Brand: KITOZER | Prepared by: Guangzhou Lain Intelligent System Development Co., Ltd. | Version: V2.0
Document-Level Disclaimer: The configuration and budget information shown in this document are provided for preliminary design, technical discussion and budgetary reference only. They do not constitute a formal commercial quotation from Guangzhou Lain Intelligent System Development Co., Ltd. Final product selection, quantities, specifications and pricing are subject to the actual project requirements and the company’s formal quotation.
1. Company Introduction
Guangzhou Lain Intelligent System Development Co., Ltd. was established in 2002 and is a high-technology enterprise specializing in computer room construction, HV/LV power distribution equipment and intelligent cabinet and environmental monitoring systems R&D, production and sales, owning the KITOZER brand. With more than two decades of experience, the company’s products cover modular cold aisles, indoor integrated cabinets, outdoor intelligent cabinets, shielding rooms and cabinets, container data centers, environmental monitoring systems and UPS power, widely used in power, municipal, industrial park, data center, medical and education fields.
Four core strengths: fast response (source-factory flexible production, 7×24 response); quality assurance (strict national/industry standards, third-party QC, full factory inspection); custom design (three free customized options, non-standard support); quality after-sales (full-lifecycle service, dedicated project follow-up).

2. Project Overview
2.1 Project Background
With urban distribution network upgrades, industrial park development and commercial infrastructure construction, the 10kV outdoor ring main unit (RMU) — offering high supply reliability, flexible connections, convenient O&M and a small footprint — has become the core node equipment of medium-voltage distribution networks. Traditional outdoor distribution equipment suffers from insufficient protection ratings, environmental sensitivity, heavy O&M and low intelligence, failing to meet modern requirements for high reliability and unattended operation. This solution designs a high-reliability, intelligent, maintenance-free 10kV outdoor RMU cabinet for harsh outdoor conditions.
2.2 Construction Objectives
– High-reliability supply: dual-source ring architecture with N-1 redundancy, greatly reducing outage scope and time.
– Strong environmental adaptability: fully sealed insulation + high-protection enclosure for high temperature, humidity, condensation, dust and corrosion.
– Complete protection: relay protection and fault detection for fast fault clearing.
– Intelligent O&M: telemetering, tele-signaling and tele-control with distribution automation integration for unattended operation.
– Full-process service: design, manufacturing, installation, commissioning, training and after-sales.
2.3 Applicable Scenarios
Urban distribution network retrofits, industrial park distribution, commercial complex supply, municipal infrastructure, data center external lines, residential communities and new energy grid connection — all 10kV outdoor distribution scenarios.

3. User Requirement Analysis
3.1 Basic Functional Requirements
– Ring connection with 2 incoming + 4 outgoing circuits (6 total) for dual-source interconnection and distribution.
– Load switching, short-circuit protection, overload protection and earth-fault protection.
– “Five-prevention” interlocking to prevent misoperation and protect personnel.
– Outdoor floor-mounted with rain, dust, corrosion, condensation and theft protection.
– Complete grounding of the shell and metal framework.
3.2 Performance Requirements
| Parameter | Value |
|---|---|
| Rated voltage / frequency | 12 kV / 50 Hz |
| Main busbar / branch rated current | 630 A / 630 A |
| Rated short-time withstand current | 20 kA / 4 s |
| Rated peak withstand current | 50 kA |
| Enclosure protection | Shell IP54; gas tank IP67 |
| Load switch mechanical life | ≥10,000 operations |
| Ambient temperature | −30 °C ~ +70 °C |
3.3 Intelligence and Communication Requirements
– Microprocessor-based protection per circuit (instantaneous, overcurrent, zero-sequence, over/undervoltage).
– Multifunction power meters for voltage, current, power, energy and harmonics.
– Standard communication (Modbus, IEC 60870-5-103/104) for distribution automation integration.
– Local/remote operation switching with remote open/close control and data viewing.
– Fault recording and event logging for analysis and traceability.
3.4 O&M and Safety Requirements
Maintenance-free or minimal-maintenance design; clear status indication and fault alarms; visible disconnection and grounding points for safe maintenance; anti-theft locks; complete documentation, O&M manuals and spare parts support.
4. Overall Design Description
4.1 Design Basis
Key standards: GB 3906-2020 (AC metal-enclosed switchgear 3.6–40.5 kV); GB/T 11022-2020 (Common specifications for HV switchgear); DL/T 593-2016; GB 50060-2013 (Design code for 3–110 kV HV distribution installations); GB 50217-2018 (Cable design standard); DL/T 5352-2018; GB/T 14285-2006 (Relay protection and safety automation); GB 4208-2017 (IP codes); State Grid and China Southern Grid 10kV outdoor RMU technical specifications. Governing editions confirmed per project.
4.2 Design Principles
Safety and reliability; advanced and practical (gas-insulated switchgear and intelligent protection); environmental adaptation (materials, structure, heating/dehumidification); convenient O&M (modular, visual monitoring); standard compliance (certified, grid-connection compliant); flexible customization (circuits, current ratings, protocols, dimensions).
4.3 Primary Main Connection
Typical single-busbar ring connection: 2 incoming feeders from different upstream sources, 4 outgoing feeders to load zones. Normally open-ring operation (one source carries all loads); on source fault/maintenance, the ring tie switch transfers to the other source for uninterrupted supply.
– Incoming circuits: load switch-fuse combination (load switching, short-circuit and overload protection).
– Outgoing circuits: three-position load switch + earthing switch (load make/break, line isolation, maintenance earthing).
– Main busbar: full-copper tinned busbar through all circuits.
4.4 Cabinet Structure Design
– Layout: front operation / rear cable compartment; front instrument and mechanism zone, rear cable termination zone, left incoming bay, right outgoing bay.
– Material/process: 2 mm 304 stainless steel outer shell (laser cut, CNC bent, brushed finish); gas tank of laser-welded stainless steel with excellent sealing.
– Compartments: metal partitions separate the gas tank, cable and instrument compartments for electrical isolation.
– Protection: EPDM waterproof door gaskets, 3-point anti-theft locks, rain shield and sloped roof, IP68 cable glands at bottom entries.
– Ventilation: natural ventilation with dust filters; fully sealed gas tank unaffected by ambient conditions.
– Ergonomics: mechanisms and instruments at 1.2–1.5 m operating height; door opening ≥120°; interior LED lighting on door opening.
4.5 Secondary Control and Monitoring
Layered distributed structure: per-circuit protection and measurement devices in the instrument compartment, connected by a communication bus.
– Protection layer: per-circuit microprocessor protection (independent protection/measurement/control).
– Monitoring layer: multifunction meters (full electrical parameters + energy), temperature/humidity controllers.
– Communication layer: RS485/Ethernet upload to the distribution automation master station for remote “three-telemetry” (遥测/遥信/遥控).

5. Equipment Configuration List
5.1 Cabinet and Structural Protection
| No. | Item | Specification | Qty |
|---|---|---|---|
| 1 | Outdoor RMU enclosure | 304 stainless, double-layer, IP54, 1800×1200×2200 mm | 1 |
| 2 | Internal compartment partitions | 1.5 mm steel, powder coated | 1 set |
| 3 | Door assemblies | Double-leaf, 3-point lock, EPDM gasket, glass observation window, grounding braid | 2 |
| 4 | Mounting base channel | No.10 galvanized channel steel frame | 1 set |
| 5 | Main grounding bar | 40×4 mm galvanized flat steel with M10 bolts | 2 |
| 6 | Cable sealing glands | 304 stainless, for 3×70–3×300 mm² armored cable, IP68 | 12 |
| 7 | Interior LED lighting | AC220V, door-triggered | 2 sets |
| 8 | Anti-condensation temperature/humidity control | Controller + PTC heater, AC220V, 50 W | 2 sets |
5.2 Primary Circuit — Incoming Feeders (×2)
| No. | Item | Specification | Qty |
|---|---|---|---|
| 1 | Gas-insulated load switch-fuse combination | 12 kV, 630 A, 20 kA/4 s, three-position, SF6 | 2 |
| 2 | HV current-limiting fuses | 12 kV, 125 A, 50 kA breaking, striker | 6 |
| 3 | ZnO surge arresters | 10 kV, composite, 5 kA, residual ≤50 kV | 6 |
| 4 | Wall bushings | 10 kV, epoxy cast, 630 A | 6 |
| 5 | Connection busbars | T2 copper TMY-60×6, tinned | 6 m |
| 6 | Current transformers | LZZBJ9, 200/5 A, dual-winding 0.5/10P10, 15 VA | 6 |
5.3 Primary Circuit — Outgoing Feeders (×4)
| No. | Item | Specification | Qty |
|---|---|---|---|
| 1 | Gas-insulated three-position load switches | 12 kV, 630 A, 20 kA/4 s, SF6 | 4 |
| 2 | ZnO surge arresters | 10 kV, composite, 5 kA | 12 |
| 3 | Wall bushings | 10 kV, epoxy cast, 630 A | 12 |
| 4 | Connection busbars | T2 copper TMY-60×6, tinned | 12 m |
| 5 | Current transformers | LZZBJ9, 100/5 A, dual-winding 0.5/10P10 | 12 |
| 6 | Earthing switches | 10 kV, 20 kA/4 s, mechanically interlocked | 4 |
5.4 Primary Circuit — Busbar and Common Parts
| No. | Item | Specification | Qty |
|---|---|---|---|
| 1 | Main busbar | T2 copper TMY-80×8, fully tinned | 4.5 m |
| 2 | Busbar support insulators | 10 kV epoxy, 4 kN bending | 12 |
| 3 | Busbar expansion joints | Copper flexible, for 80×8 | 2 |
| 4 | Internal earthing busbar | T2 copper TMY-40×4, tinned | 6 m |
| 5 | Busbar clamps | Insulating flame-retardant | 12 sets |
5.5 Secondary Control and Measurement
| No. | Item | Specification | Qty |
|---|---|---|---|
| 1 | Microprocessor protection units | 10 kV line protection (instantaneous/overcurrent/zero-seq/over-under-voltage), RS485 | 6 |
| 2 | Multifunction power meters | 3-phase 4-wire, full parameters + energy + harmonics, RS485 | 6 |
| 3 | Open/close control buttons | Red/green self-reset, φ22 mm | 12 |
| 4 | Position indicator lamps | LED red/green/yellow, AC/DC220V | 18 |
| 5 | Local/remote selector switches | Universal, two-position | 6 |
| 6 | Secondary terminal blocks | UK2.5B rail type | 180 |
| 7 | Secondary MCBs | 2P C10A AC230V | 4 |
| 8 | DC switch-mode power supply | AC220V in, DC24V/5A out | 1 |
| 9 | Motor operating mechanisms | Spring-energy, AC/DC220V | 6 |
| 10 | Auxiliary travel switches | Passive contacts | 18 |
| 11 | Secondary control cables | RVVP shielded, 1.5 mm² | 120 m |
| 12 | Wire number sleeves | Heat-shrink | 15 m |
5.6 Auxiliary and Labeling
Cable ties; galvanized bolts M8/M10 sets; conductive paste; phase sequence labels (A yellow/B green/C red); stainless nameplate; safety warning labels; secondary circuit labels.
Pricing disclaimer: The configuration and budget shown in this document are provided for preliminary design, technical discussion and budgetary reference only. They do not constitute a formal commercial quotation from Guangzhou Lain Intelligent System Development Co., Ltd. Final product selection, quantities, specifications and pricing are subject to the actual project requirements and the company’s formal quotation. Any budget references are stated in RMB/CNY only.
6. Core Product Technical Specifications
6.1 Outdoor RMU Cabinet (KITOZER-HW-12/630)
| Parameter | Value |
|---|---|
| Rated voltage / frequency | 12 kV / 50 Hz |
| Main busbar / branch current | 630 A / 630 A |
| Short-time withstand | 20 kA/4 s |
| Peak withstand | 50 kA |
| Protection | Shell IP54; gas tank IP67 |
| Enclosure | 2 mm 304 stainless shell; 1.5 mm steel internal partitions, powder coated |
| Mounting | Outdoor floor-mounted |
| Dimensions / weight | 1800 (W) × 1200 (D) × 2200 mm (H), ≈1200 kg |
| Compartments | 3 (gas tank, cable, instrument) |
| Locks / gaskets | 3-point anti-pry locks; EPDM gaskets |
| Environment | −30 °C ~ +70 °C; RH daily ≤95%, monthly ≤90%; altitude ≤2000 m; seismic intensity 8 |
| Standards | GB 3906-2020, GB 4208-2017 |
6.2 Gas-Insulated Three-Position Load Switch
6.2.1 Load Switch-Fuse Combination (incoming, KITOZER-FLR-12/630) — 12 kV, 630 A; fuse short-circuit breaking 50 kA; short-time withstand 20 kA/4 s; peak 50 kA; transfer current 1750 A; insulation: power-frequency 42 kV/1 min (phase-earth), 48 kV (open gap); lightning impulse 75 kV (phase-earth), 85 kV (open gap); SF6 insulation — rated current breakable at zero gauge pressure; tank charge 0.04 MPa @20 °C; annual leakage ≤0.05%; tank life ≥30 years; three positions (closed/open/earfhed); spring-energy motor operation with manual backup, AC/DC220V ±15%; mechanical life ≥10,000 operations; ≥1,000 rated active-load break operations; ≥50 short-circuit breaks; earthing switch 20 kA/4 s / 50 kA peak; mechanical + electrical five-prevention interlocking; per GB 3804-2020, GB 16926-2009.
6.2.2 Three-Position Load Switch (outgoing, KITOZER-FL-12/630) — 12 kV, 630 A; 20 kA/4 s; 50 kA peak; ≥1,000 load breaks; same insulation, gas tank, operation and mechanical life as the combination; no fuse — provides load make/break, isolation and earthing with upstream protection.
6.3 HV Current-Limiting Fuse (SDLAJ-12)
12 kV, 20–200 A selectable; breaking 50 kA; cut-off current ≤25 kA; power-frequency 42 kV/1 min, lightning impulse 75 kV; full-range protection (gG/gL per GB 15166.2); striker trips the load switch for three-phase linkage; −35 °C ~ +55 °C; per GB 15166.2-2008, IEC 60282-1.
6.4 Composite-Housing ZnO Surge Arrester (HY5WS-17/50)
Gapless metal-oxide; rated 17 kV, continuous 13.6 kV; nominal discharge 5 kA; lightning residual (8/20 μs) ≤50 kV; switching residual ≤42.5 kV; steep-front ≤57.5 kV; DC reference ≥24 kV; leakage at 0.75U1mA ≤50 μA; square-wave 200 A/2000 μs ×18; high-current 65 kA (4/10 μs) ×2; silicone rubber housing (hydrophobic, UV-resistant); 1000 N lateral strength; −40 °C ~ +70 °C; per GB 11032-2020, IEC 60099-4.
6.5 Cast-Resin Current Transformer (LZZBJ9-10A1G)
10 kV, 50 Hz; ratios 200/5 A (incoming) / 100/5 A (outgoing); dual windings — metering 0.5 (15 VA), protection 10P10 (20 VA); accuracy limit factor 10; instrument safety factor ≤5; insulation 42 kV/1 min, 75 kV impulse; short-time 20 kA/1 s, peak 50 kA; tanδ ≤0.005; temperature rise ≤55 K; epoxy cast body; −30 °C ~ +40 °C, altitude ≤1000 m; per GB 1208-2016, IEC 61869-2.
6.6 Main Busbar
T2 copper ≥99.95%, TMY-80×8 mm; rated 1250 A; short-time 25 kA/4 s, peak 63 kA; fully tinned ≥8 μm; resistivity ≤0.017241 Ω·mm²/m; hardness ≥65 HV; straightness ≤1 mm/m; per GB/T 5585.1-2018.
6.7 Microprocessor Protection Unit (KITOZER-MCP-100)
For 10 kV and below incoming/outgoing/transformer circuits; supply AC/DC 85–265 V (≤5 W normal, ≤10 W operation); inputs 3×100V/57.7V, 3×5A/1A, 50 Hz ±5%; protection: 3-stage phase overcurrent (instantaneous/definite-time/IDMT, independently enabled), 2-stage zero-sequence (earth fault), overvoltage, undervoltage, overload alarm/trip, control-circuit open alarm, PT-loss alarm, spring-not-charged alarm, 8 fault waveforms; measurement: 3-phase V/I, P/Q/PF/frequency (V/I 0.2 class, P/E 0.5 class); 16 DI + 4 relay outputs (trip 5A/250VAC, signal 3A/250VAC); 2×RS485 (Modbus-RTU, IEC 60870-5-103), optional Ethernet (IEC 104); 128×64 LCD Chinese menu; 2 kV/1 min insulation; EMC per GB/T 14598 (level 4); −20 °C ~ +70 °C; 120×120×110 mm, ≈0.8 kg; per GB/T 14285-2006, DL/T 478-2013.
6.8 Multifunction Power Meter (KITOZER-PM-96)
AC/DC 85–265 V, ≤3 W; 3-phase 3/4-wire selectable (100V/380V, 5A/1A with CT ratio setting); full electrical parameters, bidirectional active/reactive energy (4-quadrant), 2nd–31st harmonic + THD, demand; accuracy V/I 0.2, P/active-E 0.5, reactive 1.0, frequency ±0.01 Hz; 96×96 LCD; 4 DI + 2 relay outputs (5A/250VAC), optional 4–20 mA analog output; RS485 Modbus-RTU; 2 kV/1 min; −10 °C ~ +55 °C; 96×96×85 mm; per GB/T 22264.1-2008, DL/T 614-2007.
6.9 Temperature/Humidity Controller (KITOZER-WSK-100)
AC220V ±15%, ≤3 W; NTC temp + capacitive humidity sensors; −40~125 °C, 0–100% RH (temp ±0.5 °C, RH ±3%); heating relay 5A/220VAC and fan relay; auto heating above humidity setpoint / below low-temp setpoint, fan above high-temp setpoint; key-set thresholds with power-off memory; LED display; sensor fault alarm; rail/panel mount; per JB/T 10684-2006.
6.10 Cable Sealing Gland (KITOZER-GL-M50)
For φ30–42 mm cables; M50×1.5 thread; IP66/IP68; 304 stainless body; NBR (or silicone) seals; optional Ex d IIB T6; −40 °C ~ +120 °C; waterproof, dustproof, corrosion-resistant, anti-vibration, anti-pull; per GB 4208-2017, IEC 60529.

7. Solution Advantages and Features
1. High reliability, maintenance-free operation. Fully sealed SF6 gas tank (IP67) isolates internal components from dust, moisture and corrosion; stainless laser-welded tank with annual leakage ≤0.05% (far below the national 0.5% limit), ≥30-year service life without gas make-up; mature SF6 arc-extinguishing with ≥10,000 mechanical operations; mechanical + electrical five-prevention interlocking eliminates misoperation risk.
2. Strong environmental adaptability. 304 stainless shell with IP54 protection — rain, dust, rust and corrosion resistant for coastal, chemical and industrial areas; wide −30 °C ~ +70 °C operation; double anti-condensation design (double-layer shell + intelligent temperature/humidity control); IP68 cable glands block moisture from cable trenches.
3. High intelligence for distribution automation. Per-circuit microprocessor protection with fault clearing ≤40 ms; multifunction meters for full electrical parameter, harmonic and energy monitoring; standard protocols for seamless distribution automation integration (telemetering/tele-signaling/tele-control); fault recording and event logs; local/remote dual-mode operation for unattended service.
4. Safe, convenient O&M with lower lifecycle cost. Modular independent circuits (single-circuit maintenance without affecting others); three-position design with visible disconnection and earthing points; ergonomic layout with adequate lighting and clear terminals; maintenance-free gas tank — routine visual inspection only; full-lifecycle original spare parts and responsive support.
5. Customization. Source factory: custom circuit count, current rating, protection class, materials and dimensions; free solution/electrical schematic/3D layout design; flexible production with short lead times; deep customization of protocols, protection logic and secondary circuits to fit existing monitoring systems.
8. Technical Q&A
Q1. What is the difference between an outdoor RMU cabinet and an indoor ring main unit?
A: Both serve ring-network distribution; the difference is application and protection. Indoor ring main units are switchgear with lower protection (typically IP20/IP3X) installed in a power room; outdoor RMU cabinets are designed for open-air installation with higher protection (IP54+), corrosion, condensation and rain resistance — no power room or civil works needed, saving space and cost.
Q2. What is a three-position load switch, and what do the three positions do?
A: It integrates load switch, disconnector and earthing switch in one unit: closed (circuit conducting, normal supply), open (main circuit isolated with a visible disconnection point for safe maintenance), earthed (outgoing side connected to the earth bar to discharge residual charge, protecting personnel). Mechanical interlocking ensures only one position at a time — “open before earth, unearth before close” safety sequence.
Q3. What is the “five-prevention” interlocking?
A: The mandatory misoperation-prevention functions for HV switchgear: prevent wrong open/close of load switches; prevent opening/closing disconnectors under load; prevent closing earthing switches when energized; prevent closing for supply when earthing switches are closed; prevent entering live compartments. This solution implements mechanical + electrical interlocking: the three-position mechanism inherently prevents the first four; the door is interlocked with the earthing switch (cable compartment door opens only when earthed).
Q4. Is SF6 gas toxic? Will it leak?
A: Pure SF6 is colorless, odorless, non-toxic, non-flammable and inert — harmless to people; only under extreme high-temperature arcing can small amounts of low-fluoride byproducts form, which do not occur in normal operation. The tank is laser-welded stainless steel with annual leakage ≤0.05% (national limit 0.5%) — maintenance-free for its ≥30-year life, with a pressure gauge and alarms.
Q5. Can the RMU be remotely controlled? Which protocols?
A: Yes — telemetering (remote viewing of V/I/P/energy), tele-signaling (switch status, alarms, protection actions), tele-control (remote open/close commands) via standard Modbus-RTU and IEC 60870-5-103, optional IEC 104 over Ethernet, directly into the customer’s distribution automation, power monitoring or EMS.
Q6. What do CT accuracy classes 0.5 and 10P10 mean?
A: They describe two different windings: 0.5 is the metering winding — ratio error ≤±0.5% at rated current for accurate measurement/energy; 10P10 is the protection winding — composite error ≤10% up to 10× rated current, ensuring accurate signal transmission under short-circuit conditions for correct protection operation.
Q7. What are the foundation requirements for installation?
A: Cast concrete foundation 100–200 mm larger than the cabinet each side, raised 200–300 mm above ground; C25+ reinforced concrete; pre-embedded No.10 galvanized channel base (leveled, bolted to cabinet); grounding grid around the foundation ≤4 Ω with ≥2 reliable connections to the base; cable conduits pre-embedded with sealed openings.
Q8. What tests are required after installation?
A: Insulation resistance (primary phase-earth ≥1000 MΩ, secondary ≥1 MΩ); power-frequency withstand (primary 42 kV/1 min, secondary 2 kV/1 min); contact resistance; mechanism operation (5 manual + 5 electric open/close cycles, correct position indication); interlocking verification; protection transmission tests (simulated faults — correct action/exit/signals); communication commissioning with the master station; grounding resistance ≤4 Ω.
Q9. What are the grounding requirements?
A: Dedicated grounding grid ≤4 Ω; shell, base and earthing busbar reliably connected (≥2 points); connections with 40×4 mm galvanized flat steel or ≥16 mm² copper; galvanized bolts with conductive paste; door bonded to shell with copper braid; clear earthing marks, M10+ bolts.
Q10. What routine maintenance is needed, and how often?
A: Monthly: visual check of shell, locks, gaskets, gas pressure, indicators; quarterly: clean shell and vent filters, check heaters and grounding, cable seals; annually: mechanism operation tests, secondary circuit tightening and insulation, protection verification, arrester live-line check, grounding test. The gas tank needs no routine maintenance — test gas humidity/purity every 3–5 years.
Q11. What if condensation appears?
A: Check the temperature/humidity controller and heaters and threshold settings; check and repair sealing (door gaskets, cable glands); clear blocked vent filters; seal cable-trench openings against rising moisture; add desiccant or dehumidifier if needed.
Q12. What if the operating mechanism jams?
A: Check operating supply voltage; check interlock states (earthing position, door closed) and release; try manual operation to distinguish mechanical vs electrical faults; lubricate transmission parts and check for obstructions; check close/open coils and auxiliary contacts; if unresolved, contact the manufacturer — never force the mechanism.
Q13. How are the circuit count and current rating determined?
A: Circuit count follows incoming sources and outgoing feeders (common: 1-in-2-out, 2-in-2-out, 2-in-4-out, 3-in-3-out; ring connections generally need ≥2 incoming; reserve spares). Busbar current follows total load with margin; branch current follows the largest single circuit (630 A common, 1250 A for heavier loads). Short-circuit class per upstream capacity (20 kA common, 25 kA for high-fault areas). Free selection advice and design are provided.
Q14. Gas-insulated vs air-insulated RMU — which is better?
A: Gas-insulated (SF6): compact, fully sealed, strong environmental adaptability (outdoor, humid, dusty), maintenance-free tank, 30+ year life, slightly higher initial cost, SF6 recovery consideration. Air-insulated: larger, lower protection, requires indoor dry environments, exposed contacts needing regular cleaning, shorter life, lower initial cost, no greenhouse gas. For outdoor harsh and low-maintenance scenarios choose gas-insulated; for clean indoor power rooms air-insulated may suit.
9. Construction Schedule
Total ≈30 days including production (foundation work can run in parallel — delivery in as few as 20 days):
| Phase | Main Activities | Days |
|---|---|---|
| 1 | Project interface and solution confirmation | 2 |
| 2 | Raw material procurement and production preparation | 3 |
| 3 | Cabinet fabrication and assembly | 7 |
| 4 | Secondary wiring and factory commissioning | 3 |
| 5 | Packing and transport | 2 |
| 6 | Site arrival acceptance | 1 |
| 7 | Foundation and grounding grid works (parallel with production) | 5 |
| 8 | Cabinet positioning and fixing | 1 |
| 9 | Primary cable laying and termination | 3 |
| 10 | Secondary wiring and inspection | 2 |
| 11 | Handover tests and commissioning | 2 |
| 12 | 72-hour energized trial run | 3 |
| 13 | Final acceptance and documentation handover | 1 |
10. Construction Organization, Quality and Safety Measures

10.1 Organization
Project manager (1); technical lead (1); crew leader (1); certified HV electricians (2); secondary electricians (2); safety officer (1); QC officer (1).
10.2 Preparation
Technical: drawing/standard review, disclosure, special plans and work instructions, record templates. Materials/tools: arrival inspection with certificates; HV tester, insulation/grounding/contact-resistance testers, torque wrenches, PPE. Site: foundation complete, leveled, temporary power, safety fencing and signs, storage zones.
10.3 Key Processes
– Foundation/grounding: excavate, compact, cast C25 concrete; pre-embed No.10 channel (level ≤2 mm/m); 40×4 mm galvanized flat-steel grid with ∠50×5×2500 mm earth electrodes, resistance ≤4 Ω; ≥2 connections to the base with conductive paste.
– Cabinet installation: hoist/place carefully, plumb ≤1.5‰, bolt to base, connect grounding, bond doors with copper braid.
– Primary cabling: insulation test before laying; enter via sealed glands; cold/heat-shrink terminations per code; tinned lugs crimped with torque per spec and conductive paste; phase sequence checked (A yellow/B green/C red).
– Secondary wiring: 1.5 mm² voltage circuits / 2.5 mm² current circuits; neat bundled wiring; numbered sleeves; ≤2 wires per terminal with spare cores; shield earthed single-end; continuity and insulation ≥1 MΩ.
– Commissioning: full wiring check; insulation and withstand tests; mechanism tests (manual + electric); interlocking verification; protection transmission tests; communication commissioning.
10.4 Quality Control
Three-inspection system (self/mutual/dedicated); certified materials only; key and hidden works accepted by the customer before covering; no unauthorized design changes; complete traceable records; final acceptance report.
10.5 Safety Management
Certified workers, hard hats and harnesses; work-permit and de-energized-work systems (isolation, testing, earthing, tagging, barriers); HV testing with fencing and dedicated supervision; compliant temporary power with RCDs; firefighting equipment and hot-work permits; daily pre-shift briefings; emergency plans.
11. After-Sales Service
– Warranty: 2 years from acceptance for quality/workmanship faults — free repair, parts and on-site service; free software upgrades during warranty; exclusions (human damage, force majeure, misuse) at cost.
– Response: 7×24 hotline, answer within 1 hour; general faults — on-site within 4 h urban / 8 h suburban, resolved within 24 h; major faults — senior engineer within 2 h, resolved within 48 h; backup/emergency solutions if not immediately repairable.
– Periodic inspection: free on-site inspection every 6 months during warranty (appearance, mechanism tests, insulation, protection verification, communication, anti-condensation, grounding, fastener tightening) with formal reports and equipment archives.
– Spares: stocked wear parts (mechanisms, protection units, heaters, lamps, fuses, terminals); free during warranty, cost-price after; emergency parts within 48 h.
– Lifetime service: annual maintenance agreements, upgrades (protection, communication, intelligence), relocation and expansion support.

12. Operation and Maintenance Training Plan
12.1 Objectives
Enable the customer’s O&M personnel to understand the RMU’s structure, working principles and primary/secondary systems; master correct operation procedures and safety rules; perform routine inspection and maintenance; identify common faults and handle simple ones; read operating data and fault records and cooperate with professional repairs.
12.2 Audience
Customer distribution O&M personnel, electricians and managers — recommended 3–5 with basic electrical knowledge.
12.3 Content
– Theory: structure, principles, primary connection; load switches, fuses, arresters, CTs; protection units, power meters, temperature/humidity controllers; five-prevention principles and safety rules; power safety work regulations for HV work.
– Hands-on: local manual open/close and earthing; electric open/close; local/remote switching; protection unit menus, parameters and event queries; meter reading; de-energized maintenance procedure (isolate, test, earth, tag).
– O&M and faults: inspection content/cycles; maintenance precautions; alarm interpretation and fault analysis; simple fault handling; emergency procedures and reporting.
12.4 Method and Schedule
One-day on-site training (half theory, half hands-on) with manuals and courseware in paper and electronic form; flexible scheduling.
12.5 Assessment
Theory written test + practical examination; certificate on passing; free retraining until qualified.

13. Anonymous Typical Project Scenarios
*All scenarios below are anonymous, generalized examples for reference. They do not refer to any real customer, project address or testimonial.*
Scenario A — Industrial park 10kV ring supply project.
A provincial economic development zone’s new standard factory park (200,000 m²) required a 10kV outdoor ring distribution system with dual-source supply and distribution automation. Configuration: 8 × KITOZER outdoor RMU cabinets (2-in-4-out), gas-insulated three-position load switches, 630 A / 20 kA, per-circuit protection and meters, fiber-optic communication to the park automation system, 304 stainless IP54 shells with intelligent anti-condensation. Outcome: commissioned in 2023 with 99.99% supply reliability; fault isolation reduced from hours to minutes; significantly lower O&M workload.

Scenario B — Old-town distribution network retrofit.
An old urban district’s aging pole-mounted switches (low protection, high failure rate) were replaced with 12 outdoor RMU cabinets (1-in-3-out, 630 A, 304 stainless, intelligent boundary switches with automatic fault isolation, temperature/humidity control for winter condensation). Outcome: withstood summer storms and winter cold without water ingress or condensation; failure rate down 90%; outages and outage duration greatly reduced.

Scenario C — Tier III data center external-line ring project.
A Tier III data center required ring-supply architecture with dual-source redundancy and fast fault switching. Configuration: 4 HV ring cabinets forming a ring, load switch-fuse incoming protection, high-precision protection with fast fault clearing, dual redundant communication integrated with the DCIM, fully sealed gas-insulated design. Outcome: zero faults since commissioning, 100% accurate protection actions, switching times meeting data center requirements.
14. SEO Optimization
14.1 Keyword Classification
– Core keywords: 10kV ring main unit, outdoor RMU cabinet, HV ring main unit, RMU manufacturer.
– Long-tail keywords: 10kV outdoor floor-mounted RMU, gas-insulated RMU manufacturer, stainless outdoor RMU, intelligent RMU price, 2-in-4-out RMU, custom outdoor RMU, HV RMU technical parameters, RMU configuration list.
– Industry keywords: 10kV distribution RMU, outdoor HV ring cabinet, pole-mounted RMU, ring-type cable branch box, distribution automation RMU, three-position load switch RMU, anti-condensation RMU, outdoor switching station.
– Brand keywords: KITOZER RMU, Lain RMU, Guangzhou Lain ring main unit.
– Related/search keywords: difference between RMU cabinet and ring main unit, function of RMU, RMU protection class, RMU five-prevention interlocking, RMU installation plan, RMU O&M, RMU price, RMU manufacturer ranking.
14.2 SEO Tags
– SEO Title: 10kV Outdoor Ring Main Unit — HV Intelligent RMU Cabinet Manufacturer | Custom 2-in-4-out | Lain
– Meta Keywords: 10kV RMU, outdoor ring main unit, HV ring cabinet, intelligent RMU, 2-in-4-out RMU, gas-insulated ring cabinet, RMU manufacturer, Guangzhou Lain
– Meta Description: Guangzhou Lain manufactures 10kV outdoor ring main units and HV intelligent ring cabinets — gas-insulated three-position switches, 304 stainless IP54 shells, microprocessor protection and remote communication; source factory with custom options and free design consultation.
– H1: 10kV Outdoor Intelligent Ring Main Unit Technical Design Solution
– H2 structure: Project Overview | User Requirements | Design Description | Equipment Configuration | Technical Specifications | Solution Advantages | Technical Q&A | Construction Plan | After-Sales Service
14.3 Internal Link Anchors
– Core anchors: outdoor ring main unit, 10kV ring cabinet, HV RMU.
– Long-tail anchors: outdoor floor-mounted RMU, gas-insulated three-position ring cabinet, intelligent distribution RMU.
– Related anchors: microprocessor protection unit, ZnO surge arrester, outdoor distribution cabinet, distribution automation system.