled integrated cabinet system features a three-stage circulation architecture: primary open cold source circulation, secondary in-cabinet circulation, and chip-level cold plate heat exchange. The entire system consists of 12 core subsystems with high integration and coordinated operation, delivering full-link precise temperature control, safety protection and intelligent management.
2.1 Cabinet Body Subsystem
As the physical carrier of the entire system, it adopts a 9-fold profile thickened welded frame made of high-quality cold-rolled steel plate treated with electrostatic powder coating for anti-corrosion and rust resistance, featuring ultra-high load-bearing capacity and structural stability. Key components include cabinet frame, front/rear mesh/tempered glass doors, detachable side panels, 19-inch standard mounting uprights, L-shaped guide rails, bottom liquid collection trough, leak-proof cofferdam, cable management channels and grounding system. It supports installation of all standard 19-inch servers, blade servers and AI training servers.
2.2 Open Cold Source Circulation Subsystem (Primary Loop)
Open Cooling Tower Unit
This core heat exchange unit discharges heat absorbed from IT equipment to the outdoor environment. Its core components include open counter-flow cooling tower, primary circulation water pump set, cold storage water tank, water quality treatment unit, chemical dosing unit, filter assembly, electric regulating valve, bypass pipeline, water replenishment unit and anti-freezing unit (for low-temperature regions).
The open cooling tower operates on evaporative heat dissipation: cooling water is sprayed evenly onto packing surfaces, and axial fans drive outdoor air to flow upward in counter-flow with sprayed water. Heat and mass exchange removes heat from water, achieving high heat exchange efficiency exceeding 90%.
2.3 Chilled Water Distribution Unit (CDU) Subsystem
As the core hub connecting primary and secondary loops, CDU acts as the “heart” of the entire liquid cooling system. It isolates heat exchange between primary and secondary loops, provides circulation power for the secondary loop, precisely controls flow and temperature, and monitors system status with safety protection. Core components: plate heat exchanger, variable-frequency secondary circulation water pumps (1-working-1-standby / 2-working-1-standby redundant design), expansion tank, automatic water replenishment unit, multi-stage filter assembly, flow/temperature/pressure sensors, electric regulating valves, check valves, stop valves, safety relief valves, PLC intelligent control cabinet, HMI touch screen and communication modules.
2.4 In-Cabinet Manifold Subsystem
Installed inside each cabinet, it evenly distributes coolant delivered from CDU to cold plate units of individual servers, and collects high-temperature coolant after heat exchange to flow back to CDU for balanced and precise flow distribution. Core components: main supply/return liquid pipes, multi-branch distribution ports, manual branch ball valves, flow indicators, branch flow regulating valves, quick-disconnect fittings, pressure monitoring ports, air vent valves and drain valves.
2.5 Chip-Level Cold Plate Heat Exchange Subsystem
Cold Plate Production Workshop
The terminal heat exchange unit making direct contact with heat-generating core components of IT equipment, serving as the core component for precise heat dissipation. Core components: dedicated CPU/GPU cold plates, auxiliary cold plates for memory/chipset, thermal interface materials (thermal grease/thermal pads), quick-disconnect connectors, flexible connecting pipelines and fixing brackets.
Cold plates are fabricated from C1100 oxygen-free copper with micro-channel internal structures, supporting heat flux density above 150W/cm², fully compatible with all mainstream Intel, AMD and NVIDIA chips.
2.6 Pipeline Connection Subsystem
Responsible for coolant transportation and circulation across the system, divided into four categories: outdoor main pipelines, indoor main pipelines, cabinet branch pipelines and in-cabinet flexible pipelines. Core components: 304/316L stainless steel seamless pipes, EPDM corrosion-resistant hoses, PEX pipelines, flange assemblies, welded fittings, double-seal quick-disconnect joints, 90°/45° elbows, tees, reducers, pipe supports, thermal insulation layers and anti-condensation protective layers.
2.7 Intelligent Power Distribution Subsystem
Provides stable and safe power supply for IT equipment inside cabinets and auxiliary liquid cooling devices. Core components: dual-input automatic transfer switch (ATS), intelligent PDU (0U vertical / 1U horizontal mounting), circuit breakers, overload/short-circuit/leakage protection devices, surge protection devices (SPD), ammeters, voltmeters, energy metering modules, remote control modules and grounding busbars.
2.8 Intelligent Monitoring & Management Subsystem
Enables full-dimensional real-time monitoring, intelligent control, fault alarm and data traceability for the entire liquid cooling system. Core components: PLC main controller, industrial touch screen, temperature/pressure/flow/liquid level/conductivity/water immersion/access control/smoke sensors, video monitoring unit, data acquisition module, remote communication module (4G/5G/Ethernet), BMS docking interface and environmental monitoring system access protocols.
2.9 Leakage Prevention & Safety Protection Subsystem
A three-stage leakage protection architecture ensures absolute safe operation of the system. Core components: fully enclosed bottom liquid collection trough, regional leak-proof cofferdam, point-type water immersion sensors, positioning leak detection cables, quick shut-off valves, sound-light alarm devices, emergency drain interfaces, waste liquid collection units, insulation protection assemblies and fire linkage interfaces.
2.10 Auxiliary Air Cooling Subsystem
Serves as backup and supplement to the liquid cooling system, dissipating heat for low-power non-liquid-cooled components such as memory, hard disks and IO cards. Core components: redundant axial fans at front and rear of cabinet, intelligent temperature-controlled speed regulation module, air duct baffles, blanking plates and dust filter screens. It operates in linkage with the liquid cooling system to deliver full-device heat coverage.
2.11 Water Quality Treatment & Maintenance Subsystem
Specially designed to address contamination risks in open systems, delivering full-process water quality guarantee. Core components: multi-stage precision filters, water softener, deaerator, sterilization and algae removal unit, pH regulation module, online conductivity monitoring unit, water sampling port and online cleaning device. It effectively prevents pipeline scaling, corrosion and microbial growth to extend system service life.
2.12 Waste Heat Recovery & Utilization Subsystem (Optional)
Integrated Cabinet Cluster On-Site Installation
An expandable energy-saving value-added unit that recovers waste heat generated by IT equipment in the liquid cooling system for office heating, domestic hot water, agricultural greenhouses, swimming pool heating and other scenarios, further improving energy utilization efficiency to realize zero-carbon data center operation. Core components: waste heat recovery plate heat exchanger, heat storage tank, circulation pump set, intelligent temperature control unit and heat distribution pipelines.
3 System Classification
The full KITOZER open water-cooled integrated cabinet product line is categorized by power density, application scenario, installation form, cooling mode and redundancy level to fully cover differentiated customer demands.
3.1 Classification by Single-Cabinet Heat Dissipation Power Density
3.1.1 Low-Density Series (10kW–20kW)
Entry-level open water-cooled integrated cabinets for small/medium computer room renovation and edge computing nodes with low power density. No large-scale modification to existing air conditioning systems is required, enabling seamless switching between air cooling and liquid cooling. Featuring low deployment cost, simple operation and maintenance, and strong compatibility, it is the preferred entry solution for traditional computer rooms transitioning to liquid cooling.
3.1.2 Medium-Density Series (20kW–50kW)
Mainstream general-purpose open water-cooled integrated cabinets for enterprise-level data centers, medium-sized AI inference clusters and government cloud computer rooms. Compatible with mainstream 2U/4U rack servers and blade servers, it adopts N+1 redundant design balancing heat dissipation performance, energy efficiency and investment cost. Widely applied in new data center construction and mass renovation of existing computer rooms.
3.1.3 High-Density Series (50kW–80kW)
High-performance open water-cooled integrated cabinets for AI training clusters, HPC and research supercomputing centers. It meets extreme heat dissipation demands of 8-card/16-card GPU servers and high-end 4-way/8-way rack servers with 2N redundant architecture, delivering top-tier heat dissipation capacity and reliability to support 7×24-hour full-load continuous operation, serving as the primary model for medium and large-scale intelligent computing centers.
3.1.4 Ultra-High-Density Series (80kW–120kW)
Ultra-High-Density Liquid Cooling Cabinet Interior
Flagship open water-cooled integrated cabinets for national supercomputing centers, large model training bases, weather forecasting, petroleum exploration and other extreme computing power scenarios, compatible with whole-rack servers and AI supercomputers. Full redundant architecture and multi-layer safety protection deliver industry-leading heat dissipation capacity and stability, supporting continuous single-cabinet heat dissipation up to 120kW with chip temperature control precision of ±0.5℃.
3.2 Classification by System Installation & Deployment Form
3.2.1 Indoor Standard Rack Series
Standard 19-inch cabinet design with widths of 600mm/800mm, depths of 1000mm/1200mm/1400mm and heights of 42U/47U. It can be directly deployed in existing standard computer rooms side-by-side with traditional air-cooled racks without layout adjustments, ideal for liquid cooling renovation of existing facilities, supporting single-rack and multi-rack cluster deployment with high flexibility.
3.2.2 Micro-Module Integrated Series
Multiple open water-cooled integrated cabinets, CDU units, power distribution units and monitoring systems are integrated with cold aisle containment to form independent micro-module liquid cooling clusters. Factory prefabrication enables rapid on-site assembly, cutting delivery cycles by 60%. It supports phased construction and on-demand capacity expansion, suitable for new medium-sized data centers and park-level intelligent computing centers with fast deployment and easy scalability & management.
3.2.3 Containerized Prefabricated Series
The full open water-cooled system (cooling tower, CDU, power distribution, UPS, fire protection and monitoring) is fully integrated into standard containers (20ft/40ft), forming a mobile, rapidly deployable integrated liquid cooling data center. Containers feature waterproof, fireproof, seismic, anti-theft and thermal insulation structures for direct outdoor installation without dedicated computer room construction, suitable for edge computing sites, temporary computing clusters and remote mining/oilfield computing deployment.
3.2.4 Wall-Mounted / Desktop Small-Size Series
Outdoor CDU & Cooling Tower Equipment
Compact open water-cooled integrated cabinets developed for small office scenarios, edge computing nodes and industrial control computer rooms, ranging from 6U–18U with heat dissipation power of 2kW–10kW. Integrated mini CDU, small circulation pumps and auxiliary air cooling units support switchable open/closed circulation with compact size, low noise and flexible installation, filling market gaps for liquid cooling in small-scale scenarios.
3.3 Classification by Cooling Mode & Heat Exchange Form
3.3.1 Open Cold Plate Liquid-Cooled Integrated Cabinet
Mainstream core model adopting indirect liquid cooling technology: coolant does not make direct contact with IT chips. Heat exchange occurs via metal cold plates attached to chips, requiring minimal modification to existing servers (only replacing CPU/GPU heat sinks with cold plates) for excellent compatibility and controllable risks. The most mature and widely adopted liquid cooling solution for nearly all data center scenarios.
3.3.2 Open Spray Liquid-Cooled Integrated Cabinet
Direct liquid cooling model for ultra-high-density scenarios. Precision spray nozzles atomize coolant to make direct contact with chip surfaces for heat exchange, boosting heat exchange efficiency by over 30% compared to cold plate solutions with single-cabinet heat dissipation capacity up to 200kW. Fully insulated coolant paired with splash-proof sealed structures meets heat dissipation demands of supercomputing centers and large model training with chips above 1000W TDP.
3.3.3 Open Air-Liquid Hybrid Integrated Cabinet
Universal compatible model adopting a hybrid architecture with liquid cooling as primary and air cooling as backup. High-heat core components (CPU/GPU) use liquid cooling while low-power memory, hard disks and IO cards rely on auxiliary air cooling. No full server modification is required, balancing heat dissipation efficiency and renovation cost as a cost-effective solution for upgrading existing computer rooms to liquid cooling.
3.3.4 Open Natural Cold Source Enhanced Integrated Cabinet
Energy-saving model optimized for cold northern and high-altitude regions. It improves natural cold source utilization logic of open cooling towers, enabling over 80% annual operation without mechanical refrigeration, with PUE dropping below 1.05 to minimize data center energy consumption, aligning with low-carbon requirements of the national East Data West Computing strategy.
3.4 Classification by Redundancy Level & Reliability
3.4.1 Basic Type (N Architecture)
Single-circuit design without redundant components for cost optimization, suitable for non-core business, edge computing nodes and test computer rooms with low reliability requirements, featuring low investment cost, simple structure and easy maintenance.
3.4.2 High-Reliability Type (N+1 Architecture)
Centralized Monitoring Control Platform
Core components including circulation pumps, cooling tower fans and power modules adopt N+1 redundant design. Standby units automatically take over upon single-component failure without disrupting IT heat dissipation, applicable to enterprise data centers, government computer rooms and medium-sized intelligent computing centers meeting Class B computer room standards specified in GB 50174 Code for Design of Data Centers.
3.4.3 Fault-Tolerant Type (2N Architecture)
Fully redundant dual 2N architecture with two completely independent open circulation systems serving as mutual backups. One full system failure triggers seamless full-load takeover by the standby system for zero-interruption operation, suitable for financial data centers, carrier core computer rooms and national supercomputing centers with ultra-high reliability requirements, complying with Class A GB 50174 standards.
4 System Schematic Principles
4.1 Overall System Architecture Principle
The KITOZER open water-cooled integrated cabinet adopts a three-stage independent circulation architecture: primary open cold source circulation + secondary closed in-cabinet circulation + chip-level cold plate heat exchange. Heat transfer between the two loops occurs without contact via plate heat exchangers. This design retains the open system’s strengths of high heat exchange efficiency and natural cold source utilization while leveraging the secondary closed loop to guarantee coolant cleanliness and insulation, preventing scaling and corrosion. Complete electrical isolation between IT equipment and the outdoor environment significantly boosts system safety.
4.2 Core Circulation Flow Principles
4.2.1 Primary Open Cold Source Circulation Flow
- High-temperature cooling water after heat absorption is delivered via primary return pipelines to water distribution nozzles at the top of the open cooling tower, evenly sprayed onto packing surfaces.
- Axial fans drive outdoor air upward through packing layers in counter-flow with sprayed water; water evaporation absorbs heat to lower cooling water temperature.
- Cooled water collects in the cooling tower’s bottom water tray, filtered and pressurized by primary circulation pumps before entering the primary channel of the CDU plate heat exchanger.
- Cooling water absorbs heat from secondary coolant inside the plate heat exchanger, reheats and flows back to the cooling tower via return pipelines to complete a full open circulation.
- Auxiliary supporting processes: cold storage water tanks connected to main pipelines for water buffering and cold peak shaving; water quality treatment units continuously soften, deaerate, sterilize and remove algae from circulating water; automatic water replenishment systems add softened water based on liquid level; electric anti-freezing heaters are equipped for cold regions to avoid pipeline rupture in winter.
4.2.2 Secondary Closed In-Cabinet Circulation Flow
Multi-Rack Liquid Cooling Cabinet Cluster Indoor Layout
- Low-temperature coolant cooled by the plate heat exchanger is transported via secondary supply main pipelines to manifold units inside each cabinet, distributed to cold plate units of individual servers via branch regulating valves.
- Coolant flows at high velocity through micro-channels inside cold plates, absorbing heat generated by server CPUs, GPUs and other core components to raise coolant temperature.
- Heated coolant after heat exchange collects via cabinet return pipelines, transported back to CDU through secondary return main pipelines, filtered and pressurized by secondary circulation pumps before entering the secondary channel of the plate heat exchanger.
- High-temperature coolant exchanges heat with primary cooling water inside the plate heat exchanger, cools down and recirculates to cabinets via supply pipelines to complete the secondary closed circulation.
- Auxiliary supporting processes: expansion tanks absorb volume expansion of coolant caused by temperature changes to stabilize system pressure; automatic replenishment devices add coolant based on system pressure; multi-stage filters maintain coolant purity; real-time monitoring of temperature, pressure, flow and conductivity by sensors enables PLC automatic adjustment of pump speed and valve opening for precise temperature control according to load fluctuations.
4.2.3 Chip-Level Cold Plate Heat Exchange Principle
Cold plates are fabricated from high-thermal-conductivity oxygen-free copper with micron-scale internal micro-channels generating strong turbulence to strengthen heat exchange efficiency. Ultra-precision cold plate machining achieves flatness ≤50μm; thermal interface materials ensure tight contact with chip surfaces with contact thermal resistance ≤0.05℃/W. Heat transfer path: chip housing → thermal interface material → cold plate substrate → coolant. This stably controls chip junction temperature below 85℃, far lower than the 105℃ upper limit of air cooling, extending chip service life and eliminating server frequency throttling under high temperature to sustain full computing power output.
4.3 System Schematic Diagrams
Figure 1 Schematic of KITOZER Open Circulation Cold Plate Liquid Cooling System
Figure 2 Schematic of Open Cooling Tower Primary Circulation System
4.4 System Control Logic Principle
The system adopts a PLC + touch screen intelligent control architecture supporting three operating modes: fully automatic, manual and remote control. Core control logic:
- Temperature control: Automatically adjust primary pump speed, cooling tower fan frequency, secondary pump speed and electric regulating valve opening based on server chip temperature and secondary supply liquid temperature setpoints to achieve supply liquid temperature control precision of ±1℃.
- Flow control: Dynamically adjust branch flow distribution according to cabinet load changes to meet flow demands of each server cold plate with flow control precision of ±2%.
- Pressure control: Link variable-frequency pumps and automatic replenishment devices to stabilize the supply-return liquid pressure differential within set ranges with pressure fluctuation ≤0.05MPa.
- Redundancy switching control: Standby pumps seamlessly take over upon main pump failure; standby cooling tower fans activate automatically to maintain heat dissipation capacity without interruption.
- Safety protection logic: Sound-light alarms trigger upon detection of liquid leakage, overtemperature, overpressure, low liquid level or pump overload, paired with corresponding protective actions (emergency shut-off valve closure, standby system startup, orderly IT equipment power-off). All alarm data uploads to the environmental monitoring system.
5 Full System Configuration List
All products under the KITOZER brand are divided into three tiers: entry-level (low configuration), enterprise-level (medium configuration) and flagship-level (high configuration), covering full power segments from 10kW to 120kW.
5.1 Entry-Level Configuration List (10kW–20kW Single Cabinet, Small Computer Room Renovation & Edge Computing)
è¡¨æ ¼
| No. | Product Name | Model | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | Open Water-Cooled Integrated Cabinet Body | KITOZER-LC-LOW-42U | 42U standard 19-inch, 600W×1200D×2000H, 9-fold profile frame, cold-rolled steel, static load ≥1500kg, front/rear mesh door opening rate ≥70%, bottom integrated 304SS liquid collection trough, leak-proof cofferdam, 12 pairs L-shaped guide rails, grounding resistance ≤0.1Ω, electrostatic anti-corrosion coating | 1 | Set | KITOZER | Compatible with standard rack servers, dual air/liquid cooling mode |
| 2 | In-Cabinet Manifold Unit | KITOZER-MF-LOW-8 | 8-branch distribution, 304SS, DN25 main supply/return ports, DN8 branch ports, manual ball valves, quick-disconnect fittings, flow sight glass, air vent & drain valves, working pressure ≤1.6MPa, pressure test ≥2.4MPa | 1 | Set | KITOZER | Supports up to 8 units of 1U/2U servers |
| 3 | Dedicated CPU Cold Plate | KITOZER-CP-INT-STD | Compatible with Intel LGA1700/1200/2011, C1100 oxygen-free copper micro-channel, thermal resistance ≤0.15℃/W @3L/min, working pressure ≤1.6MPa, G1/4 interface, flatness ≤50μm, thermal grease ≥12W/m·K | 8 | Pcs | KITOZER | 1 per server, AMD interfaces customizable |
| 4 | Auxiliary GPU Cold Plate | KITOZER-CP-GPU-STD | Compatible with NVIDIA single/dual-slot GPUs, aluminum alloy micro-channel, thermal resistance ≤0.2℃/W @2L/min, working pressure ≤1.6MPa, G1/4 interface, thermal pads included | 8 | Pcs | KITOZER | Optional, 1 per graphics card |
| 5 | Distributed CDU Unit | KITOZER-CDU-LOW-20 | 20kW cooling capacity, liquid-liquid plate heat exchanger, efficiency ≥90%, 1-working-1-standby secondary variable-frequency pumps, single pump flow 6m³/h, head 25m, 0.75kW, expansion tank, precision filters, auto replenishment, temp/pressure sensors, 220V AC power | 1 | Set | KITOZER | Rack-mountable, supports max 2 cabinets |
| 6 | Open Cooling Tower | KITOZER-CT-LOW-30 | 30kW cooling capacity, counter-flow design, air volume 5000m³/h, 0.75kW fan, 0.37kW spray pump, 304SS water tray, PVC packing, inlet 37℃ / outlet 32℃ @28℃ wet bulb, noise ≤65dB(A), 380V AC | 1 | Set | KITOZER | Outdoor installation, anti-freezing model optional for cold regions |
| 7 | Primary Circulation Pump Set | KITOZER-PUMP-PRI-LOW | Horizontal centrifugal pump, flow 10m³/h, head 20m, 1.1kW, 304SS wetted parts, check/stop valves, flexible connectors, shock-absorbing base, IP55, 380V AC | 1 | Set | KITOZER | 1-working-1-standby optional, standard single pump |
| 8 | Intelligent PDU | KITOZER-PDU-LOW-16 | 0U vertical mount, 16A input, 8×C13 outlets, current/voltage monitoring, overload protection, surge protection, total power ≤3.5kW, remote switch control, Modbus | 2 | Pcs | KITOZER | Dual-input optional, standard 2 single-input PDUs |
| 9 | Intelligent Monitoring System | KITOZER-MON-LOW | 7-inch industrial touch screen, PLC, 2×temp sensors, 2×pressure sensors, 1×point water immersion sensor, 1×liquid level sensor, sound-light alarm, Modbus-RTU/TCP, 24V DC | 1 | Set | KITOZER | Local monitoring standard, remote module optional |
| 10 | Pipeline Connection System | KITOZER-PIPE-LOW-SET | DN40 304SS main pipes, DN20 branch pipes, EPDM flexible hoses, quick-disconnect fittings, elbows, tees, flanges, pipe supports, thermal insulation & anti-condensation layers, full installation accessories | 1 | Set | KITOZER | Standard for single cabinet, adjustable for multi-rack clusters |
| 11 | Water Quality Treatment System | KITOZER-WATER-LOW | 5μm precision filter, water softener, chemical dosing unit, Y-filter, filtration precision 5μm, treatment flow ≥10m³/h | 1 | Set | KITOZER | Basic standard, sterilization & algae removal optional |
| 12 | Auxiliary Air Cooling System | KITOZER-FAN-LOW-4 | 4×120mm axial fans, intelligent PWM speed regulation, 120CFM per fan, noise ≤35dB(A), dust filters, blanking plates, air baffles, 12V DC | 1 | Set | KITOZER | Front/rear cabinet mounting, backup heat dissipation |
| 13 | Safety Protection System | KITOZER-SAFE-LOW | Point water immersion sensors for liquid collection trough, DN25 quick shut-off valve, emergency drain port, waste liquid collection box, insulation components, fire linkage interface, response time ≤1s | 1 | Set | KITOZER | Basic three-stage leakage prevention |
| 14 | Coolant | KITOZER-COOL-STD | Deionized water + ethylene glycol antifreeze mixture, conductivity ≤5μS/cm, freezing point -25℃, boiling point 108℃, corrosion inhibitor & biocide, eco-friendly formula | 50 | L | KITOZER | Standard volume per system, freezing point adjustable by ambient temperature |
5.2 Enterprise-Level Configuration List (20kW–50kW Single Cabinet, Enterprise Data Center, AI Inference Cluster, Government Cloud)
(Table omitted for length; consistent bilingual table format matching entry-level structure, with upgraded parameters: thicker cabinet steel, 316SS manifolds, high-performance cold plates, centralized 100kW CDU, N+1 redundant pumps, 150kW cooling tower, 2m³ cold storage tank, dual redundant 32A PDU, 15-inch touch screen AI monitoring, three-stage filtration water treatment, three-stage leakage protection, high-conductivity coolant)
5.3 Flagship-Level Configuration List (50kW–120kW Single Cabinet, AI Training Cluster, Supercomputing Center, National Computing Hub)
(Table omitted for length; highest-spec configuration: 48U heavy-duty 2.5mm steel cabinet, 32-branch intelligent manifolds, vacuum brazed 3D stacked micro-channel CPU/GPU/NVSwitch cold plates, 300kW 2N redundant CDU, 400kW modular cross-flow cooling tower group, 5m³ cold storage tank, 63A high-voltage DC dual-redundant PDU, 27-inch 4K AI predictive health monitoring, five-stage full-intelligent water management, military-grade five-stage leakage prevention, blind-mate hot-swappable quick-disconnects, optional 300kW waste heat recovery, ultra-pure electronic-grade coolant)
6 Full Product Technical Parameters
6.1 Core Technical Parameters of Open Water-Cooled Integrated Cabinet Body
è¡¨æ ¼
| Product Series | Model | Overall Dimension | Mounting Space | Steel Thickness | Static Load | IP Rating | Operating Temp | Ground Resistance | Supported Power |
|---|---|---|---|---|---|---|---|---|---|
| Entry-Level | KITOZER-LC-LOW-42U | 600×1200×2000mm | 42U standard 19-inch | Frame 2.0mm, door 1.5mm | ≥1500kg | IP30 | 5℃–45℃ | ≤0.1Ω | 10kW–20kW |
| Enterprise-Level | KITOZER-LC-MID-47U | 800×1400×2200mm | 47U standard 19-inch | Frame 2.0mm, door 1.5mm | ≥3000kg | IP54 | 0℃–50℃ | ≤0.05Ω | 20kW–50kW |
| Flagship-Level | KITOZER-LC-HIGH-48U | 800×1600×2250mm | 48U standard 19-inch | Frame 2.5mm, door 2.0mm | ≥5000kg | IP55 | -20℃–55℃ | ≤0.05Ω | 50kW–120kW |
| Universal Technical Requirements | Comply with ANSI/EIA RS-310-D, IEC297-2, DIN41491, GB/T 3047.2-92; electrostatic coating adhesion Grade 1 per GB/T 9286-1998; salt spray resistance ≥48h (GB/T 10125-2021); fire resistance meets Class A data center standard GB 50174-2017; cabinet verticality deviation ≤1‰, flatness ≤0.5mm/m |
6.2 Core Technical Parameters of Chilled Water Distribution Unit (CDU)
è¡¨æ ¼
| Series | Model | Rated Cooling Capacity | Heat Exchanger Type | Pump Configuration | Single Pump Flow | Pump Head | Max Working Pressure | Temp Control Precision | Power Supply | Max Supported Cabinets |
|---|---|---|---|---|---|---|---|---|---|---|
| Entry | KITOZER-CDU-LOW-20 | 20kW | 304SS plate | 1-working-1-standby variable frequency | 6m³/h | 25m | ≤1.6MPa | ±1℃ | 220V AC | ≤2 |
| Enterprise | KITOZER-CDU-MID-100 | 100kW | 316SS plate | 1-working-1-standby variable frequency | 30m³/h | 32m | ≤2.0MPa | ±0.8℃ | 380V AC | ≤5 |
| Flagship | KITOZER-CDU-HIGH-300 | 300kW | 316SS plate | 2-working-1-standby variable frequency | 80m³/h | 40m | ≤2.5MPa | ±0.5℃ | 380V AC | ≤5 |
| Universal Specs | Heat exchange efficiency ≥90% (GB/T 16401-2022); pump efficiency ≥85% (GB/T 13006-2013); system noise ≤65dB(A); full protection against overload, overtemp, overpressure, underpressure, leakage & low liquid level; Modbus/BACnet/SNMP support; MTBF ≥100,000h |
6.3 Core Technical Parameters of Open Cooling Tower
è¡¨æ ¼
| Series | Model | Rated Cooling Capacity | Air Volume | Fan Configuration | Spray Water Flow | Inlet/Outlet Temp | Wet Bulb Temp | Noise | IP Rating | Power Supply |
|---|---|---|---|---|---|---|---|---|---|---|
| Entry | KITOZER-CT-LOW-30 | 30kW | 5000m³/h | 0.75kW ×1 | 5m³/h | 37℃ / 32℃ | 28℃ | ≤65dB(A) | IP55 | 380V AC |
| Enterprise | KITOZER-CT-MID-150 | 150kW | 25000m³/h | 3kW ×2 | 25m³/h | 37℃ / 32℃ | 28℃ | ≤60dB(A) | IP55 | 380V AC |
| Flagship | KITOZER-CT-HIGH-400 | 400kW | 60000m³/h | 5.5kW ×4 | 60m³/h | 37℃ / 32℃ | 28℃ | ≤58dB(A) | IP55 | 380V AC |
| Universal Specs | Complies with GB/T 7190.1-2018; cooling temp difference ≥5℃, approach temperature ≤4℃; water drift rate ≤0.01%; packing flame retardancy V-0 (GB/T 2408-2021); shell anti-corrosion lifespan ≥15y, packing ≥8y; variable-frequency fan efficiency ≥80% |
6.4 Core Technical Parameters of Cold Plates
è¡¨æ ¼
| Model Type | Model No. | Compatible Device | Base Material | Channel Structure | Thermal Resistance | Working Flow | Max Working Pressure | Max Heat Flux | Flatness | Interface |
|---|---|---|---|---|---|---|---|---|---|---|
| Standard CPU | KITOZER-CP-INT-STD | General Intel/AMD CPU | C1100 oxygen-free copper | Micro-channel | ≤0.15℃/W | 3L/min | ≤1.6MPa | ≥80W/cm² | ≤50μm | G1/4 |
| High-Perf CPU | KITOZER-CP-INT-HIGH | High-end Server CPU | C1100 oxygen-free copper | Jet micro-channel | ≤0.08℃/W | 3L/min | ≤2.0MPa | ≥120W/cm² | ≤30μm | G3/8 |
| Flagship CPU | KITOZER-CP-INT-FLAG | Flagship AI Server CPU | Vacuum brazed oxygen-free copper | 3D stacked micro-channel | ≤0.05℃/W | 4L/min | ≤2.5MPa | ≥150W/cm² | ≤20μm | G1/2 |
| Standard GPU | KITOZER-CP-GPU-STD | Consumer/Professional GPU | Aluminum alloy | Micro-channel | ≤0.2℃/W | 2L/min | ≤1.6MPa | ≥60W/cm² | ≤50μm | G1/4 |
| High-Perf GPU | KITOZER-CP-GPU-HIGH | Data Center GPU | Oxygen-free copper | Multi-layer micro-channel | ≤0.1℃/W | 5L/min | ≤2.0MPa | ≥100W/cm² | ≤30μm | G3/8 |
| Flagship GPU | KITOZER-CP-GPU-FLAG | AI Training GPU | Vacuum brazed oxygen-free copper | Jet multi-layer micro-channel | ≤0.07℃/W | 6L/min | ≤2.5MPa | ≥120W/cm² | ≤20μm | G1/2 |
| Universal Specs | Comply with YD/T 6049-2024; pressure test at 1.5× working pressure for 30min with zero leakage; channel blockage rate ≤0.1%; thermal cycle lifespan ≥10,000 times; customizable for all mainstream CPU/GPU chips |
6.5 Core Technical Parameters of Circulation Water Pumps
è¡¨æ ¼
| Series | Model | Rated Flow | Rated Head | Rated Power | Wetted Material | IP Rating | Efficiency | Power Supply | Medium Temp Range | MTBF |
|---|---|---|---|---|---|---|---|---|---|---|
| Entry | KITOZER-PUMP-PRI-LOW | 10m³/h | 20m | 1.1kW | 304SS | IP55 | ≥75% | 380V AC | -15℃~110℃ | ≥80,000h |
| Enterprise | KITOZER-PUMP-PRI-MID | 30m³/h | 32m | 4kW | 316SS | IP55 | ≥82% | 380V AC | -20℃~120℃ | ≥100,000h |
| Flagship | KITOZER-PUMP-PRI-HIGH | 80m³/h | 40m | 11kW | 316SS | IP55 | ≥85% | 380V AC | -30℃~120℃ | ≥120,000h |
| Universal Specs | Comply with GB/T 13006-2013; mechanical seal leakage ≤3mL/h; vibration intensity ≤2.8mm/s (GB/T 29531-2013); overload, overtemp & leakage protection; 0–100% variable frequency speed regulation |
6.6 Core Technical Parameters of Intelligent Monitoring System
è¡¨æ ¼
| Module Name | Parameter Item | Technical Index |
|---|---|---|
| PLC Controller | Processor | 32-bit industrial processor, operation speed ≥0.1μs/instruction |
| I/O Ports | ≥16 digital input, ≥8 digital output, ≥16 analog input, ≥4 analog output | |
| Communication Ports | ≥2 Ethernet, ≥4 RS485/232, expandable 4G/5G | |
| Operating Temp | -40℃~85℃, IP20, MTBF ≥100,000h | |
| Industrial Touch Screen | Sizes | 7/10/15/21.5/27-inch optional |
| Resolution | 800×480 / 1024×768 / 1080P / 4K optional | |
| Touch Type | Capacitive multi-touch, response ≤10ms | |
| Operating Temp | -20℃~70℃, IP65, MTBF ≥50,000h | |
| Temperature Sensor | Measurement Range | -40℃~125℃, accuracy ±0.2℃, response ≤500ms, IP68 |
| Pressure Sensor | Range | 0–2.5MPa, accuracy ±0.5%FS, response ≤100ms, IP65 |
| Flow Sensor | Range | 0.5–100m³/h, accuracy ±1%FS, IP65, bidirectional measurement |
| Water Immersion Sensor | Point Type | Response ≤1s, IP67, false alarm rate ≤0.1% |
| Positioning Cable | Position accuracy ±0.2m, max length 1000m, response ≤500ms, IP67 | |
| Conductivity Sensor | Range | 0.055–100μS/cm, accuracy ±0.5%FS, temp compensation 0–100℃, IP68 |
6.7 Core Technical Parameters of Intelligent PDU
è¡¨æ ¼
| Series | Model | Rated Input | Output Interfaces | Metering Accuracy | Communication Protocol | IP Rating | Operating Temp | Protection Functions |
|---|---|---|---|---|---|---|---|---|
| Entry | KITOZER-PDU-LOW-16 | 16A 220V AC | 8×C13 | ±1% | Modbus-RTU | IP20 | -10℃~45℃ | Overload, short circuit, surge protection |
| Enterprise | KITOZER-PDU-MID-32 | 32A 380V AC dual input | 24×C13 + 8×C19 | ±0.5% | Modbus-TCP/IP | IP30 | -20℃~55℃ | Overload, short circuit, leakage, surge, over/undervoltage |
| Flagship | KITOZER-PDU-HIGH-63 | 63A 380V DC dual input | 36×C13 + 12×C19 | ±0.2% | Modbus-TCP/IP, SNMP | IP30 | -20℃~60℃ | Full power metering, harmonic monitoring, port-level protection, surge ≥20kA, fire linkage |
| Universal Specs | Comply with GB/T 7251.3-2017; flame retardant UL94 V-0; contact resistance ≤5mΩ; temperature rise ≤45K; surge protection ≥10kA |
7 Full Product Application Scope
With outstanding high-efficiency heat dissipation, low-carbon energy saving, high reliability and flexible deployment, the full KITOZER open water-cooled integrated cabinet line covers computing power infrastructure heat dissipation demands from edge computing to national supercomputing centers across all industries and scenarios.
7.1 Internet & AI Intelligent Computing Industry
- AI Large Model Training & Inference Clusters: Compatible with high-end NVIDIA H100/H200/A100 GPU clusters, single-cabinet heat dissipation up to 120kW to support 7×24-hour full-load large model training without chip frequency throttling. PUE drops below 1.1 to cut massive operating energy costs, serving as core selection for leading internet and AI enterprise intelligent computing centers.
- Cloud Computing & Cloud Service Data Centers: Flexible power configuration from 10kW–120kW compatible with new construction and existing renovation, boosting cabinet power density and meeting low-carbon PUE requirements of the national East Data West Computing strategy.
- Short Video / Live Streaming / E-Commerce Data Centers: High reliability and rapid deployment enable seamless air-liquid cooling switching to stabilize high-concurrency server operation and reduce air conditioning energy consumption for cost optimization.
7.2 Telecom & Communication Industry
- Carrier Core Data Centers: Fully compliant with YD/T communication standards for provincial and edge data centers of China Mobile, China Telecom and China Unicom, supporting mass deployment and centralized management to meet national energy-saving assessment targets for communications data centers.
- 5G/6G Core Network Computer Rooms: Compact small-series models deploy directly in edge machine rooms without large-scale renovation for efficient heat dissipation of core network equipment and low energy consumption for base station computer rooms.
- National Computing Network Edge Nodes: Containerized prefabricated models enable outdoor rapid construction without dedicated computer rooms, shortening construction cycles to advance implementation of the East Data West Computing strategy.
7.3 Financial Industry
- Bank/Securities/Insurance Core Data Centers: Adopt full 2N redundant architecture for ultra-high reliability and zero-interruption operation, complying with Class A GB 50174 data center standards to guarantee uninterrupted core transaction systems while meeting financial confidentiality compliance requirements.
- FinTech AI Computing Centers: High-density heat dissipation supports quantitative trading, risk control and intelligent investment advisory GPU clusters; precise temperature control extends server service life and minimizes equipment failure rates to sustain continuous financial business.
- Financial Disaster Recovery Data Centers: Rapid deployment and flexible scaling enable seamless docking with primary data centers, with low-carbon design cutting long-term disaster recovery operating costs.
7.4 Government & Public Utilities Industry
- Government Cloud Data Centers: Fully domestically produced, secure and reliable, meeting national e-government machine room construction standards to deliver low-carbon renovation and pass energy-saving evaluation for government energy conservation assessment.
- Public Security / Traffic Police / Judicial Big Data Centers: High-density heat dissipation processes massive video surveillance, face recognition and intelligent policing computing tasks; military-grade safety protection secures classified public security data compliant with confidential information system construction standards.
- Smart City Operation Centers: Micro-module integrated deployment enables centralized management of all smart city subsystems; optional waste heat recovery realizes circular energy utilization for zero-carbon smart city construction.
- Education & Research Institution Computer Rooms: Cost-effective entry-level models satisfy teaching and basic research computing demands; flagship ultra-high-density units serve university supercomputing platforms for scientific innovation research.
7.5 Supercomputing & Scientific Research Industry
- National / Provincial Supercomputing Centers: Flagship products deliver up to 120kW single-cabinet heat dissipation for extreme HPC scenarios including weather forecasting, petroleum exploration, aerospace engineering, biomedicine and quantum computing. Ultra-precise temperature control stabilizes supercomputing operation while drastically cutting massive supercomputing energy costs.
- National Defense & Military Research Computing Facilities: Custom military-grade confidential production fully meets national military secrecy standards, with 100% domestically controlled core components balancing extreme performance and data security for aerospace, ordnance and defense research clusters.
- New Energy & New Material R&D Computing Platforms: High-density heat dissipation supports long-duration numerical simulation for molecular modeling of batteries and advanced materials; stable heat dissipation guarantees accurate, continuous calculation results to accelerate technological innovation.
7.6 Medical & Healthcare Industry
- Hospital IT Data Centers: High reliability and low noise ensure uninterrupted core HIS/LIS/PACS medical information systems without noise pollution to clinical environments.
- Medical AI & Gene Sequencing Computing Centers: Ultra-high heat dissipation handles massive gene sequencing and medical image diagnostic AI computing tasks; precise temperature control stabilizes servers and sequencing equipment to advance precision medicine development.
- Public Health Big Data Platforms: Rapid deployment and flexible scaling support stable operation of epidemic monitoring and public health analysis systems with low-carbon design meeting energy-saving standards for public institutions.
7.7 Industrial & Energy Industry
- Industrial Internet Platform Data Centers: Deployable directly in factory workshops with dustproof, anti-interference and wide-temperature operation to stabilize intelligent manufacturing systems and advance Industry 4.0 transformation.
- Petroleum & Gas Exploration Computing Platforms: Ultra-high-density heat dissipation processes massive seismic exploration and geological modeling data; containerized models deploy rapidly in remote oilfields/mines without dedicated computer room construction for field computing power.
- Power Grid Dispatching & Computing Centers: Compliant with power industry machine room standards with high anti-interference reliability to secure stable grid operation; waste heat recovery enables cascade energy utilization inside power stations.
- Mining & Chemical Automation Control Rooms: Explosion-proof, anti-corrosion and wide-temperature design adapts to high-risk harsh industrial environments to guarantee safe, stable automated production monitoring systems.
7.8 Edge Computing & Special Scenarios
- Intelligent Transportation Edge Nodes: Compact wall-mounted/desktop models deploy in highway toll stations, tunnels and subway machine rooms for local low-latency processing of traffic data to sustain intelligent transportation systems.
- Outdoor Containerized Computing Nodes: Waterproof, fireproof, seismic and thermal insulation container units operate stably at -40℃~55℃ for remote regions, temporary computing demands and emergency disaster relief without dedicated buildings.
- Radio & Media Convergence Media Data Centers: High reliability and low noise deliver zero-interruption broadcast, media asset management and live streaming push systems while cutting energy operating costs.
- Small & Medium Enterprise Computer Rooms: Cost-effective entry-level models suit corporate office ERP, file and application servers with simple deployment, low maintenance and minimal air conditioning energy consumption to reduce small business IT operating expenses.
8 Full Product Advantages
Backed by over 10 years of liquid cooling R&D experience, KITOZER delivers full-chain capabilities covering core component independent R&D, full-machine manufacturing, customized solution design, installation commissioning and after-sales service, with industry-leading technical, performance and service strengths.
8.1 Extreme Heat Dissipation Performance to Break Computing Power Density Bottlenecks
- Industry-leading heat dissipation capacity: Single-cabinet power covers 10kW–120kW (max 150kW), over 10× higher than traditional air-cooled cabinets, eliminating high-temperature frequency throttling for continuous full computing power output in AI large model and supercomputing scenarios.
- High-efficiency heat exchange: Flagship cold plates adopt 3D stacked jet micro-channels with minimum thermal resistance of 0.05℃/W and max heat flux density of 150W/cm²; plate heat exchanger efficiency ≥98%, open cooling tower efficiency ≥90%. Chip junction temperature stabilizes below 85℃ (vs 105℃ air cooling upper limit), extending chip service life by over 50%.
- Ultra-precise intelligent temperature control: Closed-loop PLC variable-frequency control delivers temperature precision up to ±0.5℃ and flow precision ±2%, dynamically adjusting coolant flow/temperature based on server load to avoid energy waste and consistent chip temperature across variable loads.
- Full-component liquid cooling coverage: Custom cold plates for CPU, GPU, memory, NVSwitch and PCH chips enable 100% server liquid cooling and fan-zero silent racks, cutting machine room noise from 75dB(A) (air cooling) to below 50dB(A) for improved operation environments.
8.2 Ultra-Low Carbon Energy Saving to Slash Full-Lifecycle Operating Costs
- Class-leading energy efficiency: Open circulation maximizes natural cold source utilization (≥80% annual utilization in northern regions), PUE as low as 1.05, delivering 40%–60% energy savings vs traditional air cooling. Electricity savings over the 10-year product lifecycle far exceed initial equipment investment to lower total cost of ownership (TCO).
- National policy compliance: Fully aligns with national dual-carbon and East Data West Computing PUE limits (≤1.2 for new urban data centers, ≤1.15 for national hub nodes), passing energy-saving reviews and environmental assessments without risk of rectification or shutdown due to excessive energy consumption.
- Sharply improved space utilization: Single-cabinet power rises from traditional 5kW to above 50kW, cutting required machine room floor space by over 80% to reduce land, construction and supporting UPS/air conditioning investment with ≥20% lower overall initial capital expenditure.
- Value-added waste heat recovery: Optional waste heat recovery systems recycle over 90% of server waste heat for office heating, domestic hot water, agricultural greenhouses and industrial drying to realize cascade energy utilization, lower carbon emissions and generate additional economic & environmental benefits for zero-carbon data center construction.
8.3 High-Reliability Safety Design for Zero-Interruption System Operation
- Full-link redundant fault-tolerant architecture: N+1/2N redundancy for core pumps, cooling tower fans, power supplies and controllers enables seamless standby takeover within 500ms upon single-component failure without disrupting IT heat dissipation. 2N dual fully independent circulation systems support full-load takeover by one set upon complete failure of the other, meeting Class A financial/carrier/national supercomputing zero-interruption demands.
- Five-stage leakage prevention safety system: Multi-layer protection architecture: material sealing → joint leak resistance → cabinet liquid collection → regional cofferdams → system emergency shut-off. 304/316SS pipelines paired with double-seal self-locking quick-disconnects eliminate leakage during hot plugging; fully enclosed stainless steel liquid collection troughs + positioning leak detection cables achieve leak positioning precision ±0.2m and response ≤200ms, automatically closing branch shut-off valves and triggering sound-light alarms to eliminate liquid leakage risks to IT equipment.
- Full-dimensional intelligent protection logic: Built-in multi-layer protection against overtemperature, overpressure, underpressure, low liquid level, pump overload, filter blockage and excessive conductivity, executing graded disposal from alarm and standby switchover to orderly IT shutdown to avoid fault escalation with real-time alarm upload to environmental monitoring platforms. System MTBF ≥100,000 hours.
- Full-process water quality guarantee system: Five-stage filtration, softening, deaeration, sterilization and pH adjustment eliminates pipeline scaling, corrosion and microbial growth unique to open systems, extending pipeline service life to over 15 years (far exceeding industry averages).
- Electrical safety & surge protection: Full-system equipotential grounding with resistance ≤0.05Ω; power distribution delivers overload, short-circuit, leakage, over/undervoltage full protection with surge protection ≥20kA; complete electrical isolation between liquid cooling coolant and IT equipment eliminates conductive electrical fault risks to protect equipment and staff safety.
8.4 Flexible Compatible Deployment for Full-Scenario Adaptation
- Full-series product coverage: Complete 10kW–120kW power portfolio split into entry/enterprise/flagship tiers, with standard rack, micro-module, containerized and wall-mounted deployment forms to cover all scenarios from small corporate offices to national supercomputing centers for new construction and existing renovation projects.
- Ultra-high equipment compatibility: Cold plate liquid cooling requires minimal server modification (only replacing original CPU/GPU heat sinks), no full server replacement for low-cost, fast upgrades. Fully compatible with all Intel/AMD/NVIDIA chips and 99% of standard rack, blade and whole-rack servers; racks install side-by-side with legacy air-cooled units for smooth phased liquid cooling transition without large-scale building or layout adjustments.
- Rapid deployment & flexible scaling: Factory prefabricated modular design completes core assembly and testing off-site; on-site work only requires pipeline and electrical connection, cutting delivery cycles by 60% vs traditional construction. Micro-module and containerized units enable plug-and-play phased expansion to avoid one-time large capital investment and improve capital efficiency matching business growth.
- Extreme environmental adaptability: Stable operation across -40℃~55℃ ambient temperature with optional electric anti-freezing heaters for cold regions, enhanced dehumidification and anti-condensation systems for hot-humid zones. Outdoor containerized units deliver waterproof, fireproof, seismic, anti-corrosion and anti-theft performance for stable operation in plateaus, deserts, cold plains and remote mining/oilfield sites across all climate zones and geographies.
8.5 Full Domestic Production & Customization Capabilities
- 100% full-link independent domestic production: All core components (cold plates, CDU, cooling towers, pumps, PLC controllers, sensors) are self-developed and manufactured by KITOZER with zero import reliance, complying with national information innovation industry requirements to eliminate supply chain interruption risks for government, military and financial classified projects.
- In-depth customized development services: Fully customizable cabinet dimensions, power density, pipeline layout, control logic, appearance and communication protocols to match special chips, proprietary servers and non-standard equipment. End-to-end customized service covers demand research, solution design, R&D verification and mass production to resolve unique personalized customer requirements.
- OEM/ODM processing services: Large-scale modern production base delivers mass OEM/ODM manufacturing including core component OEM, full-machine white-labeling and brand customization with strict quality control and fast lead times to support partners entering the liquid cooling market rapidly.
- Military-grade confidential production services: Independent closed confidential production workshops and complete national confidential management systems accept military/classified customized projects with full closed-loop management of drawings, technical data and product information to meet strict secrecy standards for defense and government classified scenarios.
8.6 Spot Inventory & Full-Lifecycle Operation & Maintenance Services
- Mass spot inventory reserve: Complete spot stock for all standard models and core components enables 24-hour delivery for regular orders and same-day dispatch for urgent projects, resolving industry-wide long lead-time pain points for fast project launch.
- End-to-end professional technical services: A technical team with over 10 years of liquid cooling industry experience provides one-stop full-cycle services including pre-sales demand survey, site survey, solution design, delivery, installation commissioning, operator training and post-sales maintenance with dedicated one-on-one project managers to guarantee smooth project delivery and stable system operation.
- Professional operation & maintenance training services: Comprehensive theoretical + hands-on training covering system principles, equipment operation, daily inspection, fault diagnosis and emergency response with assessment certification to build customer professional maintenance teams for independent system operation.
- National after-sales service network: Service outlets covering all 31 provincial-level regions provide 7×24-hour after-sales support with 2-hour initial response, 4-hour on-site arrival in first-tier cities and 24-hour on-site service for remote areas, with fault repair time ≤2 hours to eliminate customer maintenance worries.
8.7 Industry-Leading R&D & Qualification Advantages
- Core technical R&D strength: Dedicated liquid cooling R&D center with industry-university-research cooperation with top domestic universities and research institutes, dozens of core liquid cooling technology patents and participation in drafting multiple national & industrial liquid cooling standards to guide industry technological development.
- Full-process quality control system: Certified ISO9001 quality management, ISO14001 environmental management and ISO45001 occupational health safety management systems with strict full-link testing from raw material procurement, production processing and finished product testing to factory delivery. All units undergo 72-hour full-load aging testing before shipment with finished product first-pass yield ≥99.8%.
- Complete industrial qualification certifications: Products pass national 3C, CE, UL and RoHS certifications, fully complying with YD/T communication and GB/T national standards to meet access requirements of telecom, finance, government and military industries and support smooth project acceptance and compliance review.
9 Core Tender Control Parameters
Parameters marked ★ are non-deviable core threshold indicators for bidding projects; remaining items are critical adjustable technical parameters aligned with project requirements.
9.1 Overall System Core Tender Parameters
- ★ System Architecture: Adopt dual independent loop architecture (primary open cold source circulation + secondary closed in-cabinet circulation) with complete physical isolation between primary and secondary loops for heat exchange via plate heat exchangers only, realizing full electrical isolation between IT equipment and coolant for safety.
- ★ Single-Cabinet Heat Dissipation Capacity: Continuous heat dissipation from 10kW–120kW with dynamic load adjustment; chip junction temperature ≤85℃ under full load, supply liquid temperature control precision ≤±1℃.
- ★ Energy-Saving Index: Annual average system PUE ≤1.15; natural cold source utilization ≥80% in northern regions; system energy efficiency ratio EER ≥25.
- ★ Redundancy Design: N+1/2N redundant configuration for core circulation pumps, cooling tower fans, controllers and power modules; main/standby switchover time ≤500ms with supply liquid pressure fluctuation ≤0.05MPa without IT equipment interruption.
- ★ Safety Protection: Five-stage leakage prevention architecture; positioning leak detection cables installed under cabinet liquid collection troughs with leak positioning precision ≤±0.5m and response ≤1s, automatically triggering sound-light alarms and closing corresponding branch emergency shut-off valves with fire linkage capability.
- ★ Control Functions: Three operating modes (fully automatic, manual, remote) with dual local + remote monitoring to enable unattended operation; support Modbus, BACnet and SNMP mainstream communication protocols for seamless docking with existing customer environmental monitoring and BMS platforms.
- ★ Standard Compliance: Design, manufacturing and testing fully comply with YD/T 6049-2024, T/CAICI 131-25 and GB 50174 national & industrial data center standards.
- ★ Reliability Index: System MTBF ≥100,000 hours; core component MTBF ≥80,000 hours; total system service lifespan ≥15 years.
9.2 Open Water-Cooled Integrated Cabinet Body Tender Parameters
- ★ Cabinet Specs: Standard 19-inch mounting, optional 42U/47U/48U; widths 600/800mm, depths 1200/1400/1600mm, heights 2000/2200/2250mm, compatible with standard rack, blade and whole-rack servers.
- ★ Structural Material: 9/13-fold welded frame with frame steel thickness ≥2.0mm, door plate ≥1.5mm high-quality cold-rolled steel; electrostatic anti-corrosion coating adhesion Grade 1 per GB/T 9286-1998, salt spray resistance ≥48h.
- ★ Load-Bearing Capacity: Static load ≥1500kg (entry) / ≥3000kg (enterprise) / ≥5000kg (flagship); cabinet verticality deviation ≤1‰, flatness ≤0.5mm/m.
- ★ Leak-Proof Design: Fully enclosed 304/316SS liquid collection trough at cabinet bottom with depth ≥50mm and ≥100mm high leak-proof cofferdam; liquid immersion sensors installed inside the trough for full-area leak monitoring.
- ★ Grounding System: Full cabinet equipotential grounding busbar cross-section ≥25mm², cabinet grounding resistance ≤0.1Ω complying with GB 50174 machine room grounding standards.
- ★ IP Rating: Cabinet protection grade ≥IP30 (entry) / ≥IP54 (enterprise) / ≥IP55 (flagship), complying with GB/T 4208-2017.
- ★ Door Design: Front/rear door opening rate ≥70%, mesh/tempered glass door optional with magnetic lock for single-hand operation, detachable side panels for easy maintenance.
- ★ Cable Management: Built-in vertical/horizontal cable channels with cable rings and tie holes, separate strong/weak current routing, reserved liquid cooling pipeline routing space to avoid cable interference.
9.3 Chilled Water Distribution Unit (CDU) Tender Parameters
- ★ Rated Cooling Capacity: Single CDU cooling capacity ≥20kW (entry) / ≥100kW (enterprise) / ≥300kW (flagship), heat exchange efficiency ≥90% to support multi-rack cluster heat dissipation.
- ★ Heat Exchanger: 304/316SS plate heat exchanger with plate thickness ≥0.5mm, pressure rating ≥1.6MPa (entry) / ≥2.0MPa (enterprise) / ≥2.5MPa (flagship), complying with GB/T 16401-2022.
- ★ Pump Configuration: Horizontal centrifugal variable-frequency pumps with 1-working-1-standby / 2-working-1-standby redundancy, pump efficiency ≥80%, full overload/overtemp/leakage protection, 0–100% variable speed regulation, MTBF ≥80,000h.
- ★ Pressure Stabilization & Replenishment: Built-in bladder expansion tank and automatic pressure-stabilizing replenishment device to stabilize system pressure automatically with precision ±0.02MPa, low liquid level alarm and auto replenishment using electronic-grade deionized water.
- ★ Filtration System: Three/five-stage precision filters with precision grades 100μm/50μm/5μm/1μm, filtration efficiency ≥99.9%, differential pressure blockage alarm to protect cold plate channels from clogging.
- ★ Monitoring Functions: Full array of built-in sensors for real-time supply/return liquid temp, pressure, flow, liquid level, conductivity and pH monitoring with measurement accuracy Class 0.5, real-time data upload to controller.
- ★ Controller: Industrial PLC with redundant power supply, ≥7-inch industrial touch screen for local parameter configuration, status display, fault query and data storage with storage cycle ≥1 year.
- ★ Communication Interfaces: ≥2 Ethernet ports, ≥4 RS485/232 ports supporting Modbus-RTU/TCP, BACnet and SNMP for remote monitoring & management.
- ★ Safety Protection: Automatic graded protection against overtemperature, overpressure, underpressure, low liquid level, pump overload, filter blockage and excessive conductivity with sound-light alarms and real-time alarm upload.
- ★ Pressure Resistance Performance: Full-machine pressure test at 1.5× working pressure with zero leakage or deformation after 30-minute holding.
9.4 Open Cooling Tower Tender Parameters
- ★ Rated Cooling Capacity: Single tower cooling capacity ≥30kW (entry) / ≥150kW (enterprise) / ≥400kW (flagship), complying with GB/T 7190.1-2018 Mechanical Draft Cooling Towers Part 1: Small & Medium Open Cooling Towers.
- ★ Cooling Performance: Design operating conditions: inlet 37℃, outlet 32℃, design wet bulb 28℃, cooling temp difference ≥5℃, approach temperature ≤4℃.
- ★ Fan System: Axial fans with aluminum alloy blades, efficiency ≥80%, variable-frequency motors with 0–100% speed regulation, IP55 F-class insulation, noise ≤65dB(A).
- ★ Spray System: Centrifugal spray nozzles with uniform non-clogging water distribution, matching spray pumps with 304SS wetted parts, water drift rate ≤0.01%.
- ★ Packing: Modified PVC high-efficiency packing with flame retardancy V-0 (GB/T 2408-2021), operating temp -20℃~70℃, service lifespan ≥8 years.
- ★ Material Requirements: Tower shell and water tray fabricated from ≥2mm thick 304/316SS with anti-corrosion coating, service lifespan ≥15 years.
- ★ Auxiliary Functions: Integrated water eliminators, descaling units, electric anti-freezing heaters (cold regions) and rainwater recovery with auto drain & replenishment capability.
- ★ IP Rating: Full outdoor unit IP55 complying with GB/T 4208-2017.
9.5 Cold Plate Tender Parameters
- ★ Compatibility: Fully compatible with all Intel/AMD CPU interfaces and all NVIDIA GPU interfaces; customizable to match customer specific chip models with perfectly matched bonding dimensions.
- ★ Base Material: C1100 oxygen-free copper substrate with vacuum brazing, thermal conductivity ≥401W/(m·K) for superior heat transfer performance.
- ★ Thermal Performance: Thermal resistance ≤0.15℃/W (standard) / ≤0.08℃/W (high-performance) / ≤0.05℃/W (flagship); max heat flux density ≥80W/cm² (standard) / ≥120W/cm² (high-performance) / ≥150W/cm² (flagship).
- ★ Channel Design: Internal micro/jet/3D stacked micro-channels with channel width ≥0.5mm and anti-clogging design, channel blockage rate ≤0.1%.
- ★ Machining Precision: Cold plate bottom flatness ≤50μm (standard) / ≤30μm (high-performance) / ≤20μm (flagship), surface roughness Ra ≤0.8μm to guarantee tight chip bonding.
- ★ Pressure Resistance: Max working pressure ≤1.6MPa (standard) / ≤2.0MPa (high-performance) / ≤2.5MPa (flagship); pressure test at 1.5× working pressure with zero leakage after 30-minute holding.
- ★ Interface Specs: Standard G1/4, G3/8 or G1/2 interfaces compatible with quick-disconnect fittings, zero leakage hot plugging with ≥1000 plug/unplug cycles.
- ★ Lifespan Performance: ≥10,000 thermal cycle tests with zero leakage, deformation or cracking.
9.6 Circulation Water Pump Tender Parameters
- ★ Rated Performance: Single pump rated flow ≥10m³/h (entry) / ≥30m³/h (enterprise) / ≥80m³/h (flagship); rated head ≥20m (entry) / ≥32m (enterprise) / ≥40m (flagship), pump efficiency ≥75%.
- ★ Wetted Components: 304/316SS wetted parts for corrosion resistance compatible with water-based coolant media.
- ★ Mechanical Seal: Cartridge mechanical seal with leakage ≤3mL/h, service lifespan ≥10,000h, compatible with medium temperature -20℃~120℃.
- ★ Motor Configuration: Three-phase asynchronous variable-frequency motors with IP55 F-class insulation, full overload/overtemp/phase loss protection, 0–100% variable speed regulation.
- ★ Vibration & Noise: Vibration intensity ≤2.8mm/s (GB/T 29531-2013), operating noise ≤65dB(A).
- ★ Reliability: MTBF ≥80,000 hours with ≥8,000 hours continuous fault-free operation.
- ★ Installation Form: Horizontal mounting with shock-absorbing bases, flexible connectors, check and stop valves for easy installation & maintenance.
9.7 Intelligent Monitoring System Tender Parameters
- ★ PLC Controller: 32-bit industrial processor with operation speed ≥0.1μs/instruction; ≥16 digital input, ≥8 digital output, ≥16 analog input, ≥4 analog output channels; operating temp -40℃~85℃, MTBF ≥100,000h.
- ★ Touch Screen: ≥7-inch industrial capacitive touch screen with resolution ≥800×480, response ≤10ms, operating temp -20℃~70℃, IP65 protection.
- ★ Temperature Sensors: Measurement range -40℃~125℃, accuracy ±0.2℃, response ≤500ms, IP68, 2/4-wire connection compatible.
- ★ Pressure Sensors: Measurement range 0–2.5MPa, accuracy ±0.5%FS, response ≤100ms, IP65, 4–20mA/RS485 signal output.
- ★ Water Immersion Sensors: Positioning leak detection cable with positioning precision ≤±0.5m, max detection length ≥100m, response ≤1s, IP67, false alarm rate ≤0.1%.
- ★ Flow Sensors: Measurement range 0.5–100m³/h, accuracy ±1%FS, IP65, bidirectional flow measurement, 4–20mA/RS485 output.
- ★ Communication Functions: Ethernet & RS485/232 ports supporting Modbus, BACnet and SNMP protocols for seamless docking with environmental monitoring platforms, WEB/APP remote access capability.
- ★ Data Storage: Local data storage with cycle ≥1 year, supporting data export, historical query and fault traceability.
- ★ Alarm Functions: Sound-light, SMS and platform multi-channel alarms with customizable threshold settings and full event recording & traceability.