Table of Contents
ToggleTechnical Design Solution
Prepared by: Guangzhou Lain Intelligent System Development Co., Ltd. | Date: August 2026
Document-Level Disclaimer: The configuration and budget information shown in this document are provided for preliminary design, technical discussion and budgetary reference only. They do not constitute a formal commercial quotation from Guangzhou Lain Intelligent System Development Co., Ltd. Final product selection, quantities, specifications and pricing are subject to the actual project requirements and the company’s formal quotation.
1. Company Introduction
Guangzhou Lain Intelligent System Development Co., Ltd. was established in 2002 and is a high-technology enterprise specializing in computer room construction, electromagnetic shielding engineering, modular data centers and intelligent shielding equipment R&D and production. The company owns the KITOZER brand and has more than two decades of industry experience, mastering core technologies for efficient green computer rooms and providing customized shielding rooms and overall computer room solutions for government agencies, scientific research institutes, electronics manufacturers, medical testing and defense customers.
The company operates a modern production base with flexible customization lines covering sheet metal processing, module forming and finished assembly in-house. All products follow strict quality standards with traceable processes and third-party inspection support, ensuring punctual delivery and stable quality. The company provides free multiple differentiated design options highly matched to site conditions and functional needs, supported by a 7×24 professional after-sales team with dedicated personnel following the full project cycle.
With years of technical accumulation and project experience, the company holds multiple high-technology patents and industry qualifications, has completed over a thousand successful projects nationwide, and has built core competitiveness in electromagnetic shielding, cold aisle micro-modules, integrated cabinets and outdoor intelligent cabinets.
2. Project Overview
2.1 Project Background
With the rapid development of electronic information technology, electromagnetic interference and electromagnetic information leakage risks are increasingly prominent. Electromagnetic shielding rooms have become essential infrastructure for classified information offices, EMC testing, precision electronic equipment debugging and RF/microwave experiments. Modular assembled shielding rooms — easy to install, relocatable and with stable shielding performance — are the preferred choice for small and medium shielding spaces.
This project designs a high-performance standard modular assembled electromagnetic shielding room for an interior clear space of 4.4 m (L) × 2.9 m (W) × 2.8 m (H), covering eight systems — shielding enclosure, door access, ventilation, power distribution, signal filtering, anti-static finishing, lighting and grounding — meeting wideband shielding effectiveness requirements of 10 kHz–10 GHz while ensuring indoor comfort and electrical safety.
2.2 Project Objectives
– Shielding performance: ≥100 dB over 10 kHz–10 GHz, meeting the national B-level classified shielding room standard, effectively blocking external interference and preventing internal electromagnetic information leakage.
– Complete functions: integrated personnel access, ventilation, power supply and distribution, data transmission, electrostatic protection and lighting for daily office and equipment testing use.
– Reliable structure: standardized modular assembly, stable and reliably sealed, service life ≥20 years, with relocation and reuse capability.
– Safety compliance: strict adherence to national design, construction and acceptance standards for fire, electrical and grounding safety, passing third-party inspection and acceptance.
– Economy: optimized configuration to control construction and maintenance costs while ensuring performance.
2.3 Applicable Scenarios
– Classified information offices for government and defense organizations.
– EMC test rooms for electronics enterprises and research institutes.
– RF/microwave and wireless communications R&D laboratories.
– Precision electronic instrument metrology and calibration rooms.
– Medical device EMC testing rooms.
– University and research electromagnetic environment laboratories.
3. User Requirement Analysis
3.1 Core Functional Requirements
– EMI shielding: six-sided fully enclosed shielding structure with good attenuation of magnetic fields, electric fields, plane waves and microwaves across 10 kHz–10 GHz.
– Personnel access: high-performance manual side-hung shielding door, convenient opening with reliable sealing, integrated observation window.
– Ventilation: honeycomb ventilation waveguide windows with low-noise axial fans for indoor air circulation, equipment heat dissipation and shielding integrity.
– Power supply: utility power enters through a power line filter; indoor distribution box and sockets with branch control and overload protection.
– Signal transmission: reserved fiber, network and USB interfaces; all signal lines filtered/waveguided to prevent conducted leakage.
– Electrostatic protection: permanent anti-static PVC flooring with a complete grounding system for rapid dissipation of human and equipment static.
– Lighting: embedded LED panel lights with adequate illumination, flicker-free and interference-free.
3.2 Performance Requirements
| Category | Requirement |
|---|---|
| Shielding effectiveness | ≥60 dB magnetic field at 10 kHz; ≥100 dB electric field/plane wave/microwave at 100 kHz–10 GHz |
| Indoor environment | Working temperature 10 °C–35 °C, RH 30%–80%, ventilation noise ≤40 dB |
| Electrical performance | 220V/50 Hz, grounding resistance ≤1 Ω, insulation resistance ≥2 MΩ |
| Structural life | Main structure ≥20 years; shielding door ≥50,000 switching cycles |
| Fire performance | Indoor finishing materials and electrical equipment B1 fire rating or above |
| Environmental | Odor-free, low VOC, meeting indoor air quality standards |
3.3 Construction and Maintenance Requirements
– On-site assembly without large-scale civil works; short installation period; minimal site impact.
– Modular design with independently replaceable components for convenient, low-cost maintenance.
– The room can be disassembled and relocated with no performance degradation after re-assembly, reducing future relocation cost.
– Complete technical documentation and operator training enable the customer to perform routine O&M independently.

4. Design Description
4.1 Design Basis
The solution strictly follows current national standards, codes and industry guidelines, primarily:
| No. | Standard |
|---|---|
| 1 | GB/T 12190-2006 — Measurement method for shielding effectiveness of electromagnetic shielding enclosures |
| 2 | GB 50174-2017 — Code for design of data centers |
| 3 | GJB 5792-2006 — General specification for military electromagnetic shielding enclosures |
| 4 | BMB3-1999 — Technical requirements and test methods for electromagnetic shielding rooms handling classified information |
| 5 | GB 50054-2011 — Code for design of low-voltage electrical installations |
| 6 | GB 50016-2014 (2018 ed.) — Code for fire protection design of buildings |
| 7 | GB/T 2887-2011 — General specification for computer field |
| 8 | GB 50343-2012 — Technical code for protection against lightning of building electronic information systems |
| 9 | SJ/T 11236-2001 — General specification for anti-static veneer panels |
| 10 | Customer-provided site dimensions and functional requirements |
*Note: for export projects, the governing standard set is confirmed with the customer at project kick-off.*
4.2 Design Principles
4.2.1 Safety and Reliability — shielding safety, electrical safety and structural safety come first; mature reliable core components; verified structural mechanics; electrical systems strictly per low-voltage code; complete reliable grounding.
4.2.2 Advanced Technology — mainstream modular assembly technology with beryllium-copper spring sealing; high-performance two-stage filter circuits; cutoff-waveguide ventilation; leading shielding effectiveness with proven maturity and stability.
4.2.3 Economy and Practicality — configuration based on actual needs without unnecessary redundancy; long-life, low-maintenance products to reduce lifecycle cost.
4.2.4 Standards Compliance — full process compliance from design, materials and production to construction; all materials, equipment and processes traceable to standards, passing authoritative inspection and acceptance.
4.2.5 Expandability and Maintainability — reserved interface margin for future signal interfaces and HVAC upgrades; modular structure for convenient maintenance.
4.3 Overall Design
The room uses a six-sided fully enclosed steel-plate modular assembly structure with 2 mm high-quality cold-rolled steel as the shielding material. Standardized modules form the complete shielding enclosure; beryllium-copper conductive springs are embedded in all joints and bolted for electrical continuity.
The system comprises eight core subsystems:
– Shielding enclosure: wall, ceiling and floor shielding modules + support frame + conductive sealing assemblies.
– Shielding door and access: manual side-hung shielding door + integrated observation window + door grounding flexible connection.
– Ventilation waveguide: honeycomb ventilation waveguide windows + low-noise axial fans + outdoor rain louvers + volume control dampers.
– Power filtering and distribution: single-phase power line filter + indoor distribution box + sockets + wiring accessories.
– Signal interface filtering: fiber feed-through waveguide + RJ45 network filters + USB signal filters + metal panels.
– Anti-static finishing: permanent anti-static PVC flooring + conductive adhesive + skirting + edge strips.
– Lighting control: embedded LED panel lights + wall switches + lighting wiring.
– Grounding and equipotential: main grounding copper busbar + grounding cables + equipotential bonding + grounding terminals.

4.4 Shielding Continuity Design
– Module joints: dedicated slots along all module edges filled with beryllium-copper finger springs; bolts tightened evenly for full spring compression, contact resistance ≤5 mΩ.
– Feed-through components: all lines passing through the enclosure use dedicated filters or waveguide devices; flanges connected to the shell with conductive rubber rings.
– Shielding door: knife-edge insertion sealing with multiple rows of beryllium-copper springs against the door frame knife edge, forming a continuous conductive loop; door flexibly grounded to the shell with copper braid.
– Overall grounding: the shell connects at multiple points to the indoor equipotential copper busbar, then to the building common grounding grid via the main grounding cable.
4.5 Indoor Layout Design
– Shielding door centered on one long wall, opening 900×2100 mm for personnel and small equipment.
– 4 ventilation waveguide windows arranged diagonally (2 supply, 2 exhaust) for diagonal air circulation.
– Power sockets and signal panels evenly along walls at 0.3 m height.
– 2 units of 600×600 mm LED panel lights evenly on the ceiling for uniform illumination.
– Main grounding copper busbar along the indoor wall base with multiple grounding terminals.
5. Recommended Configuration and Reference Budget
The following is the recommended configuration for one 4.4 m × 2.9 m × 2.8 m shielding room. Quantities, model codes and specifications follow the source document’s standard offering and are provided for preliminary design and budgetary reference only. No official price database is available for this trial; final pricing is confirmed in the company’s formal quotation.
5.1 Shielding Enclosure System
| No. | Item | Specification | Qty | Unit | Remark |
|---|---|---|---|---|---|
| 1 | Wall shielding modules | 2 mm cold-rolled steel, powder coated, modular stamped, gasket slots | 40.88 | m² | 2 long walls 4.4×2.8×2 + 2 wide walls 2.9×2.8×2 |
| 2 | Ceiling shielding modules | 2 mm cold-rolled steel, powder coated, modular | 12.76 | m² | 4.4×2.9 m |
| 3 | Floor shielding modules | 2 mm cold-rolled steel, epoxy anti-rust back coating | 12.76 | m² | 4.4×2.9 m |
| 4 | Vertical support studs | 50×50×3 mm galvanized square steel | 24 | pcs | Around walls, ~1.2 m spacing |
| 5 | Horizontal reinforcing studs | 50×50×3 mm galvanized square steel | 58.4 | m | Wall top/bottom/middle, ceiling joists |
| 6 | Ceiling hanger assembly | φ10 mm galvanized threaded rod + expansion bolts | 16 | set | 1.5×1.5 m grid |
| 7 | Floor anti-vibration pads | NBR rubber, 50×50×5 mm | 36 | pcs | Leveling and vibration isolation |
| 8 | Beryllium-copper finger springs | QBe2, 0.15 mm, finger type | 125 | m | All module joints |
| 9 | Joint bolts | M8×20 mm, 8.8 galvanized hex socket + washers | 1200 | set | Module joint fixing |
| 10 | Anti-rust treatment | Epoxy zinc-rich paint on welds and cuts | 1 | item | Internal corrosion protection |
5.2 Shielding Door and Access System
| No. | Item | Specification | Qty | Unit | Remark |
|---|---|---|---|---|---|
| 1 | Manual side-hung shielding door | Opening 900×2100 mm, single leaf, knife-edge multi-seal, 3-stage clamp handle | 1 | set | Cold-rolled steel shell, powder coated |
| 2 | Shielding observation window | 300×400 mm, metal-mesh laminated glass, transmittance ≥70% | 1 | pcs | Upper part of door |
| 3 | Door grounding flexible connector | 25 mm² copper braid, 500 mm | 2 | set | Door-to-shell continuity |
| 4 | Magnetic door catch | Powder coated, holding force ≥50 N | 1 | set | Open-door positioning |
| 5 | Lock cover | ABS plastic | 1 | set | Lock mechanism protection |
5.3 Ventilation Waveguide System
| No. | Item | Specification | Qty | Unit | Remark |
|---|---|---|---|---|---|
| 1 | Honeycomb ventilation waveguide window | 300×300×150 mm, galvanized steel honeycomb core, 3 mm cell | 4 | pcs | 2 supply + 2 exhaust, diagonal |
| 2 | Low-noise axial fan | 220V, 200 m³/h, 30 W, noise ≤35 dB | 2 | units | Exhaust side |
| 3 | Outdoor rain louver | 300×300 mm, aluminum, insect screen | 4 | pcs | Outdoor side |
| 4 | Fan mounting bracket | Galvanized steel | 2 | set | Fan fixing |
| 5 | Fireproof flexible connection | 1 mm, flame-retardant | 2 | m | Fan-to-waveguide |
| 6 | Manual volume damper | 300×300 mm, multi-leaf | 2 | pcs | Supply/exhaust adjustment |
5.4 Power Filtering and Indoor Distribution System
| No. | Item | Specification | Qty | Unit | Remark |
|---|---|---|---|---|---|
| 1 | Single-phase power line filter | 220V/32A, two-stage, insertion loss 10 kHz–10 GHz ≥60 dB | 1 | unit | Wall feed-through |
| 2 | Indoor lighting distribution box | 6 circuits, metal shell, 2P 32A main + 3×1P 10A MCBs | 1 | unit | Wall-mounted, 1.4 m |
| 3 | Anti-static 5-hole socket | 10A/250V, 86-type zinc alloy metal panel | 4 | pcs | 0.3 m height |
| 4 | Single wall switch | 10A/250V, 86-type zinc alloy panel | 1 | pcs | 1.3 m inside door |
| 5 | Distribution copper wire | BV-2.5 mm², red/blue/yellow-green | 120 | m | Lighting and socket circuits |
| 6 | Galvanized conduit | φ20 mm, wall 1.0 mm + fittings | 70 | m | Concealed wall routing |
| 7 | Galvanized junction boxes | Type 86 | 8 | pcs | Socket/switch/light wiring |
| 8 | Wiring accessory kit | Ties, tape, lugs, caps | 1 | lot | General accessories |
5.5 Signal Interface Filtering System
| No. | Item | Specification | Qty | Unit | Remark |
|---|---|---|---|---|---|
| 1 | Fiber feed-through waveguide | φ50 mm, cutoff waveguide, SE ≥100 dB | 2 | pcs | Sealed wall feed-through |
| 2 | RJ45 Gigabit network filter | Single port, 1000 Mbps, all-metal shell | 4 | pcs | For 4 network points |
| 3 | USB2.0 signal filter | Single port, data + power filtering | 2 | pcs | Reserved peripheral ports |
| 4 | Metal shielding interface panel | Type 86, zinc alloy | 4 | pcs | Wall-mounted |
| 5 | Cat5e shielded network cable | 8-core shielded twisted pair | 50 | m | Indoor network wiring |
| 6 | Conductive sealant | Silver-copper type, low resistance | 4 | pcs | Feed-through gap sealing |
5.6 Indoor Anti-Static Finishing System
| No. | Item | Specification | Qty | Unit | Remark |
|---|---|---|---|---|---|
| 1 | Permanent anti-static PVC flooring | 2.0 mm homogeneous, resistance 10⁶–10⁹ Ω, B1 fire rating | 12.76 | m² | Full floor coverage |
| 2 | Anti-static conductive adhesive | Water-based, 20 kg | 1 | drum | Flooring bonding |
| 3 | Anti-static PVC skirting | 100 mm high, matching color | 14.6 | m | Around walls |
| 4 | Aluminum arc edge strip | 10 mm high, matte silver | 14.6 | m | Floor-wall junction |
| 5 | PVC welding rod | Matching color | 2 | rolls | Seam welding |
| 6 | Floor cleaner | Neutral eco-friendly | 2 | bottles | Pre-installation cleaning |
5.7 Lighting and Switch Control System
| No. | Item | Specification | Qty | Unit | Remark |
|---|---|---|---|---|---|
| 1 | Embedded LED panel light | 600×600 mm, 36 W, cool white, flicker-free, Ra≥80 | 2 | sets | Even ceiling embedding |
| 2 | Light mounting frame | Custom galvanized steel | 2 | sets | For shielding ceiling |
| 3 | Lighting sheathed wire | RVV 2×1.5 mm² | 30 | m | Light wiring |
| 4 | Metal junction box | Explosion-proof type | 2 | pcs | Light wiring |
5.8 Grounding and Equipotential System
| No. | Item | Specification | Qty | Unit | Remark |
|---|---|---|---|---|---|
| 1 | Main grounding copper busbar | T2 copper, 40×4 mm, pre-drilled M8 | 6 | m | Along indoor wall base |
| 2 | Brass grounding terminal | M8 with nut/washers | 16 | sets | Busbar grounding points |
| 3 | Main grounding cable | BVR-16 mm², yellow-green | 15 | m | Room to building grid |
| 4 | Equipotential bonding wire | BVR-6 mm², yellow-green | 40 | m | Metal parts, sockets |
| 5 | Grounding terminal box | 300×200 mm, metal shell | 1 | pcs | Indoor grounding collection |
| 6 | Grounding test terminal | Dedicated test point | 1 | pcs | Grounding resistance test |
5.9 Installation, Commissioning and Other
| No. | Item | Description | Qty | Unit | Remark |
|---|---|---|---|---|---|
| 1 | On-site installation | Enclosure assembly, system installation, wiring and commissioning | 1 | item | Professional crew |
| 2 | Shielding effectiveness pre-test | On-site test and tuning | 1 | item | Professional instruments |
| 3 | Transport and handling | Delivery to site | 1 | item | Incl. labor |
| 4 | Technical service | Design, technical guidance, acceptance support | 1 | item | Full-cycle service |
Pricing disclaimer: The configuration and budget shown in this document are provided for preliminary design, technical discussion and budgetary reference only. They do not constitute a formal commercial quotation from Guangzhou Lain Intelligent System Development Co., Ltd. Final product selection, quantities, specifications and pricing are subject to the actual project requirements and the company’s formal quotation. Any budget references are stated in RMB/CNY only.
6. Detailed Technical Specifications
6.1 Shielding Enclosure System
6.1.1 Shielding Modules
– Base material: Q235B low-carbon cold-rolled steel, 2.0 mm (tolerance ±0.1 mm), per GB/T 700-2006; conductivity ≥10⁷ S/m; yield strength ≥235 MPa, tensile 375–500 MPa, elongation ≥26%.
– Fabrication: CNC stamping and bending in one pass; standard module width 1200 mm, size tolerance ±1 mm, surface flatness ≤2 mm/m², diagonal deviation ≤3 mm.
– Surface treatment: degreasing, acid wash, phosphating (2–5 μm) and passivation; electrostatic powder coating 60–80 μm, adhesion grade 0, pencil hardness ≥2H, impact 50 kg·cm no peeling, salt spray ≥500 h no rust; floor modules additionally coated with epoxy zinc-rich paint ≥40 μm.
– Shielding performance: single panel 1 MHz–1 GHz ≥120 dB; assembled enclosure ≥100 dB overall.
6.1.2 Support Frame
– Q235B galvanized square steel 50×50×3 mm, zinc layer ≥85 μm (per GB/T 13912-2002); straightness ≤1 mm/m; single stud load ≥500 kg; indoor corrosion life ≥15 years.
– Ceiling hangers: φ10 mm fully threaded galvanized rods with M10 expansion bolts, tensile strength ≥5 kN per rod (5× safety factor).
– Floor pads: NBR rubber, Shore A 60±5, compression set ≤20%, damping factor ≥0.3, load ≥200 kg each, RoHS compliant.
6.1.3 Beryllium-Copper Conductive Springs
– QBe2 beryllium bronze (Be 1.8%–2.1%, per GB/T 5231-2022); 0.15 mm thick, 10 mm high, finger type, 5 mm finger pitch.
– Hardness HV370–420 after aging, elastic modulus 130 GPa, yield ≥1000 MPa, resilience ≥95%; conductivity ≥22% IACS; single-point contact resistance ≤5 mΩ; joint shielding effectiveness ≥100 dB; insertion life ≥1,000,000 cycles; −55 °C ~ +150 °C; salt spray ≥1000 h; service life ≥20 years.
6.2 Shielding Door and Access System
6.2.1 Manual Side-Hung Shielding Door
– Opening 900 (W) × 2100 mm (H); door leaf 1050×2250×150 mm, single right-hand (left-hand optional).
– Door leaf: 2 mm cold-rolled steel with internal steel frame reinforcement; frame 3 mm cold-rolled steel welded, mounting flange connected to wall modules.
– Sealing: knife-edge insertion multi-seal; beryllium-copper finger springs around the frame against the stainless knife edge; ≥200 contact points/m; contact resistance ≤10 mΩ/m.
– Locking: 3-stage clamp linkage lock, chrome-plated zinc alloy handle, 6 lock points, 15 mm clamping travel, operating force ≤80 N, C-level anti-theft, life ≥50,000 cycles.
– Grounding: 25 mm² copper braid at top and bottom connecting door to shell.
– Auxiliary: magnetic catch (auto-positioning ≥90°), automatic drop seal at bottom.
– Overall: SE 10 kHz ≥60 dB, 100 kHz–10 GHz ≥100 dB; average sound insulation ≥35 dB; air leakage ≤0.5 m³/h; design life ≥20 years.
6.2.2 Shielding Observation Window
– Visible 260×360 mm, external 300×400 mm, 30 mm thick; double tempered glass with 80-mesh 316L stainless mesh, aluminum frame, conductive rubber sealing.
– Transmittance ≥70%, reflectance ≤8%, haze ≤3%; SE 10 kHz–10 GHz ≥80 dB, frame contact resistance ≤10 mΩ; −40 °C ~ +80 °C; life ≥15 years.
6.3 Ventilation Waveguide System
6.3.1 Honeycomb Ventilation Waveguide Window
– Cutoff-waveguide principle; 300×300×150 mm, flange 380×380×5 mm, opening 320×320 mm; hexagonal honeycomb core 3 mm cell, 0.2 mm wall, depth/width 50:1, galvanized steel; porosity ≥95%; SE ≥100 dB (10 kHz–10 GHz), cutoff ≈19 GHz; at 5 m/s air speed resistance ≤15 Pa, max airflow ≥800 m³/h; −40 °C ~ +80 °C; salt spray ≥500 h; life ≥20 years; per GJB 5792-2006, GB/T 12190-2006.
6.3.2 Low-Noise Axial Fan
– Duct axial fan, 300 mm, horizontal; 220V/50 Hz, 30 W, 1450 rpm; airflow 200 m³/h, total pressure 80 Pa, noise ≤35 dB(A) @1 m, vibration ≤2.8 mm/s; galvanized steel housing, die-cast aluminum impeller; IP44, Class B insulation, life ≥50,000 h.
6.3.3 Outdoor Rain Louver
– 6063-T5 aluminum, anodized silver; 45° louvres, 20 mm pitch; ventilation ≥70%, rain rating IP54, wind load ≥1.6 kPa, watertight ≥250 Pa; built-in 18-mesh 304 stainless insect screen (removable); salt spray ≥1000 h; life ≥15 years.
6.4 Power Filtering and Indoor Distribution System
6.4.1 Single-Phase Power Line Filter
– 250V AC, 32 A, 50/60 Hz; two-stage common-mode + differential-mode filter (nanocrystalline CM chokes, ferrite DM chokes, X/Y capacitors, bleeder resistor); insertion loss: 10 kHz ≥20 dB, 100 kHz ≥40 dB, 1 MHz ≥60 dB, 10 MHz ≥70 dB, 100 MHz ≥65 dB, 1 GHz ≥60 dB, 10 GHz ≥50 dB; withstand AC 1500V/1min, insulation ≥100 MΩ, leakage ≤0.5 mA; metal shell wall feed-through; MTBF ≥100,000 h; per GB/T 7343-2017.
6.4.2 Indoor Lighting Distribution Box
– PZ30 6-circuit wall-mounted, 230×300×90 mm, 1.2 mm steel powder coated, IP30; 2P 32A main MCB + 3×1P 10A MCBs (lighting, socket, fan circuits); copper neutral/PE bars; C-curve breakers per GB 10963.1; transparent door.
6.4.3 Anti-Static 5-Hole Socket
– 86-type flush, 10A/250V; zinc alloy die-cast metal panel, shielding ≥30 dB; tin-phosphor bronze contacts 0.6 mm, ≥10,000 cycles, contact resistance ≤50 mΩ; panel system resistance 10⁶–10⁹ Ω; UL94 V-0; grounded to equipotential system.
6.5 Signal Interface Filtering System
6.5.1 RJ45 Gigabit Network Filter
– RJ45 8P8C single port, 10/100/1000 Mbps auto-negotiation; IEEE 802.3/802.3u/802.3ab; two-stage filtering, all-metal shell; insertion loss ≤1 dB (100 MHz), return loss ≥20 dB, crosstalk ≥40 dB, 100 Ω±15% impedance; SE ≥60 dB (10 kHz–1 GHz); gold-plated contacts 1.27 μm; ≥1000 insertion cycles; −20 °C ~ +70 °C.
6.5.2 Fiber Feed-Through Waveguide
– Cutoff waveguide, φ63 mm OD, 150 mm long, φ50 mm bore, φ100 mm flange 5 mm thick; galvanized steel, welded flange; SE ≥100 dB (10 kHz–10 GHz), cutoff ≈3.5 GHz; up to 24 fibers per port with rubber protective sleeve; conductive sealant at both ends; flange wall mounting with 4×M6 bolts and conductive rubber ring; −40 °C ~ +80 °C; life ≥20 years.
6.6 Indoor Anti-Static Finishing System
6.6.1 Permanent Anti-Static PVC Flooring
– 2.0 mm homogeneous through-body conductive; surface and volume resistance 1.0×10⁶–1.0×10⁹ Ω per SJ/T 11236-2001; static decay ≤0.1 s (1000V→100V), triboelectric voltage ≤50V; Taber abrasion ≥10,000 cycles; tensile ≥15 MPa; B1 fire rating (GB 8624-2012), smoke density ≤75; formaldehyde ≤0.05 mg/m³ (E0), VOC ≤0.5 mg/(m²·h), RoHS; antibacterial ≥99% (E. coli, S. aureus); slip-resistant R9; life ≥15 years.
6.6.2 Anti-Static Conductive Adhesive
– Water-based acrylic with conductive carbon black; solids 35±2%, pH 7–8, viscosity 3000–5000 mPa·s; coverage 0.3–0.5 kg/m²; open time 10–20 min; peel strength ≥50 N/25 mm; volume resistivity ≤1.0×10⁵ Ω·cm; B1 flame rating; solvent-free, low VOC.
6.7 Lighting and Switch Control System
– Embedded LED panel light: 595×595×12 mm for 600×600 mm opening; 120× SMD2835 LEDs; 36 W, 3240 lm, 90 lm/W; 6500K cool white (4000K optional); Ra≥80; UGR ≤19; flicker-free per IEEE 1789; AC220V/50 Hz, PF ≥0.9, THD ≤15%; Class II, IP40; aluminum frame, diffuser; life ≥50,000 h (L70); per GB 7000.1, GB/T 17743; RoHS.
6.8 Grounding and Equipotential System
– Main copper busbar: T2 pure copper ≥99.90% (per GB/T 5585.1-2018); 40×4 mm, pre-drilled M8 at 100 mm pitch; conductivity ≥97% IACS, resistivity ≤0.01777 Ω·mm²/m; continuous current ≥500 A; tensile ≥290 MPa; passivated surface; indoor life ≥30 years.
– Grounding cable: BVR 16 mm² soft copper (49×0.64 mm), yellow-green, per GB/T 5023-2008; DC resistance ≤1.15 Ω/km; insulation ≥36.7 MΩ·km; withstand 2500V AC/5min; ampacity ≥83 A; flame class C; life ≥20 years.
– Equipotential bonding: BVR 6 mm²; grounding terminal box 300×200 mm; dedicated test terminal; system grounding resistance ≤1 Ω.

7. Core Advantages and Customer Value
7.1 Stable and Reliable Shielding Performance
The mature steel-plate modular assembly structure with multi-seal beryllium-copper spring technology delivers stable shielding effectiveness at the national B-level standard, satisfying most classified, testing and R&D scenarios. All wall feed-through interfaces use dedicated filter/waveguide devices — no leakage points, with uniform performance across the full band. The shell is grounded at multiple points with complete equipotential design, keeping shielding performance stable regardless of ambient temperature and humidity changes.
7.2 Flexible Modular Design
Standardized modules are assembled on site without welding — short installation period, low civil works requirements, and suitable for retrofitting existing buildings. Dimensions are flexibly customizable; this 4.4×2.9×2.8 m solution can be adjusted per the customer’s site and needs. The room can be disassembled and relocated with no performance degradation, reducing long-term cost.
7.3 Complete and Practical Configuration
One-stop integration of eight systems — enclosure, door, ventilation, power, signal, anti-static, lighting and grounding — delivered ready for use with no additional supporting equipment. Configuration is based on actual needs without redundant features, offering outstanding value; expansion interfaces are reserved for future upgrades. The indoor environment is comfortable with ample ventilation, uniform soft lighting and complete anti-static protection for long-duration occupancy and stable equipment operation.
7.4 Quality and Service Assurance
Core components use premium industry materials with strict production QC and item-by-item factory testing. A professional crew performs on-site installation with standardized workmanship and orderly site management. A complete after-sales system provides free on-site maintenance during warranty, lifetime technical support and spare parts supply with rapid response.
8. Technical Q&A
Q1. How does an electromagnetic shielding room work?
A: It uses the reflection, absorption and guidance of metal conductors to block electromagnetic waves. For electric field waves and microwaves, reflection loss at the metal surface dominates; for magnetic field waves, high-permeability material shunts and absorbs them. Maintaining electrical continuity of the enclosure prevents leakage through gaps and openings, creating a clean electromagnetic environment inside that both blocks external interference and prevents internal information from leaking out.
Q2. What is the difference between assembled and welded shielding rooms?
A: Welded rooms are formed by on-site steel plate welding — higher shielding effectiveness for high-performance requirements, but long construction periods, non-relocatable and demanding site conditions. Assembled rooms use factory-prefabricated modules bolted on site — short installation, relocatable, lower cost, meeting B-level and below standards — the mainstream choice for small and medium rooms with better value.
Q3. What does the dB value of shielding effectiveness mean? Is higher always better?
A: dB expresses attenuation of electromagnetic waves through the shield, calculated as SE = 20lg(E1/E2) where E1 is incident and E2 is transmitted field strength. Higher values mean stronger attenuation and better shielding: 60 dB attenuates to one-thousandth, 100 dB to one-hundred-thousandth. It is not blindly “higher is better” — select per actual needs, as excessive specs significantly increase cost.
Q4. What shielding level does this solution achieve, and which standard does it meet?
A: Design SE: ≥60 dB magnetic field at 10 kHz; ≥100 dB electric field/plane wave/microwave at 100 kHz–10 GHz — meeting the B-level standard of BMB3-1999 for classified shielding rooms, and also GB/T 12190 and GJB 5792. It can pass third-party authoritative inspection and acceptance.
Q5. Does frequent door operation affect sealing performance?
A: No. The door uses beryllium-copper spring sealing — beryllium bronze has excellent elasticity and fatigue resistance with ≥1,000,000 insertion cycles; normal use of over 50,000 cycles shows no significant degradation. Regular cleaning of the knife edge and springs, and avoiding hard impacts, maintains sealing long-term. Worn springs are individually replaceable.
Q6. Do ventilation waveguide windows affect shielding?
A: No. They are based on the cutoff-waveguide principle — the honeycomb cells act as parallel cutoff waveguides in which waves far below cutoff frequency attenuate rapidly, providing both ventilation and excellent shielding. This solution’s waveguide windows achieve ≥100 dB, matching the shell — they are not weak points.
Q7. What floor conditions are required for installation?
A: The floor must be flat and solid: levelness error ≤5 mm/m², load capacity ≥2 kN/m². Ordinary concrete floors only need leveling; tile or wooden floors should be removed or assessed per site conditions. A grounding terminal must be预留 on the floor.
Q8. How long does installation take?
A: For this size, the standard installation period is 5–7 working days — enclosure assembly 3 days, system installation 2 days, commissioning and testing 1 day. The schedule adjusts per site conditions and configuration.
Q9. Can the room be relocated? Will performance degrade?
A: Yes. Relocatability is the core advantage of assembled rooms — all modules are bolted; disassembly causes minimal damage. After re-assembly, as long as the conductive springs are intact and joints are properly tightened, shielding effectiveness reaches the original design values.
Q10. What should be noted in daily use?
A: (1) Open/close the door gently to avoid damaging the sealing structure; (2) keep the knife edge and springs clean of dust and oil; (3) never drill holes or run cables without authorization — additions must be done by professionals; (4) check the grounding system regularly; (5) avoid scratching the anti-static floor with sharp objects.
Q11. What is the service life?
A: Main steel structure ≥20 years indoors; sealing springs and locks ≥50,000 cycles; filters, fans and electrical components ≥10 years. Regular maintenance extends life.
Q12. What are the grounding requirements?
A: Single-point grounding to the building common grounding grid or a dedicated ground electrode; grounding resistance ≤1 Ω. Grounding affects shielding effectiveness, electrical safety and static dissipation and must be reliably connected, with annual resistance testing.
Q13. Can air conditioning be added without affecting shielding?
A: Yes, two options: (1) AC feed-through waveguide — copper pipes, drains and signal lines pass through the waveguide for shielding continuity; (2) indoor AC unit — the whole unit inside with power via filter. Both preserve shielding effectiveness.
Q14. Can additional observation windows be added, with custom sizes?
A: Yes. Independent shielding observation windows can be installed on walls with custom sizes (commonly 500×600 mm, 800×1000 mm). The frame connects to the shielding wall via flanges with conductive sealing, matching wall performance.
Q15. Can more signal interfaces be added, and which types are supported?
A: Yes. Beyond the standard network, USB and fiber, HDMI, VGA, BNC, serial and audio filters can be configured, plus waveguide tubes, AC waveguides and fire waveguide feed-throughs. All interfaces are shielded/filtered to preserve overall performance.
9. Construction Schedule
| Phase | Main Activities | Duration | Responsible | Remark |
|---|---|---|---|---|
| Construction preparation | Site survey and dimension verification; material/equipment arrival and inventory; tool and PPE preparation; safety and technical disclosure | 1 day | Project manager | Completed before site entry |
| Foundation treatment | Floor cleaning and leveling; floor shielding module installation; leveling and fixing; grounding busbar embedment and connection | 1 day | Crew leader | Ensure floor levelness |
| Enclosure assembly | Vertical stud installation; wall module assembly piece by piece; ceiling studs and hangers; ceiling module assembly; joint sealing and tightening | 2 days | Crew | Joint quality is key |
| Component installation | Shielding door installation and commissioning; ventilation waveguide windows; fans and louvers; power filter; signal interfaces | 1 day | Technical engineer | Ensure feed-through sealing |
| Power distribution and wiring | Distribution box installation; conduit and wiring; socket and switch installation; lighting installation; grounding connection | 1 day | Electrician crew | Per low-voltage code |
| Finishing | Floor cleaning and conductive adhesive; anti-static flooring; skirting and edge strips; indoor cleanup | 1 day | Finishing crew | Ensure floor conductivity |
| Commissioning and testing | Power-on function tests; shielding effectiveness pre-test; rectification and sealing optimization; grounding resistance test | 1 day | Test engineer | Ensure performance |
| Acceptance and handover | Joint acceptance; technical documents and keys; usage and maintenance training; acceptance signing | 0.5 day | Project manager | Complete delivery |
Total: approximately 8.5 working days, adjustable per site conditions and customer requirements.
10. Construction Organization, Quality and Safety Measures
10.1 Organization
– Project manager (1): overall coordination, schedule control, quality supervision, customer communication, acceptance and handover.
– Technical engineer (1): technical disclosure, on-site guidance, shielding performance commissioning, technical problem resolution.
– Crew leader (1): leads the on-site crew, controls workmanship and schedule, manages site safety.
– Installers (3–4): enclosure assembly, equipment installation, wiring and finishing.
– Safety officer (1, part-time): site safety inspection, safety measure implementation, safety education.
10.2 Preparation
10.2.1 Technical — familiarize all personnel with drawings and solution; technical and safety disclosure; verify site dimensions against drawings; confirm access routes, construction power and storage; prepare test instruments and tools with valid calibration.
10.2.2 Materials — all equipment inspected before shipment with certificates and test reports; materials arrive in batches and are stacked by category with moisture and impact protection; joint inventory check on arrival; wear parts and spares stored separately under dedicated management.
10.2.3 Site — clear the site, confirm flatness and working space; arrange temporary power with residual current protection; set up material and tool zones with finished-product protection.
10.3 Main Construction Processes
10.3.1 Shielding Enclosure Assembly — floor layout marking; floor module installation with leveling and even joints; vertical studs installed plumb (deviation ≤2 mm/m); wall modules assembled bottom-up with verticality/flatness checks per layer, aligned joints, springs in place and bolts evenly tightened; ceiling studs and hangers fixed to the building; ceiling modules assembled and leveled; junction sealing between ceiling and walls; final inspection of all joints with conductive sealant touch-up.
10.3.2 Shielding Door Installation — door frame positioning and reliable connection to wall modules with plumb/level verification; hinge installation and door leaf hanging with even gaps and smooth operation; spring and lock installation with clamp force adjustment for uniform sealing; door grounding braid installation and continuity test; repeated open/close testing and tuning.
10.3.3 Waveguide and Filter Installation — wall openings per design with accurate size and smooth edges; waveguide/filter flanges against the wall with cleaned contact surfaces, conductive gaskets and even bolt tightening; fans, ducts and louvers connected in sequence with firm sealing and stable brackets; all wall gaps sealed with conductive sealant.
10.3.4 Grounding System — main copper busbar along the indoor wall, straight and firm; multiple shell grounding leads connected to the busbar with tinned connection points; distribution box, socket grounds and metal parts connected to the busbar; main grounding cable to the outdoor grounding grid with firm crimped terminals and anti-corrosion treatment; grounding resistance tested ≤1 Ω after completion.
10.4 Quality Assurance
– Strict three-inspection system: crew self-inspection, leader re-inspection, engineer final inspection; each process accepted before proceeding.
– Key processes controlled with records: joint sealing, feed-through sealing, door sealing and grounding continuity.
– All materials inspected on arrival; non-conforming materials prohibited.
– Full shielding effectiveness pre-test after completion with rectification of weak points.
– Complete construction, test and acceptance records for traceability.
10.5 Safety and Civilized Construction
– Hard hats mandatory; safety harnesses for work at height; strict compliance with safety operating procedures.
– Temporary power wired per code with residual current devices; no unauthorized wiring; certified electricians.
– Hot work requires permits, fire extinguishers and dedicated supervision.
– Materials stacked neatly; construction waste cleared daily.
– Protect the customer’s existing facilities from damage.
– Comply with customer site rules; schedule work to minimize disruption to normal office activities.
10.6 Schedule Assurance
Detailed construction plan with daily workload and clear responsibilities, reviewed daily; all materials pre-stocked to avoid delays; parallel and cross operations for efficiency; sufficient personnel and tools; risk points identified in advance with contingency plans.
11. After-Sales Service
11.1 Warranty Commitment
– Overall warranty period: 12 months from acceptance.
– During warranty, faults and damage caused by product quality or workmanship are repaired on-site free of charge with free part replacement.
– Regular visits during warranty: at least one free on-site inspection per year covering shielding performance, electrical systems and grounding, with hidden risk identification.
11.2 Response Commitment
– 7×24 service hotline for consultation and fault reports.
– Response within 1 hour with an initial solution; if on-site dispatch is needed, arrival within 24 hours within the province and 48 hours outside (remote areas may take longer).
– Simple faults resolved on the spot; complex faults within 2 working days.
11.3 Lifetime Maintenance
– After warranty: lifetime maintenance at parts cost plus reasonable labor — no high service fees.
– Long-term supply of original spare parts at preferential prices for full-lifecycle support.
– Free lifetime technical consultation and upgrade advice.
11.4 Service Content
Periodic shielding effectiveness testing and evaluation; shielding door and spring cleaning, adjustment and replacement; distribution and lighting system maintenance; ventilation cleaning and fan service; grounding system testing and maintenance; anti-static floor cleaning; system upgrades and interface expansion; emergency repair.
11.5 Service Philosophy
Customer-centered: rapid response, professional handling, complete resolution — keeping the shielding room running stably long-term with no worries for the customer.
12. Training Plan
12.1 Objectives
Enable the customer’s operators to master correct usage, daily maintenance points and common troubleshooting, allowing independent daily operation and basic maintenance.
12.2 Audience
Customer personnel responsible for shielding room management, operation and maintenance — recommended 2–3 persons.
12.3 Content
12.3.1 Theory (≈1 hour) — shielding room fundamentals and structure; subsystem functions and working principles; shielding effectiveness meaning and influencing factors; safety usage rules; maintenance content and cycles.
12.3.2 Operation (≈1 hour) — correct door open/close; distribution box operation and circuits; lighting and ventilation usage; correct socket and signal interface use; grounding check; power-on/off procedures and daily inspection points.
12.3.3 Maintenance and Troubleshooting (≈1 hour) — door cleaning and care; spring inspection and cleaning; common fault handling (e.g., light not working, socket no power); emergency procedures; reporting process.
12.4 Method
On-site face-to-face explanation + hands-on demonstration; trainees operate with engineer guidance and correction; a “Usage and Maintenance Manual” is provided.
12.5 Schedule
On the acceptance day, about 3 hours total, adjustable per the customer’s schedule.
12.6 Assessment and Q&A
On-site operation assessment after training; reserved Q&A time; ongoing support via the service hotline.
13. Anonymous Typical Project Scenarios
*All scenarios below are anonymous, generalized examples for reference. They do not refer to any real customer, project address or testimonial.*

Scenario A — Research institute EMC test shielding room.
A 5m×3m×2.8m assembled shielding room for electronic component EMC testing, configured with a high-performance shielding door, honeycomb ventilation waveguides, power filtering, signal filtering, anti-static flooring, lighting and independent grounding. Shielding effectiveness ≥100 dB (10 kHz–18 GHz). Outcome: passed third-party metrology inspection, stable for years of research testing.
Scenario B — Defense organization classified office shielding room.
A 6m×4m×3m assembled room for classified information processing, configured with a double-leaf shielding door, observation window, AC waveguide, fire waveguide, multi-stage power filtering, classified signal interfaces, anti-static finishing and an independent grounding grid. Meets BMB3 C-level standard. Outcome: passed classified system acceptance with stable, reliable operation.
Scenario C — Enterprise RF R&D laboratory shielding room.
A 4m×3m×2.8m assembled room for wireless product R&D testing, configured with a manual shielding door, ventilation, power filter, RF signal interfaces, fiber waveguide, anti-static flooring and dedicated test grounding. SE ≥100 dB (10 kHz–10 GHz). Outcome: effective isolation of external interference, improved test data accuracy and faster product development.
Scenario D — Hospital medical device testing shielding room.
A 4.5m×3m×2.8m assembled room for medical device EMC testing, configured with a shielding door, observation window, fresh-air waveguide, medical-grade power filtering, multiple signal interfaces, anti-static grounding and temperature control. Meets medical device EMC test standards. Outcome: stable test environment with repeatable data.
14. SEO Optimization
14.1 Keyword Classification
– Core keywords: electromagnetic shielding room, assembled shielding room, shielding room, EMI shielding computer room.
– Long-tail keywords: 4.4×2.9×2.8 m shielding room, small assembled shielding room, shielding room manufacturer, shielding room design solution, shielding room configuration list, shielding room technical parameters, classified shielding room, EMC test shielding room, modular shielding room, shielding room installation.
– Industry keywords: shielding room standards, shielding effectiveness, working principle, grounding requirements, ventilation waveguide, power line filter, anti-static shielding room, shielding door parameters, shielding room construction, acceptance standards.
– Brand keywords: KITOZER shielding room, Guangzhou Lain shielding room.
– Geographic keywords: Guangzhou shielding room, Guangdong shielding room manufacturer, Shenzhen EMI shielding room, Dongguan shielding room production, Foshan shielding room installation.
14.2 SEO Tags
– SEO Title: 4.4×2.9×2.8m Standard Modular Electromagnetic Shielding Room — Technical Design Solution | Lain
– Meta Keywords: electromagnetic shielding room, assembled shielding room, shielding room design solution, shielding room configuration list, shielding room technical parameters, small shielding room, EMC shielding room, classified shielding room, Guangzhou shielding room manufacturer
– Meta Description: Guangzhou Lain provides 4.4m×2.9m×2.8m standard modular assembled electromagnetic shielding room design and construction — shielding enclosure, shielding door, ventilation waveguide, power filtering, signal interfaces and anti-static systems, shielding effectiveness ≥100 dB, customizable, free design consultation.
– H1: 4.4m×2.9m×2.8m Standard Modular Electromagnetic Shielding Room Technical Design Solution
– H2 structure: Project Overview | User Requirement Analysis | Design Description | Recommended Configuration | Technical Specifications | Core Advantages | Technical Q&A | Construction Plan | After-Sales Service
14.3 Internal Link Anchor Suggestions
– Core anchors: electromagnetic shielding room, assembled shielding room, shielding computer room.
– Long-tail anchors: shielding room configuration list, shielding room technical parameters, shielding room design solution, small electromagnetic shielding room.
– Related anchors: shielding door, ventilation waveguide window, power line filter, anti-static flooring, shielding room construction.
*Note: keywords are placed naturally; no keyword stuffing.*
15. Official Contact Information
– Company: Guangzhou Lain Intelligent System Development Co., Ltd.
– Website: https://gdlain.com
– Phone: +86 139 2228 9957 / +86 185 2066 8845
– Address: No. 5 Huashan Road, Shilou Town, Panyu District, Guangzhou, Guangdong, China