Table of Contents
Toggle1. System Overview
The KITOZER liquid cooling integrated cabinet is a prefabricated, integrated, intelligent computing infrastructure oriented to new-generation high-density computing power scenarios, with liquid as the core heat transfer medium. It integrates cabinet frame, liquid cooling heat dissipation system, intelligent power distribution system, environmental monitoring system and safety protection system as a whole. Breaking through the technical bottlenecks of traditional air-cooled cabinets in heat dissipation efficiency, power density, energy consumption control and space occupation, the product adopts factory full prefabrication and whole-cabinet delivery mode to realize plug-and-play and rapid deployment, perfectly meeting the full-scenario demands of high heat density computing power such as AI large model training, high-performance computing, cloud computing and edge computing.
Driven by the dual catalysts of global “dual carbon” strategy implementation and explosive growth of computing power industry, traditional air-cooled cabinets can no longer meet the continuous heat dissipation demand above 20kW per cabinet, suffering core pain points including persistently high PUE, frequent local hotspots, high equipment failure rate and restricted computing power density. Leveraging the far higher specific heat capacity and thermal conductivity of liquid compared with air, the KITOZER liquid cooling integrated cabinet delivers over 1,000 times higher heat dissipation efficiency than air cooling. The single-cabinet power density can be lifted from 5–15kW of traditional air cooling to over 200kW, with the system PUE stably controlled within 1.05–1.15. It cuts cooling energy consumption by more than 40% compared with traditional air-cooled data centers, reduces machine room space occupation by 85%, drastically lowers equipment operating noise and extends the service life of IT devices, serving as a benchmark core infrastructure for new-generation green data centers and intelligent computing centers.
All KITOZER liquid cooling integrated cabinet full-series products strictly comply with national and industrial standards including YD/T 6049-2024 Technical Requirements and Test Methods for Cold Plate Liquid-Cooled Whole-Rack Servers and T/TAF 324—2026 Technical Requirements and Test Methods for Cold Plate Liquid-Cooled Cabinet Systems, while compatible with liquid cooling system provisions in the revised GB50174 Code for Design of Data Centers. Featuring full independent intellectual property rights with standardized design, production and delivery across all procedures, we provide full-dimensional services including standardized products, customized development, OEM/ODM processing, customized confidential scenarios and spot supply, fully covering computing power heat dissipation demands ranging from edge computing to national supercomputing centers.
2. System Composition
Adopting a modular integrated architecture, the KITOZER liquid cooling integrated cabinet system consists of six core subsystems and supporting auxiliary components. All subsystems complete factory prefabrication and joint commissioning tests to ensure rapid online operation after whole-cabinet delivery.
2.1 Cabinet Frame Bearing System
The cabinet frame acts as the physical bearing foundation of the entire system, providing installation space and structural support for IT equipment and liquid cooling/power distribution systems, while delivering core functions of protection, sealing and electromagnetic shielding. Key components are listed below:
- Cabinet main frame: Made of high-strength cold-rolled steel/stainless steel with frame thickness ≥2.0mm and door/side panel thickness ≥1.5mm. Surfaces undergo acid pickling, phosphating and anti-static epoxy powder spraying, reaching anti-corrosion grade C4 to adapt to complex high-humidity and salt-fog environments.
- Mounting uprights: Adopt standard 19-inch mounting holes compliant with EIA-310-D international standards. Uprights can be adjusted forward and backward to fit IT devices and liquid cooling components of varying depths, with clear U-position markings. Standard 42U/47U specifications are available, plus customized non-standard heights.
- Sealing protection components: Front/rear doors adopt high-density mesh doors or tempered glass doors with mesh opening rate ≥75% to support auxiliary air cooling. Door frames are fitted with EPDM rubber sealing strips for optional IP30–IP55 protection grades, preventing liquid leakage diffusion and dust ingress.
- Load-bearing & moving components: Heavy-duty load-bearing casters and support feet are installed at the cabinet bottom, with static load ≥1,600kg and dynamic load ≥1,200kg to meet load demands of high-density IT equipment. Lifting rings are mounted on the top for transportation and on-site installation.
- Electromagnetic shielding components: Optional six-sided metal shielding layers, waveguide windows and RF filters comply with GB/T 12190 Class A/B electromagnetic shielding standards, applicable to high-security scenarios such as confidential and financial machine rooms.
2.2 Core Liquid Cooling Heat Dissipation System
As the core functional unit of the entire cabinet, the liquid cooling heat dissipation system exports heat from core heating components of IT devices and realizes circulating heat dissipation, serving as the core carrier to achieve high heat density cooling. Key sub-components are detailed as follows:
2.2.1 Cooling Distribution Unit (CDU)
The CDU functions as the “control hub” of the liquid cooling system, responsible for coolant temperature regulation, flow distribution, pressure stabilization, water quality control and status monitoring. It realizes complete heat isolation and efficient heat exchange between the primary cold source loop and secondary load loop, divided into three types: cabinet-integrated CDU, side-mounted CDU and centralized CDU. Core components include:
- Plate heat exchanger: 316L stainless steel brazed plate heat exchanger with heat exchange efficiency ≥95%, fully isolating the primary and secondary sides to avoid impurities from the cold source entering the IT device side and guarantee IT equipment safety.
- Circulating pump set: Redundant variable-frequency centrifugal pumps (main + backup dual redundancy) with pump efficiency ≥85%. Pump speed and flow can be automatically adjusted according to load heat load, with automatic fault switching to ensure 7×24h uninterrupted system operation.
- Pressure stabilization & liquid replenishment module: Comprising diaphragm pressure expansion tank, automatic liquid replenishment pump, liquid replenishment water tank and filter, it automatically stabilizes system pressure, replenishes coolant and filters impurities to protect pipelines and cold plates from blockage.
- Safety protection components: Equipped with pressure relief valves, check valves, ball valves, butterfly valves and safety valves, with system burst pressure ≥3 times working pressure. It delivers overpressure, underpressure and reverse flow protection.
- Intelligent measurement & control module: Integrated with temperature, pressure, flow, liquid level and conductivity sensors to monitor real-time system operating status. It supports local display and remote monitoring, with linkage adjustment of valves and pump operation to realize closed-loop intelligent control.
2.2.2 Heat Exchange Execution Components
Directly contacting heating parts of IT equipment to complete heat exchange, these core heat exchange components fall into three technical categories:
- Cold plate heat exchange components: Fabricated from high thermal conductivity aluminum alloy/copper with micro-channel flow channels, directly attached to core heating parts including CPU, GPU, memory and SSD. Thermal resistance ≤0.05℃·cm²/W, covering over 90% of equipment heat generation, compatible with standard 1U/2U servers and AI accelerator cards.
- Immersion heat exchange tank: Sealed tank made of 304/316L stainless steel with built-in IT equipment mounting brackets, inlet/outlet flow channels and liquid level sensors. Tank pressure resistance ≥1.0MPa with IP67 sealing grade, fully accommodating IT equipment and cooling medium for full-device immersion heat dissipation.
- Rear door liquid cooling heat exchange components: Integrated into cabinet rear doors with air-liquid heat exchanger structure, replacing traditional cabinet rear doors to directly bear hot air exhausted by servers and realize heat exchange via coolant. Its heat exchange efficiency exceeds that of traditional air-cooled backboards by over 50 times, requiring no major modification to server bodies and ideal for rapid liquid cooling upgrade of legacy machine rooms.
2.2.3 Pipeline & Fluid Delivery System
Acting as the “vessels” of the liquid cooling system to transport and distribute coolant between CDU and heat exchange components, its core parts include:
- Main supply/return liquid pipelines: 304/316L stainless steel seamless tubes or food-grade PFA hoses with smooth inner walls and corrosion resistance, pressure resistance ≥1.6MPa to fit pipeline layout demands of various scenarios.
- Cabinet manifold: Made of 304 stainless steel with built-in multi-branch flow regulating valves and shut-off valves for uniform flow distribution among multiple IT devices inside a single cabinet. Each branch is equipped with an independent shut-off valve to support separate maintenance without disrupting overall system operation.
- Fluid quick connectors: Bidirectional self-sealing blind-mate quick connectors supporting pressure-bearing plug/unplug, with plug/unplug cycles ≥5,000 and pull-out force >800N. Leakage rate ≤1×10⁻⁹Pa·m³/s, featuring anti-misplug and anti-drop designs for fast installation and maintenance of servers.
- Sealing & connection components: Fluororubber/EPDM sealing gaskets compatible with multiple cooling media including mineral oil, fluorinated liquid and ethylene glycol aqueous solution, with temperature resistance range -40℃~120℃ and excellent anti-aging performance.
2.2.4 Cooling Medium
The heat transfer core medium of the system. KITOZER full-series products support multiple cooling media with flexible selection based on scenario demands:
- Water-based coolant: Deionized pure water/ethylene glycol aqueous solution featuring high thermal conductivity, large specific heat capacity and low cost, applicable to cold plate liquid cooling systems. Conductivity ≤5μS/cm with anti-corrosion, anti-scaling and anti-freezing properties.
- Insulating mineral oil: High insulation and chemical stability without corrosion, suitable for single-phase immersion liquid cooling systems. Breakdown voltage ≥35kV with kinematic viscosity matching system circulation requirements.
- Fluorinated liquid: Perfluoropolyether insulating coolant with outstanding insulation and stable chemical properties, non-flammable and non-explosive. Applicable to single-phase/phase-change immersion liquid cooling systems, enabling direct contact with electronic components without corrosion.
2.3 Intelligent Power Distribution System
The KITOZER liquid cooling integrated cabinet integrates a full-link intelligent power distribution system to realize full-process power supply, protection, monitoring and management from mains input to IT device terminals. Adopting a centralized bus power supply architecture that replaces traditional column cabinets, it improves power supply efficiency and reliability. Core components include:
- Input power distribution unit: Equipped with molded case circuit breakers, isolating switches and surge protection devices (SPD) to realize on/off control, overload protection, short-circuit protection and lightning protection for input power. Dual mains automatic switching is supported to meet power supply demands of Class A machine rooms.
- Centralized power shelf: High-efficiency rectifier modules with N+N/N+1 redundancy design and power conversion efficiency ≥96%. Multiple output formats (48V DC / 380V HVDC / 220V AC) are available, with maximum single-cabinet output power up to 200kW to fit power demands of different IT equipment.
- Copper busbar system: Oxygen-free copper busbars installed on cabinet sides/rears, replacing traditional cables to realize cable-free power supply inside cabinets. Nodes support hot swapping, cutting power supply loss by over 30% while greatly improving deployment and operation & maintenance efficiency.
- Branch power distribution & protection unit: Each IT equipment branch is fitted with miniature circuit breakers, fuses and energy metering modules to deliver branch-level overload/short-circuit protection, real-time monitoring of branch voltage, current, power and energy consumption, and support branch-level on/off control.
- Uninterruptible Power Supply (UPS) / backup energy storage unit: Optional rack-mounted UPS and lithium iron phosphate battery energy storage modules for seamless power switching upon power failure, with backup runtime selectable from 10 minutes to 4 hours to guarantee safe shutdown of IT and liquid cooling systems.
2.4 Intelligent Monitoring & Management System
Serving as the “intelligent brain” of the entire system, it realizes full-dimensional real-time monitoring, intelligent control, alarm management and data upload of cabinet liquid cooling, power distribution and environmental status. Core components include:
- Rack Management Controller (RMC): Industrial ARM architecture processor with multi-channel analog and digital signal acquisition interfaces, paired with a local 7-inch touchscreen for display and operation. It completes centralized data collection, logical operation, closed-loop control and alarm output for the whole system.
- Sensor cluster: Comprising temperature sensors (supply/return liquid temp, equipment temp, cabinet ambient temp), pressure sensors (supply/return liquid pressure, system differential pressure), flow sensors (total flow, branch flow), liquid level sensors, liquid leakage detection sensors, humidity sensors, smoke sensors and door magnetic sensors, delivering blind-spot-free monitoring of full system status.
- Intelligent control module: Adopting PID closed-loop control algorithm, it automatically adjusts coolant flow, pump speed and valve opening according to IT equipment load temperature to realize on-demand heat dissipation and minimize system energy consumption. Linkage control is supported to trigger graded alarms and protective actions including flow limiting, pump shutdown and power cut in response to abnormalities such as leakage, overtemperature and overload.
- Communication & upload module: Supporting standard communication protocols including Modbus TCP/IP, SNMP, B/S architecture and Redfish, it can connect to environment monitoring systems and Data Center Infrastructure Management (DCIM) platforms. Remote WEB access and mobile APP monitoring are available to realize unattended operation & maintenance.
- Data storage & analysis module: Supporting local storage of over 1 year of operating data, it generates energy consumption reports, operating trend analysis and fault early warning reports to enable predictive maintenance and reduce equipment failure rate.
2.5 Safety Protection System
A multi-layer safety protection architecture is built to address liquid cooling system operation safety and IT equipment protection demands, with core components as follows:
- Anti-leakage safety system: Triple anti-leakage protection mechanism. Layer 1: Highly reliable sealing design for pipelines and connectors; Layer 2: full-area liquid leakage detection ropes + point liquid leakage sensors inside cabinets; Layer 3: liquid collection trays, diversion grooves and shut-off valves to realize second-level leakage alarms, precise positioning, automatic isolation and collection, preventing liquid contact with live parts of IT equipment.
- Electrical safety system: Delivering overvoltage, undervoltage, overload, short-circuit, electric leakage and lightning protection. Grounding resistance ≤0.1Ω and insulation resistance ≥10MΩ. Strong and weak current systems are physically isolated, with liquid cooling pipelines and power distribution systems arranged in separate layers to eliminate electrical safety hazards caused by liquid leakage.
- Fire & environmental safety system: Integrated smoke and temperature sensors, with optional rack-mounted gas fire suppression modules for early fire warning and rapid extinguishing. Door magnetic locks and permission locks are equipped to control equipment access and prevent unauthorized operation.
- Emergency protection system: Fitted with emergency manual shut-off valves, emergency power interfaces and manual pressure relief valves for manual emergency operation upon power outages or system failures to protect IT equipment and the whole system.
2.6 Auxiliary Supporting System
- Cabinet cable management & fixing components: Vertical cable racks, horizontal cable organizers, cable fixing buckles and tie rods to standardize layout of strong/weak current cables and liquid cooling pipelines and avoid disorder and abrasion.
- Identification & labeling system: Standardized labels are installed on all system pipelines, valves, cables and interfaces to clearly mark medium flow direction, equipment name and interface numbers for convenient operation & maintenance and fault troubleshooting.
- Grounding system: Equipotential grounding for all cabinet frames, pipelines and power distribution equipment to avoid equipment damage caused by static accumulation and potential difference.
3. System Classification
Based on four dimensions (core liquid cooling technical route, single-cabinet power density, application scenario and deployment mode), the KITOZER liquid cooling integrated cabinet forms a full-series product matrix covering all scenario demands.
3.1 Classification by Core Liquid Cooling Technical Route
3.1.1 Cold Plate Liquid Cooling Integrated Cabinet Series
The mainstream liquid cooling solution in the current market, it realizes heat exchange by attaching cold plates directly to core heating parts of IT devices, with auxiliary air cooling for remaining components. It requires no major modification to server bodies and features strong compatibility and flexible deployment, serving as the preferred solution for new data center construction and legacy machine room upgrades. Divided into three sub-series based on cold plate coverage and deployment form:
- KITOZER-LC-CP Precision Cold Plate Liquid Cooling Cabinet: Cold plates are only installed on core heating chips such as CPU and GPU, applicable to medium-density scenarios with single-cabinet power of 15–30kW. Featuring low transformation cost and fast launch speed, it fits enterprise office machine rooms, edge computing nodes and small/medium-scale computing clusters.
- KITOZER-LC-FCP Full Cold Plate Liquid Cooling Cabinet: Cold plates fully cover all major heating components inside servers including CPU, GPU, memory, hard disks and power modules, with liquid cooling heat dissipation ratio ≥90%. Suitable for high-density scenarios with single-cabinet power of 30–100kW and stable PUE ≤1.09, it is the mainstream selection for AI inference clusters and enterprise-level data centers.
- KITOZER-LC-RCP Rear Door Cold Plate Liquid Cooling Cabinet: No server modification required. Liquid cooling heat exchange backboards are integrated into cabinet rear doors to directly bear hot air exhausted by servers for heat dissipation. Applicable to scenarios with single-cabinet power of 30–60kW, its transformation cost is 30%–50% lower than immersion cooling. Modular installation requires no extra machine room space, perfectly fitting rapid high-density upgrade of legacy machine rooms with transformation cycles shortened to 2 weeks.
3.1.2 Immersion Liquid Cooling Integrated Cabinet Series
IT equipment is fully immersed in insulating cooling medium to realize full-contact heat exchange via medium flow or phase change, delivering industry-leading heat dissipation efficiency and fan-free zero-noise operation, suitable for ultra-high density computing power scenarios. Divided into two sub-series based on medium heat exchange form:
- KITOZER-LC-SL Single-Phase Immersion Liquid Cooling Cabinet: Adopting insulating mineral oil/fluorinated liquid as cooling medium for liquid-phase circulating heat exchange without phase change. Featuring simple system structure and stable operation, its single-cabinet power density reaches 50–200kW with PUE as low as 1.05, applicable to ultra-high density computing power scenarios including AI large model training, supercomputing centers and gene sequencing.
- KITOZER-LC-PL Phase-Change Immersion Liquid Cooling Cabinet: Using low-boiling fluorinated liquid as cooling medium. The medium boils and vaporizes upon contact with heating components, with heat exchange completed via steam condensation to further lift heat dissipation efficiency and eliminate high-power circulating pumps for lower system energy consumption. Single-cabinet power density ranges from 100–900kW with PUE below 1.04, applicable to national supercomputing centers and large-scale AI training clusters with extreme computing power demands.
3.1.3 Spray Liquid Cooling Integrated Cabinet Series
Model KITOZER-LC-SP spray liquid cooling cabinet sprays insulating coolant directly onto heating surfaces of IT equipment via precision nozzles to form liquid films for efficient heat exchange. Coolant flows back to liquid storage tanks under gravity to complete circulation. Its heat dissipation efficiency falls between cold plate and immersion cooling, with coolant consumption only 20% of immersion systems and single-cabinet power density reaching 30–120kW, applicable to customized high-density computing power scenarios and special industrial computing scenarios.
3.2 Classification by Single-Cabinet Power Density
表格
| Product Tier | Rated Power Range | Core Applicable Scenarios | Compatible Technical Routes |
|---|---|---|---|
| Entry-level (Economical) | 15kW–30kW | Edge computing nodes, small/medium enterprise machine rooms, branch machine rooms, weak current rooms | Precision cold plate, rear door type |
| Mainstream (General) | 30kW–60kW | Enterprise-level data centers, cloud computing nodes, carrier local machine rooms, medium-scale AI inference clusters | Full cold plate, rear door type |
| High-density (Intelligent Computing) | 60kW–120kW | AI intelligent computing centers, large model training clusters, High-Performance Computing (HPC) centers, financial quantitative trading machine rooms | Full cold plate, single-phase immersion |
| Ultra-high Performance (Supercomputing) | 120kW–900kW | National supercomputing centers, large-scale AI pre-training clusters, weather forecasting centers, petroleum exploration data centers | Phase-change immersion, single-phase immersion |
3.3 Special Classification by Application Scenario
3.3.1 Edge Computing Dedicated Liquid Cooling Integrated Cabinet
KITOZER-LC-Edge series designed for edge computing scenarios with limited space, complex environments, unattended operation and low power consumption demands. It integrates liquid cooling heat dissipation, power distribution, UPS and environment monitoring in one unit with single-cabinet power of 15–30kW. Optional outdoor, wall-mounted and small rack-mounted types with maximum IP55 protection grade, supporting operation within -30℃~55℃ wide temperature range. Suitable for 5G edge nodes, smart transportation, industrial internet edge sites and park edge machine rooms.
3.3.2 AI Intelligent Computing Dedicated Liquid Cooling Integrated Cabinet
KITOZER-LC-AI series customized for high-density GPU clusters for AI large model training, with single-cabinet power of 60–200kW, compatible with full-series AI accelerator cards including NVIDIA, AMD and Ascend. Adopting full blind-mate design with electric, network and liquid three-bus architecture and cable-free cabinet interior, nodes support hot swapping to boost operation & maintenance efficiency by 10 times. Built-in precise GPU temperature control system enables single-card flow adjustment to guarantee stable full-load operation of GPU clusters, lifting computing power density by 3–10 times compared with traditional air cooling.
3.3.3 Confidential Scenario Dedicated Liquid Cooling Integrated Cabinet
KITOZER-LC-SEC series for military, government and confidential unit machine rooms, featuring four core characteristics: electromagnetic shielding, audio/video shielding, physical anti-theft and full autonomous controllability with localization compatibility. Shielding performance meets national BMB standards, compatible with localized CPUs, operating systems and servers. Full-process confidential production and customized development are supported, with customized confidentiality agreements and full-process control schemes for on-site deployment and operation & maintenance in confidential scenarios.
3.3.4 Containerized Liquid Cooling Integrated Cabinet Cluster
KITOZER-LC-Container series integrates multiple liquid cooling integrated cabinets, CDU, cold source, power distribution and monitoring systems inside standard containers with full factory prefabrication and integral transportation for plug-and-play on-site deployment without machine room civil construction. Full system deployment and launch can be completed within 7 days, with single-container power reaching 1MW–5MW. Applicable to rapidly deployed temporary computing clusters, remote supercomputing nodes and emergency computing power support scenarios.
3.3.5 High-Performance Computing (HPC) Dedicated Liquid Cooling Integrated Cabinet
KITOZER-LC-HPC series for research institutes, supercomputing centers, petroleum exploration, weather forecasting and life science HPC scenarios with single-cabinet power over 100kW, supporting phase-change immersion liquid cooling technology for extreme heat dissipation efficiency. It guarantees long-term stable full-load operation of CPU/GPU clusters with ultra-high reliability and redundant design to meet 7×24h uninterrupted operation demands, while delivering extreme energy saving and consumption reduction to support green low-carbon certification of supercomputing centers.
3.4 Classification by Deployment Mode
- Integrated liquid cooling cabinet: CDU, power distribution and monitoring systems are all integrated inside a single cabinet. Each cabinet operates as an independent system requiring no external supporting facilities, only mains and cold source access for rapid deployment, suitable for small-scale distributed deployment scenarios.
- Modular liquid cooling cabinet cluster: Multiple cabinets share one set of centralized CDU and power distribution systems for cluster deployment and unified management, suitable for medium/large data centers and computing clusters with flexible on-demand horizontal expansion.
- Whole-cabinet prefabricated delivery solution: All installation, wiring, pressure testing and joint commissioning are completed in factories. Whole cabinets are transported to sites, requiring only connection of external cold source, mains and network for rapid launch. On-site construction workload is cut by 90% and business launch cycle shortened by over 80%.
4. System Schematic Principles
4.1 Operating Principle of Cold Plate Liquid Cooling Integrated Cabinet System
The KITOZER cold plate liquid cooling integrated cabinet system adopts a dual-cycle isolated architecture divided into primary cold source cycle and secondary load cycle. Heat isolation and efficient exchange between the two cycles are realized via plate heat exchangers inside CDU, completely preventing impurities and scale from the primary cold source from entering the secondary IT device side to guarantee IT equipment safety.
4.1.1 Primary Cold Source Cycle Workflow
- Low-temperature coolant output by outdoor cold sources (closed cooling towers, chillers, natural cold sources) enters the primary channel of CDU internal plate heat exchangers via primary supply liquid pipelines.
- Low-temperature coolant absorbs heat from secondary high-temperature coolant during heat exchange inside plate heat exchangers and rises in temperature.
- Heated coolant flows back to outdoor cold sources via primary return liquid pipelines for heat dissipation and cooling to complete a closed primary cycle.
- Electric regulating valves are installed on the primary cycle to automatically adjust valve opening based on secondary return liquid temperature and control primary coolant flow for precise temperature control of heat exchange.
4.1.2 Secondary Load Cycle Workflow
- Cooled low-temperature coolant inside plate heat exchangers is pressurized by CDU internal circulating pump sets and delivered to secondary main supply liquid pipelines.
- Low-temperature coolant enters cabinet internal manifolds via main supply pipelines and is evenly distributed to cold plate branches of each server.
- Low-temperature coolant flows into server cold plates to complete heat exchange with attached heating chips such as CPU and GPU, absorbing chip heat and turning into high-temperature coolant.
- High-temperature coolant flows back to cabinet return liquid manifolds via server return ports, converges and flows back to secondary channels of CDU plate heat exchangers through secondary main return liquid pipelines.
- High-temperature coolant transfers heat to primary coolant inside plate heat exchangers, cools down and re-enters circulating pump sets to complete a closed secondary cycle.
- Variable-frequency control is equipped on the secondary cycle to automatically adjust circulating pump speed and branch flow according to server load temperature and return liquid temperature for on-demand heat dissipation and maximum system energy reduction.
4.1.3 Safety & Monitoring Closed-Loop Principle
A full-dimensional sensor cluster is built into the system to real-time monitor primary/secondary supply/return liquid temperature, pressure, flow, differential pressure, liquid level, conductivity, server chip temperature, cabinet ambient temperature/humidity and liquid leakage status. Graded alarms are triggered automatically when monitored data exceeds normal thresholds:
- Level 1 Early Warning: Slight overtemperature or abnormal pressure. The system automatically adjusts pump speed and valve opening while pushing early warning notifications.
- Level 2 Alarm: Severe overtemperature or liquid leakage detected. The system triggers audible/visual alarms, pushes remote alarm notifications and executes flow limiting and branch valve shut-off automatically.
- Level 3 Emergency Protection: Major leakage or severe overtemperature threatening equipment safety. The system automatically executes full-process protective actions including pump shutdown, main supply liquid valve cut-off and IT equipment power cut to guarantee equipment safety.
4.2 Operating Principle of Single-Phase Immersion Liquid Cooling Integrated Cabinet System
The KITOZER single-phase immersion liquid cooling integrated cabinet system also adopts a dual-cycle isolated architecture, differing from cold plate systems in that secondary cycle heat exchange is immersion-based, requiring no cold plate modification to servers with full immersion of IT equipment in insulating cooling medium for full-contact heat exchange.
4.2.1 Primary Cold Source Cycle Workflow
Consistent with cold plate liquid cooling systems: heat export and dissipation are completed via outdoor cold sources, primary pipelines and CDU plate heat exchangers to realize complete isolation between secondary side and cold source.
4.2.2 Secondary Load Cycle Workflow
- Cooled low-temperature insulating cooling medium inside plate heat exchangers is pressurized by CDU circulating pump sets and enters the bottom liquid inlet of immersion liquid cooling tanks.
- Low-temperature cooling medium flows upward evenly via diversion structures at tank bottoms, fully wrapping servers, switches and other IT equipment to directly contact all heating components and absorb heat generated by equipment operation, with medium temperature rising.
- Heated high-temperature cooling medium flows out via tank top return ports, flows back to CDU plate heat exchangers through secondary return liquid pipelines and transfers heat to primary coolant.
- Cooled cooling medium is pressurized again by circulating pump sets and delivered into immersion tanks to complete a closed secondary cycle.
- Liquid level and temperature sensors are built into the system to real-time monitor medium liquid level and temperature inside tanks, automatically adjust medium flow and circulating pump speed, and support automatic liquid replenishment upon low liquid level and overtemperature protection.
4.3 Operating Principle of Phase-Change Immersion Liquid Cooling Integrated Cabinet System
The KITOZER phase-change immersion liquid cooling integrated cabinet system operates on phase-change heat transfer principles, eliminating high-power circulating pump sets for simpler system structure, lower energy consumption and higher heat exchange efficiency.
- IT equipment is fully immersed in low-boiling insulating fluorinated liquid with a boiling point of 30–50℃. Heat generated by equipment operation heats contacted fluorinated liquid to boiling point for vaporization from liquid to gas phase.
- Fluorinated liquid vapor rises to condensation coils at immersion tank tops. Low-temperature cooling water flows inside condensation coils, and vapor releases heat upon contact with condensation coils before recondensing into liquid fluorinated liquid, which flows back to tank bottoms under gravity to complete natural medium circulation.
- Cooling water inside condensation coils absorbs vapor heat and rises in temperature, flowing back to outdoor cold sources for heat dissipation and cooling before re-entering condensation coils to complete the cold source cycle.
- Pressure, temperature and liquid level sensors are built into the system to real-time monitor tank internal pressure, temperature and medium liquid level, automatically adjust cooling water flow and maintain stable system pressure and temperature ranges, while supporting overtemperature, overpressure and low liquid level alarms and protection.
4.4 Operating Principle of Rear Door Cold Plate Liquid Cooling Integrated Cabinet System
The KITOZER rear door cold plate liquid cooling integrated cabinet system requires no server modification and realizes heat dissipation via air-liquid heat exchange backboards installed on cabinet rear doors, ideal for rapid liquid cooling upgrade of existing air-cooled servers. Operating workflow as follows:
- Built-in server fans exhaust heat generated by heating components such as CPU and GPU in the form of hot air, which blows directly toward liquid cooling heat exchange backboards on cabinet rear doors.
- Low-temperature coolant flows through internal flow channels of heat exchange backboards. Hot air contacts heat exchange backboards and transfers heat to internal coolant, with hot air cooling down and coolant absorbing heat to rise in temperature.
- Heated coolant flows back to CDU via return liquid pipelines, completes heat exchange with primary cold sources through plate heat exchangers, cools down and is delivered to rear door heat exchange backboards again by circulating pumps to complete a closed cycle.
- The system can automatically adjust coolant flow and pump speed based on cabinet internal hot air temperature and server chip temperature to realize on-demand heat dissipation, fully replacing cabinet-level heat dissipation of traditional precision air conditioners and drastically cutting machine room cooling energy consumption.
5. Full System Configuration List
The KITOZER liquid cooling integrated cabinet system configuration list is divided into three tiers: Entry-level (Economical), Mainstream (General) and High-density (Intelligent Computing). All series adopt unified KITOZER brand standards.
5.1 Entry-level (Economical) Liquid Cooling Integrated Cabinet Configuration List
Single-cabinet power: 15–30kW, precision cold plate / rear door type, applicable to edge computing and small/medium machine rooms
表格
| No. | Product Name | Model Specification | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | Liquid Cooling Special Standard Cabinet | KITOZER-LC-CAB-42U-E | 42U standard 19-inch cabinet, dimensions 600mm×1200mm×2200mm; frame thickness 2.0mm, door panel thickness 1.5mm; cold-rolled steel with anti-static spraying; static load ≥1,600kg; IP30 protection grade; front/rear high-density mesh doors with opening rate ≥75%; equipped with mounting uprights, cable racks, load-bearing feet, casters and door locks | 1 | Set | KITOZER | Main cabinet body, 47U customizable |
| 2 | Cabinet-Integrated Mini CDU | KITOZER-LC-CDU-30-E | Rated heat exchange power 30kW; 316L stainless steel plate heat exchanger with efficiency ≥95%; single circulating pump, power 0.75kW, head 20m, flow 10m³/h; built-in expansion tank, precision filter, shut-off valve, check valve and pressure relief valve; real-time monitoring of supply/return liquid temperature, pressure and flow; Modbus TCP communication; AC220V input; IP20 protection grade | 1 | Set | KITOZER | Installed at cabinet bottom, dual pump redundant version optional |
| 3 | Cabinet Supply/Return Liquid Manifold | KITOZER-LC-MAN-8-E | 304 stainless steel; 1 main inlet + 1 main outlet, 8 branch supply/return channels; each branch equipped with needle flow regulating valve, shut-off valve and pressure gauge; design pressure resistance 1.0MPa; DN15 main pipeline, DN8 branch pipeline; equipped with quick connector interfaces | 1 | Set | KITOZER | Fits 8 standard 2U servers, expandable branch quantity |
| 4 | Server CPU Special Cold Plate | KITOZER-LC-CP-CPU-E | Compatible with full-series Intel/AMD/Hygon/Feiteng CPUs; aluminum alloy micro-channel structure, thermal resistance ≤0.08℃·cm²/W; design pressure resistance 1.0MPa; fits standard 2U servers; matched thermal grease and fixing buckles; leakage rate ≤1×10⁻⁹Pa·m³/s | 8 | Pcs | KITOZER | Configured by server CPU quantity, 2 plates per single server |
| 5 | Blind-Mate Self-Sealing Quick Connector | KITOZER-LC-QC-04-E | DN8 specification; bidirectional self-sealing, pressure-bearing plug/unplug; 316L stainless steel; plug/unplug cycles ≥5,000; working pressure 1.0MPa; temperature resistance -40℃~120℃; leakage rate ≤1×10⁻⁹Pa·m³/s; compatible with PFA hoses/steel pipes | 16 | Sets | KITOZER | 1 set each for supply/return liquid per server, including male/female heads |
| 6 | Liquid Cooling Special Pipeline System | KITOZER-LC-PIPE-E | DN20 304 stainless steel seamless main pipelines; DN8 PFA food-grade branch hoses; matched pipe fittings, elbows, tees, fixing buckles and pipe clamps; smooth inner wall with corrosion resistance; design pressure resistance 1.6MPa; full set supplied per cabinet | 1 | Set | KITOZER | Includes all cabinet internal pipelines and connecting fittings |
| 7 | Intelligent Power Distribution Unit | KITOZER-LC-PDU-32-E | 32A input, 20 C13 output ports, 4 C19 output ports; AC220V input; real-time display of voltage, current, power and energy; overload/short-circuit protection supported; remote on/off control and monitoring; Modbus TCP communication protocol; industrial-grade design | 2 | Sets | KITOZER | Vertically installed inside cabinets, main/backup dual configuration |
| 8 | Input Power Distribution Protection Unit | KITOZER-LC-IB-63-E | 63A 3P molded case circuit breaker; 2P surge protection device (SPD), In=20kA, Imax=40kA; dual mains automatic transfer switch; matched distribution box, mounting rails and wiring terminals; IP30 protection grade | 1 | Set | KITOZER | Installed at cabinet top for input power protection and switching |
| 9 | Rack Management Controller | KITOZER-LC-RMC-E | Industrial ARM processor; 7-inch industrial touchscreen; 16 AI analog inputs, 32 digital inputs, 16 relay outputs; supports collection of temperature, pressure, flow and liquid leakage signals; PID closed-loop control; Modbus TCP/IP & SNMP protocols; remote WEB access supported; AC220V input | 1 | Set | KITOZER | Core system controller for full-system monitoring and management |
| 10 | Sensor Cluster | KITOZER-LC-SEN-E | 4 supply/return liquid PT100 temperature sensors (accuracy ±0.2℃); 2 supply/return liquid pressure sensors (range 0–1.6MPa, Class 0.5 accuracy); 1 flow sensor (range 0–15m³/h, Class 1 accuracy); 2 cabinet temperature/humidity sensors (0–50℃, 0–100%RH); 2 point liquid leakage sensors, 5m liquid leakage detection rope (response time ≤1s); 1 smoke sensor, 1 door magnetic sensor | 1 | Set | KITOZER | Full-system status monitoring including all installation fittings |
| 11 | Anti-Leakage Safety Components | KITOZER-LC-LEAK-E | Stainless steel full-size liquid collection tray at cabinet bottom matching cabinet dimensions; diversion grooves and drain joints; EPDM rubber sealing gaskets for all pipelines; 2 emergency manual shut-off valves; matched fixing installation fittings | 1 | Set | KITOZER | Leakage protection and collection to guarantee equipment safety |
| 12 | Auxiliary Cooling Fan Unit | KITOZER-LC-FAN-E | 4 pcs 12038 cabinet cooling fans with EC variable-frequency speed regulation; automatic speed adjustment based on temperature; air volume ≥120CFM per fan; noise ≤55dB; DC24V input | 1 | Set | KITOZER | Auxiliary air cooling for heat dissipation of memory, hard disks and other components |
| 13 | Cabinet Accessories | KITOZER-LC-ACC-E | 10 cabinet blanking plates, U-position marking strips, 2 vertical cable racks, cable fixing buckles, grounding copper bars, equipotential connecting wires, equipment identification labels and pipeline flow direction labels | 1 | Set | KITOZER | Supporting installation and operation & maintenance accessories |
5.2 Mainstream (General) Liquid Cooling Integrated Cabinet Configuration List
Single-cabinet power: 30–60kW, full cold plate type, applicable to enterprise data centers and AI inference clusters
表格
| No. | Product Name | Model Specification | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | High-Density Liquid Cooling Special Cabinet | KITOZER-LC-CAB-47U-M | 47U standard 19-inch cabinet, dimensions 800mm×1200mm×2200mm; frame thickness 2.5mm, door panel thickness 2.0mm; premium cold-rolled steel with acid pickling, phosphating and anti-static epoxy spraying; static load ≥2,000kg; IP40 protection grade; front/rear double-opening mesh doors with opening rate ≥80%; equipped with adjustable mounting uprights, vertical cable racks, heavy-duty feet, lifting rings and anti-theft door locks | 1 | Set | KITOZER | Customizable non-standard sizes, stainless steel and electromagnetic shielding versions |
| 2 | Side-Mounted CDU Cooling Distribution Unit | KITOZER-LC-CDU-60-M | Rated heat exchange power 60kW; 316L stainless steel brazed plate heat exchanger with efficiency ≥96%; dual variable-frequency centrifugal pump redundancy design with automatic main/backup switching, single pump power 1.5kW, head 30m, flow 20m³/h; built-in diaphragm expansion tank, automatic liquid replenishment unit, two-stage precision filter, electric regulating valve, check valve, pressure relief valve and safety valve; full-dimensional sensor monitoring of supply/return liquid temperature, pressure, flow, liquid level and conductivity; industrial PLC controller with 7-inch touchscreen and adaptive PID closed-loop control; Modbus TCP/IP, SNMP and Redfish protocols supported; AC380V input; IP30 protection grade | 1 | Set | KITOZER | Single CDU fits 2–4 cabinets, centralized CDU customizable |
| 3 | Cabinet Supply/Return Liquid Manifold | KITOZER-LC-MAN-16-M | 304 stainless steel; 1 main inlet + 1 main outlet, 16 branch supply/return channels; each branch equipped with high-precision flow regulating valve, shut-off valve, digital pressure gauge and check valve; design pressure resistance 1.6MPa; DN25 main pipeline, DN10 branch pipeline; matched blind-mate quick connector interfaces with exhaust and drain valves | 1 | Set | KITOZER | Fits 16 pcs 1U/2U servers, expandable branch quantity |
| 4 | Full-Cover CPU+GPU Cold Plate Assembly | KITOZER-LC-CP-FULL-M | Compatible with full-series Intel/AMD/Ascend/NVIDIA CPUs/GPUs; copper-aluminum composite micro-channel structure, thermal resistance ≤0.05℃·cm²/W; design pressure resistance 1.6MPa; fits 1U/2U standard servers and AI accelerator cards; matched high thermal conductivity thermal pads and fixing brackets; leakage rate ≤1×10⁻⁹Pa·m³/s; customized flow channel design supported | 16 | Sets | KITOZER | Each set includes CPU cold plate + GPU cold plate, configured by server quantity |
| 5 | High-Reliability Blind-Mate Fluid Quick Connector | KITOZER-LC-QC-06-M | DN10 specification; bidirectional self-sealing supporting dynamic pressure plug/unplug; 316L stainless steel main body with fluororubber sealing gaskets; plug/unplug cycles ≥5,000; working pressure 1.6MPa; temperature resistance -40℃~120℃; leakage rate ≤1×10⁻⁹Pa·m³/s; anti-misplug and anti-drop design, compatible with steel pipes/hoses | 32 | Sets | KITOZER | 1 set each for supply/return liquid per server, including male/female heads |
| 6 | Full-System Liquid Cooling Pipeline System | KITOZER-LC-PIPE-M | DN25 304/316L stainless steel seamless main pipelines; DN10 316L stainless steel corrugated pipes/PFA branch hoses; matched elbows, tees, reducers, loose joints, pipe clamps and fixing brackets; passivated inner walls for corrosion resistance and anti-scaling; design pressure resistance 1.6MPa; hydraulic test pressure 2.4MPa; full set including cabinet internal and inter-cabinet connecting pipelines per cabinet | 1 | Set | KITOZER | 316L stainless steel customizable for special media |
| 7 | Centralized Intelligent Power Distribution System | KITOZER-LC-PDB-100-M | Rated input current 100A, 3P AC380V input; dual mains automatic transfer with switching time ≤50ms; equipped with molded case circuit breakers and surge protection devices (In=40kA, Imax=80kA), branch miniature circuit breakers; optional 380V HVDC / 220V AC output; matched distribution box, mounting rails and wiring terminals; IP30 protection grade; full input/output electrical parameter monitoring supported | 1 | Set | KITOZER | Integrated installation at cabinet top, compatible with bus power supply systems |
| 8 | Rack-Mounted UPS Power System | KITOZER-LC-UPS-10k-M | Online rack-mounted UPS, rated capacity 10kVA/10kW; AC380V input, AC220V output; dual-conversion online type with 0ms switching time; built-in lithium iron phosphate battery pack with 15-minute backup runtime; parallel expansion supported; LCD touchscreen display, remote monitoring supported; full overload, short-circuit, overvoltage and undervoltage protection; 3U rack-mounted installation | 1 | Set | KITOZER | Customizable backup runtime, 48V DC power supply system optional |
| 9 | Intelligent Bus Power Distribution System | KITOZER-LC-BUSBAR-M | Oxygen-free copper busbar with rated current 160A; 3P+N+PE structure, insulation Class F; compatible with 8 hot-swappable plug-in boxes, each fitted with 32A miniature circuit breaker and energy metering module; supports branch-level electrical parameter monitoring and on/off control; vertically installed inside cabinets for cable-free layout; IP20 protection grade | 1 | Set | KITOZER | Replaces traditional PDU to lift power supply efficiency and operation & maintenance convenience |
| 10 | Industrial-Grade Rack Management Controller | KITOZER-LC-RMC-M | Industrial ARM Cortex-A9 dual-core 1GHz processor; 10.1-inch industrial touchscreen (1024×600 resolution); 32 AI analog inputs, 64 digital inputs, 32 relay outputs; supports full-system sensor data collection and adaptive PID closed-loop control for precise flow/temperature/pressure regulation; graded alarms and linkage protection logic for faults; Modbus TCP/IP, SNMP and BACnet protocols supported; remote WEB access, mobile APP monitoring and DCIM platform access; dual redundant power supply, industrial wide-temperature operation | 1 | Set | KITOZER | Core system control and management unit for intelligent operation & maintenance |
| 11 | High-Precision Sensor Cluster | KITOZER-LC-SEN-M | 6 supply/return liquid Class A PT100 temperature sensors (accuracy ±0.15℃); 4 supply/return liquid pressure sensors (range 0–2.5MPa, Class 0.2 accuracy); 1 total flow sensor + 16 branch flow sensors (Class 0.5 accuracy); 2 liquid level sensors, 1 conductivity sensor; 4 cabinet temperature/humidity sensors (-20℃~80℃, 0–100%RH); 10m full-area liquid leakage detection rope, 4 point liquid leakage sensors (response time ≤1s); 2 smoke sensors, 2 door magnetic sensors, 2 vibration sensors | 1 | Set | KITOZER | Blind-spot-free full-system status monitoring including all installation fittings and calibration certificates |
| 12 | Triple Anti-Leakage Safety System | KITOZER-LC-LEAK-M | Full-size 304 stainless steel liquid collection tray at cabinet bottom with liquid level monitoring; full-pipeline diversion grooves and splash guards; 4 emergency manual shut-off valves, 16 branch emergency cut-off solenoid valves; fluororubber sealing gaskets for full system with anti-aging and corrosion resistance; liquid leakage alarm and automatic cut-off linkage system; liquid leakage emergency handling kit | 1 | Set | KITOZER | Realizes second-level leakage alarms, automatic isolation and emergency protection |
| 13 | Auxiliary Air Cooling Unit | KITOZER-LC-AUX-M | EC variable-frequency fan group on cabinet front/rear doors with 8 pcs 12038 fans; automatic speed regulation based on cabinet internal temperature; air volume ≥150CFM per fan; noise ≤50dB; redundant hot-swappable design; DC24V input | 1 | Set | KITOZER | Auxiliary heat dissipation for non-liquid-cooled components |
| 14 | Rack-Mounted Gas Fire Suppression Unit | KITOZER-LC-FIRE-M | Full-hexanone clean gas fire suppression, 2U rack-mounted installation; 2kg fire suppressant dosage; matched composite smoke/temperature detectors, audible/visual alarms; manual/automatic start modes; high fire-extinguishing efficiency with no residue and no damage to electronic equipment, compliant with fire protection codes | 1 | Set | KITOZER | Optional for high-safety demand scenarios |
| 15 | Cabinet Supporting Accessories | KITOZER-LC-ACC-M | 20 cabinet blanking plates, U-position marking strips, 4 vertical cable racks, 8 horizontal cable organizers, cable fixing buckles and ties; grounding copper bars, equipotential connecting wires and jumpers; full-system equipment labels, pipeline flow direction labels, valve labels and safety warning labels; special operation & maintenance tool kit | 1 | Set | KITOZER | Full supporting accessories for installation and operation & maintenance |
5.3 High-Density (Intelligent Computing) Liquid Cooling Integrated Cabinet Configuration List
Single-cabinet power: 60–200kW, single-phase immersion / full cold plate type, applicable to AI intelligent computing centers and large model training clusters
表格
| No. | Product Name | Model Specification | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | Ultra-High Density Immersion Liquid Cooling Cabinet | KITOZER-LC-CAB-47U-H | 47U immersion liquid cooling dedicated cabinet, dimensions 1200mm×1500mm×2200mm; 304 stainless steel frame with thickness 3.0mm; tank sealing grade IP67; design pressure resistance 1.0MPa; static load ≥3,000kg; built-in IT equipment mounting brackets, diversion structures, inlet/outlet ports and maintenance doors; matched heavy-duty feet, lifting rings and anti-static grounding system; anti-corrosion sprayed surface, anti-corrosion Grade C5 | 1 | Set | KITOZER | Customizable phase-change immersion specifications over 200kW and sizes |
| 2 | Centralized High-Performance CDU Cooling Distribution Unit | KITOZER-LC-CDU-200-H | Rated heat exchange power 200kW; dual-loop 316L stainless steel plate heat exchanger with efficiency ≥98%; dual variable-frequency pump set with 1+1 redundancy design, single pump power 4kW, head 40m, flow 60m³/h; equipped with automatic liquid replenishment system, pressure stabilization system, two-stage precision filtration system and deionization unit; full set of electric regulating valves, check valves, pressure relief valves, safety valves, drain and exhaust valves; full-dimensional sensor monitoring of supply/return liquid temperature, pressure, flow, liquid level, conductivity and PH value; industrial redundant PLC controller with 15-inch industrial touchscreen, adaptive PID control, fault self-diagnosis and linkage protection; Modbus TCP/IP, SNMP and OPC UA protocols supported; dual redundant AC380V power input; IP54 protection grade | 1 | Set | KITOZER | Single CDU fits 1–6 cabinets, MW-level centralized cold station customizable |
| 3 | Immersion Liquid Cooling Heat Exchange Tank | KITOZER-LC-TANK-200-H | 316L stainless steel sealed tank, dimensions 1100mm×1400mm×1800mm; design pressure resistance 1.0MPa; IP67 sealing grade; built-in server mounting guide rails, upper/lower diversion structures, supply/return liquid distribution ports, liquid level monitoring ports and maintenance ports; matched quick connector interfaces, exhaust and drain valves; tank welded via argon arc welding with 100% air tightness testing; burst pressure ≥3 times working pressure | 1 | Set | KITOZER | Built inside cabinet, multi-chamber structure customizable |
| 4 | Insulating Cooling Medium | KITOZER-LC-FLUID-H | Electronic-grade fluorinated liquid with insulation property; breakdown voltage ≥40kV; kinematic viscosity 1.2mm²/s@25℃; boiling point 47℃; operating temperature range -50℃~150℃; stable chemical property, non-flammable and non-explosive, fully compatible with electronic components without corrosion; recyclable with service life ≥10 years | 300 | L | KITOZER | Configured by tank volume, mineral oil/customized medium optional |
| 5 | Condensation Heat Exchange Unit (Exclusive for Phase-Change Immersion) | KITOZER-LC-COND-H | Rated heat exchange power 200kW; 316L stainless steel condensation coils with heat exchange efficiency ≥98%; design pressure resistance 1.6MPa; matched gas-liquid separation and diversion structures; built-in temperature and pressure sensors; installed at immersion tank tops for parallel expansion of multiple groups | 1 | Set | KITOZER | Only configured for phase-change immersion systems, not required for single-phase immersion |
| 6 | High-Flow Fluid Pipeline System | KITOZER-LC-PIPE-H | DN50 316L stainless steel seamless main pipelines; DN20 316L stainless steel seamless branch pipelines; matched elbows, tees, reducers, loose joints, flanges, pipe clamps and fixing brackets; electrolytically polished inner walls for corrosion resistance, anti-scaling and low flow resistance; design pressure resistance 1.6MPa; hydraulic test pressure 2.4MPa with 100% air tightness testing; full set including cabinet internal, inter-cabinet and CDU connecting pipelines | 1 | Set | KITOZER | Dual-loop redundant pipeline system customizable |
| 7 | High-Reliability Fluid Quick Connector | KITOZER-LC-QC-15-H | DN15 specification; bidirectional self-sealing supporting pressure-bearing plug/unplug; 316L stainless steel main body with perfluoroether sealing gaskets; plug/unplug cycles ≥10,000; working pressure 1.6MPa; temperature resistance -50℃~150℃; leakage rate ≤1×10⁻¹⁰Pa·m³/s; anti-misplug, anti-drop and self-locking design; flange/thread connection optional | 8 | Sets | KITOZER | For connection between main supply/return liquid pipelines and tanks, including male/female heads |
| 8 | HVDC Intelligent Power Distribution System | KITOZER-LC-PDB-250-H | Rated input current 250A, 3P AC380V input; dual mains + diesel generator automatic transfer; equipped with frame circuit breakers and surge protection devices (In=80kA, Imax=120kA), branch protection circuit breakers; 380V HVDC output with conversion efficiency ≥96%; N+1 redundant rectifier modules; matched power distribution cabinet, mounting rails and wiring terminals; IP30 protection grade; full-link real-time electrical parameter monitoring supporting remote monitoring and linkage control | 1 | Set | KITOZER | 48V DC power supply system customizable for GPU cluster demands |
| 9 | Centralized Power Bus System | KITOZER-LC-BUSBAR-H | Oxygen-free copper dense bus duct with rated current 400A; 3P+N+PE structure, insulation Class F, IP40 protection grade; compatible with 16 hot-swappable plug-in boxes each with rated current 63A, molded case circuit breaker and intelligent energy metering module; supports branch-level on/off control, energy consumption monitoring and overload alarms; vertically installed inside cabinets for cable-free layout with hot-swappable expansion supported | 1 | Set | KITOZER | For power supply demands of high-density GPU clusters |
| 10 | Modular UPS & Energy Storage System | KITOZER-LC-UPS-40k-H | Online modular UPS, rated capacity 40kVA/40kW; N+X redundant modules with hot-swappable replacement; AC380V input, AC220V/380V output; dual-conversion online type with 0ms switching time; matched lithium iron phosphate battery pack (rated voltage 51.2V, capacity 200Ah) with 30-minute backup runtime; parallel expansion supported; LCD touchscreen display and remote monitoring supported; full electrical protection; rack/side cabinet installation compatible | 1 | Set | KITOZER | Customizable backup runtime, lithium energy storage system expansion supported |
| 11 | Redundant Rack Management Controller | KITOZER-LC-RMC-H | Industrial redundant PLC dual-core processor; 15-inch industrial touchscreen (1920×1080 resolution); 64 AI analog inputs, 128 digital inputs, 64 relay outputs; supports full-system sensor data collection, fault self-diagnosis and predictive maintenance; adaptive PID closed-loop control for precise temperature/flow/pressure management; graded alarms and emergency linkage protection logic to automatically execute full-process protection upon leakage/overtemperature; Modbus TCP/IP, SNMP, BACnet and OPC UA protocols supported; remote WEB access, mobile APP monitoring and DCIM platform access; dual redundant power supply, industrial wide-temperature operation with strong anti-interference performance | 1 | Set | KITOZER | Dual redundant controller design to guarantee uninterrupted system control |
| 12 | Industrial High-Precision Sensor Cluster | KITOZER-LC-SEN-H | 8 supply/return liquid Class A PT100 temperature sensors (accuracy ±0.1℃); 6 supply/return liquid pressure sensors (range 0–2.5MPa, Class 0.2 accuracy); 2 total flow sensors + 8 branch flow sensors (Class 0.2 accuracy); 4 liquid level sensors, 2 conductivity sensors, 1 PH sensor; 16 tank internal temperature sensors, 6 cabinet temperature/humidity sensors; 20m full-area liquid leakage detection rope, 8 point liquid leakage sensors (response time ≤1s); 4 smoke sensors, 2 door magnetic sensors, 2 vibration sensors, 2 oxygen concentration sensors | 1 | Set | KITOZER | Full-dimensional full-system status monitoring including all installation fittings and metrological verification certificates |
| 13 | Full-Link Anti-Leakage Safety System | KITOZER-LC-LEAK-H | Full-size 316L stainless steel liquid collection tank at cabinet bottom with liquid level monitoring and automatic drain function; full-pipeline diversion structures and splash guards; 6 main pipeline emergency manual shut-off valves, 4 electric emergency cut-off valves; perfluoroether sealing gaskets for full system with wide temperature resistance, corrosion resistance and anti-aging performance; liquid leakage detection linkage with automatic cut-off, pressure relief and liquid replenishment; tank anti-overflow and overpressure protection structures; liquid leakage emergency handling kit and special protective tools | 1 | Set | KITOZER | Four-layer anti-leakage protection for full-process safety control |
| 14 | Fire & Safety Protection System | KITOZER-LC-SAFE-H | Rack-mounted full-hexanone gas fire suppression unit with 4kg fire suppressant dosage; 4 composite smoke/temperature detectors; audible/visual alarms and manual emergency start/stop buttons; supports automatic/manual start with linked power cut-off; anti-static grounding and equipotential connection system; permission access control with dual fingerprint+password authentication; 2 video surveillance cameras supporting local storage and remote viewing | 1 | Set | KITOZER | For high-safety and high-confidentiality demand scenarios |
| 15 | Intelligent Operation & Maintenance System | KITOZER-LC-OPS-H | Industrial edge computing gateway; built-in operation & maintenance management platform supporting real-time display of operating data, historical data storage, energy consumption analysis, fault early warning and report generation; supports remote operation & maintenance, unattended operation and robot inspection adaptation; digital twin visual interface supported; matched industrial 8-port gigabit switch with fiber uplink | 1 | Set | KITOZER | Realizes digital and visual unattended intelligent operation & maintenance |
| 16 | Cabinet Supporting Accessories | KITOZER-LC-ACC-H | Server mounting guide rails and fixing brackets; cabinet blanking plates and U-position marking strips; cable racks and cable fixing components; grounding copper bars, equipotential connecting wires and jumpers; full-system equipment labels, pipeline flow direction labels, valve labels and safety warning labels; special operation & maintenance tool kit and spare parts box | 1 | Set | KITOZER | Full supporting accessories for installation and operation & maintenance |
6. Full Product Technical Parameters
6.1 Full-Series Technical Parameters of Liquid Cooling Cabinet Frames
表格
| Product Series | Model Spec | Overall Dimensions (W×D×H) | Available U Height | Material | Static Load Capacity | Protection Grade | Adaptable Power Range | Operating Temp Range | Anti-Corrosion Grade |
|---|---|---|---|---|---|---|---|---|---|
| Economical Cold Plate Cabinet | KITOZER-LC-CAB-42U-E | 600mm×1200mm×2200mm | 42U | Premium Cold-Rolled Steel | ≥1,600kg | IP30 | 15–30kW | 5℃–40℃ | C4 |
| General Cold Plate Cabinet | KITOZER-LC-CAB-47U-M | 800mm×1200mm×2200mm | 47U | Premium Cold-Rolled Steel | ≥2,000kg | IP40 | 30–60kW | 0℃–45℃ | C4 |
| High-Density Cold Plate Cabinet | KITOZER-LC-CAB-47U-H | 800mm×1500mm×2200mm | 47U | Cold-Rolled Steel / 304 Stainless Steel | ≥2,500kg | IP40 | 60–120kW | 0℃–50℃ | C4–C5 |
| Single-Phase Immersion Cabinet | KITOZER-LC-CAB-47U-SL | 1200mm×1500mm×2200mm | 47U | 304/316L Stainless Steel | ≥3,000kg | IP67 | 60–200kW | -10℃~55℃ | C5 |
| Phase-Change Immersion Cabinet | KITOZER-LC-CAB-47U-PL | 1200mm×1500mm×2200mm | 47U | 316L Stainless Steel | ≥3,500kg | IP67 | 120–900kW | -10℃~55℃ | C5 |
| Rear Door Liquid Cooling Cabinet | KITOZER-LC-CAB-47U-RCP | 600mm×1100mm×2200mm | 47U | Premium Cold-Rolled Steel | ≥1,800kg | IP30 | 30–60kW | 5℃–40℃ | C4 |
| Edge Computing Dedicated Cabinet | KITOZER-LC-CAB-42U-Edge | 600mm×800mm×1800mm | 22U/32U/42U | Cold-Rolled Steel / Stainless Steel | ≥1,200kg | IP30–IP55 | 5–30kW | -30℃~55℃ | C4–C5 |
| Electromagnetic Shielding Liquid Cooling Cabinet | KITOZER-LC-CAB-42U-SEC | 700mm×1500mm×2200mm | 42U | Cold-Rolled Steel + Shielding Material | ≥2,000kg | IP40 | 15–60kW | 5℃–40℃ | C4 |
6.2 Full-Series Technical Parameters of CDU Cooling Distribution Units
表格
| Product Series | Model Spec | Rated Heat Exchange Power | Heat Exchanger Type | Circulating Pump Configuration | Working Pressure | Control Precision | Adaptable Power Supply | Communication Protocol | Protection Grade | Applicable Scenarios |
|---|---|---|---|---|---|---|---|---|---|---|
| Economical Integrated CDU | KITOZER-LC-CDU-30-E | 30kW | 316L Stainless Steel Plate Heat Exchanger | Single pump, 0.75kW, head 20m | 0–1.0MPa | Temp control precision ±0.5℃ | AC220V | Modbus TCP | IP20 | Edge computing, small/medium machine rooms |
| General Side-Mounted CDU | KITOZER-LC-CDU-60-M | 60kW | 316L Stainless Steel Plate Heat Exchanger | Dual redundant pumps, 1.5kW per pump, head 30m | 0–1.6MPa | Temp control precision ±0.3℃ | AC380V | Modbus TCP, SNMP | IP30 | Enterprise data centers, AI inference clusters |
| High-Performance Centralized CDU | KITOZER-LC-CDU-200-H | 200kW | 316L Stainless Steel Dual-Loop Plate Heat Exchanger | Dual redundant pumps, 4kW per pump, head 40m | 0–1.6MPa | Temp control precision ±0.2℃ | AC380V | Modbus TCP, SNMP, OPC UA, BACnet | IP54 | AI intelligent computing centers, supercomputing centers |
| Supercomputing-Grade CDU | KITOZER-LC-CDU-1000-S | 1,000kW | 316L Stainless Steel Multi-Loop Plate Heat Exchanger | Four redundant pumps, 11kW per pump, head 50m | 0–2.5MPa | Temp control precision ±0.1℃ | AC380V | Full protocol support, customized development available | IP54 | National supercomputing centers, large-scale computing clusters |
| Rack-Mounted CDU | KITOZER-LC-CDU-20-R | 20kW | 316L Stainless Steel Plate Heat Exchanger | Dual redundant pumps, 0.55kW per pump, head 15m | 0–1.0MPa | Temp control precision ±0.5℃ | AC220V | Modbus TCP | IP20 | Rack integration, small machine rooms |
6.3 Core Technical Parameters of Cold Plate Heat Exchange Components
表格
| Product Type | Model Spec | Adaptable Components | Material | Thermal Resistance | Design Pressure Resistance | Operating Temp Range | Flow Channel Type | Leakage Rate | Compatible Server Specs |
|---|---|---|---|---|---|---|---|---|---|
| CPU Dedicated Cold Plate | KITOZER-LC-CP-CPU | Intel/AMD/Localized CPUs | Aluminum Alloy / Copper-Aluminum Alloy | ≤0.08℃·cm²/W | 1.0MPa | -40℃~120℃ | Micro-Channel | ≤1×10⁻⁹Pa·m³/s | Standard 1U/2U/4U Servers |
| GPU Dedicated Cold Plate | KITOZER-LC-CP-GPU | NVIDIA/AMD/Ascend AI Accelerators | Copper-Aluminum Alloy | ≤0.05℃·cm²/W | 1.6MPa | -40℃~120℃ | Porous Micro-Channel | ≤1×10⁻⁹Pa·m³/s | Full-Series AI Accelerator & GPU Servers |
| Memory Dedicated Cold Plate | KITOZER-LC-CP-RAM | DDR4/DDR5 Memory | Aluminum Alloy | ≤0.1℃·cm²/W | 1.0MPa | -40℃~120℃ | Straight Flat Flow Channel | ≤1×10⁻⁹Pa·m³/s | Standard Server Memory |
| Full-Device Coverage Cold Plate | KITOZER-LC-CP-FULL | CPU+GPU+Memory+Hard Disk | Copper-Aluminum Composite Alloy | ≤0.05℃·cm²/W | 1.6MPa | -40℃~120℃ | Customized Micro-Channel | ≤1×10⁻⁹Pa·m³/s | 2U/4U High-Density Servers |
| Rear Door Liquid Cooling Heat Exchange Plate | KITOZER-LC-RCP-BD | Cabinet Rear Door Heat Exchange | Aluminum Alloy / Stainless Steel | Heat Exchange Efficiency ≥90% | 1.0MPa | -40℃~120℃ | Tube-Fin Flow Channel | ≤1×10⁻⁹Pa·m³/s | Standard 19-inch Cabinets, Compatible with All Air-Cooled Servers |
6.4 Core Technical Parameters of Fluid Quick Connectors
表格
| Model Spec | Nominal Diameter | Main Body Material | Sealing Material | Working Pressure | Temp Resistance Range | Plug/Unplug Cycles | Leakage Rate | Core Features | Applicable Scenarios |
|---|---|---|---|---|---|---|---|---|---|
| KITOZER-LC-QC-04 | DN8 | 316L Stainless Steel | Fluororubber | 1.0MPa | -40℃~120℃ | ≥5,000 | ≤1×10⁻⁹Pa·m³/s | Bidirectional self-sealing, pressure-bearing plug/unplug | Economical & General Cold Plate Systems |
| KITOZER-LC-QC-06 | DN10 | 316L Stainless Steel | Fluororubber | 1.6MPa | -40℃~120℃ | ≥5,000 | ≤1×10⁻⁹Pa·m³/s | Bidirectional self-sealing, anti-misplug, pressure-bearing plug/unplug | General & High-Density Cold Plate Systems |
| KITOZER-LC-QC-10 | DN15 | 316L Stainless Steel | Perfluoroether | 1.6MPa | -50℃~150℃ | ≥10,000 | ≤1×10⁻¹⁰Pa·m³/s | Bidirectional self-sealing, self-locking design, dynamic pressure plug/unplug | High-Density Immersion Systems, Main Pipeline Connection |
| KITOZER-LC-QC-15 | DN20 | 316L Stainless Steel | Perfluoroether | 2.5MPa | -50℃~150℃ | ≥10,000 | ≤1×10⁻¹⁰Pa·m³/s | Bidirectional self-sealing, flange connection, high-pressure compatibility | Supercomputing-Grade Systems, Large-Flow Main Pipeline Connection |
| KITOZER-LC-QC-BLIND | DN10 | 316L Stainless Steel | Fluororubber | 1.6MPa | -40℃~12 |