KITOZER Standard Air-Cooled Integrated Cabinet Full-Series Solution

Table of Contents

1 System Overview

1.1 System Definition & Industry Positioning

The KITOZER standard air-cooled integrated cabinet is a highly integrated, standardized, prefabricated miniature data center solution built for new-generation digital infrastructure. Taking a 19-inch standard industrial cabinet as the physical carrier, it deeply integrates ten core subsystems: cabinet body, forced air cooling refrigeration system, uninterruptible power supply & distribution system, intelligent environmental monitoring system, access control security system, fire linkage system, integrated cabling system, lightning protection & grounding system, emergency ventilation system and lighting system. Within the limited space of a single cabinet or multi-cabinet cluster, it builds a fully enclosed, high-reliability, intelligent independent computer room environment that meets the safe and stable operation of IT equipment. It truly delivers a minimalist delivery model of “one cabinet equals a computer room, deploy right out of the box, put into operation once powered on”.

The system strictly complies with national and industrial standards including GB/T 41783-2022 General Specification for Modular Data Centers, GB/T 28571.1-2012 Telecommunication Equipment Cabinets Part 1: General Specification, GB/T 40815.2-2021 Mechanical Structures for Electrical and Electronic Equipment Thermal Management of Cabinets Complying with Inch and Metric Series Part 2: Determination Method of Forced Air Cooling. It is also compatible with international standards IEC60297 and IEC60917, fully adapting to the installation and operation requirements of all standard 19-inch IT equipment. It serves as a revolutionary alternative to traditional distributed computer room construction and a core infrastructure carrier for edge computing, small-to-medium scale IT deployment and digital construction of branch offices.

1.2 Industry Development Background & Design Philosophy

Driven by the explosive growth of 5G, AI, big data, industrial internet, edge computing and other technologies, digital infrastructure is evolving in two directions: centralized cloud deployment and distributed edge deployment. Over 70% of industrial data is generated and processed on the network edge side. However, traditional computer room construction models suffer from long construction cycles, large floor space occupation, high investment costs, difficult operation and maintenance, low energy efficiency and inflexible capacity expansion, failing to meet the core demands of edge scenarios for rapid deployment, elastic scaling, unattended operation and low Total Cost of Ownership (TCO).

Meanwhile, as the most widely adopted, technically mature, easy-to-maintain and cost-controllable heat dissipation solution worldwide, air cooling boasts unparalleled comprehensive advantages over liquid cooling in low-to-medium power density scenarios, making it the preferred heat dissipation scheme for most edge computer rooms, branch offices and small-to-medium IT deployments. According to industry statistics, the market scale of integrated cabinets in China exceeded 38 billion RMB in 2025, with air-cooled integrated cabinets accounting for over 85% of the market share and becoming the mainstream industry option.

Centered on the design philosophy of standardization, integration, intelligence, green development and domestic production, the KITOZER standard air-cooled integrated cabinet addresses pain points of traditional computer room construction and undergoes full-system R&D and design from the perspective of full-lifecycle TCO optimization:

  • Standardized Design: The full product line adopts a 19-inch standard rack design. All components are modularly and standardizedly manufactured with strong universal interchangeability, supporting flexible configuration and elastic expansion on demand.
  • Integrated Design: The ten subsystems that require separate procurement, installation and commissioning in traditional computer rooms complete pre-integration, pre-testing and pre-commissioning in the factory, drastically shortening on-site deployment time and lowering construction difficulty.
  • Intelligent Design: Equipped with a self-developed intelligent environmental monitoring system, it realizes 24/7 real-time monitoring, intelligent analysis, linkage control, fault early warning and remote management of all equipment and environmental parameters across the system, enabling truly unattended operation.
  • Green Design: Adopting a fully enclosed cold-hot isolated air duct design paired with an efficient variable-frequency air cooling refrigeration system, near-end cooling eliminates local hot spots. It delivers over 30% energy savings compared with traditional computer room cooling, with the overall rack PUE reduced to below 1.4, fully aligning with national “Dual Carbon” targets.
  • Domestic Production Design: 100% domestically produced core system components, fully compatible with domestic servers, operating systems, databases and security equipment. It meets domestic substitution demands for government, finance, military and other classified scenarios and safeguards information security.

1.3 Core System Values

1.3.1 Dramatically Simplify the Entire Construction Process

Traditional computer room construction involves dozens of procedures including scheme design, computer room renovation, fire protection reconstruction, power distribution construction, air conditioner installation, monitoring deployment, equipment racking and joint commissioning, with a construction cycle ranging from 1 to 3 months. For the KITOZER standard air-cooled integrated cabinet, all subsystems complete pre-integration and pre-testing at the factory. On-site work only requires fixing, mains power access and network access to finish full deployment: single-cabinet deployment takes no more than 1 day, and multi-cabinet cluster deployment takes less than 3 days, significantly shortening project delivery cycles and reducing project management and construction costs.

Additionally, the system enables one-stop procurement. Users only need a single procurement interface to complete full-process services covering procurement, delivery, installation, commissioning and after-sales support for the entire system, greatly simplifying procurement workflows and cutting business and communication costs.

1.3.2 Significantly Reduce Space & Investment Costs

Traditional computer rooms require dedicated premises with ample space reserved for cooling, power distribution and operation aisles, resulting in space utilization below 30%. The KITOZER standard air-cooled integrated cabinet adopts a fully integrated design that eliminates the need for a dedicated computer room. It can be directly installed in regular indoor spaces such as offices, corridors, storage rooms and basements without computer room renovation, raised flooring, wall reconstruction or other supporting works. It saves over 40% floor space compared with traditional computer rooms, with a minimum deployment footprint of only 0.7㎡, drastically cutting site rental and construction costs.

In terms of investment costs, the system features modular on-demand configuration. Users can select power density and configuration tiers based on current business demands to avoid one-time over-investment. Capacity expansion via cabinet paralleling can be flexibly carried out as business grows, enabling phased investment scaled to actual needs, lowering initial investment thresholds and improving capital utilization efficiency.

1.3.3 Maximize System Reliability & Availability

The fully enclosed structural design of the KITOZER standard air-cooled integrated cabinet fully isolates the internal space from the external environment, effectively shielding IT equipment from dust, moisture, corrosive gas, rodents and other external hazards, reducing equipment failure rates and extending IT equipment service life. Meanwhile, the system integrates multiple protection mechanisms including high-reliability UPS, dual redundant power distribution, lightning protection & grounding, emergency ventilation and fire linkage. Customizable N+1 or 2N high-redundancy architectures meet Class A and B national computer room standards, ensuring 24/7 stable and uninterrupted operation of IT equipment.

The built-in intelligent environmental monitoring system achieves real-time monitoring of all equipment operating status with a fault early warning accuracy rate exceeding 99%. Rapid fault localization paired with a national service network enables fast fault resolution and drastically reduces system downtime risks, delivering an overall system availability of up to 99.999%.

1.3.4 Streamlined Operation & Maintenance for Unattended Deployment

Traditional computer rooms require dedicated operation and maintenance staff for daily inspections, equipment maintenance and fault handling, incurring high labor costs while manual inspections carry risks of omissions. The intelligent environmental monitoring system of the KITOZER integrated cabinet automates full-system operation and maintenance management, collecting full-dimensional data including temperature & humidity, voltage, current, power, access control, water immersion and smoke in real time, and automatically generating operation, alarm and energy consumption reports. Upon detecting abnormalities, it delivers multi-channel notifications including local sound-light alarms, SMS, phone calls, emails and APP push alerts to notify management personnel instantly.

The system supports rich linkage control functions: automatic air conditioner adjustment linked to temperature & humidity, video monitoring linked to access control, power cut-off linked to fire protection, emergency ventilation activation linked to air conditioner faults and more. Automated disposal eliminates manual intervention. Adopting a B/S architecture for remote management, administrators can view system operation status, adjust parameters, conduct remote commissioning and upgrade firmware anytime and anywhere via computers, mobile phones or tablets, realizing true 24/7 unattended operation and maintenance and drastically cutting O&M difficulty and costs.

1.3.5 Full-Scenario Adaptability & Flexible Expansion

The full-series KITOZER standard air-cooled integrated cabinets cover the complete power range from 3kW to 20kW, supporting single-cabinet, dual-cabinet and multi-cabinet cluster deployment modes with cascading expansion for up to 16 cabinets. Customized configurations can be flexibly designed based on business scale, power density, application scenarios and redundancy requirements, perfectly matching deployment demands from small office nodes to medium-scale edge computer rooms.

Furthermore, the system boasts strong environmental adaptability, operating stably within a wide ambient temperature range of -10℃ to 55℃. It adapts to complex indoor environments including high altitude, high humidity and heavy dust without extra environmental reconstruction, satisfying differentiated deployment requirements across all industries.

1.4 Applicable National, Industrial & International Standards

The design, production, testing, installation and delivery of the full-series KITOZER standard air-cooled integrated cabinets strictly comply with the following national, industrial and international standards:

National Standards

  • GB/T 41783-2022 General Specification for Modular Data Centers
  • GB/T 28571.1-2012 Telecommunication Equipment Cabinets Part 1: General Specification
  • GB/T 40815.2-2021 Mechanical Structures for Electrical and Electronic Equipment Thermal Management of Cabinets Complying with Inch and Metric Series Part 2: Determination Method of Forced Air Cooling
  • GB 50174-2017 Code for Design of Data Centers
  • GB 50054-2011 Code for Design of Low-Voltage Electrical Installations
  • GB 50057-2010 Code for Design of Lightning Protection of Buildings
  • GB 50116-2013 Code for Design of Automatic Fire Alarm System
  • GB 8624-2025 Classification of Combustion Performance of Building Materials and Products
  • GB 4208-2025 Degrees of Protection Provided by Enclosures (IP Code)
  • GB 7251.1-2013 Low-Voltage Switchgear and Controlgear Assemblies Part 1: General Rules
  • GB/T 14715-2017 General Specification for Uninterruptible Power Supplies Used in Information Technology Equipment

Industrial Standards

  • YD/T 1058-2025 High-Frequency Switching Combined Power Supply for Telecommunications
  • YD/T 2165-2020 Modular Uninterruptible Power Supply for Telecommunications
  • YD/T 1821-2020 Environmental Conditions for Telecommunication Central Computer Rooms
  • GA 308-2017 Acceptance Rules for Security & Protection Systems
  • JB/T 10780-2024 Technical Conditions for Air Coolers and Control Cabinets of Transformers

International Standards

  • IEC 60297 Mechanical Structures of Electronic Equipment 482.6 mm (19 in) Series Cabinets
  • IEC 60917 Mechanical Structures of Electronic Equipment Test for Inch and Metric Series
  • IEC 62610-2:2018 Mechanical Structures for Electronic Equipment Cabinet Thermal Management Part 2: Determination Method of Forced Air Cooling
  • IEC 62040-3 Uninterruptible Power Supply Systems (UPS) Part 3: Method of Specifying Performance and Test Requirements
  • ISO 9001 Quality Management Systems Requirements
  • ISO 14001 Environmental Management Systems Requirements
  • ISO 45001 Occupational Health and Safety Management Systems Requirements

2 System Composition

The KITOZER standard air-cooled integrated cabinet is an organic whole formed by deep integration of multiple systems rather than simple equipment stacking. All subsystems feature seamless hardware integration, interconnected software communication and intelligent linkage control under unified design standards, communication protocols and mounting interfaces. The complete system consists of ten core subsystems, with detailed composition and functions as follows:

2.1 Cabinet Body Subsystem

The cabinet body subsystem acts as the physical load-bearing frame of the entire integrated cabinet, serving as the mounting carrier for all subsystems and IT equipment, as well as the core barrier for cold-hot isolation and safety protection. Its structural design, material craftsmanship, load-bearing capacity and sealing performance directly determine overall system stability and reliability.

Main components of the cabinet body subsystem:

  1. Cabinet Frame Main Body: Adopts a combined integral welding & assembling structure composed of front frame, rear frame, uprights, cross beams, top frame and base frame. Uprights feature a 19-inch standard rack design with precisely marked U-height scales, compatible with mounting of all standard 19-inch IT equipment and functional modules.
  2. Cabinet Door Assembly: Includes front door, rear door and side doors. The front door is equipped with a single-opening double-layer tempered glass door or mesh metal sheet door; the rear door supports single or double-opening fully sealed metal sheet or mesh doors; side doors are detachable two-section fully sealed metal sheet doors. All door panels are fitted with EPDM flame-retardant sealing strips to guarantee full-system sealing, alongside position-limiting locking devices and anti-theft locks to prevent unauthorized access.
  3. Mounting Auxiliary Components: L-brackets, guide rails, fixing screws, square nut strips, blanking panels, cable management frames, cable rings, wiring troughs, grounding copper bars, etc., used for mounting and fixing IT equipment and functional modules, cable routing management and grounding connection.
  4. Cabinet Auxiliary Accessories: Leveling casters, support foot pads, cabinet paralleling connectors, waterproof cable glands, sealing plugs, identification nameplates, etc., for cabinet fixing, movement, cascading expansion, sealing of cable entry points and equipment labeling.

2.2 Air-Cooled Refrigeration Subsystem

The air-cooled refrigeration subsystem serves as the core temperature control unit of the integrated cabinet, critical to maintaining IT equipment within a suitable temperature & humidity operating environment. The KITOZER integrated cabinet adopts near-end forced air cooling paired with a fully enclosed cold-hot isolated air duct design, completely resolving pain points of traditional remote cooling including cold loss, local hot spots and low cooling efficiency, delivering precise temperature control and high energy efficiency.

Main components of the air-cooled refrigeration subsystem:

  1. Rack-Mounted Precision Air Conditioner Indoor Unit: The core cooling component with a 19-inch standard rack design for internal cabinet installation without extra space occupation. It consists of scroll/rotary variable-frequency compressors, evaporators, electronic expansion valves, internal fans, filter dryers, sight glasses, liquid receivers and control mainboards, responsible for compressing, throttling and evaporating refrigerants to absorb heat inside the cabinet.
  2. Air Conditioner Outdoor Unit: Composed of condensers, outdoor fans, auxiliary throttling components and rainproof dustproof enclosures, installed in well-ventilated outdoor areas. Connected to the indoor unit via refrigerant pipelines, it dissipates heat carried by refrigerants into outdoor air and condenses refrigerants back to liquid state.
  3. Refrigerant Circulation Pipeline Assembly: Copper tubes, thermal insulation cotton, branch pipes, sealing joints, stop valves, etc., forming a closed refrigerant circulation loop connecting indoor and outdoor units. Thermal insulation cotton reduces cold loss and prevents pipeline condensation.
  4. Condensate Drainage Assembly: Water trays, UPVC drain pipes, drain pumps, liquid level sensors, etc., collecting and discharging condensate generated during air conditioning operation while triggering alarms upon detecting overflow risks via liquid level sensors.
  5. Temperature Control & Linkage Control Unit: Temperature sensors, humidity sensors, air conditioner controllers and communication linkage modules that collect real-time cabinet temperature & humidity data, automatically adjust compressor frequency, fan speed and cooling output based on threshold settings, interconnect with the environmental monitoring system to receive remote control commands and upload operating status and fault information.

2.3 Uninterruptible Power Supply & Distribution Subsystem

The uninterruptible power supply & distribution subsystem acts as the “heart” of the integrated cabinet, delivering stable, reliable and uninterrupted power to IT equipment, cooling units, monitoring devices, security hardware and other loads. It eliminates disruptions caused by mains power outages, voltage fluctuations and harmonic interference to guarantee business continuity.

Main components of the uninterruptible power supply & distribution subsystem:

  1. UPS Host: 19-inch rack-mounted high-frequency online double-conversion topology as the core power supply unit, including rectifier, inverter, bypass, charging, battery management and control modules. It converts mains AC to DC to charge batteries while inverting clean, stable AC for loads. It instantly switches to battery power upon mains failure to deliver zero-interruption power supply.
  2. Energy Storage Battery Pack / Battery Module: Rack-mounted maintenance-free VRLA lead-acid or lithium iron phosphate battery packs with a 19-inch standard rack design, matching the UPS host as standby energy storage. Batteries store electricity during normal mains operation and discharge to power loads during outages; capacity and quantity can be flexibly configured based on required backup runtime.
  3. Input Power Distribution Unit: Mains input circuit breakers, Automatic Transfer Switch (ATS) for dual power sources, Surge Protection Devices (SPD), isolating switches, ammeters, voltmeters, energy meters and indicator lights, responsible for mains input switching, lightning surge protection and parameter monitoring. B+C two-stage SPD configuration effectively mitigates lightning and surge damage to equipment.
  4. Output Power Distribution Unit: Output main circuit breakers, branch circuit breakers, contactors, fuses and power monitoring modules, distributing stabilized UPS power to individual load circuits with independent overload and short-circuit protection for each loop, while monitoring real-time voltage, current, power and energy consumption per circuit.
  5. Rack-Mounted PDU (Power Distribution Unit): 19-inch rack-mounted power distribution hardware installed on cabinet uprights as the direct power supply interface for IT equipment, categorized into basic, metering, intelligent and switchable models with multiple socket specifications including domestic 10A/16A and IEC C13/C19. Intelligent PDUs support independent port switching, power monitoring and overload alarming with remote control capabilities.
  6. Grounding & Equipotential Connection Assembly: Grounding copper bars, grounding cables, equipotential jumpers and terminals for system grounding protection, establishing equipotential bonding for all equipment, cabinet metal frames and enclosures to protect personnel safety and enhance equipment anti-interference performance.

2.4 Intelligent Environmental Monitoring Subsystem

The intelligent environmental monitoring subsystem serves as the “brain” of the integrated cabinet, the core of system intelligence, automation and unattended O&M. It realizes full-dimensional real-time monitoring, intelligent analysis, linkage control, fault early warning and remote management of all power equipment, environmental parameters and security status via various sensors and acquisition hardware.

Main components of the intelligent environmental monitoring subsystem:

  1. Environmental Monitoring Host: 19-inch rack-mounted core processing unit with industrial embedded processors and operating systems, equipped with abundant acquisition, control and communication interfaces to collect, process, judge, store and transmit data from all sensors and equipment. It supports protocol conversion for interconnection with third-party platforms.
  2. Local Touch Display Terminal: Standard 7-inch or 10-inch industrial color touch LCD screen embedded on the cabinet front door for on-site real-time data visualization, parameter configuration, equipment control, alarm query and log review with an intuitive operation interface for field maintenance personnel.
  3. Environmental Monitoring Sensor Group
    • Temperature & Humidity Sensors: Mounted at cabinet air inlet, air outlet and IT equipment zones for real-time temperature & humidity monitoring with precision up to ±0.2℃ and ±2%RH.
    • Water Immersion Sensors: Point-type and rope-type detectors installed at air conditioner water trays, cabinet bottoms and cable entry points to detect water leakage and overflow.
    • Smoke Sensors: Photoelectric smoke detectors mounted at cabinet tops to monitor smoke concentration and trigger early warnings of fire hazards.
    • Dust Sensors (Optional): Installed at air inlets to monitor airborne dust concentration entering the cabinet and maintain a clean operating environment for IT hardware.
    • Hydrogen Sensors (Optional): Deployed in battery compartments to monitor hydrogen accumulation during battery charging and prevent explosion risks.
  4. Power Equipment Monitoring & Control Modules: Dedicated acquisition modules for UPS, air conditioners, power distribution, PDUs and batteries that collect real-time operating parameters, status and fault data while supporting remote switching and parameter adjustment of equipment via relay control modules.
  5. Alarm & Notification Module: Local sound-light alarms, SMS alert modules, phone call alert modules, email alert modules and APP push modules to deliver multi-channel notifications to management personnel upon detecting abnormalities. Alarms are classified into four tiers: critical, major, minor and prompt, with customized notification rules per tier.
  6. Communication & Transmission Module: Ethernet, 4G/5G wireless, WiFi and fiber optic modules supporting TCP/IP, Modbus-RTU/TCP, SNMP, HTTP, national Class B interface and other communication protocols for interconnection with local area networks, internet and superior environmental monitoring platforms, enabling remote access, management and firmware upgrades.
  7. Data Storage & Management Module: Built-in high-capacity storage for long-term archiving of real-time operating data, alarm records, operation logs and energy consumption data (storage cycle ≥1 year). It supports data export, automatic report generation and data analysis to produce daily, weekly, monthly and annual operational summaries.

2.5 Access Control Security Subsystem

The access control security subsystem forms the physical safety barrier of the integrated cabinet, preventing unauthorized personnel from opening the cabinet and accessing internal equipment to protect physical hardware and data security. It supports personnel access permission management and traceable entry records to meet compliance audit requirements.

Main components of the access control security subsystem:

  1. Access Control Main Controller: Industrial embedded core hardware for permission management, access status monitoring, door opening command execution, entry log storage and linkage with the environmental monitoring system.
  2. Identity Authentication Terminal: Mounted on the cabinet front door with multi-mode authentication support including password, fingerprint, IC/ID card, facial recognition and QR code. Single or combined authentication modes can be configured per security tier, supporting storage of thousands of user credentials and access records.
  3. Electric Lock Assembly: Electromagnetic locks, electric deadbolts or motor locks installed on cabinet door panels, receiving unlocking signals from the access controller with real-time door open/closed status feedback and abnormal prying detection.
  4. Mechanical Emergency Lock: Backup unlocking hardware for scenarios including power outages and access control system failures, enabling emergency maintenance access via physical keys.
  5. Video Monitoring Unit (Optional): High-definition network cameras, Network Video Recorders (NVR) and storage hard disks. Cameras are installed in front of or inside the cabinet to monitor surrounding and internal conditions, supporting motion detection, video recording, remote playback and linkage with access control to automatically capture snapshots and record footage upon door opening.
  6. Anti-Prying & Abnormal Alarm Module: Door magnetic sensors, vibration sensors and anti-tamper detectors that monitor abnormal cabinet prying, sustained open doors and heavy vibration, triggering local sound-light alarms and uploading alert information to the environmental monitoring system to notify management staff.

2.6 Fire Linkage Subsystem

The fire linkage subsystem acts as the ultimate safety safeguard for the integrated cabinet, detecting early fire hazards, executing rapid suppression and enabling full-system fire linkage to contain fire spread and protect equipment and personnel safety.

Main components of the fire linkage subsystem:

  1. Fire Detection Unit: Photoelectric smoke detectors, temperature-sensitive detectors and flame detectors for multi-dimensional monitoring of smoke, temperature and flame fire indicators, improving alarm accuracy and minimizing false alarms.
  2. Automatic Fire Suppression Unit: Rack-mounted or cabinet-installed clean gas fire suppression devices including HFC-227ea, Novec 1230 and aerosol extinguishants. These non-conductive, residue-free clean agents avoid secondary damage to IT equipment and achieve full-cabinet flooding suppression upon fire alarm activation.
  3. Fire Control Unit: Core control module receiving fire detector signals, executing logical judgment, triggering sound-light alarms and activating suppression devices to automate the full detection-alarm-suppression workflow.
  4. Fire Linkage Interface: Enables cross-system linkage between fire control, environmental monitoring, power distribution, cooling and access control systems. Upon fire confirmation, it automatically cuts non-fire power supplies, shuts down air conditioner fans and air dampers, unlocks cabinet doors and uploads fire alerts to remote platforms to optimize suppression effectiveness and personnel safety.
  5. Manual Emergency Control Unit: Manual emergency activation and stop buttons installed at easily accessible positions on the cabinet exterior. Emergency activation triggers fire suppression when automatic control fails, while emergency stop terminates suppression deployment during false alarms to avoid accidental agent discharge.

2.7 Integrated Cabling Subsystem

The integrated cabling subsystem serves as the “neural network” of the integrated cabinet, transmitting network and control signals while enabling organized cable routing, clear labeling and physical isolation of wiring to eliminate heat dissipation obstruction, maintenance difficulties and electromagnetic interference caused by messy cables.

Main components of the integrated cabling subsystem:

  1. Cable Management Assembly: Vertical cable management frames, horizontal cable organizers, cable rings, wiring troughs, cable ties and identification sleeves for separate routing of power and signal cables, physical isolation to reduce electromagnetic interference and standardized labeling.
  2. Network Patch Panel: 19-inch rack-mounted Cat5e, Cat6 or Cat6a shielded/unshielded patch panels installed inside the cabinet for termination, management and cross-connection of Ethernet cables, enabling flexible interconnection between switches and terminal equipment.
  3. Optical Distribution Frame (ODF): 19-inch rack-mounted single/multi-mode optical frames with LC/SC/FC interfaces for fiber splicing, termination, management and cross-connection to support long-distance high-bandwidth optical signal transmission.
  4. Cable Entry Assembly: Waterproof cable glands, sealed cable entry ports, cable sleeves and blanking plugs to seal external cable entry points and prevent dust, moisture and rodents from entering the cabinet through wiring openings.
  5. Signal Lightning Protection Unit: Network, serial port and video signal surge protectors installed at cable entry points to mitigate surge and lightning damage to network and signal equipment and stabilize signal transmission.

2.8 Lightning Protection & Grounding Subsystem

The lightning protection & grounding subsystem is a critical protective unit for the integrated cabinet, shielding hardware from lightning strikes, grid surges, static electricity and electromagnetic interference while protecting stable equipment operation and personnel safety, serving as the foundational guarantee of reliable system performance.

Main components of the lightning protection & grounding subsystem:

  1. Power Surge Protection Unit: Adopting B+C two-stage surge protection. Class B SPDs installed at the mains input main switch with nominal discharge current ≥40kA and maximum discharge current ≥60kA; Class C SPDs installed at UPS output and PDU input terminals with nominal discharge current ≥20kA and maximum discharge current ≥40kA, adopting 3+1 protection mode to mitigate damage from direct and induced lightning surges.
  2. Signal Surge Protection Unit: Dedicated surge protectors for network, serial and video signal lines installed at corresponding signal entry points with nominal discharge current ≥10kA to shield signal hardware from surge impacts.
  3. Equipotential Grounding Unit: Special T2 copper grounding bars (cross-sectional area ≥50mm²), multi-strand copper grounding cables and equipotential jumpers connecting all cabinet metal components, equipment enclosures and SPDs to eliminate potential differences across the full system.
  4. Grounding Lead Assembly: Grounding cables, terminals and optional ground electrodes connecting the cabinet grounding bar to the building’s combined grounding grid, with grounding resistance controlled to ≤4Ω (≤1Ω for special classified scenarios) to reliably discharge lightning and fault currents.
  5. Static Protection Assembly: Optional anti-static raised floors, anti-static wristband ports and anti-static signage to eliminate static electricity generated by human contact and prevent ESD damage to IT equipment.

2.9 Emergency Ventilation Subsystem

The emergency ventilation subsystem acts as a backup safeguard for the refrigeration system. It automatically activates temporary heat dissipation for IT equipment when air conditioning fails or undergoes maintenance, preventing rapid temperature rise and equipment downtime and buying sufficient time for fault resolution or controlled equipment shutdown.

Main components of the emergency ventilation subsystem:

  1. Motorized Air Damper Assembly: Normally closed inlet and outlet motorized dampers installed at the cabinet’s lower air inlet and upper air outlet. They remain closed during normal operation to preserve cabinet sealing and open automatically during emergency ventilation to form a dedicated air circulation duct.
  2. Axial Ventilation Fans: High-static, low-noise axial fans mounted at cabinet air outlets to drive forced air circulation between the cabinet interior and exterior, expelling internal heat for temporary cooling of IT hardware.
  3. Dust Filtration Assembly: G4-grade primary efficiency filters installed inside inlet dampers to filter airborne dust and debris and avoid cabinet contamination during emergency ventilation operation.
  4. Ventilation Control Unit: Linked with the environmental monitoring and air conditioning systems to track air conditioner operating status and internal cabinet temperature. It automatically opens dampers and activates ventilation fans upon air conditioner failure or temperature exceeding emergency thresholds, and closes all ventilation hardware once air conditioning resumes or temperatures return to safe ranges.
  5. Manual Control Unit: Local manual switches for on-site forced activation/deactivation of emergency ventilation to support equipment maintenance and emergency manual disposal workflows.

2.10 Lighting Subsystem

The lighting subsystem provides sufficient illumination for internal cabinet maintenance operations with intelligent sensor control that automatically activates lights upon door opening and cuts power when doors close, delivering convenient, maintenance-friendly lighting without manual intervention.

Main components of the lighting subsystem:

  1. LED Lighting Fixtures: Low-voltage DC LED strips or panels mounted at the cabinet interior top, delivering high brightness, low power consumption, long service life and minimal heat generation with uniform full-cabinet illumination free of blind spots.
  2. Intelligent Sensor Control Unit: Door magnetic induction switches and human infrared sensors that trigger LED lighting upon front/rear cabinet door opening and automatically shut down lights after door closure to save energy and simplify operation.
  3. Emergency Lighting Power Supply (Optional): Built-in compact backup battery packs that power lighting even during mains outages or UPS failures, ensuring visibility for emergency maintenance in dark conditions.
  4. Manual Control Switch: Local physical switches to manually turn lighting on/off for special maintenance scenarios requiring extended internal cabinet illumination.

3 System Classification

The full-series KITOZER standard air-cooled integrated cabinets form a complete product matrix categorized by application scenario, power density, deployment scale, redundancy tier, refrigeration architecture and security grade, enabling flexible adaptation and customized configuration for all industry use cases.

3.1 Classification by Deployment Scale & Cluster Architecture

Classified by IT equipment volume and cabinet quantity into single-cabinet, dual-cabinet and multi-cabinet cluster systems, supporting elastic expansion from individual units to clustered deployments with cascading for up to 16 cabinets.

3.1.1 Single-Cabinet Integrated System

The minimum deployment unit integrating all ten core subsystems within a single standard cabinet to realize the “one cabinet equals a computer room” concept. All functional modules adopt a 19-inch rack design with full factory integration and testing; only mains and network access are required for on-site commissioning and operation.

  • Core Features: Minimum deployment footprint (0.7㎡ floor space), shortest deployment cycle, lowest investment cost and simplest O&M. Direct installation in offices, corridors and storage rooms without dedicated computer room supporting works.
  • Power Coverage: 3kW ~ 10kW
  • Standard U Sizes: 22U, 32U, 42U, 47U
  • Applicable Scenarios: Small enterprise offices, chain retail stores, community bank branches, police stations, community health service centers, primary and secondary school multimedia computer rooms, edge computing nodes and other low-volume, low-power IT deployment scenarios.
  • Typical Configuration: 42U standard cabinet integrated with 3kVA/6kVA/10kVA rack-mounted UPS, 3.5kW/5kW/7.5kW rack-mounted precision air conditioner, intelligent environmental monitoring system, access control, power distribution unit, PDU, battery pack, emergency ventilation and fire suppression systems.

3.1.2 Dual-Cabinet Integrated System

Adopting a “1 main infrastructure cabinet + 1 IT equipment cabinet” architecture. The main cabinet integrates all infrastructure subsystems including UPS, batteries, air conditioning, power distribution, monitoring, access control and fire protection, while the dedicated IT cabinet exclusively houses servers, switches and storage hardware. Physical separation of infrastructure and IT equipment improves system safety and maintainability and supports isolated cold-hot channel airflow for higher cooling efficiency.

  • Core Features: Larger IT equipment installation space, higher power density and stronger expandability. Separate maintenance workflows for infrastructure and IT hardware with isolated cold and hot air channels to boost cooling performance.
  • Power Coverage: 5kW ~ 15kW
  • Standard U Sizes: 42U/47U main cabinet, 42U/47U IT cabinet
  • Applicable Scenarios: Medium enterprise computer rooms, district government computer rooms, hospital department computer rooms, university faculty computer rooms, secondary financial branches and small-to-medium edge computer rooms requiring expanded IT installation space.
  • Typical Configuration: 1×42U infrastructure main cabinet + 1×42U IT cabinet, integrated with 10kVA/15kVA rack-mounted UPS, 7.5kW/12.5kW rack-mounted precision air conditioner, dual-cabinet access control, power distribution, PDU, battery bank, emergency ventilation and fire suppression systems. Interconnected via sealed cabinet paralleling joints to form unified isolated cold-hot air ducts.

3.1.3 Multi-Cabinet Cluster Integrated System

Also known as single-row micro-module integrated systems, adopting a “1 master control cabinet + N IT equipment cabinets” cluster architecture. The master control cabinet integrates core power distribution, monitoring, security and fire suppression subsystems, paired with dedicated cooling cabinets and flexible quantities of IT cabinets (max. 16 cascaded units) to form a complete single-row micro-module computer room with unified power supply, cooling, monitoring and management.

  • Core Features: Extensive IT installation space, ultra-high expandability and high power density. Supports N+1/2N redundant architectures for elevated reliability and availability, with fully enclosed cold-hot channels for superior cooling efficiency and reduced PUE, meeting Class A/B national computer room standards.
  • Power Coverage: 10kW ~ 200kW
  • Standard Cabinet Quantity: 3 ~ 16 cabinets, single cabinet U height 42U/47U
  • Applicable Scenarios: Large enterprise headquarters computer rooms, government central computer rooms, Grade A hospital central computer rooms, university data centers, operator edge computer rooms, industrial internet data centers and medium-sized IDCs with large-scale IT hardware and high reliability requirements.
  • Typical Configuration: 1×47U master control cabinet, 1~2×47U cooling cabinets, 2~13×47U IT cabinets, equipped with 20kVA~200kVA modular UPS, 12.5kW~30kW row-level air-cooled precision air conditioners, centralized environmental monitoring, unified access control security, clustered fire linkage, dual redundant power distribution and fully enclosed cold-hot channel systems for unified full-system management and linkage control.

3.2 Classification by Power Density & Heat Dissipation Capacity

Categorized by single-cabinet IT load power density and air cooling heat dissipation capacity into low-density, medium-density and high-density models, covering the full 3kW~20kW power spectrum to match heat dissipation demands of different power density IT hardware.

3.2.1 Low-Density Air-Cooled Integrated Cabinet

Single-cabinet IT load power ≤5kW, adopting basic rack-mounted air conditioning and front-supply rear-return base air duct design to satisfy heat dissipation requirements of low-power hardware including conventional switches, routers, low-power servers and security storage equipment.

  • Core Features: Simple structure, low cost, low noise, low power consumption, stable operation and easy maintenance.
  • Single Cabinet Heat Dissipation Capacity: 3kW ~ 5kW
  • Air Conditioner Configuration: 3.5kW/5kW rack-mounted precision air conditioner (fixed-frequency or variable-frequency optional)
  • Applicable Scenarios: Office network computer rooms, chain retail stores, security monitoring computer rooms, small branches and weak current closets with low-power density IT deployments.
  • PUE: ≤1.5 under full-load operating conditions

3.2.2 Medium-Density Air-Cooled Integrated Cabinet

Single-cabinet IT load power ranging from 5kW to 10kW, adopting high-efficiency variable-frequency rack-mounted air conditioning and optimized isolated cold-hot air ducts with horizontal or front-supply rear-return airflow options. It accommodates mainstream rack servers, storage devices and virtualization hosts of medium power density, the most widely used mainstream model in the market with optimal overall cost performance.

  • Core Features: High cooling efficiency, superior energy savings and precise temperature control, compatible with most mainstream IT hardware heat dissipation requirements with the best comprehensive cost performance ratio.
  • Single Cabinet Heat Dissipation Capacity: 5kW ~ 10kW
  • Air Conditioner Configuration: 7.5kW/10kW high-efficiency variable-frequency rack-mounted precision air conditioner with sensible heat ratio ≥95%
  • Applicable Scenarios: Enterprise computer rooms, financial branches, government computer rooms, hospital computer rooms, education computer rooms, edge computing nodes and mainstream medium-power IT deployment scenarios.
  • PUE: ≤1.4 under full-load operating conditions

3.2.3 High-Density Air-Cooled Integrated Cabinet

Single-cabinet IT load power ranging from 10kW to 20kW, adopting dual-system redundant variable-frequency air conditioning paired with rear door air cooling or bottom-supply top-return high-efficiency air ducts and fully enclosed isolated cold-hot channels. It meets heat dissipation demands of high-power hardware including AI servers, GPU computing servers and high-density storage clusters, representing the upper power density limit of air cooling technology.

  • Core Features: Strong heat dissipation capacity with N+1 redundant dual cooling systems for elevated reliability, temperature control precision of ±0.5℃, eliminating local hot spots for high-power concentrated IT loads.
  • Single Cabinet Heat Dissipation Capacity: 10kW ~ 20kW
  • Air Conditioner Configuration: 12.5kW/15kW/20kW dual-system variable-frequency rack or rear door precision air conditioners with N+1 redundancy and sensible heat ratio ≥98%
  • Applicable Scenarios: AI computer rooms, High-Performance Computing (HPC) computer rooms, core government computer rooms, core financial computer rooms, industrial internet edge computing nodes and other high-power density IT deployment scenarios.
  • PUE: ≤1.45 under full-load operating conditions

3.3 Classification by Application Scenario & Industrial Characteristics

Customized for eight major industry verticals with unique scenario pain points, compliance requirements and optimized design for differentiated industry demands: general office, financial branch, government classified, industrial edge, medical compliance, communication base station, transportation outdoor and energy station models.

3.3.1 General Office Air-Cooled Integrated Cabinet

Designed for small and medium enterprises, chain retail stores and office spaces, prioritizing cost performance, easy deployment and simplified O&M with complete basic functionality to support conventional office IT hardware operation.

  • Core Optimizations: Simplified redundant configurations to lower initial investment, intuitive operation interfaces compatible with non-professional maintenance staff, low noise design for direct installation within office areas without disrupting daily work.
  • Core Configuration: Basic rack-mounted UPS, fixed-frequency rack air conditioner, entry-level environmental monitoring, password access control and standard fire suppression hardware in a standard 42U cabinet.
  • Applicable Scenarios: SME office computer rooms, chain retail stores, office building weak current closets and general office network computer rooms.

3.3.2 Financial Branch Air-Cooled Integrated Cabinet

Built for banks, securities firms, insurance agencies and other financial industry branches and subsidiaries, prioritizing business continuity, data security, compliance audit and ultra-high reliability core demands specific to the financial sector.

  • Core Optimizations: Dual redundant power supply, dual hot standby UPS and redundant battery banks to eliminate business downtime risks; financial-grade environmental monitoring with full traceable operation logs and complete data audit trails to meet China Banking and Insurance Regulatory Commission compliance standards; high-security multi-factor fingerprint + facial recognition access control and full-video surveillance to guarantee physical and data security.
  • Core Configuration: High-frequency online double-conversion UPS with N+1 redundancy, long-duration energy storage battery packs, dual-input ATS power distribution, high-efficiency variable-frequency precision air conditioning, financial-grade environmental monitoring, multi-factor authentication access control, high-definition video surveillance, HFC-227ea clean gas fire suppression and fully sealed cabinet construction.
  • Applicable Scenarios: Community bank branches, securities business departments, insurance subsidiaries, self-service banking outlets and financial data backup nodes across the financial industry.

3.3.3 Government Classified Air-Cooled Integrated Cabinet

Developed for government agencies, public institutions and classified confidential units, focused on domestic hardware compatibility, information security, classified management, ultra-high reliability and regulatory compliance core requirements.

  • Core Optimizations: 100% domestically produced core system components fully compatible with domestic servers, operating systems, databases and security hardware; certified by national confidential technology evaluation authorities with complete physical isolation, data encryption and granular permission management; fully shielded cabinet construction with electromagnetic shielding efficiency ≥60dB to prevent electromagnetic signal leakage; multi-tier permission access control with full operation traceability to comply with confidential information system management standards.
  • Core Configuration: Domestic UPS hosts, domestic lithium iron phosphate battery packs, domestic precision air conditioning, domestic environmental monitoring systems, national cryptographic algorithm access control, electromagnetically shielded cabinet frames, classified-grade fire suppression, lightning protection & grounding and full-process design aligned with national confidentiality standards.
  • Applicable Scenarios: Government agency computer rooms, classified unit computer rooms, district government service centers, police stations, procuratorates and courts and other government classified scenarios.

3.3.4 Industrial Edge Air-Cooled Integrated Cabinet

Tailored for factories, mines, oil & gas fields and manufacturing industrial sites, engineered to withstand harsh complex industrial environments and satisfy high-reliability operation demands for industrial internet and edge computing automation control systems.

  • Core Optimizations: Wide-temperature design stable from -10℃ to 55℃; elevated dust, moisture and corrosion resistance with IP54/IP55 protection rating; industrial-grade hardware with robust electromagnetic interference resistance complying with industrial EMC standards; dual redundant power supply and wide input voltage range to adapt to fluctuating industrial grid power; rail mounting compatibility for industrial control equipment installation.
  • Core Configuration: Industrial-grade UPS hosts, wide-temperature rack-mounted precision air conditioners, industrial environmental monitoring, high-protection cabinet frames, anti-seismic mounting brackets, anti-corrosion coating treatment, industrial-grade surge lightning protection and redundant power distribution systems.
  • Applicable Scenarios: Factory automation computer rooms, industrial edge computing nodes, mine monitoring computer rooms, oil & gas field station computer rooms, manufacturing production line control computer rooms and industrial IoT gateway computer rooms across industrial verticals.

3.3.5 Medical Compliance Air-Cooled Integrated Cabinet

Designed for hospitals, community health service centers and disease control institutions, addressing core medical industry demands for data security, uninterrupted business operation, electromagnetic compatibility and clean operating environments while aligning with medical industry regulatory specifications.

  • Core Optimizations: High-reliability redundant architecture to guarantee 24/7 uninterrupted operation of core medical systems including HIS, LIS and PACS; low electromagnetic radiation design certified for medical device EMC to avoid interference with precision clinical instruments; antibacterial dust-proof cabinet coating and high-efficiency internal air filters to inhibit bacterial and dust accumulation and meet hospital clean environment standards; comprehensive alarm and emergency response workflows to secure medical data and business continuity.
  • Core Configuration: Medical-grade dual redundant UPS systems, long-duration energy storage battery banks, high-efficiency variable-frequency clean precision air conditioning, medical-grade environmental monitoring, antibacterial dust-proof cabinet frames, high-security access control, clean gas fire suppression and low electromagnetic radiation design.
  • Applicable Scenarios: Hospital central computer rooms, department computer rooms, PACS imaging equipment computer rooms, community health service center computer rooms, disease control center computer rooms and physical examination center computer rooms across the healthcare industry.

3.3.6 Communication Base Station Air-Cooled Integrated Cabinet

Built for telecom operator 5G base stations, transmission nodes, communication computer rooms and edge data centers, prioritizing wide-temperature operation, ultra-high reliability, unattended remote management and energy efficiency core communication industry requirements.

  • Core Optimizations: Ultra-wide-temperature design stable from -20℃ to 60℃ for extreme environmental conditions; high energy efficiency with automatic free cooling switching in low-temperature environments to drastically cut power consumption; telecom-grade environmental monitoring supporting national Class B interface protocol for seamless integration with operator central monitoring platforms for centralized remote management; comprehensive lightning, anti-theft, dust and moisture protection engineered for unattended base station operation.
  • Core Configuration: Telecom-grade high-frequency UPS systems, lithium iron phosphate battery packs, wide-temperature high-efficiency air-cooled precision air conditioners, telecom-grade environmental monitoring, anti-theft cabinet frames, B+C two-stage surge lightning protection and remote O&M management platforms with IP55 protection rating construction.
  • Applicable Scenarios: Telecom operator 5G base station computer rooms, transmission node computer rooms, communication business hall computer rooms, edge data centers and radio & television transmission computer rooms across the communications industry.

3.3.7 Transportation Outdoor Air-Cooled Integrated Cabinet

Developed for highway, rail transit, tunnel, airport and port transportation industry outdoor/semi-outdoor complex environments, delivering low-latency, high-reliability unattended operation capabilities for transportation infrastructure.

  • Core Optimizations: High-strength anti-seismic structural design to withstand continuous vibration from vehicle traffic; elevated waterproof, dust-proof, anti-corrosion and salt-spray resistance with IP55 protection rating for tunnel, coastal and outdoor harsh environments; ultra-wide-temperature operation range of -30℃ to 65℃ for extreme climate conditions; dual redundant power supply compatible with solar + mains dual input for remote transportation site power limitations; automotive-grade EMC anti-interference performance for high electromagnetic interference environments.
  • Core Configuration: Industrial anti-seismic UPS systems, wide-temperature air cooling systems, high-protection outdoor cabinet frames, anti-corrosion salt-spray coating treatment, industrial environmental monitoring, multi-stage surge lightning protection and solar power supply adaptation modules with unattended O&M workflows.
  • Applicable Scenarios: Highway ETC gantry computer rooms, tunnel monitoring computer rooms, subway platform equipment computer rooms, airport terminal node computer rooms, port terminal control computer rooms and railway signal computer rooms across the transportation industry.

3.3.8 Energy Station Air-Cooled Integrated Cabinet

Customized for photovoltaic power stations, wind farms, substations and energy storage power stations, engineered to operate reliably in remote energy station locations with harsh environmental conditions and unattended core operation demands.

  • Core Optimizations: Ultra-wide-temperature design stable from -40℃ to 70℃ for extreme climate environments including Gobi, grasslands, coastal and mountain regions; high dust, moisture, corrosion and salt-spray resistance to withstand remote energy station site conditions; robust grid compatibility with wide input voltage range to adapt to grid voltage fluctuations and harmonic interference at energy facilities; compatibility with wind-solar-storage hybrid power supply systems for off-grid and semi-off-grid operation scenarios; power industry-grade environmental monitoring supporting standard power system communication protocols for integration with power dispatch platforms and centralized remote monitoring.
  • Core Configuration: Power industry-grade UPS systems, long-cycle-life energy storage battery banks, wide-temperature high-efficiency air cooling systems, power-grade environmental monitoring, high-protection cabinet frames, power-dedicated surge lightning protection, grid harmonic filtering modules and wind-solar-storage hybrid power adaptation modules.
  • Applicable Scenarios: Photovoltaic power station monitoring computer rooms, wind farm control computer rooms, substation auxiliary computer rooms, energy storage power station supporting computer rooms, hydropower plant monitoring computer rooms and remote energy station computer rooms across the energy industry.

3.4 Classification by Refrigeration Architecture & Airflow Organization

Classified by air cooling system architecture, air supply mode and airflow organization into four categories: front-supply rear-return, horizontal air supply, bottom-supply top-return and rear door air cooling models, selectable based on cabinet deployment mode, IT equipment air intake orientation and power density to deliver optimal heat dissipation performance.

3.4.1 Front-Supply Rear-Return Air-Cooled Integrated Cabinet

The most fundamental and widely adopted refrigeration architecture with rack-mounted precision air conditioners installed at the cabinet lower front section. Cool air is blown forward from the air conditioner to the front cold channel, passes through IT equipment front air intakes to absorb heat, and hot air exhausts from equipment rear outlets back to the air conditioner rear return air inlet, forming a complete front-supply rear-return airflow cycle sealed by blanking panels to isolate cold and hot airflows effectively.

  • Core Features: Simple structure, convenient installation and maintenance, low cost, no extra air duct design required, fully compatible with front intake rear exhaust standard servers, optimal for single-cabinet deployment scenarios.
  • Adaptable Power Density: 3kW ~ 10kW
  • Air Conditioner Mounting Position: Lower front interior of the cabinet, 19-inch rack-mounted installation
  • Applicable Scenarios: Single-cabinet deployment, dual-cabinet deployment, standard rack servers and low-to-medium power density scenarios.

3.4.2 Horizontal Air Supply Air-Cooled Integrated Cabinet

Also known as row-level air conditioner architecture with precision air conditioners mounted in parallel with IT cabinets within the cabinet row. Air conditioners draw hot air from the rear hot channel, cool it and blow cold air horizontally forward into the front cold channel, which enters IT equipment front air intakes; heated air exhausts to the rear fully enclosed hot channel and circulates back to the row-level air conditioner, forming a horizontal airflow cycle supported by fully enclosed cold-hot channel containment.

  • Core Features: Near-end cooling with minimal cold loss, high cooling efficiency, complete cold-hot airflow isolation eliminating hot spots and precise temperature control with superior energy savings, ideal for multi-cabinet cluster deployment scenarios.
  • Adaptable Power Density: 5kW ~ 20kW
  • Air Conditioner Mounting Position: Within the cabinet row, parallel with IT cabinets via row-level rack mounting
  • Applicable Scenarios: Multi-cabinet cluster deployment, single-row micro-module computer rooms, medium-to-high power density and high-density server deployment scenarios.

3.4.3 Bottom-Supply Top-Return Air-Cooled Integrated Cabinet

Precision air conditioners installed at the cabinet bottom or dedicated cooling cabinet lower section blow cold air upward through a static pressure plenum for uniform distribution across IT equipment air intakes. Cold air flows vertically upward through IT hardware to absorb heat, and hot air exhausts from the cabinet top back to the air conditioner upper return inlet, forming a bottom-supply top-return airflow cycle aligned with natural hot air buoyancy characteristics.

  • Core Features: Airflow organization aligned with natural hot air upward buoyancy for superior heat dissipation efficiency and uniform internal cabinet temperature distribution without vertical temperature gradients, eliminating overheating of upper rack equipment and compatible with high-power density IT hardware heat dissipation demands.
  • Adaptable Power Density: 10kW ~ 20kW
  • Air Conditioner Mounting Position: Cabinet bottom or dedicated cooling cabinet lower section
  • Applicable Scenarios: High-power density servers, GPU computing servers, cabinets taller than 47U and deployments with multi-layer vertically distributed IT equipment.

3.4.4 Rear Door Air Cooling Integrated Cabinet

Also referred to as cabinet rear door air conditioning architecture, with air cooling hardware directly mounted as a replacement for the standard cabinet rear door. Hot air exhausted from IT equipment rear outlets flows directly into the rear door air conditioner evaporator for instantaneous cooling; cooled air circulates back to the IT equipment front cold channel, forming an ultra-short airflow circulation path to deliver ultimate near-end cooling performance.

  • Core Features: Near-zero cold loss with the shortest possible cooling airflow path, maximum heat dissipation capacity to fully eliminate local hot spots for ultra-high-power density IT hardware, no occupation of internal cabinet U mounting space to maximize usable IT installation area.
  • Adaptable Power Density: 10kW ~ 20kW
  • Air Conditioner Mounting Position: Cabinet rear door position via rear door integrated mounting
  • Applicable Scenarios: Ultra-high-power density AI servers, GPU computing clusters, High-Performance Computing (HPC) scenarios and high-density deployments with limited internal cabinet installation space.

3.5 Classification by System Redundancy Tier & Availability

Classified by redundant architecture and availability tier into basic N architecture, standard N+1 redundant and premium 2N redundant models, selectable based on business criticality and uptime requirements to match tiered business continuity demands.

3.5.1 Basic N Architecture Air-Cooled Integrated Cabinet

Single non-redundant system design with standalone UPS, air conditioning and power distribution hardware, featuring simple structure, low cost and convenient deployment for non-critical business scenarios allowing short-duration downtime.

  • Core Features: Single-system construction, low upfront investment, minimal floor space footprint and simplified maintenance workflows for non-core business workloads.
  • Redundancy Configuration: Standalone UPS host, single air conditioning system, single-path power input with no backup redundancy
  • Availability Tier: 99.9%, annual downtime ≤8.76 hours
  • Applicable Scenarios: Office network computer rooms, security monitoring computer rooms, chain retail stores, non-critical IT hardware deployments and scenarios permitting brief equipment downtime.

3.5.2 Standard N+1 Redundant Air-Cooled Integrated Cabinet

Core components adopt N+1 redundant architecture including modular N+1 redundant UPS, dual-system N+1 redundant air conditioning and dual-input N+1 redundant power distribution. Backup systems automatically take over load operation upon primary system failure to guarantee uninterrupted service without business outages, delivering optimal cost performance for most core business uptime requirements.

  • Core Features: Redundant backup of core hardware eliminates single points of failure with high reliability and business continuity, optimal comprehensive cost performance matching uptime demands of the vast majority of core business workloads.
  • Redundancy Configuration: Modular N+1 redundant UPS, dual-system N+1 redundant air conditioning, dual-input N+1 redundant power distribution and dual backup critical circuits
  • Availability Tier: 99.99%, annual downtime ≤52.56 minutes
  • Applicable Scenarios: Enterprise core computer rooms, financial branches, government computer rooms, hospital computer rooms, education core computer rooms, operator edge computer rooms and core business scenarios requiring near-zero downtime.

3.5.3 Premium 2N Redundant Air-Cooled Integrated Cabinet

Fully active-active 2N redundant architecture with two completely independent parallel power supply systems, two independent cooling systems and two separate monitoring systems operating simultaneously as mutual backups. Either full system can bear 100% of total load upon failure or maintenance of the other with zero switching latency, completely eliminating all single points of failure to meet Class A national computer room standards and the highest uptime demands of mission-critical business workloads.

  • Core Features: Fully active-active 2N redundant architecture with no single points of failure, maximum system availability enabling online maintenance and firmware upgrades without business interruption, meeting Class A data center standards for top-tier mission-critical business scenarios.
  • Redundancy Configuration: Dual active-active 2N redundant UPS, dual-system 2N redundant air conditioning, fully independent dual-path 2N power distribution, dual redundant PDUs and dual power supply compatibility for IT hardware alongside dual redundant monitoring systems
  • Availability Tier: 99.999%, annual downtime ≤5.256 minutes
  • Applicable Scenarios: Financial core computer rooms, government core computer rooms, hospital HIS system computer rooms, operator core computer rooms, industrial core control computer rooms and mission-critical business scenarios demanding zero service interruption.

4 System Schematic Principles

The system schematics of the KITOZER standard air-cooled integrated cabinet provide standardized visual descriptions of operating logic, data flow and energy transfer across the full system, divided into five core schematic categories: electrical system schematic, air cooling refrigeration cycle schematic, intelligent environmental monitoring system topology schematic, airflow organization schematic and fire linkage control schematic, fully illustrating full-system operating workflows and functional logic.

4.1 Electrical System Schematic

The electrical system schematic visualizes core logic for power transmission, distribution, conversion and protection across the integrated cabinet, describing the complete power flow path from mains input to terminal load utilization, split into main circuit schematic, UPS operating principle schematic and power distribution protection schematic.

4.1.1 Main Circuit Electrical Operating Principle

The complete mains-to-load power workflow covers five core phases: dual mains input switching, rectification & inversion, backup energy storage, output power distribution and terminal load power supply.

  1. Dual Mains Input Phase: Two independent mains power sources connect to the Automatic Transfer Switch (ATS) dual input terminals. The ATS continuously monitors voltage, frequency and phase of both power feeds, switching to the backup feed within ≤100ms upon overvoltage, undervoltage, phase loss or power failure of the primary feed to guarantee continuous input power. The mains input loop integrates Class B Surge Protection Devices (SPD) to mitigate lightning and grid surge impacts, paired with a main input circuit breaker for overload/short-circuit protection and full-system power isolation.
  2. Rectification Conversion Phase: Stabilized mains power post-ATS switching enters the UPS rectifier module, adopting three-phase full-bridge PFC rectifier topology to convert AC to stable DC power, simultaneously supplying charging current to battery packs and DC input to the inverter module. The rectifier features power factor correction with input power factor ≥0.99 to drastically reduce grid harmonic pollution and supports wide input voltage range to accommodate severe grid voltage fluctuations.
  3. Backup Energy Storage Phase: DC output from the rectifier feeds the Battery Management System (BMS), which continuously monitors battery pack voltage, current, temperature, State of Charge (SoC) and State of Health (SoH). It automatically adjusts charging voltage and current to execute intelligent float and equalized charging with multi-layer protection against overcharge, overdischarge, overcurrent, overtemperature and short circuits to safeguard battery safety and service life. During normal mains operation, batteries remain in float standby mode; upon mains failure, batteries instantaneously discharge DC power to the inverter for uninterrupted load power supply. Mains restoration triggers automatic rectifier restart to resume normal operation and recharge battery packs.
  4. Inversion Conversion Phase: DC power from the rectifier or battery bank enters the UPS inverter module, adopting IGBT high-frequency inverter topology to convert DC to pure, stable low-distortion sine-wave AC power for distribution to load circuits. The inverter delivers regulated voltage (output precision ≤±1%) and frequency (output precision ≤±0.1%), completely eliminating mains voltage fluctuation, harmonic interference and frequency drift to supply clean, stable power to loads. The UPS integrates a static bypass switch with seamless switching (≤2ms latency) to mains bypass power upon inverter failure, overload or overheating, paired with a manual maintenance bypass switch enabling online UPS maintenance without load power interruption.
  5. Output Power Distribution & Load Supply Phase: Stabilized AC power from the UPS inverter feeds the output power distribution unit, integrating Class C SPD secondary surge protection, a main output circuit breaker and multiple independent branch circuit breakers each equipped with dedicated overload and short-circuit protection to distribute power across isolated load loops: IT load loops connect to rack-mounted PDUs for servers, switches and storage hardware; cooling loops supply air conditioner indoor/outdoor units and ventilation fans; auxiliary loops power monitoring, access control, lighting and fire suppression hardware. All load loops integrate power monitoring modules to capture real-time per-loop voltage, current, power, energy consumption and power factor data uploaded to the environmental monitoring system for full-loop power tracking and management.

4.1.2 UPS Uninterruptible Power Supply Operating Principle

Adopting high-frequency online double-conversion topology as the core of the power distribution system, the UPS operates across four distinct modes with dedicated functional workflows for each state:

  1. Normal Operating Mode: With stable mains input, AC power passes through input EMI filtering to the rectifier, which converts AC to DC to simultaneously charge batteries and supply power to the inverter. The inverter converts DC to clean sine-wave AC filtered via output EMI circuits to power loads. Full electrical isolation between mains and loads eliminates all mains interference, fluctuation and harmonic distortion for the purest stable power supply to hardware.
  2. Battery Power Mode: Upon mains power loss or mains parameter deviation outside acceptable operating ranges, the rectifier ceases operation and battery packs instantaneously discharge DC power to the inverter, which continues converting DC to stable AC for load power supply with zero switching latency to deliver fully uninterrupted operation. Battery backup runtime is determined by battery pack capacity and total load power, configurable to user-specified requirements. Once mains power recovers within acceptable parameter thresholds, the rectifier automatically restores normal operating mode and initiates battery recharging.
  3. Bypass Operating Mode: In the event of inverter failure, load overload or overheating, the UPS control system automatically triggers the static bypass switch to seamlessly shift load power supply from inverter output to mains bypass power (switching latency ≤2ms) to eliminate load downtime, simultaneously generating fault alerts to notify maintenance personnel. Once faults are resolved and overload conditions lifted, the UPS automatically switches back to normal inverter operating mode.
  4. Maintenance Bypass Mode: For internal UPS maintenance, component replacement or repair, the manual maintenance bypass switch is closed to supply loads directly via mains maintenance bypass power. The UPS input, output and battery circuit breakers are opened to fully isolate the UPS unit for maintenance with uninterrupted load power supply throughout the workflow. Post-maintenance, the UPS input/output breakers are closed to start the unit and enter normal operating mode, followed by opening the manual maintenance bypass switch to restore standard power delivery workflows.

4.1.3 Power Distribution Protection Operating Principle

The power distribution protection system serves as the full electrical system safety barrier, adopting a multi-tier linked protection architecture implementing full-circuit protection spanning from mains input to terminal loads with core protection workflows as follows:

  1. Multi-Tier Protection Architecture: Three-tier selective protection sequence: main input protection → branch circuit protection → terminal PDU protection, with progressively smaller rated current breakers at each tier to ensure only the faulted terminal loop disconnects during short-circuit or overload events without disrupting upstream circuits or other load branches, containing fault scope and preventing system-wide outages.
  2. Overload & Short-Circuit Protection: All power distribution loops deploy high breaking capacity miniature or molded case circuit breakers with inverse-time long-delay overload protection and instantaneous short-circuit protection to automatically isolate faulted circuits upon overcurrent to safeguard wiring and hardware integrity. Circuit breaker ultimate breaking capacity Icu ≥10kA, operational short-circuit breaking capacity Ics ≥6kA, meeting power distribution system breaking requirements.
  3. Surge Lightning Protection: Two-stage B+C surge protection architecture with Class B SPDs installed at the mains input main switch (nominal discharge current ≥40kA, maximum discharge current ≥60kA, 3+1 protection mode) mitigating high-current surges from direct and induced lightning strikes, and Class C SPDs deployed at UPS output and PDU input terminals (nominal discharge current ≥20kA, maximum discharge current ≥40kA) absorbing residual surges and grid switching overvoltage to protect terminal load hardware. Decoupling devices with ≥5m separation distance are installed between two-stage SPDs to ensure coordinated multi-tier surge protection performance for full-circuit lightning surge mitigation.
  4. Earth Leakage Protection: Residual current circuit breakers integrated into the main input, air conditioning and auxiliary loops with 30mA leakage operating current and ≤0.1s action latency to instantly cut power upon circuit leakage or human electric shock and protect personnel and equipment safety.
  5. Isolation Protection: Optional isolation transformers integrated into the UPS input/output to deliver full electrical isolation between mains and loads, eliminating ground potential difference and common-mode interference impacting IT hardware. Physical separation (≥300mm spacing) between high-voltage power and low-voltage signal wiring prevents electromagnetic interference from power circuits disrupting signal transmission.
  6. Grounding & Equipotential Protection: All equipment metal enclosures, cabinet frames, door panels, cable trays, copper bars and metal piping connect reliably to the dedicated cabinet grounding copper bar via multi-strand copper cables to form full-system equipotential bonding and eliminate potential differences between discrete hardware units, mitigating equipment damage and electric shock hazards from differential potential. The grounding copper bar links to the building combined grounding grid via dedicated grounding cables with grounding resistance controlled to ≤4Ω for reliable discharge of fault and lightning currents.

4.2 Air Cooling Refrigeration Cycle Schematic

The KITOZER standard air-cooled integrated cabinet adopts vapor-compression refrigeration cycle principles to transfer heat from the cabinet interior to the external environment via refrigerant phase change for precise internal cabinet temperature regulation. The complete refrigeration cycle consists of four core processes: compression, condensation, throttling and evaporation, paired with fan-driven air circulation to deliver cold and heat transfer, with full cycle operating logic detailed below.

4.2.1 Core Vapor-Compression Refrigeration Cycle Operating Principle

The full refrigeration cycle operates within a sealed refrigerant pipeline loop, utilizing refrigerants as heat transfer media to absorb and release thermal energy via gas-liquid phase change across four sequential core processes:

  1. Compression Process: Low-temperature low-pressure gaseous refrigerant flows out of the evaporator into the compressor suction port. The scroll/rotary variable-frequency compressor rotates internal scroll or rotor components at high speed to compress gaseous refrigerant into high-temperature high-pressure gaseous refrigerant discharged from the compressor exhaust port. As the power core of the refrigeration cycle, the compressor automatically adjusts operating frequency and cooling output to match real-time cabinet thermal load demand via variable-frequency control, delivering on-demand cooling and drastically reducing power consumption.
  2. Condensation Process: High-temperature high-pressure gaseous refrigerant discharged from the compressor flows through refrigerant pipelines into the outdoor unit condenser, a finned tube heat exchanger. Outdoor unit axial fans drive ambient air to flow rapidly across condenser fins for heat exchange with internal high-temperature gaseous refrigerant, which releases heat into outdoor ambient air and condenses from high-temperature high-pressure gas into medium-temperature high-pressure liquid refrigerant. Condensate pressure regulating valves adjust condenser pressure automatically based on ambient temperature to guarantee stable refrigeration system operation within the -10℃ ~ 55℃ wide ambient temperature range.
  3. Throttling Process: Medium-temperature high-pressure liquid refrigerant exiting the condenser passes through a filter dryer to remove impurities and moisture and avoid system ice and dirt blockages, followed by a sight glass for refrigerant status and fill level inspection before entering the electronic expansion valve. The electronic expansion valve acts as the refrigeration system throttling component, automatically adjusting valve opening via control system instructions to throttle high-pressure liquid refrigerant into low-temperature low-pressure gas-liquid mixed-phase refrigerant fed to the evaporator. With adjustment precision of 0.1 steps, the electronic expansion valve precisely regulates refrigerant flow based on evaporator superheat to maintain optimal refrigeration cycle operating conditions and boost cooling efficiency.
  4. Evaporation Process: Low-temperature low-pressure gas-liquid mixed-phase refrigerant flows into the air conditioner indoor unit evaporator, another finned tube heat exchanger. Indoor unit centrifugal fans drive hot cabinet air to flow rapidly across evaporator fins for heat exchange with internal low-temperature refrigerant, which absorbs airborne heat and fully evaporates from gas-liquid mixed phase into low-temperature low-pressure gaseous refrigerant while cooling air into cold air recirculated into the cabinet interior to cool IT hardware. The evaporation phase represents the refrigeration cycle heat absorption process, extracting thermal energy generated by IT equipment via refrigerant phase change cooling. Low-temperature low-pressure gaseous refrigerant exiting the evaporator re-enters the compressor suction port to complete the full closed refrigeration cycle.

4.2.2 Air Circulation & Airflow Organization Operating Principle

Air circulation delivers cold transfer to IT hardware and heat transfer to the evaporator, optimized via cabinet air duct design to isolate cold and hot airflows, eliminate airflow mixing and local hot spots and boost cooling efficiency with core operating logic as follows:

  1. Internal Cabinet Air Circulation: The air conditioner indoor unit centrifugal fan draws hot air exhausted from IT hardware out of the rear cabinet hot channel into the evaporator for heat exchange and cooling into low-temperature cold air. The fan pressurizes cold air and delivers it forward into the front cabinet cold channel, a fully sealed static pressure plenum distributing cold air uniformly across all vertical cabinet U heights to eliminate vertical temperature gradients and guarantee consistent cold air supply to all IT hardware. Cold air enters IT equipment front intake ports via internal hardware cooling fans, absorbs heat from CPU, memory, hard disk and other heating components and exhausts heated air from equipment rear outlets back into the fully isolated rear hot channel to return to the air conditioner return air inlet and complete internal cabinet air circulation.
  2. Cold-Hot Isolated Air Duct Design: Blanking panels seal all unoccupied cabinet U-height positions, with EPDM sealing strips installed at cabinet uprights, door panels and joint seams to form fully enclosed independent front cold and rear hot cavities, preventing direct cold air short-circuit flow from cold channel to hot channel bypassing IT hardware. This guarantees 100% of cold air passes through IT equipment to absorb heat, eliminates local hot spots and maximizes cooling efficiency.
  3. Outdoor Side Air Circulation: Outdoor unit axial fans drive ambient outdoor air to flow rapidly across condenser fins for heat exchange with internal high-temperature refrigerant, absorbing refrigerant-released heat and exhausting hot air into the external atmosphere to complete outdoor air circulation and ultimate heat dissipation from the refrigeration system.
  4. Intelligent Air Volume Regulation Principle: Both indoor and outdoor air conditioner fans adopt EC DC variable-frequency fans that automatically adjust rotational speed and air volume output based on internal cabinet temperature and air conditioner operating conditions. Fan speed increases to boost heat exchange efficiency under high cabinet temperature and heavy thermal load conditions and reduces rotational speed to cut power consumption and noise under low thermal load and low internal temperature conditions for intelligent on-demand airflow adjustment.

4.2.3 Dehumidification & Humidification Control Operating Principle

Beyond temperature regulation, the refrigeration system delivers integrated humidity control to maintain cabinet relative humidity within the 40%~60% optimal operating range for IT hardware, mitigating condensation leakage risks from excessive humidity and static electricity hazards from insufficient humidity with dedicated operating workflows for dehumidification and humidification:

  1. Cooling Dehumidification Principle: When cabinet relative humidity exceeds upper thresholds, evaporator surface temperature drops below air dew point temperature. Water vapor in air condenses into liquid water droplets on evaporator fin surfaces, collected in the condensate water tray and drained externally via drainage piping to reduce airborne moisture content and achieve dehumidification. The air conditioner control system automatically adjusts evaporator temperature based on humidity sensor readings to deliver precise dehumidification alongside cooling capacity, maintaining stable dehumidification performance even under low load conditions to eliminate evaporator condensation risks.
  2. Humidification Control Principle (Optional): Optional wet film humidification modules automatically activate when cabinet relative humidity falls below lower thresholds to boost air moisture content via natural water evaporation through polymer wet film media. Zero-power natural evaporation wet film humidification delivers clean atomization-free operation without white powder residue, integrated with anti-overflow and dry-burn protection functions to guarantee safe, reliable humidification workflows.

4.3 Intelligent Environmental Monitoring System Topology Schematic

The KITOZER intelligent environmental monitoring system adopts a layered distributed architecture split into five tiers: field perception layer, core control layer, local interaction layer, remote transmission layer and upper application layer, delivering end-to-end full-process management spanning data collection, logical processing, local control, remote transmission and platform application with detailed tiered topology operating logic as follows:

4.3.1 Tiered Topology Architecture Operating Principle

  1. Field Perception Layer: The source of all monitoring system data, collecting full-system physical parameters, equipment status and alarm signals via dedicated sensors and hardware acquisition modules:
    • Environmental Perception Sensors: Temperature & humidity, water immersion, smoke, dust and hydrogen sensors converting physical environmental metrics to electrical signals transmitted to the core control layer.
    • Power Equipment Acquisition Modules: Dedicated monitoring modules for UPS, air conditioning, power distribution, batteries and PDUs collecting real-time power hardware operating parameters, status and fault data for transmission to the core control layer.
    • Security Status Acquisition Modules: Door magnetic, access control status, camera video and anti-tamper vibration sensors capturing security system status and image data uploaded to the core control layer.
    • Fire Signal Acquisition Modules: Smoke, temperature and flame fire detectors collecting fire hazard signal data transmitted to the core control layer for fire risk assessment and alert processing. All field perception layer hardware supports standard Modbus-RTU/TCP, SNMP and other communication protocols, interconnecting with the core control layer via RS485, Ethernet and WiFi interfaces for stable, anti-interference data transmission.
  2. Core Control Layer: The “brain” of the environmental monitoring system centered on the industrial embedded environmental monitoring host with real-time embedded operating systems designed for 24/7 uninterrupted stable operation, executing core functional workflows as follows:
    • Data Collection & Parsing: Real-time capture of all field perception layer sensor and equipment data, parsed, calibrated and standardized into normalized numerical and status information per corresponding communication protocols.
    • Data Processing & Storage: Filtering, calibration and analysis of raw collected data to eliminate anomalous readings and guarantee data accuracy; built-in high-capacity storage for long-term archiving of real-time operational data, historical metrics, alarm records and operation logs with minimum 1-year storage retention.
    • Logical Judgment & Linkage Control: Built-in programmable logic control engine executing conditional judgment against user-defined threshold and linkage rule sets upon receiving abnormal data or status signals to automatically trigger corresponding linkage control actions, eliminating manual intervention for full-system intelligent automation workflows.
    • Alarm Processing & Tiered Notification: Four-tier alarm management engine categorizing alerts as critical, major, minor and prompt with dedicated processing workflows and notification channels per tier. Alarms auto-record timestamp, location, content and severity, triggering local sound-light alarms alongside multi-channel remote notifications including SMS, phone call, email and APP push to guarantee timely alert delivery to management personnel.
    • Protocol Conversion & Data Forwarding: Extensive built-in industrial communication protocol library supporting Modbus-RTU/TCP, SNMP v1/v2c/v3, HTTP, MQTT, national Class B interface, power 104 protocol and more for cross-hardware cross-system protocol conversion, forwarding standardized data to local interaction, remote transmission and upper application layers for full cross-platform interoperability.