KITOZER Air-Cooled Integrated Classified Cabinet Full-Series Solution

1 System Overview

1.1 Core System Definition

The KITOZER air-cooled integrated classified cabinet is a highly integrated carrier for classified information security, independently developed by Guangzhou Lai’an Intelligent System Development Co., Ltd. Drawing on over 20 years of technical expertise in computer room infrastructure construction and classified information security protection, the product strictly complies with national and industrial mandatory specifications including the Law of the People’s Republic of China on Guarding State Secrets and its implementing regulations, national secrecy bureau BMB series standards, GB50174-2017 Code for Design of Data Centers, and GJB5792-2006 Classification and Measurement Methods for Electromagnetic Shielding Enclosures of Military Classified Information Systems.

Custom-built for IT equipment processing, storing and transmitting state secrets, the unit integrates state-level electromagnetic shielding protection, cabinet-level precision air cooling heat dissipation, fully redundant classified power supply and distribution, domestic intelligent environmental monitoring, full-link security control, and clean gas fire suppression into a single compact device.

Taking a single cabinet as the minimum deployment unit, the system completely overturns the traditional fragmented construction model of classified computer rooms, which involves separate construction, multi-vendor supply and distributed operation & maintenance. It delivers factory prefabrication, plug-and-play on-site deployment, full-lifecycle confidentiality compliance control, and unattended intelligent operation & maintenance, covering all classified information system security levels from Confidential to Top Secret. It serves as the core information security infrastructure carrier for Party and government organs, military industrial entities, research institutes, financial institutions, energy central SOEs and other core classified scenarios.

1.2 Policy R&D Drivers & Industry Background

1.2.1 Driven by National Confidentiality Strategic Policies

With the comprehensive advancement of Digital China construction, digital, networked and intelligent storage & transmission of state secrets have become mainstream, elevating the security protection of classified information systems to national strategic security priority.

Article 24 of the Law of the People’s Republic of China on Guarding State Secrets clearly stipulates that classified information equipment must be used in premises meeting confidentiality requirements with reliable anti-electromagnetic leakage protection measures. Article 21 of the Cybersecurity Law of the People’s Republic of China mandates that operators of critical information infrastructure implement classified data protection, electromagnetic leakage shielding and full-link auditing technical controls for classified data. The revised BM/Z 1-2023 Technical Requirements for Classified Information Systems released by the State Secrecy Bureau in 2023 further enforces mandatory technical specifications for electromagnetic shielding, isolated power distribution, permission control and audit traceability for classified information equipment, providing clear policy foundations for the R&D and application of integrated classified cabinets.

Meanwhile, the full rollout of the national IT innovation (Xinchuang) localization strategy requires full domestic independent controllability of core hardware and basic software for classified information systems, eliminating reliance on foreign technologies and products. This drives the technical upgrade of integrated classified cabinets from simple functional integration to full-link domestic independent controllability, defining clear R&D directions for the KITOZER air-cooled integrated classified cabinet.

1.2.2 Core Pain Points of Traditional Classified Computer Room Construction

Decades-old traditional classified computer room construction models fail to meet modern demands of rapid deployment, elastic scaling, high compliance, low operation & maintenance costs and high reliability, presenting four irreconcilable industry pain points:

  1. High full-link confidentiality compliance risks and difficult acceptance Electromagnetic shielding, power distribution, heat dissipation, monitoring and security systems for traditional classified computer rooms are supplied and constructed by separate vendors with inconsistent interfaces, standards and protection grades, creating a “barrel effect” where any weak link compromises overall system confidentiality compliance. Electromagnetic shielding rooms pose particularly high construction risks: on-site welding, cable penetration sealing and shielding interface workmanship are highly variable, frequently causing incomplete welds, loose shielding seals and electromagnetic leakage through cable penetrations. Failed shielding performance leads to project rework rates exceeding 30%, delaying classified system commissioning.
  2. Long construction cycles and inflexible deployment unable to support rapid business iteration End-to-end delivery of traditional classified computer rooms spans 3–6 months, with large classified data centers taking over one year to complete, failing to support urgent rapid deployment of classified business for Party and military entities. Additionally, computer rooms are sized for long-term maximum load, resulting in high upfront investment and low resource utilization. Business expansion requires secondary renovation that disrupts existing classified system operation and damages shielding integrity, introducing new confidentiality compliance risks.
  3. Excessive energy consumption and persistently high operation & maintenance costs Traditional classified computer rooms adopt room-level air conditioning with severe hot-cold air mixing, resulting in low cooling efficiency and PUE values above 1.8 (exceeding 2.2 for aging facilities). Energy costs account for over 60% of full-lifecycle operating expenses. 24/7 dedicated on-site operation & maintenance staff with cross-system professional expertise are mandatory, creating prohibitive labor costs for grassroots classified units and remote branch sites lacking specialized teams. Unattended equipment suffers frequent failures and shortened service lifespans, creating severe security hazards.
  4. Large footprint and strict site requirements limiting full-scenario deployment Traditional classified computer rooms require dedicated independent premises with rigid constraints on building floor height, load-bearing capacity, raised flooring, fire protection and power supply support. They cannot be deployed in ordinary office spaces, branch offices, field training camps, vehicle-mounted emergency command platforms and other special sites. Most grassroots classified units and remote stations lack conditions for dedicated classified computer rooms, forcing non-compliant deployment of classified equipment with critical information leakage risks.

1.2.3 Technical Evolution & Market Demand Landscape

Widespread adoption of cloud computing, big data and artificial intelligence in classified environments has drastically increased IT equipment power density: single server power has risen from 300W to over 3kW, with high-density GPU classified computing nodes exceeding 5kW per unit. This imposes unprecedented demands on cabinet heat dissipation, power delivery and shielding performance. Traditional shielded cabinets rely on natural ventilation or basic fans with heat dissipation capacities below 3kW, incapable of cooling high-density classified IT hardware, leading to overheating, system outages and data loss that bottleneck classified informatization development.

According to the 2025 White Paper on the Development of Classified Information Infrastructure Industry released by the China Academy of Information and Communications Technology, the domestic integrated classified cabinet market reached RMB 6.87 billion in 2024 with a compound annual growth rate exceeding 28.6%. Party and government and military industrial customers account for over 70% of market share, with projections forecasting the market to surpass RMB 20 billion by 2028 amid explosive demand. However, mainstream industry products suffer from universal flaws: overemphasis on shielding at the expense of heat dissipation, hardware-focused design neglecting software control, and isolated single-component architecture lacking cross-system coordination. The KITOZER air-cooled integrated classified cabinet leverages full industrial chain R&D capabilities to resolve these industry pain points and fill gaps in the domestic high-end integrated classified cabinet market.

1.3 Core Design Philosophy

The KITOZER air-cooled integrated classified cabinet adheres to four core design principles throughout R&D and manufacturing: Confidentiality Compliance as the Core, Reliable Operation as the Foundation, Intelligent O&M as the Support, Flexible Adaptability as the Extension, ensuring every product detail meets national secrecy standards and addresses core requirements of all classified scenarios.

  1. Full-Link Confidentiality Compliance Design End-to-end confidentiality compliance controls are implemented across hardware, software and management dimensions:
  • Hardware: All core components hold certifications from the National Secrecy Science and Technology Evaluation Center; shielding enclosures, filter interfaces, red-black power isolation and grounding systems fully comply with mandatory BMB series standards.
  • Software: The environmental monitoring system runs on domestic operating systems, with immutable, undeletable operation logs and audit records that satisfy the three-staff separation management requirements for classified information systems.
  • Management: Full confidentiality management protocols govern product R&D, production, testing, delivery and O&M to guarantee end-to-end lifecycle confidentiality compliance.
  1. High-Reliability Redundant Design All core subsystems feature redundant architecture to ensure single-point failures cannot disrupt overall system operation:
  • Power distribution: Dual mains input, 1+1 redundant UPS backup and dual distribution circuits
  • Air cooling: 1+1 redundant air conditioning backup and emergency ventilation redundancy
  • Monitoring: Dual power supply and dual network redundancy
  • Shielded doors: Dual-lock redundancy System availability exceeds 99.995%, meeting Class A computer room standards under GB50174 to guarantee 24/7 uninterrupted stable operation of classified systems.
  1. Unattended Intelligent O&M Design An industrial-grade embedded environmental monitoring host delivers 24/7 full-spectrum real-time monitoring of shielding performance, temperature/humidity, power status, access permissions, fire conditions and water leakage risks. Built-in AI analytics enable proactive fault early warning, precise fault localization and automated remediation, with local audible/visual alarms and multi-channel remote alert notifications. The architecture eliminates mandatory dedicated on-site staff, resolving staffing and skill shortages at grassroots classified units to realize fully unattended intelligent operation & maintenance.
  2. Modular Flexible Adaptation Design All subsystems—shielded cabinet enclosure, air cooling, power distribution, monitoring, security and fire suppression—are built as independent modular units configurable on demand based on confidentiality grade, load power, deployment scenario and expansion requirements. The product supports standalone single-cabinet deployment, seamless multi-cabinet side-by-side stacking and micro-module cluster deployment with elastic capacity expansion without interrupting existing classified system operation, covering all use cases from desktop classified terminals to large-scale classified data centers.

1.4 Core System Value

  1. End-to-End Confidentiality Compliance for One-Time Pass of Classified Acceptance All core components pass testing by the National Secrecy Science and Technology Evaluation Center, with shielding performance meeting the highest Class C standard of BMB19-2006. Red-black power isolation, signal filtering, access audit and fire suppression linkage functions fully align with national secrecy standards. Full-system pre-integration and pre-testing are completed at the factory, eliminating on-site shielding structural modifications and guaranteeing 100% compliant shielding performance for seamless one-time classified system acceptance, eliminating confidentiality compliance risks at the source.
  2. Ultra-Fast Deployment to Significantly Shorten Construction Cycles Full system integration, commissioning and testing are completed in the factory; on-site deployment only requires mains power connection for immediate operation. Single-cabinet deployment cycles are reduced from the traditional 3–6 months to under 1 day, while medium-scale 10-cabinet classified computer rooms take no more than 7 days to commission. The solution rapidly addresses urgent classified business launch demands and minimizes confidentiality management risks during project implementation.
  3. Maximized Space & Energy Efficiency to Cut Full-Lifecycle Costs The smallest single cabinet footprint is only 0.72㎡, eliminating requirements for dedicated computer rooms, raised flooring and standalone air conditioning, drastically cutting site costs. Cabinet-level enclosed air cooling delivers targeted cooling to IT equipment heat sources without hot-cold air mixing, lowering PUE to as low as 1.25 and delivering over 40% energy savings vs. traditional computer rooms. Unattended intelligent O&M reduces labor costs by more than 90%, cutting overall full-lifecycle operating expenses by over 60% compared with conventional classified computer room builds.
  4. Full-Scenario Adaptability Covering All Classified Deployment Needs The full product line spans 22U–47U cabinet sizes with heat dissipation capacities from 3kW to 20kW, compatible with all IT hardware from desktop classified terminals to high-density GPU classified computing clusters. Customized reinforced vehicle-mounted, field moisture/corrosion-resistant and explosion-proof variants are available to support fixed office, field training, mobile vehicle-mounted, edge computing and emergency command deployments, resolving the inability of traditional classified computer rooms to serve special scenarios.
  5. Full Domestic Independent Controllability to Reinforce Classified Information Security Defenses All core hardware and basic software are fully domestically substituted: environmental monitoring hosts adopt Loongson and Phytium domestic processors running Kylin and Tongxin domestic operating systems, with independently developed proprietary algorithms and protocols free of foreign technical backdoors. All core components are manufactured via fully domestic supply chains to fully satisfy national Xinchuang classified information system construction requirements, fortifying classified information security defenses across hardware and software layers.

1.5 System Compliance Standard Framework

The entire lifecycle of KITOZER air-cooled integrated classified cabinet R&D, production, testing and delivery adheres to the following national, military and industrial standards to guarantee product compliance, safety and reliability:

  1. National Confidentiality Laws & Standards
  • Law of the People’s Republic of China on Guarding State Secrets and its implementing regulations
  • BMB19-2006 Technical Requirements and Test Methods for Electromagnetic Leakage Emission Shielded Cabinets
  • BMB3-1999 Technical Requirements and Test Methods for Electromagnetic Shielded Rooms Processing Classified Information
  • BMB54-2020 Technical Requirements for Confidential Cabinets
  • BMB20-2007 Technical Requirements for Graded Protection of State Secret-Related Information Systems
  • BM/Z 1-2023 Technical Requirements for Confidential Information Systems
  • Measures for the Administration of Qualifications for Classified Information System Integration
  1. National Data Center & Computer Room Construction Standards
  • GB50174-2017 Code for Design of Data Centers
  • GB/T 2887-2011 General Specification for Computer Sites
  • GB50057-2010 Code for Design of Building Lightning Protection
  • GB50169-2016 Code for Design of Earthing Devices for Electrical Installations
  • GB50370-2005 Code for Design of Gas Fire Extinguishing Systems
  • GB50462-2008 Code for Construction and Acceptance of Electronic Information System Computer Rooms
  1. Military & Military Industrial Standards
  • GJB5792-2006 Classification and Measurement Methods for Electromagnetic Shielding Enclosures of Military Classified Information Systems
  • GJB151B-2013 Requirements and Measurements of Electromagnetic Emission and Susceptibility for Military Equipment and Subsystems
  • GJB2438A-2002 Specification for General Valve-Regulated Sealed Lead-Acid Batteries
  • GJB9001C-2017 Quality Management System Requirements for Weaponry Equipment
  1. EMC & Electrical Safety National Standards
  • GB/T 12190-2021 Measurement Methods of Shielding Effectiveness for High-Performance Shielded Enclosures
  • GB9254-2008 Limits and Measurement Methods of Radio Disturbance for Information Technology Equipment
  • GB/T 17626-2018 series Electromagnetic Compatibility – Test and Measurement Techniques
  • GB7251.1-2013 Low-Voltage Assembled Switchgear and Controlgear Assemblies Part 1: General Rules
  • GB4943.1-2022 Information Technology Equipment Safety Part 1: General Requirements
  1. Xinchuang Localization Adaptation Standards
  • IT Innovation Industry Alliance Specification for Adaptation Verification of Information Technology Innovation Products
  • GB/T 25645-2010 Technical Requirements for Domestic Linux Operating Systems
  • Kylin & Tongxin OS adaptation certification standards
  • Loongson, Phytium, Zhaoxin, Hygon processor adaptation certification standards

2 System Composition

The KITOZER air-cooled integrated classified cabinet system adopts a layered modular, fully coordinated closed-loop architecture design. Six core interconnected subsystems form a complete end-to-end classified information security protection framework:

  1. Electromagnetic Shielded Cabinet Enclosure System
  2. Air Cooling Temperature Control System
  3. Classified Power Supply & Distribution System
  4. Intelligent Environmental Monitoring & Security Control System
  5. Shielded Cabling & Cable Management System
  6. Clean Gas Fire Suppression System

Each subsystem operates independently with dedicated functions while exchanging data, synchronizing status and executing coordinated intelligent control via industrial buses. The unified framework integrates physical protection, electromagnetic shielding, environmental regulation, power assurance, security governance, intelligent O&M and emergency response, enabling rapid cross-subsystem detection and remediation of any abnormal condition to guarantee absolute security of classified systems.

2.1 Electromagnetic Shielded Cabinet Enclosure System

The electromagnetic shielded cabinet enclosure serves as the core physical and electromagnetic protection carrier, forming the primary barrier against electromagnetic radiation leakage of classified information. All subsystems and IT hardware are integrated within the fully enclosed shielded cavity, strictly engineered to BMB19-2006, BMB3-1999 and GJB5792-2006 standards. Rigorous controls over plate material selection, welding techniques, structural design, shielding accessory sourcing and validation testing deliver stable full-band shielding performance alongside superior structural strength, load capacity and environmental adaptability for secure equipment operation.

2.1.1 Main Shielded Cabinet Structure

  1. Plate Material & Welding Process
  • General confidentiality grade cabinets use 1.5–2.0mm thick high-quality cold-rolled steel plates; Top Secret grade variants adopt 2.0–3.0mm double-layer cold-rolled steel.
  • Fully automatic argon arc full-welding forms a six-sided closed Faraday cage shielding cavity with 100% continuous welds free of gaps, incomplete welds or leakage points. Weld surface resistance ≤2.5mΩ/㎡ to guarantee electrical continuity of the shielding enclosure and eliminate electromagnetic leakage via structural defects.
  • Post-welding automatic shaping controls plate flatness ≤4mm per 2㎡, cabinet vertical deviation ≤10mm/m and dimensional tolerance ±2mm, ensuring precision fitting of shielded doors, honeycomb waveguides and shielding interfaces without shielding performance degradation from structural deformation.
  1. Reinforced Frame Structure
  • The cabinet frame is reinforced with 2.0mm cold-rolled steel nine-fold profiles roll-formed in a single pass, welded integrally to the cabinet body for high structural rigidity. Static load capacity ≥1500kg (≥1800kg for high-density models) to support heavy servers, storage arrays and GPU computing nodes. The structure meets Grade 8 seismic resistance standards for stable shielding performance under vibration in vehicle-mounted and field deployments.
  • Four adjustable standard 19-inch internal mounting columns are fabricated from 2.5mm cold-rolled steel with galvanized passivation treatment for excellent conductivity. Precise U-scale markings with hole tolerance ±0.5mm support front/back depth adjustment for compatibility with varying IT equipment dimensions; all columns are reliably bonded to the frame for equipotential grounding.
  1. Surface Treatment & Anti-Corrosion Process Multi-stage automated pretreatment (degreasing, pickling, phosphating, passivation) precedes outdoor-grade epoxy powder electrostatic spraying: phosphating film thickness ≥5μm with Class 1 adhesion per GB/T 9286-1998. Coating thickness ≥60μm delivers salt spray resistance exceeding 300 hours for long-term durability in humid, salt-laden and dusty environments, with customizable color finishes. All internal conductive and shielding contact surfaces remain uncoated with tin passivation treatment, contact resistance ≤0.1Ω to preserve full shielding cavity electrical continuity.
  2. Cabinet Form & Door Opening Configuration Standard cabinets feature front single shielded doors with rear single/dual shielded doors; left/right door swing directions are customizable for on-site operational convenience. Removable side panels sealed with full-perimeter beryllium copper shims bolt to the cabinet frame, enabling seamless multi-cabinet side-by-side stacking without compromising overall shielding effectiveness. A detachable bottom base plate reserves cable penetration ports with customizable inlet layouts; adjustable load-bearing feet (≥50mm travel) and swivel casters accommodate uneven flooring and simplify cabinet transport, positioning and fixation.

2.1.2 Shielded Door System

Shielded doors represent the highest electromagnetic leakage risk point in the shielding cavity. KITOZER’s proprietary labyrinth seal + multi-layer beryllium copper shim shielding patented structure maintains consistent shielding performance after over 300,000 opening/closing cycles while integrating anti-prying, anti-technical intrusion, permission monitoring and alarm functionality compliant with national secrecy standards.

  1. Door Body Structure Shielded door panels are welded from 2.0–3.0mm cold-rolled steel with internal reinforcing ribs to maintain flatness and impact resistance. A knife-edge mating design between door and 304 stainless steel tin-plated doorframe delivers flatness ≤0.2mm/m for full 360° reliable contact with shielding shims. Single doors up to 1000mm×2000mm and double doors up to 1800mm×2000mm are available with opening angles ≥110° for unobstructed maintenance access without jamming or deformation.
  2. Electromagnetic Sealing Architecture Perimeter multi-layer gold-plated beryllium copper elastic shims offer high conductivity, elasticity and fatigue resistance with a service life of ≥300,000 open/close cycles and shielding performance attenuation ≤5% after maximum cycling. Interchangeable plug-and-play shims enable rapid tool-free replacement for simplified maintenance. A labyrinth sealing structure extends electromagnetic leakage paths through repeated reflection and attenuation, delivering door seam shielding attenuation ≥90% of full cabinet shielding effectiveness to eliminate gap leakage.
  3. Locking & Permission Control Shielded doors are equipped with National Secrecy Test Center certified classified dedicated locks with tiered unlocking modes by confidentiality grade:
  • Confidential Grade: Password + mechanical key dual-mode lock, ≥6-digit password, automatic lockout and alarm after 3 incorrect entries, anti-technical intrusion time ≥15 minutes
  • Secret Grade: Fingerprint + password + mechanical key triple-mode lock, ≥1000 fingerprint/password storage, dual-person dual-lock support for mandatory dual-staff oversight compliance
  • Top Secret Grade: Iris + fingerprint + password + mechanical key four-mode lock, three-staff dual-lock + three-person review workflow, full authorization tracking and immutable audit logs for all unlock operations

304 stainless steel lock bodies resist prying, drilling and forced entry with anti-drill duration ≥30 minutes complying with BMB54-2020. Built-in door contact and tamper sensors continuously monitor door/lock status; forced prying or unauthorized opening triggers immediate audible/visual alarms, linked video capture and footage upload to the environmental monitoring system.

  1. Auxiliary Functions Built-in door closers and position limiters automatically close doors to prevent incomplete sealing-induced leakage, with full lock engagement upon proper closure. Optional shielded observation windows use metal wire mesh laminated glass with mesh frame bonding matching cabinet shielding effectiveness and ≥70% light transmittance for real-time internal equipment monitoring without compromising shielding performance.

2.1.3 Cutoff Waveguide Ventilation System

The honeycomb hexagonal cutoff waveguide ventilation window resolves the core conflict between cabinet heat dissipation airflow and electromagnetic leakage. KITOZER’s proprietary design balances maximum ventilation volume and high shielding performance, satisfying full air cooling thermal requirements while attenuating all electromagnetic signals below 10GHz.

  1. Waveguide Vent Window Principle & Structure Each hexagonal honeycomb cell acts as an independent cutoff waveguide tube: when cross-sectional dimensions are smaller than half the electromagnetic wavelength, signal transmission is blocked to simultaneously deliver airflow and shielding. KITOZER waveguides feature single cell size ≤3mm, length ≥30mm and cutoff frequency ≥10GHz with shielding effectiveness ≥90dB meeting Class C BMB19-2006 standards. 304 stainless steel one-piece molded ventilation windows with tin-plated surfaces weld directly to the cabinet for zero contact resistance and unbroken electrical continuity, ventilation rate ≥70% and wind resistance ≤5Pa to avoid cooling efficiency losses. Internal protective mesh prevents foreign matter ingress alongside removable air filter cartridges for equipment dust protection.
  2. Vent Window Layout & Configuration Distributed multi-group vent windows align fully with air cooling duct designs for standard 42U cabinets: 1 front door, 1 rear door, 2 top and 2 bottom waveguides delivering total ventilation area ≥0.8㎡ to support maximum 20kW cooling capacity. Front supply / rear return closed-loop airflow eliminates dead zones for uniform cooling distribution.
  3. Emergency Ventilation Waveguides Two dedicated top emergency waveguide windows pair with backup emergency fans. Upon primary air conditioning failure, emergency waveguides automatically open and auxiliary fans activate to maintain thermal dissipation. Emergency waveguides adopt identical cutoff waveguide construction to preserve full shielding effectiveness during emergency ventilation without electromagnetic leakage.

2.1.4 Shielded Interfaces & Filtering System

All power, signal, fiber and pipeline penetrations through the shielded cabinet must pass through dedicated shielding interfaces and filter assemblies, eliminating conductive electromagnetic leakage via cabling—the primary vulnerability of conventional shielded cabinets. KITOZER provides application-specific shielding interfaces and filters for all penetration types to block all conductive leakage pathways end-to-end.

  1. Power Filters All cabinet power feedlines connect to National Secrecy Test Center certified dedicated power filters with three-stage common-mode/differential filtering networks permitting 50Hz mains power while attenuating 10kHz–10GHz leakage signals with insertion loss ≥60dB complying with BMB19-2006. Single/three-phase variants cover rated currents 10A–200A with fully shielded sealed housings bonded to the cabinet (ground resistance ≤0.1Ω). Complete input/output isolation prevents cross-coupling filter failure. Three-tier full-link power filtering architecture eliminates conductive signal leakage: primary mains inlet filters, secondary UPS output distribution filters and tertiary red-black terminal isolation filters at IT equipment loads.
  2. Signal Filters All low-voltage signal cabling (network, serial, video, audio, control) connects to customized signal filters engineered for signal frequency and impedance characteristics, preserving native signal transmission while delivering ≥60dB attenuation of high-frequency leakage signals without bandwidth or quality degradation. Modular panel-mounted filter housings offer RJ45, RS232/485, BNC, USB expandable ports with full metal shielding seamlessly bonded to cabinet shielding panels for unbroken electrical continuity and zero interface leakage.
  3. Fiber Waveguide Penetrations While optical fiber carries no conductive signals, metal strength members and sheaths create leakage pathways. All fiber penetrations pass through dedicated stainless steel copper-lined fiber waveguides with cutoff frequency ≥10GHz and shielding effectiveness ≥90dB to block electromagnetic transmission via metal fiber components while maintaining unobstructed light signal flow. Single/4/8/12/24-core customizable waveguides feature sealed end connectors for full penetration sealing and weld integration with the cabinet frame for stable shielding performance.
  4. Additional Shielded Interfaces Custom welded waveguide interfaces accommodate air conditioning piping and fire suppression line penetrations to preserve cabinet shielding integrity. Standardized modular shielding interfaces support on-demand expansion for all deployment scenarios.

2.1.5 Equipotential Earthing System

The equipotential earthing system eliminates potential differences between internal cabinet components, prevents static accumulation, boosts shielding effectiveness and guarantees electrical safety. KITOZER’s full-perimeter closed-loop equipotential bonding design unifies all internal metal hardware at identical potential to eliminate radiation and electrostatic discharge risks from voltage disparities.

  1. Ground Copper Busbar Design A closed-loop T2 pure tin-plated copper ground busbar with cross-section ≥50mm² runs the full internal cabinet perimeter via multi-point welding to the cabinet body for equipotential alignment with zero voltage differential. Sufficient pre-drilled grounding terminals with dedicated bolts and washers enable reliable bonding of all internal equipment, shielding assemblies, filters and metal frames with contact resistance ≤0.1Ω per connection point.
  2. Full-System Equipotential Bonding All internal metal components—mounting columns, shielded doors, waveguides, filters, air conditioners, UPS, distribution cabinets and cable management racks—bond to the ground busbar via ≥6mm² multi-strand insulated copper flexible wire to eliminate cross-component potential differences and static discharge risks. All filter and shielding interface ground terminals connect directly to the ground busbar via minimal-length cabling to limit earthing impedance and preserve full filtering/shielding performance.
  3. External Ground Terminals & Specifications Two dedicated external M10 stainless steel ground terminals hardlink to the internal copper busbar for connection to facility grounding grids or dedicated earth electrodes, system ground resistance ≤4Ω. When disconnected from facility ground, cabinet-to-ground insulation resistance ≥1000Ω complying with national secrecy standards. Single-point and multi-point grounding modes are configurable for compatibility with all facility earthing architectures to avoid ground circulation currents.
  4. Anti-Static Design Full equipotential bonding of all accessible internal hardware eliminates static charge buildup. Optional internal anti-static flooring and wrist strap grounding terminals enable controlled static discharge during maintenance to prevent electrostatic damage to classified IT hardware. Anti-static coating on cabinet exterior surfaces delivers surface resistance ≤10⁹Ω for inherent static dissipation.

2.1.6 Real-Time Shielding Effectiveness Monitoring System

Top Secret grade cabinets include KITOZER patented real-time shielding effectiveness monitoring hardware, resolving the limitation of traditional shielded cabinets that only support periodic offline testing. The system delivers 24/7 continuous shielding performance tracking, proactive leakage attenuation warning and precise leak point localization to sustain permanent confidentiality compliance.

  1. System Composition Internal full-band signal transmitters (14kHz–10GHz test signal output), external leakage signal receivers, data processing units and multi-tier alarm modules form the complete monitoring stack. Internal transmitted signals are cross-referenced against external captured leakage signals to calculate real-time cabinet shielding effectiveness with measurement accuracy ±2dB aligned to national secrecy standard test frequency bands.
  2. Core Functionalities
  • Full-Band Real-Time Monitoring: Continuous tracking across the complete 14kHz–10GHz standard test spectrum with ±2dB precision
  • Abnormality Early Warning & Emergency Alarms: Tiered pre-alert and critical alarm triggers upon shielding performance dropping below threshold standards, with local audible/visual, SMS and WeChat remote notifications to O&M staff
  • Leakage Point Localization: Multi-point external receivers pinpoint exact electromagnetic leakage locations for rapid targeted remediation
  • Immutable Data Storage & Audit: ≥5 years of encrypted, non-deletable shielding performance historical data with full export and query capabilities to satisfy classified system audit traceability mandates
  • Interlock Control: Automatic disconnection of internal classified equipment network and power feeds upon detection of severe electromagnetic leakage to block classified information exfiltration

2.2 Air Cooling Temperature Control System

The air cooling temperature control system maintains stable classified IT hardware operation, engineered specifically for fully enclosed shielded cabinet architectures. KITOZER’s patented cabinet-level isolated hot/cold aisle, targeted precision cooling and AI intelligent temperature regulation architecture resolves core industry pain points of insufficient heat dissipation, hot-cold air mixing, localized hotspots, excessive energy consumption and high noise. The product supports 3kW–20kW full power range thermal loads, sustaining optimal operating temperatures for classified hardware at all times.

2.2.1 Core System Design Principles

  1. Isolated Closed Hot/Cold Aisle Architecture Conventional shielded cabinets suffer unregulated internal air mixing with drastically reduced cooling efficiency. KITOZER’s dedicated independent cold air plenum and hot air return duct fully separate supply and exhaust airflow without cross-contamination. Cool air is delivered directly to IT equipment air intakes, while all hot exhaust air returns exclusively to air conditioning evaporators, doubling cooling efficiency and cutting energy consumption.
  2. Targeted Precision Cooling Adjustable duct baffles dynamically redirect airflow to match heat generation profiles of installed IT hardware, delivering uniform cooling coverage to all heat sources and eliminating localized hotspots. Temperature differential across all rack-mounted equipment is limited to ≤2°C even under full high-density server loading to prevent thermal outages and data loss.
  3. AI Intelligent Energy-Saving Temperature Regulation Built-in AI algorithms dynamically adjust compressor speed, fan RPM and electronic expansion valve opening based on multi-point cabinet temperature/humidity readings, IT equipment load and ambient external temperatures to match cooling output precisely to heat generation. Continuous full-load compressor operation is eliminated, lowering PUE to as low as 1.25 with over 40% energy savings vs. conventional computer room cooling systems.
  4. Full Redundancy High-Reliability Architecture All core cooling components feature redundant design: 1+1 backup air conditioning units with seamless <10s failover, N+1 redundant fan arrays and independent emergency ventilation systems to guarantee thermal dissipation under all failure scenarios, delivering system availability ≥99.995%.

2.2.2 Rack-Mounted Precision Air Conditioning Units

Rack-mounted precision air conditioning units form the core cooling hardware, designed for standard 19-inch internal cabinet rack mounting without external footprint occupation. Cooling capacities range from 3kW to 20kW configurable by IT load power demand.

  1. Core Refrigeration Circuit Components Vapor compression refrigeration cycles use scroll compressors, evaporators, condensers, electronic expansion valves, liquid receivers and dry filters with premium domestic or international brand components configurable per localization requirements for high reliability and extended service life.
  • Scroll Compressors: Hermetically sealed scroll compressors deliver high energy efficiency, low noise and stable operation with volumetric efficiency ≥95% (20% energy savings vs. piston compressors). Integrated overload, overheat, over/under pressure protection delivers ≥100,000-hour service life.
  • Evaporator & Condenser: High-efficiency internal threaded copper tube hydrophilic aluminum fin heat exchangers maximize heat transfer area with V-shaped evaporator geometry boosting heat exchange efficiency by 30%. Internal cabinet air-cooled condensers or external remote condenser variants support all deployment environments.
  • Electronic Expansion Valves: High-precision variable flow throttling delivers 15% energy savings vs. capillary tube control with wide dynamic load adjustment range for fluctuating IT heat output.
  • Eco Refrigerants: ODP-zero R134a and R410A environmentally compliant refrigerants eliminate ozone layer depletion risks while maintaining superior thermodynamic cooling performance.
  1. Key Technical Parameters Model SeriesRated Cooling CapacityMounting FormRated VoltageEERTemp Control RangeTemp PrecisionHumidity RangeOperating NoiseKITOZER-FL-3KW3kW19” rack, 3UAC220V 50Hz≥3.018–30℃±1℃40–80%RH≤50dBKITOZER-FL-5KW5kW19” rack, 4UAC220V 50Hz≥3.218–30℃±1℃40–70%RH≤52dBKITOZER-FL-8KW8kW19” rack, 5UAC220V 50Hz≥3.218–30℃±0.5℃40–60%RH≤53dBKITOZER-FL-12KW12kW19” rack, 6UAC380V 50Hz≥3.118–30℃±0.5℃40–60%RH≤55dBKITOZER-FL-20KW20kW19” rack, 8UAC380V 50Hz≥3.018–30℃±0.5℃40–60%RH≤58dB
  2. Core Functional Features
  • Precision Temperature & Humidity Regulation: Stable cabinet operating environment locked to 18–25℃, 40–60%RH optimal IT hardware range with temperature accuracy ±0.5–1℃ and humidity control precision ±5%RH.
  • Intelligent Dehumidification & PTC Heating: Built-in condensing dehumidification removes excess moisture to eliminate equipment condensation; integrated PTC auxiliary heating automatically raises internal temperatures in low-ambient deployments to prevent cold-start hardware failures, supporting all seasonal climate conditions nationwide.
  • Full-Spectrum Protection Logic: Comprehensive overvoltage, undervoltage, overload, short-circuit, compressor high/low pressure, fan overload, evaporator frost and condenser overheat protection with automatic alarm upload to environmental monitoring systems upon fault detection.
  • Communication & Interlock Control: Standard RS485 Modbus-RTU and SNMP interfaces enable seamless integration with the environmental monitoring host for remote status tracking, parameter configuration and on/off control, with automated cooling capacity adjustment linked to internal temperature/humidity sensor readings.
  • Power Failure Auto Restart & State Memory: Automatic resumption of pre-fault operating parameters upon mains power restoration, eliminating manual intervention for unattended deployments.
  • Energy-Saving Operation Modes: Customizable economy, night and holiday operating profiles reduce idle energy draw; free cooling mode automatically disables compressors when external ambient temperatures drop below threshold, relying solely on fan ventilation for passive heat dissipation to cut power consumption drastically.
  1. Redundant Backup Architecture Secret and Top Secret grade cabinets ship standard with 1+1 redundant air conditioning units operating in primary/backup rotation. Failover switch time ≤10s eliminates cooling interruption upon primary unit failure; alternating primary/backup duty cycles extend overall air conditioning service lifespan.

2.2.3 Intelligent Air Circulation System

The intelligent air circulation system forms a closed-loop airflow circuit paired with air conditioning units to optimize internal air distribution, eliminate thermal dead zones and deliver uniform cooling across all racked hardware.

  1. Closed Duct Architecture Front cold air plenum supply and rear hot air return ducting forms a fully isolated closed cooling circuit. The full-width front plenum distributes equal airflow to every IT equipment intake U-slot, while rear return channels channel all hot exhaust air directly back to air conditioning evaporators without mixing cold/hot streams. Ductwork is fabricated from 1.0mm cold-rolled steel with internal thermal insulation to prevent cold energy loss and condensation, featuring smooth inner surfaces for minimal air resistance and maximum ventilation efficiency.
  2. Intelligent EC Centrifugal Fan Arrays Stepless variable-speed DC brushless EC centrifugal fans installed in front supply and rear return duct zones deliver high energy efficiency, low noise and ≥50,000-hour service life with 0–100% real-time RPM adjustment linked to internal cabinet temperature readings for dynamic energy conservation and noise reduction. Standard 42U cabinets deploy 8–16 EC fans with total airflow capacity 3200–8000CFM matched to cooling power rating. Tool-free snap-in fan mounting simplifies replacement; integrated overload/overheat protection triggers automated alarms upon single fan failure, with automatic RPM boost of remaining units to compensate airflow volume without cooling performance loss. Fan operational status, RPM and current draw are continuously relayed to the environmental monitoring system for full visibility.
  3. Optimized Airflow Organization Adjustable duct baffles enable manual or automated airflow redirection to target cooling precisely to rack-mounted heat sources, eliminating vertical temperature stratification and localized hotspots between top and bottom cabinet U-slots. Standard U-slot blanking panels block airflow bypass through empty rack positions, ensuring 100% of cool air passes through active IT equipment to maximize cooling efficiency.
  4. Emergency Ventilation Redundant Unit Independent emergency ventilation hardware (emergency waveguides, backup fans, dedicated control modules) activates automatically upon primary air conditioning unit failure and rapid internal temperature rise. A dedicated isolated emergency airflow path draws cool external air through bottom inlet waveguides across IT hardware heat loads, exhausting hot air via top outlet waveguides to sustain safe internal operating temperatures for ≥30 minutes, providing sufficient response window for O&M staff remediation and preventing thermal hardware outages. Emergency ventilation draws power from an independent backup circuit to guarantee operation even during main power distribution failures.

2.2.4 Air Filtration & Purification System

Multi-stage air filtration eliminates dust, particulate contaminants and corrosive gases to prevent electrostatic discharge, short-circuiting and heat dissipation degradation inside IT hardware, extending equipment service life and maintaining internal air cleanliness aligned with precision computing hardware operating requirements.

  1. G4 Primary Air Filters G4-class folded polyester fiber primary filters installed at all air conditioning, fan and emergency ventilation intakes deliver ≥90% filtration efficiency for particles ≥5μm, blocking dust, lint and large airborne contaminants from entering the cabinet. Tool-free snap-in mounting enables rapid disassembly, cleaning and replacement; integrated differential pressure sensors trigger automated maintenance alerts upon filter clogging from elevated pressure drop.
  2. Optional Medium/High-Efficiency Filter Stages F8 medium-efficiency or H13 HEPA filter upgrades are available for high-dust and high-contamination environments, delivering ≥99.97% filtration efficiency for 0.5μm fine particulates (PM2.5, dust, pollen) to achieve ISO 14644-1 Class 8 internal air cleanliness for precision classified instruments and high-end server deployments.
  3. Optional Activated Carbon Purification Modules Honeycomb high-adsorption activated carbon cartridges absorb sulfur dioxide, hydrogen sulfide, ammonia and other corrosive gaseous contaminants alongside excess moisture and odors in humid industrial environments, preventing circuit board and component corrosion while providing supplementary humidity regulation.
  4. Anti-Static & Bacteriostatic Design Filter frames use anti-static ABS material (surface resistance ≤10⁹Ω) to eliminate static charge buildup and discharge risk; filter media is infused with bacteriostatic agents to suppress bacterial/mold growth in humid cabinet environments and prevent microbial hardware degradation.

2.2.5 Auxiliary Temperature Control Hardware

  1. PTC Auxiliary Heating Units Standard PTC positive temperature coefficient self-limiting heating modules (500W–3000W power range configurable by cabinet size) automatically activate when internal cabinet temperatures drop below 18℃ to raise ambient operating temperatures and eliminate cold-start condensation risks for northern unheated site deployments. Multiple overheat protection circuits cut power automatically above 85℃ to eliminate fire hazards, with full linkage to the environmental monitoring system for status tracking and fault alerting.
  2. Condensate Collection & Drainage Assembly A thermally insulated condensate drain pan collects all dehumidification wastewater with integrated liquid level sensors for real-time water volume tracking. Dedicated drainage piping routes condensate outside the cabinet; optional condensate lift pumps automatically evacuate water for installations below facility drain elevations to eliminate overflow short-circuit risks. All drainage piping penetrates the cabinet via dedicated shielded waveguide interfaces to preserve full shielding effectiveness at penetration points.

2.3 Classified Power Supply & Distribution System

The power distribution system acts as the cabinet’s power core, delivering uninterrupted, reliable, leakage-isolated power to IT hardware, cooling, monitoring, security and fire suppression subsystems. Fully engineered to national secrecy standards, GB50054 Code for Design of Low-Voltage Electrical Installations and GB50174, the architecture implements end-to-end redundant backup, filtering isolation, intelligent metering and safety protection to guarantee 24/7 classified hardware operation while completely blocking conductive leakage of classified signals via power cabling.

2.3.1 Core System Design Principles

  1. Full Redundancy High-Reliability Architecture All critical power links feature redundant design: dual independent mains input, ATS automatic transfer switching, 1+1 redundant UPS, dual distribution circuits and redundant surge protection to eliminate power disruption from single-point faults, achieving ≥99.999% system availability meeting Class A top-tier data center power delivery requirements under GB50174.
  2. End-to-End Confidential Isolation Architecture Three-tier power filtering, red-black power isolation, shielded cable routing and physical separation of high/low voltage circuits fully comply with national secrecy standards, eliminating all conductive pathways for classified signal leakage via power lines.
  3. Full-Dimensional Intelligent Metering Control Granular real-time electrical parameter tracking spans mains inlet, UPS operation, battery health, distribution branch and PDU terminal loads to deliver precise individual equipment power consumption visibility, proactive fault early warning and targeted maintenance optimization.
  4. Comprehensive Safety Protection Architecture Integrated overload, short-circuit, earth leakage, overvoltage, undervoltage, overcurrent, overheat and lightning surge protection circuits isolate faults to individual distribution branches without disrupting parallel load circuits, safeguarding both classified IT hardware and on-site O&M personnel from electrical hazards.

2.3.2 Dual Mains Input & Transfer Assembly

The power distribution system inlet supports dual independent mains feeders to enable seamless automatic failover between separate power sources and eliminate single-source power outage risks.

  1. Dual Mains Input Design Two independent primary and backup mains feeds sourced from separate transformers/substations eliminate simultaneous dual-feed failure risks, supporting single-phase AC220V or three-phase AC380V input configurable by site power infrastructure and total load capacity with rated input currents ranging 63A–400A. A dedicated inlet distribution cabinet houses main disconnect circuit breakers, isolation switches and current/voltage transducers for real-time tracking of dual-feed voltage, current, frequency and power metrics, alongside dedicated maintenance isolation switches for safe offline servicing.
  2. ATS Automatic Dual Power Transfer Switch Dual mechanical + electrical interlock ATS transfer switches eliminate cross-grid short-circuit hazards between mains feeds, supporting automatic and manual switching modes with seamless transfer time ≤4ms to maintain uninterrupted load power during single-feed outages. Overvoltage, undervoltage, overload and short-circuit protection automatically switch to the healthy mains feed upon grid anomalies outside ±15% rated voltage tolerance. Auxiliary contact and RS485 communication ports relay ATS operational state and dual mains health data to the environmental monitoring system with automated fault alert triggers for abnormal grid conditions.
  3. Inlet Lightning Surge Protection Class I surge protection devices (SPDs) with combined gap/varistor architecture are installed at the mains inlet front-end, delivering maximum discharge current Imax ≥100kA (8/20μs), nominal discharge In ≥50kA and response time ≤25ns with full L-N, L-PE, N-PE protection mode to suppress direct lightning strikes and high-magnitude grid surges complying with GB50057 lightning protection standards. Visual degradation indicator windows and remote fault alarm contacts trigger automated notifications to the monitoring system upon SPD failure requiring replacement.

2.3.3 Rack-Mounted Online UPS Uninterruptible Power Supply System

The UPS forms the core energy backup hardware, delivering seamless power transition to battery reserves during mains outages to eliminate classified system downtime, data loss and service collapse while filtering grid harmonics, surges, voltage fluctuations and frequency drift to supply pure, stable sine-wave power to IT loads.

  1. UPS Host Core Architecture & Variants Dual-conversion online UPS architecture is the only compliant topology for classified information systems, delivering zero millisecond transfer time and stable output voltage/frequency with low harmonic distortion vs. standby and line-interactive alternatives. All units adopt standard 19-inch rack-mount design for internal cabinet integration without external footprint occupation, with heights spanning 2U–12U and capacities from 1kVA to 20kVA single/three-phase configurable by total load power. Overall efficiency ≥96%, input power factor ≥0.99 and output harmonic distortion ≤3% minimize grid pollution and maximize energy efficiency.
  2. Core Operating Principle – Three Modes
  • Normal Mains Mode: AC mains power rectified to DC to simultaneously charge battery reserves and feed inverters generating clean stabilized sine-wave AC power to loads, filtering all grid interference.
  • Battery Backup Mode: Upon mains power loss or grid anomaly, battery DC power feeds inverters to deliver uninterrupted AC load power with 0ms transfer time, eliminating visible power disruption to classified hardware.
  • Maintenance Bypass Mode: Automatic transfer to direct mains load power upon UPS host overload, short-circuit or internal fault to sustain load operation during UPS servicing with simultaneous fault alarm notification.
  1. Key Technical Parameters Model SeriesRated CapacityMounting FormInput Voltage RangeOutput VoltageOutput FrequencyOverall EfficiencyTransfer TimeOverload ToleranceKITOZER-PD-UPS1K1kVA/0.9kW19” rack, 2UAC120–275VAC220V ±1%50Hz ±0.1%≥95%0ms110% load sustained 60min; 125% load 10minKITOZER-PD-UPS3K3kVA/2.7kW19” rack, 3UAC120–275VAC220V ±1%50Hz ±0.1%≥95%0ms110% load sustained 60min; 125% load 10minKITOZER-PD-UPS6K6kVA/5.4kW19” rack, 3UAC120–275VAC220V ±1%50Hz ±0.1%≥96%0ms110% load sustained 60min; 125% load 10minKITOZER-PD-UPS10K10kVA/9kW19” rack, 4UAC120–275VAC220V ±1%50Hz ±0.1%≥96%0ms110% load sustained 60min; 125% load 10minKITOZER-PD-UPS20K20kVA/18kW19” rack, 6UAC380V ±20%AC220V/380V ±1%50Hz ±0.1%≥96.5%0ms110% load sustained 60min; 125% load 10min
  2. Core Functional Capabilities
  • Intelligent BMS Battery Management: Automated float/equal charge switching with temperature-compensated charging voltage/current regulation to prevent overcharge/over-discharge and extend battery service life. Real-time per-cell voltage, internal resistance, charge/discharge current and temperature tracking delivers proactive battery degradation fault early warning.
  • Full-Spectrum Protection Logic: Integrated input over/undervoltage, output over/undervoltage, overload, short-circuit, overcurrent, overheat, battery overcharge and over-discharge protection circuits safeguard UPS hardware and connected loads with automated fault alarm upload to environmental monitoring systems.
  • Redundant Parallel Operation Support: 1+1 and N+1 redundant parallel architecture supporting up to 8 synchronized UPS units with balanced load sharing; failed units automatically offload to remaining parallel hardware to eliminate power disruption, meeting ultra-high reliability Top Secret grade requirements.
  • Multi-Protocol Communication & Interlock Control: Standard RS485, dry contact and SNMP interfaces with Modbus-RTU protocol integration enable seamless environmental monitoring host linkage for remote real-time status tracking, parameter configuration and on/off control of UPS operational modes, fault logs and battery health metrics with automated anomaly alerting.
  • Auto-Restart & State Memory Post Power Failure: Automatic restoration of pre-outage UPS operating parameters upon mains power recovery eliminating manual intervention for unattended deployments; scheduled automated battery capacity self-testing proactively identifies degraded battery packs before operational failure.
  • Energy-Saving ECO Mode: Economy bypass mode activates under stable healthy mains power to deliver ≥99% energy efficiency, switching instantly back to full dual-conversion online mode upon grid anomalies to balance energy conservation and power quality protection.
  1. Domestic Localization Option Fully domestic UPS variants are available featuring native domestic IGBT power semiconductors, DSP control chips and embedded operating systems with zero foreign technical backdoor risks, fully certified for Kylin/Tongxin OS and Loongson/Phytium processor Xinchuang classified system deployments.

2.3.4 Battery Pack Assembly

Battery packs serve as UPS energy reserves to deliver backup power during mains outages; capacity, performance and reliability directly determine available UPS runtime. KITOZER supplies two core battery product lines configurable by required backup duration, deployment environment and localization demands: valve-regulated sealed lead-acid and lithium iron phosphate batteries.

  1. Valve-Regulated Sealed Lead-Acid Maintenance-Free Batteries Mainstream cost-effective mature technology suitable for nearly all standard classified deployment scenarios with fully sealed AGM construction eliminating electrolyte leakage and zero routine fluid top-up maintenance.
  • Core Specifications: 12V/2V rated cells with capacities 7Ah–200Ah configurable via series/parallel stacking to match UPS DC bus voltage and target backup runtime. Float design lifespan ≥10 years at 25℃ ambient temperature, ≥500 full discharge cycle life.
  • Key Characteristics: High-purity lead-calcium grid alloy delivers superior corrosion resistance and low self-discharge (≤3% monthly); ultra-fine glass fiber separators maximize electrolyte retention without stratification; explosion-proof safety relief valves automatically regulate internal pressure while isolating external sparks and flammable gas ingress for enhanced operational safety. Operating temperature range -15℃~45℃ supports nationwide deployment across all climate zones.
  • Mounting Form: Standard 19-inch rack-mount sealed battery cabinets with internal fixed brackets, insulating partitions and overcurrent DC fuses, bonded to cabinet equipotential ground busbars for direct internal cabinet installation without external space consumption. Cabinet heights span 2U–12U matching battery pack capacity requirements.
  1. Lithium Iron Phosphate Battery Packs High-performance long-life alternative offering superior energy density, extended cycle life, high charge/discharge efficiency, lightweight form factor and enhanced intrinsic safety for high-reliability, long-lifespan and space-constrained deployments.
  • Core Specifications: 3.2V monomer cells with capacities 50Ah–200Ah configurable via series/parallel stacking to match UPS DC bus voltage requirements. ≥6000 full discharge cycle life and ≥15-year float lifespan at 25℃ ambient temperature.
  • Key Characteristics: Integrated dedicated BMS cell management system delivers real-time per-cell voltage, temperature and current tracking with full overcharge, over-discharge, overcurrent, short-circuit, overheat and cold-temperature protection plus automatic cell balancing to guarantee uniform charge/discharge across the battery pack and extend service life. Energy density delivers 1/3 the weight and 2/3 the volume of equivalent lead-acid packs to minimize cabinet footprint; lithium iron phosphate cathode chemistry delivers exceptional thermal stability with zero fire/explosion risk under fault conditions, ≥95% charge/discharge efficiency for superior energy savings and fully non-toxic heavy-metal-free construction for eco-friendly disposal.
  • Mounting Form: Modular 19-inch rack-mount battery packs with native BMS integration for seamless UPS and environmental monitoring system communication delivering complete battery health visibility and control.
  1. Backup Runtime Capacity Configurations Battery pack capacity is sized flexibly by total load power and target backup duration; standard factory configuration delivers 30-minute runtime with optional 15min, 1h, 2h, 4h and 8h extended runtime variants as shown in the table below: | UPS Rated Capacity | Total Load Power | 15-Min Backup | 30-Min Backup | 1-Hour Backup | 2-Hour Backup | 4-Hour Backup | |——————–|——————|—————|—————|—————|—————|—————| | 1kVA | 0.9kW | 4×12V 17Ah | 4×12V 24Ah | 4×12V 38Ah | 4×12V 65Ah | 4×12V 120Ah | | 3kVA | 2.7kW | 8×12V 38Ah | 8×12V 65Ah | 8×12V 100Ah | 8×12V 150Ah | 16×12V 200Ah | | 6kVA | 5.4kW | 16×12V 65Ah | 16×12V 100Ah | 16×12V 150Ah | 32×12V 200Ah | 64×12V 200Ah | | 10kVA | 9kW | 16×12V 100Ah | 16×12V 150Ah | 32×12V 200Ah | 64×12V 200Ah | 128×12V 200Ah |
  2. Battery Cabinet & Supporting Accessories All battery packs install within dedicated 1.5mm cold-rolled steel rack-mount battery enclosures with electrostatic spray coating and internal insulating partitions to prevent short-circuit hazards. Internal dedicated battery copper busbars, insulated wiring sleeves and DC fuses per battery string deliver reliable low-resistance interconnection and short-circuit overload protection. Battery cabinets hardlink to the cabinet ground copper busbar for full equipotential bonding and integrate dedicated battery power filters to eliminate electromagnetic leakage from battery cabling complying with classified shielding requirements.

2.3.5 Rack-Mounted Precision Distribution Cabinets

Rack-mounted precision distribution cabinets form the core power allocation hardware, distributing conditioned UPS output power to IT loads, auxiliary cooling/monitoring hardware and spare expansion circuits with full granular electrical metering and fault protection for secure, reliable, granular power management.

  1. Cabinet Structure & Mounting Form Standard 3U–6U height 19-inch rack-mount distribution cabinets fabricated from 1.5mm cold-rolled steel with IP30 protection rating and transparent tempered glass front observation doors with integrated internal LED lighting for easy maintenance visibility. Fully modular plug-and-play internal components support flexible output branch expansion with simplified servicing workflows.
  2. Core Architecture & Circuit Configuration Single or dual redundant input architectures are configurable for high-reliability deployments with main input circuit breakers (63A–250A rated) delivering integrated overload, short-circuit and earth leakage protection. Output branches are categorized into three customizable load groups:
  • IT Load Branches: Dedicated power feeds for classified servers, switches, routers, firewalls and storage hardware with 8–32 independent 10A/16A/32A miniature circuit breakers each with dedicated earth leakage protection, breaking capacity ≥6kA
  • Auxiliary Equipment Branches: Power for air conditioning, fans, monitoring systems and cabinet lighting with 4–16 independent 10A/16A circuit breakers
  • Spare Expansion Branches: Reserved feeds for temporary and future expansion hardware with 2–8 independent 16A/32A circuit breakers Vertical separated high/low voltage routing physically isolates input and output cabling to eliminate cross-circuit electromagnetic interference; internal T2 tin-plated pure copper busbars deliver high current carrying capacity with minimal temperature rise and superior conductive performance.
  1. Intelligent Metering Functionalities High-precision Class 0.5 intelligent power meters deliver real-time tracking of input voltage, current, active/reactive power, power factor, frequency and total energy consumption across the main input feed. Individual current transducers per output branch enable granular per-circuit current, power and energy metering for equipment-level refined power consumption management with automatic threshold-crossing alarm triggers relayed to the environmental monitoring system upon parameter anomalies. A built-in 7-inch color touchscreen locally displays all metering data, circuit breaker status and fault alerts with on-site parameter configuration and branch status query capabilities; standard RS485 Modbus-RTU communication enables full remote integration with the environmental monitoring host for off-site tracking and control.
  2. Safety Protection & Auxiliary Capabilities
  • Comprehensive Protection Logic: Class II secondary surge protection SPDs installed at the distribution cabinet input with maximum discharge current ≥40kA; independent overload, short-circuit and earth leakage breakers isolate faulted branches without disrupting parallel healthy circuits. Lockable cabinet doors block unauthorized personnel access to live distribution hardware.
  • Electrical Isolation Design: Complete input/output circuit separation, physical high/low voltage segregation and isolated load branch routing eliminate cross-circuit interference. All power cabling uses shielded wiring routed within galvanized steel conduits with minimum 300mm separation distance from low-voltage signal cabling to prevent power-line electromagnetic interference with classified IT hardware.
  • Visual Status Indicators: Dedicated mains power, circuit breaker close and fault alarm LED indicators provide instant visual operational status visibility; auxiliary contact sensors on every circuit breaker continuously track open/closed state and trigger automated fault alerts upon tripping with notifications sent to the environmental monitoring system.

2.3.6 Red-Black Power Isolation & Filtering System

Red-black power isolation filtering hardware represents the mandatory core confidentiality protection component of classified power distribution systems, required by national secrecy standards to suppress conductive leakage of classified electromagnetic signals via power lines. All classified IT equipment power feeds must connect to National Secrecy Test Center certified red-black isolation sockets to eliminate signal exfiltration via mains cabling pathways.

  1. Core Operating Principle Classified IT hardware generates high-frequency electromagnetic signals carrying sensitive classified data that couple into power lines and propagate externally for interception and data reconstruction. Red-black isolation sockets integrate high-isolation transformers and multi-stage filtering networks delivering ≥60dB attenuation of 10kHz–1GHz leakage signals while permitting unimpeded 50Hz mains power transmission to connected hardware, fully blocking conductive classified signal leakage pathways.
  2. Core Product Technical Specifications Model SeriesRated VoltageRated CurrentSocket Configuration & QuantityIsolation AttenuationProtection FeaturesMounting FormCertification QualificationKITOZER-PD-HH08AC220V 50Hz10A8×10A national standard 5-hole outlets≥60dB (10kHz–1GHz)Overload, short-circuit, surge protection19” rack, 1UNational Secrecy Science & Technology Evaluation Center CertifiedKITOZER-PD-HH16AC220V 50Hz16A8×10A + 2×16A national standard 5-hole outlets≥60dB (10kHz–1GHz)Overload, short-circuit, surge protection19” rack, 1UNational Secrecy Science & Technology Evaluation Center CertifiedKITOZER-PD-HH24AC220V 50Hz32A16×10A + 4×16A national standard 5-hole outlets≥60dB (10kHz–1GHz)Overload, short-circuit, surge protection19” rack, 2UNational Secrecy Science & Technology Evaluation Center Certified
  3. Key Product Characteristics
  • High Isolation Attenuation Performance: Three-stage filtering architecture delivers ≥60dB full-band attenuation of conductive leakage signals complying with mandatory national secrecy standards to block classified data transmission via power cabling.
  • Superior Safety Reliability: High-isolation separation transformers deliver ≥2500V input/output electrical isolation to eliminate cross-circuit grid interference ingress into the cabinet and protect classified hardware from grid anomalies.
  • Full-Spectrum Integrated Protection: Built-in overload, short-circuit, lightning surge, overvoltage and undervoltage protection automatically cuts power upon fault conditions to prevent permanent classified IT hardware damage.
  • Shielded Enclosure Architecture: Fully sealed aluminum alloy shielding housing with ≥60dB shielding effectiveness hardbonded to the cabinet equipotential ground busbar for zero contact resistance and complete electrostatic dissipation.
  • Simplified Installation: Standard 19-inch rack-mount design for direct internal cabinet installation with plug-and-play wiring and optional daisy-chain expansion ports supporting multi-unit stacking for high-density classified equipment deployments.
  1. Mandatory Configuration Rules Every classified IT hardware unit (servers, switches, routers, firewalls, storage, classified terminals) must draw power via a dedicated individual red-black isolation socket port; shared multi-device single-port connections are strictly prohibited. Red-black sockets mount adjacent to connected IT hardware to minimize output cable length and eliminate coupling-induced filter performance degradation; complete physical separation of socket input and output wiring eliminates cross-coupling interference that neutralizes filtering effectiveness.

2.3.7 Intelligent Rack-Mounted PDU Terminal Power Distribution Units

Intelligent rack-mounted PDUs deliver terminal power allocation and granular smart management for racked IT hardware, offering superior load capacity, safety performance and remote control functionality vs. standard consumer-grade power strips as the primary end-point power distribution hardware within each cabinet.

  1. Product Variants & Core Specifications KITOZER supplies four PDU product tiers configurable by customer functional requirements, all standard 19-inch rack-mount 1U/2U aluminum alloy chassis designs: | Model Series | Product Tier | Rated Voltage | Rated Current | Socket Configuration & Quantity | Core Functionalities | Chassis Material | |————–|————–|—————|—————|———————————-|———————-|——————| | KITOZER-PD-PDU08-B | Basic Tier | AC220V 50Hz | 16A | 8×10A national standard 5-hole outlets | Base power distribution + overload protection | Aluminum alloy housing, phosphor bronze contact sleeves | | KITOZER-PD-PDU16-M | Metering Tier | AC220V 50Hz | 32A | 8×10A + 2×16A national standard 5-hole outlets | Total voltage/current/power/energy metering + overload protection | Aluminum alloy housing, phosphor bronze contact sleeves | | KITOZER-PD-PDU16-S | Switch Tier | AC220V 50Hz | 32A | 8×10A + 2×16A national standard 5-hole outlets | Independent per-port switching + total metering + overload protection | Aluminum alloy housing, phosphor bronze contact sleeves | | KITOZER-PD-PDU24-I | Intelligent Tier | AC220V 50Hz | 32A | 16×10A + 4×16A national standard 5-hole outlets | Independent per-port metering/switching, remote management, threshold alarms, cross-system interlock control | Aluminum alloy housing, phosphor bronze contact sleeves |
  2. Core Functional Characteristics
  • High Load Capacity & Intrinsic Safety: High-strength aluminum alloy chassis delivers superior heat dissipation with UL94 V-0 flame retardant rating; high-elasticity phosphor bronze contact sleeves support ≥10,000 insertion cycles with minimal contact resistance and low temperature rise under continuous full-load operation. Rated currents span 16A–63A matching all IT hardware power draw profiles with 30% reserve load margin for long-term safe continuous operation.
  • Full-Spectrum Integrated Protection: Built-in overload, short-circuit, lightning surge and over/undervoltage protection with Class III surge suppression (maximum discharge current ≥20kA) to shield IT hardware from grid transients and lightning damage; optional integrated earth leakage protection cuts power automatically at leakage current exceeding 30mA to eliminate O&M personnel electrocution hazards.
  • Granular Intelligent Metering & Control: Intelligent tier PDUs integrate high-precision metering modules tracking total and per-port voltage, current, active/reactive power and cumulative energy consumption for equipment-level refined power utilization tracking with automated threshold-crossing alert triggers upon overload risk detection.
  • Remote Control & Cross-System Interlock: Standard RS485 and Ethernet communication ports supporting Modbus-RTU and SNMP protocols enable seamless environmental monitoring host integration for remote real-time status tracking, independent per-port on/off switching and scheduled power cycling. Native interlock support links PDU operation to access control and fire suppression systems: non-critical load power auto-disconnects upon fire detection, while specified classified hardware power feeds cut upon unauthorized cabinet door opening to block classified data leakage risks.
  • Flexible Mounting & Expansion: Horizontal or vertical internal cabinet rack mounting via adjustable brackets compatible with all cabinet depth variants; daisy-chain expansion ports support multi-PDU stacking for high-density load deployments with simplified wiring.
  • Shielding & Earthing Architecture: Fully shielded aluminum housing hardbonded to the cabinet equipotential ground busbar (ground resistance ≤0.1Ω) for superior electromagnetic interference suppression and zero radiated signal leakage from PDU hardware; all input/output power cabling uses shielded wiring to preserve full cabinet shielding performance.
  1. Mandatory Configuration Rules Standard 42U cabinets deploy 2–4 PDUs mounted on left/right rear cabinet frame rails with dedicated individual ports assigned to every racked IT hardware unit to eliminate shared multi-device single-port load risks. PDU rated current exceeds total combined peak load of all connected equipment with minimum 30% reserve capacity for long-term safe continuous operation. All classified IT hardware PDUs must connect downstream of red-black isolation socket outputs to guarantee end-to-end classified power confidentiality compliance.

2.3.8 Three-Tier Lightning Surge Protection System

Lightning surge protection hardware forms the power distribution safety barrier against lightning strikes, grid switching transients and overvoltage surges that risk permanent classified IT hardware damage. A three-tier cascaded SPD architecture delivers full end-to-end surge protection from mains inlet to terminal IT loads complying with GB50057 and GB50343 national electronic facility lightning protection standards.

  1. Three-Tier Cascaded Protection Architecture
  • Tier 1 Class I Inlet Protection: Installed upstream of the ATS transfer switch at the mains inlet feed with Class I SPD hardware (Imax ≥100kA 8/20μs, In ≥50kA, response time ≤25ns) limiting primary lightning surge voltage to ≤2500V to block direct lightning strike high-magnitude transients.
  • Tier 2 Class II Intermediate Protection: Deployed between UPS output and distribution cabinet input with Class II SPD hardware (Imax ≥40kA 8/20μs, In ≥20kA, response time ≤25ns) further attenuating residual surge voltage to ≤1500V to protect UPS downstream distribution and IT loads.
  • Tier 3 Class III Terminal Load Protection: Integrated at each PDU terminal port upstream of IT hardware with Class III SPD hardware (Imax ≥20kA 8/20μs, In ≥10kA, response time ≤1ns) limiting residual surge voltage to safe levels ≤1000V tolerable by sensitive classified computing hardware for granular load-level surge suppression.
  1. SPD Core Product Characteristics
  • High-Performance Protection Elements: Combined zinc oxide varistor + gas discharge tube architecture delivers high surge current capacity, low residual clamping voltage and ultra-fast response with zero follow current and extended service lifespan.
  • Full-Mode Surge Suppression: Complete L-N, L-PE, N-PE differential/common-mode protection blocks all surge voltage propagation pathways across power conductors.
  • Thermal Disconnect & Failure Safety Circuitry: Built-in thermal trip hardware automatically isolates degraded/overheated SPD units from the mains circuit to eliminate fire and short-circuit hazards with remote fault alarm contacts relaying SPD health status to the environmental monitoring system for automated replacement alerts upon component failure.
  • Visual Operational Status Indication: Color-coded visual status windows (green = healthy, red = degraded/failed) enable rapid on-site visual inspection of SPD functionality during routine O&M rounds.
  • Simplified DIN Rail Mounting: Standard DIN rail form factor for direct installation inside distribution cabinets with straightforward wiring and rapid replacement workflows fully compliant with GB/T 18802.1 low-voltage SPD national testing standards with third-party authoritative certification.
  1. Equipotential Lightning Earthing Architecture All SPD ground terminals connect directly to the cabinet internal ground copper busbar via minimum-length (≤0.5m) ≥6mm² multi-strand copper flexible earthing wire to minimize grounding impedance and maximize surge suppression effectiveness. All internal cabinet metal hardware, equipment enclosures and cable shielding layers hardlink to the ground busbar to form a unified equipotential plane eliminating cross-component potential differences during lightning events that risk hardware damage from induced voltage transients.

2.4 Intelligent Environmental Monitoring & Security Control System

The intelligent environmental monitoring and security control system functions as the cabinet’s central intelligent control brain, enabling unattended O&M, end-to-end physical security governance and immutable full-lifecycle audit traceability. Strictly engineered to classified information system graded protection specifications and three-staff separation authority management mandates, the fully domestic embedded architecture delivers 24/7 uninterrupted data collection, state tracking, AI analytics, automated interlock control, multi-channel alert notification and tamper-proof audit logging across all cabinet subsystems. Every abnormal event triggers rapid automated remediation with complete immutable audit trails to guarantee secure, stable, compliance-aligned classified cabinet operation.

2.4.1 Core System Design Principles

  1. Full Domestic Independent Controllability Architecture All core monitoring hardware and base software adopt 100% domestic supply chains: Loongson/Phytium native quad-core processors, Kylin/Tongxin domestic embedded operating systems and fully proprietary self-developed application control algorithms with zero foreign technical dependency or hidden backdoor vulnerabilities to fully satisfy national Xinchuang classified system construction security mandates and eliminate supply chain confidentiality risks at the source.
  2. Full-Dimensional Closed-Loop Governance Architecture End-to-end closed-loop control spans environmental sensing, data analytics, automated interlock response, multi-channel alert notification and immutable audit logging for all cabinet environmental, power, hardware, physical security, fire suppression and shielding performance metrics. All anomaly events trigger instant automated remediation and permanent traceable records without mandatory manual intervention to realize fully unattended intelligent operation & maintenance.
  3. Classified-Grade Immutable Security Audit Architecture Strict three-staff separation authority control enforces independent segregated roles for System Administrator, Security Operator and Security Auditor with mutually exclusive non-overlapping permissions. All user operations, hardware state transitions, fault alert events and access entry records generate encrypted, undeletable, unalterable audit logs retained for minimum 5 years with full search, export and trace functionality fully satisfying classified information system mandatory audit compliance requirements.
  4. High-Reliability Redundant Architecture Dual redundant power supply, dual redundant network communication and dual redundant storage eliminate single-point failure risks disrupting monitoring system operation. Industrial-grade wide-temperature host hardware operates reliably across -20℃~70℃ with superior electromagnetic interference resistance and shock/vibration tolerance to sustain uninterrupted 24/7 operation across all complex cabinet internal environments with ≥99.999% system availability.
  5. Expandable Cross-Platform Compatibility Architecture Modular plug-and-play hardware supports analog, digital dry contact, serial, Ethernet and fiber optic interface compatibility with all third-party sensors