ToggleKITOZER KTR-DPS1 Surge Protective Device (DC 48V Power SPD)
Brand: KITOZER Series: KTR-DPS1 Category: Power System 2 / Lightning Protection
DC SPD48V surge protectorsurge protective devicetelecom powerclass C/D
1. Overview
KITOZER KTR-DPS1 is a DC power surge protective device (SPD) designed for data center -48V DC power systems. The DC 48V system comes from high-frequency switching rectifiers outputting -48V (nominally -53.5 V float), powering telecom, transmission and DC server loads. Though not directly tied to mains, DC cables run long distances from the power room; lightning-induced surges and switching transients still ride the conductors and destroy expensive boards. The SPD is a shunt “discharge path” across the DC bus — high impedance at rest, instantly clamping voltage to a safe value and diverting surge current to earth when a surge hits.
KTR-DPS1 uses a pluggable modular design on DIN rail: each module has a status window (green = OK, red = failed) and can be hot-swapped without powering down. Built to IEC 61643-21 and YD/T, Uc ≥65 V (covering -48V float at -53.5 V with margin), In = 10~20 kA (8/20µs), Imax = 40 kA. It is a Class C (Class D) device installed on the DC distribution bus as final-stage fine protection at the switching-rectifier output.
AC and DC SPDs are not interchangeable: an AC SPD rated for 220/380 V has too-high Uc and won’t conduct at 48 V; a DC SPD’s arc-extinguishing is designed for DC (which has no zero-crossing, making arc suppression hard), so an AC SPD on a DC circuit may follow-current and catch fire. KTR-DPS1 is purpose-built for -48V DC with DC arc extinction. DC distribution uses three-stage protection: upstream AC Class C → DC bus Class C (KTR-DPS1) → equipment input Class D (surge terminal).
2. Key Features
DC-specific
- Uc ≥65 V, for -48V float at -53.5 V.
- DC arc-extinguishing design, no follow-current fire risk.
- Response time ≤25 ns, fast clamping.
Pluggable module
- DIN rail mount, hot-swappable modules.
- Status window: green OK / red replace.
- Form-C dry contact remote alarm to DCIM.
Discharge ratings
- In (8/20µs) = 10/20 kA selectable.
- Imax = 40 kA.
- Voltage protection level Up ≤1.5 kV.
Wiring & structure
- Shunt across DC bus (+/−/earth).
- Terminals 6~25 mm², crimp or busbar.
- Thermal disconnector auto-disconnects on overheat.
3. Specifications
| Item | KTR-DPS1-10 | KTR-DPS1-20 | KTR-DPS1-40 |
|---|---|---|---|
| Protection class | Class D (fine) | Class C (medium) | Class C (medium) |
| Rated voltage Uc | 65 V DC | 65 V DC | 75 V DC |
| In (8/20µs) | 10 kA | 20 kA | 20 kA |
| Imax | 20 kA | 40 kA | 40 kA |
| Protection level Up | ≤1.2 kV | ≤1.5 kV | ≤1.8 kV |
| Response time | ≤25 ns | ≤25 ns | ≤25 ns |
| Mount | DIN rail | DIN rail | DIN rail |
| Remote contact | Optional | Standard | Standard |
| Indicator | Window | Window + remote | Window + remote |
4. Reference Prices
KTR-DPS1-10 Class D DC48V SPD module (10 kA, DIN rail, window indicator): Reference USD 11~28 / pc (ref. CNY 80~200 at ~7.2)
KTR-DPS1-20/40 Class C DC48V SPD (20~40 kA, remote contact, pluggable): Reference USD 35~97 / pc (ref. CNY 250~700 at ~7.2)
Reference only; final quote depends on discharge current, class, remote contact and quantity. DC cabinet and earth bar excluded; replacement modules priced separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Telecom room -48V DC distribution bus SPD.
- Base station and edge room rectifier output protection.
- DC UPS and HVDC output protection.
- Transmission and server DC input Class D protection.
- Outdoor base station feeder/conductors induced-surge protection.
6. Installation & Maintenance
Installation
- Shunt SPD across DC bus +/− and earth bar.
- Keep earth lead short and straight, ≤0.5 m (lead inductance affects clamping).
- Clip on DIN rail, crimp terminals firmly.
- Wire remote contact to DCIM digital input.
- After install, test +/− to earth insulation.
- Record install date and model (SPD has service life).
Maintenance
- Check status window (green OK, red replace).
- After thunderstorm season, check if SPD has conducted.
- Replace failed modules on remote alarm.
- Evaluate replacement every 3~5 years (2~3 years in high-lightning areas).
- De-energize or hot-swap per design when replacing.
7. FAQ
- Q: Does the -48V DC system need lightning protection? It’s not on mains.
A: Yes. DC cables run long distances; lightning-induced surges ride the conductors, and rectifier/load switching creates transients. SPD is standard for DC systems. - Q: Can I use an AC SPD instead?
A: No. An AC SPD rated at 220/380 V has too-high Uc and won’t conduct at 48 V; and DC has no zero-crossing, so AC arc-extinguishing is insufficient and follow-current may ignite. Use a DC-specific SPD. - Q: SPD shows red but equipment still runs — must I replace?
A: Yes. Red means the SPD has failed (disconnector opened); the circuit is now unprotected. Normal supply is unaffected (SPD is high impedance at rest), but protection is gone — replace the module immediately. - Q: Why must the earth lead be short?
A: Tens of kA through the lead develops extra voltage across lead inductance (~1 µH/m); a longer lead means higher residual voltage at the equipment. Keep ≤0.5 m, shorter is better.
8. Trend & Selection
DC power evolves from “-48V telecom” to “HVDC 240 V/336 V”, and SPDs must scale from 48 V to HVDC. The trend is smart SPDs with online monitoring (leakage current, discharge count, temperature) linked to DCIM. Select Uc ≥65 V DC-specific for -48V; choose In by grounding class (usually Class C 20 kA, Class D 10 kA); pluggable modules (no-power-down replacement); remote contact mandatory to DCIM; short straight earth leads; coordinate three stages (C bleeds bulk, D fine-clamps) for energy coordination.
9. Delivery & Service
KITOZER provides DC SPD selection: based on DC voltage (-48V/HVDC), grounding type, lightning protection class and number of circuits, we configure SPD class, discharge current and remote-alarm scheme. We produce the SPD configuration drawing (per-busbar SPD position, earth leads, remote wiring). Bundled with DC distribution cabinets, rectifiers and DCIM. Delivery includes SPD module, base, DIN rail, terminals and alarm signal wires. Warranty covers failed-module replacement guidance.
10. Additional Notes
The most common pitfall is “substituting an AC SPD”. Buyers looking for cheap options or wrong models install an AC 220 V SPD on the -48V bus. An AC SPD with Uc ~275 V never conducts at 48 V — installed but useless; the next surge still destroys equipment. Acceptance must check the nameplate for Uc and the “DC” marking.
Another pitfall: “earth lead routed in a loop”. The SPD mounts on the cabinet door, and the earth lead loops from the door to the bottom earth bar — 2~3 m long. Surge current through the lead’s inductance doubles the clamping voltage, rendering the SPD useless. The earth lead must run short and straight from the SPD to the nearest earth bar, ≤0.5 m.
Selection summary: DC-specific Uc ≥65 V; Class C 20 kA / Class D 10 kA; pluggable modules; remote contact to DCIM; earth lead short ≤0.5 m; three-stage energy coordination. The SPD is the power system’s lightning arrestor — dormant in normal times, instantly conducting on surge to protect thousands of expensive boards downstream.