KITOZER KTR-DPS1 Surge Protective Device (DC 48V Power SPD)

KITOZER KTR-DPS1 Surge Protective Device (DC 48V Power SPD)

Brand: KITOZER Series: KTR-DPS1 Category: Power System 2 / Lightning Protection

DC SPD48V surge protectorsurge protective devicetelecom powerclass C/D

1. Overview

KITOZER KTR-DPS1 is a DC power surge protective device (SPD) designed for data center -48V DC power systems. The DC 48V system comes from high-frequency switching rectifiers outputting -48V (nominally -53.5 V float), powering telecom, transmission and DC server loads. Though not directly tied to mains, DC cables run long distances from the power room; lightning-induced surges and switching transients still ride the conductors and destroy expensive boards. The SPD is a shunt “discharge path” across the DC bus — high impedance at rest, instantly clamping voltage to a safe value and diverting surge current to earth when a surge hits.

KTR-DPS1 uses a pluggable modular design on DIN rail: each module has a status window (green = OK, red = failed) and can be hot-swapped without powering down. Built to IEC 61643-21 and YD/T, Uc ≥65 V (covering -48V float at -53.5 V with margin), In = 10~20 kA (8/20µs), Imax = 40 kA. It is a Class C (Class D) device installed on the DC distribution bus as final-stage fine protection at the switching-rectifier output.

AC and DC SPDs are not interchangeable: an AC SPD rated for 220/380 V has too-high Uc and won’t conduct at 48 V; a DC SPD’s arc-extinguishing is designed for DC (which has no zero-crossing, making arc suppression hard), so an AC SPD on a DC circuit may follow-current and catch fire. KTR-DPS1 is purpose-built for -48V DC with DC arc extinction. DC distribution uses three-stage protection: upstream AC Class C → DC bus Class C (KTR-DPS1) → equipment input Class D (surge terminal).

2. Key Features

DC-specific

  • Uc ≥65 V, for -48V float at -53.5 V.
  • DC arc-extinguishing design, no follow-current fire risk.
  • Response time ≤25 ns, fast clamping.

Pluggable module

  • DIN rail mount, hot-swappable modules.
  • Status window: green OK / red replace.
  • Form-C dry contact remote alarm to DCIM.

Discharge ratings

  • In (8/20µs) = 10/20 kA selectable.
  • Imax = 40 kA.
  • Voltage protection level Up ≤1.5 kV.

Wiring & structure

  • Shunt across DC bus (+/−/earth).
  • Terminals 6~25 mm², crimp or busbar.
  • Thermal disconnector auto-disconnects on overheat.

3. Specifications

Item KTR-DPS1-10 KTR-DPS1-20 KTR-DPS1-40
Protection class Class D (fine) Class C (medium) Class C (medium)
Rated voltage Uc 65 V DC 65 V DC 75 V DC
In (8/20µs) 10 kA 20 kA 20 kA
Imax 20 kA 40 kA 40 kA
Protection level Up ≤1.2 kV ≤1.5 kV ≤1.8 kV
Response time ≤25 ns ≤25 ns ≤25 ns
Mount DIN rail DIN rail DIN rail
Remote contact Optional Standard Standard
Indicator Window Window + remote Window + remote

4. Reference Prices

KTR-DPS1-10 Class D DC48V SPD module (10 kA, DIN rail, window indicator): Reference USD 11~28 / pc (ref. CNY 80~200 at ~7.2)

KTR-DPS1-20/40 Class C DC48V SPD (20~40 kA, remote contact, pluggable): Reference USD 35~97 / pc (ref. CNY 250~700 at ~7.2)

Reference only; final quote depends on discharge current, class, remote contact and quantity. DC cabinet and earth bar excluded; replacement modules priced separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Telecom room -48V DC distribution bus SPD.
  • Base station and edge room rectifier output protection.
  • DC UPS and HVDC output protection.
  • Transmission and server DC input Class D protection.
  • Outdoor base station feeder/conductors induced-surge protection.

6. Installation & Maintenance

Installation

  • Shunt SPD across DC bus +/− and earth bar.
  • Keep earth lead short and straight, ≤0.5 m (lead inductance affects clamping).
  • Clip on DIN rail, crimp terminals firmly.
  • Wire remote contact to DCIM digital input.
  • After install, test +/− to earth insulation.
  • Record install date and model (SPD has service life).

Maintenance

  • Check status window (green OK, red replace).
  • After thunderstorm season, check if SPD has conducted.
  • Replace failed modules on remote alarm.
  • Evaluate replacement every 3~5 years (2~3 years in high-lightning areas).
  • De-energize or hot-swap per design when replacing.

7. FAQ

  • Q: Does the -48V DC system need lightning protection? It’s not on mains.
    A: Yes. DC cables run long distances; lightning-induced surges ride the conductors, and rectifier/load switching creates transients. SPD is standard for DC systems.
  • Q: Can I use an AC SPD instead?
    A: No. An AC SPD rated at 220/380 V has too-high Uc and won’t conduct at 48 V; and DC has no zero-crossing, so AC arc-extinguishing is insufficient and follow-current may ignite. Use a DC-specific SPD.
  • Q: SPD shows red but equipment still runs — must I replace?
    A: Yes. Red means the SPD has failed (disconnector opened); the circuit is now unprotected. Normal supply is unaffected (SPD is high impedance at rest), but protection is gone — replace the module immediately.
  • Q: Why must the earth lead be short?
    A: Tens of kA through the lead develops extra voltage across lead inductance (~1 µH/m); a longer lead means higher residual voltage at the equipment. Keep ≤0.5 m, shorter is better.

8. Trend & Selection

DC power evolves from “-48V telecom” to “HVDC 240 V/336 V”, and SPDs must scale from 48 V to HVDC. The trend is smart SPDs with online monitoring (leakage current, discharge count, temperature) linked to DCIM. Select Uc ≥65 V DC-specific for -48V; choose In by grounding class (usually Class C 20 kA, Class D 10 kA); pluggable modules (no-power-down replacement); remote contact mandatory to DCIM; short straight earth leads; coordinate three stages (C bleeds bulk, D fine-clamps) for energy coordination.

9. Delivery & Service

KITOZER provides DC SPD selection: based on DC voltage (-48V/HVDC), grounding type, lightning protection class and number of circuits, we configure SPD class, discharge current and remote-alarm scheme. We produce the SPD configuration drawing (per-busbar SPD position, earth leads, remote wiring). Bundled with DC distribution cabinets, rectifiers and DCIM. Delivery includes SPD module, base, DIN rail, terminals and alarm signal wires. Warranty covers failed-module replacement guidance.

10. Additional Notes

The most common pitfall is “substituting an AC SPD”. Buyers looking for cheap options or wrong models install an AC 220 V SPD on the -48V bus. An AC SPD with Uc ~275 V never conducts at 48 V — installed but useless; the next surge still destroys equipment. Acceptance must check the nameplate for Uc and the “DC” marking.

Another pitfall: “earth lead routed in a loop”. The SPD mounts on the cabinet door, and the earth lead loops from the door to the bottom earth bar — 2~3 m long. Surge current through the lead’s inductance doubles the clamping voltage, rendering the SPD useless. The earth lead must run short and straight from the SPD to the nearest earth bar, ≤0.5 m.

Selection summary: DC-specific Uc ≥65 V; Class C 20 kA / Class D 10 kA; pluggable modules; remote contact to DCIM; earth lead short ≤0.5 m; three-stage energy coordination. The SPD is the power system’s lightning arrestor — dormant in normal times, instantly conducting on surge to protect thousands of expensive boards downstream.