ToggleKITOZER KTR-WC7 8-Zone Locating Leak Controller
Brand: KITOZER Series: KTR-WC7 Category: Environmental Monitoring 2 / Leak Detection
leak controller8-zone locatingsensing cableDCIMdata center
1. Overview
KITOZER KTR-WC7 is an 8-zone locating leak controller, the core device for detecting AC condensate leaks and under-floor water-pipe seepage in data center environmental monitoring. Water leaks are among the most common data hall disasters: a disconnected AC condensate fitting, damaged chilled-water insulation, or a blocked fresh-air drain can flood the raised floor. By the time staff see water on the floor, damage is done. KTR-WC7 works with locating sensing cable routed around AC units, along pipes and under cabinets: when the cable contacts water, the controller alarms and the LCD shows the exact meter position on the cable. Eight independent zones pinpoint the leak, eliminating hours of floor-panel removal.
Compared with non-locating detection (alarm without location), the value of locating is fast response. An 800 m² hall may have 100+ meters of sensing cable; non-locating alarms force staff to open floor panels section by section for hours. Locating shows “Zone 3, 12.5 m” — go straight to the spot. KTR-WC7 supports 8 zones, each up to 100 m of cable (total 800 m). The cable uses conductive polymer principle: steady resistance when dry; water changes conductivity; the controller measures the resistance gradient to calculate distance.
KTR-WC7 offers flexible outputs: RS485 (Modbus RTU) to the environmental host, relay dry contacts to audible/visual alarms or fire integration, and optional RJ45 SNMP to the network platform. LCD shows all eight zone statuses and leak position. Wall or rack mount, near AC units or conduit runs.
2. Key Features
8-zone locating
- 8 independent zones, 100 m cable each.
- LCD shows leak position (0.1 m resolution).
- Locating accuracy ≤±1 m.
Conductive polymer cable
- Detects condensate, chilled water, electrolyte.
- No false alarms from dry dust.
- Reusable: dries and recovers automatically.
Multiple outputs
- RS485 Modbus RTU to DCIM host.
- 4 relay dry contacts (alarm/fault).
- Optional RJ45 SNMP module.
Local display & alarm
- LCD shows 8-zone status.
- Built-in audible buzzer.
- Wall / rack dual mount.
3. Specifications
| Item | KTR-WC7 |
|---|---|
| Zones | 8 |
| Cable per zone | ≤100 m |
| Locating accuracy | ≤±1 m |
| Cable type | Conductive polymer locating cable |
| Output | RS485 Modbus RTU |
| Relay | 4 dry contacts (30V/1A) |
| Network | RJ45 SNMP (optional) |
| Display | LCD |
| Power | DC12V / 220VAC optional |
| Operating temp | -10~50℃ |
| Mount | Wall / 19-inch rack |
4. Reference Prices
KTR-WC7 8-zone locating controller (RS485 + relay, LCD, cable not included): Reference USD 111~208 / unit (ref. CNY 800~1,500 at ~7.2)
KTR-WC7 complete kit (controller + 100 m locating cable + mounts): Reference USD 167~306 / set (ref. CNY 1,200~2,200 at ~7.2)
Reference only; priced by zones, cable length and SNMP option. DCIM host excluded. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- AC condensate leaks around precision units.
- Under-floor chilled/water pipe seepage.
- Battery room electrolyte spill detection.
- Cabinet base and UPS room leak warning.
- Campus water-system leakage monitoring.
6. Installation & Maintenance
Installation
- Mount controller (wall or rack).
- Route cable around AC units and along pipes.
- Clip cable to floor/wall surface.
- Terminate far end with end-of-line resistor.
- Connect cable near end to corresponding zone terminals.
- Wire RS485 to DCIM host, relays to audible alarm.
- Test with water; verify displayed position.
Maintenance
- Monthly test with damp cloth.
- Check cable for rodent/foot damage.
- Cable recovers automatically after drying.
- Clean terminals annually.
- Cut and replace damaged cable sections.
7. FAQ
- Q: Locating vs non-locating?
A: Small rooms (one AC, a few meters of pipe) use non-locating; large halls with multiple ACs and complex piping use locating to go straight to the leak. - Q: Does dirt affect the cable?
A: Dust and dry grime do not trigger alarms; only conductive liquids (water, electrolyte) do. Wipe clean for reuse. - Q: How to connect RS485 to DCIM?
A: Daisy-chain A/B to the host 485 port, set zone address, read status via Modbus. - Q: What after a leak alarm?
A: Use the LCD zone and position to find the spot, shut the valve, dry the cable, repair the leak. The cable recovers automatically when dry.
8. Trend & Selection
Environmental monitoring moves from “after-the-fact” to “early warning”; leak detection is mandatory. Trend is locating cable + wireless transmission + AI prediction. Select: 8-zone locating for large halls and multiple ACs; route cable along ACs and pipes; end-of-line resistor per zone; RS485 to DCIM; relays to audible alarm; annual simulated test.
9. Delivery & Service
KITOZER supplies leak detection systems: based on the floor plan and AC/pipe layout, we plan cable routing and zone configuration, supply the 8-zone controller and cable, and produce the detection system drawing. Delivery includes controller, cable, end-of-line resistors and clips. Warranty covers commissioning and position calibration.
10. Additional Notes
The most common install error: “cable floating off the floor.” Loosely hung on a bracket, the water spreads under the floor while the cable sits centimeters above — no alarm. Cable must lie flat on the floor or wall so water contacts it.
Another pitfall: “missing end-of-line resistor.” Locating cables require the matching EOL resistor at the far end; the controller relies on its voltage divider to calculate position. Without it, the whole zone alarms or position calculation fails.
Selection summary: 8-zone locating; 100 m per zone; lay flat; EOL resistor mandatory; RS485 to DCIM; annual test. The leak controller is the water sentry of the data hall — it alarms the moment water appears, before servers get soaked.