KITOZER
KITOZER

KITOZER KTR-PSB2 Wall-mounted 3-Phase 40KA SPD

KITOZER KTR-PSB2 Wall-mounted 3-Phase 40KA SPD

Brand: KITOZER Series: KTR-PSB2 Category: Power Distribution / Surge Protection

SPD3-phase surge protector40KAwall mountpower surge protectionKTR-PSB2

[Product image: KITOZER KTR-PSB2 wall-mounted 3-phase SPD with status indicator window]

1. Overview

KITOZER KTR-PSB2 is a wall-mounted 3-phase surge protective device (SPD) installed on the feeder side of the data-center distribution panel, protecting all downstream electronics from lightning surges and switching transients. A lightning strike on the external supply or nearby ground grid injects tens of thousands of volts of transient overvoltage along the power line — lasting microseconds but high enough to destroy switch power supplies, motherboard chips and UPS rectifiers. The SPD clamps L-PE voltage to a level the equipment can survive (residual voltage) and diverts surge current to earth.

KTR-PSB2 is a wall-mounted integrated unit containing 3P+N+PE modules: nominal discharge current In 20 kA (8/20μs), max Imax 40 kA. Full 5-wire protection (L1/L2/L3/N/PE), one MOV per phase, and a spark gap between N and PE. Each module has a status window: green = OK, red = replace. A remote dry contact reports SPD failure to the DCIM host. Wall-mount next to the panel, or DIN-rail inside the panel.

Compared with rack-mounted SPDs, the wall version fits panels without spare rail slots, or when adding a standalone stage of protection outside the panel. KTR-PSB2 has an integrated disconnector (Uc 385 V): when an MOV fails short, it disconnects from the line to prevent fire. Response time ≤25 ns, voltage protection level Up ≤1.5 kV. Suits TT/TN-S/TN-C-S systems, 50/60 Hz.

2. Key Features

3-phase 40 kA full protection

  • 3P+N+PE 5-wire.
  • In 20 kA / Imax 40 kA (8/20μs).
  • Up ≤1.5 kV.

Status + remote alarm

  • Green/red window at a glance.
  • Dry contact to DCIM.
  • Field-replaceable modules.

Safe disconnector

  • Auto-disconnect on MOV short.
  • Fire prevention.
  • Uc 385 V continuous.

Wall / DIN dual mount

  • Wall or 35 mm rail.
  • ≤25 ns response.

3. Specifications

Item KTR-PSB2
Poles 3P+N+PE
Max continuous Uc 385 V AC
Nominal In 20 kA (8/20μs)
Max Imax 40 kA (8/20μs)
Voltage protection Up ≤1.5 kV
Response time ≤25 ns
Earthing TT / TN-S / TN-C-S
Remote alarm 1 dry contact (250V/0.5A)
Mount Wall / 35 mm rail
Operating temp -40~85℃
Size ~90×80×65 mm/module

4. Reference Prices

KTR-PSB2 wall 3-phase 40 kA SPD (3P+N, remote contact): Reference USD 63~111 / unit (ref. CNY 450~800 at ~7.2)

KTR-PSB2 complete (SPD + upstream breaker + terminals + wall box): Reference USD 97~167 / set (ref. CNY 700~1,200 at ~7.2)

Reference only; priced by poles, kA rating and enclosure. Ground bus and cable not included. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Main distribution panel primary protection.
  • UPS input secondary surge protection.
  • Row/PDU feeder protection.
  • Overhead feed and rooftop equipment.
  • Telecom shelters and outdoor cabinets.

6. Installation & Maintenance

Installation

  • De-energize; choose feeder side of panel.
  • Wall-box or DIN-rail mount.
  • Series upstream backup breaker per coordination study.
  • Line L1/L2/L3/N to feed; PE to ground bus.
  • Ground lead short and fat (≥6 mm²).
  • Wire dry contact to DCIM DI port.
  • Energize; confirm green window.
  • Record residual voltage on surge test.

Maintenance

  • Check indicator window monthly.
  • Red window → replace module immediately.
  • Review remote alarms after thunderstorms.
  • Test earth resistance annually.
  • Replace modules every 5 years.

7. FAQ

  • Q: Is 40 kA enough for a data hall?
    A: For a secondary feeder-side SPD, In 20 kA/Imax 40 kA is adequate. Building main needs 100 kA Class I; row/UPS tertiary uses 10 kA Class III. Multi-stage coordination is best.
  • Q: Why the upstream breaker?
    A: MOVs fail short over time; without a backup breaker this causes a line-to-earth short and fire. The breaker trips to isolate the failed SPD.
  • Q: Longer ground lead better?
    A: No — shorter is better, ≤0.5 m, ≥6 mm². Long leads add inductance and raise residual voltage during surges.
  • Q: Green window means never stressed?
    A: Green means still functional, but it has absorbed surges and degraded. In lightning-prone regions, proactively replace every 3~5 years.

8. Trend & Selection

Power protection moves from single-point to multi-stage coordination — main panel Class I, UPS Class II, row cabinet Class III, with decreasing kA and residual voltage. Select: 40 kA wall unit at feeder; mandatory upstream breaker; short fat ground; remote contact to DCIM; indicator in inspection route; check after storms. The SPD is the data hall’s lightning sentinel — it absorbs the surge so the downstream equipment survives.

9. Delivery & Service

KITOZER supplies wall 3-phase SPDs per the power single-line diagram, with backup breakers, terminals and wall enclosure. We provide the surge-protection drawing and ground bonding plan. Warranty covers module replacement and remote-contact commissioning.

10. Additional Notes

The most common mistake: long looped ground lead. Cable-management aesthetics route the SPD ground in a long loop to the bus; lead inductance doubles the residual voltage and negates the SPD. Run the ground straight to the earth bus.

Another pitfall: no backup breaker. To save space, the SPD is bolted directly to the bus; when the MOV fails short, the bus dead-shorts to earth, tripping the main breaker — or worse. Always use the specified SPD backup breaker.

Selection summary: 3P+N; Imax 40 kA; wall/rail; remote contact to DCIM; upstream breaker; short fat ground. The SPD is a consumable — don’t wait for a surge to kill equipment before you replace it.