KITOZER KTR-FB24SC Rack-mount 24-Port SC Fully Loaded Fiber Box

KITOZER KTR-FB24SC Rack-mount 24-Port SC Fully Loaded Fiber Box

Brand: KITOZER Series: KTR-FB24SC Category: Data Center Engineering / Fiber Cabling

fiber box24-port SCrack mountloaded adapterODF unitKTR-FB24SC

[Product image: KITOZER KTR-FB24SC 19-inch rack fiber box, 24 SC ports fully loaded]

1. Overview

KITOZER KTR-FB24SC is a rack-mount 24-port SC fiber distribution box (also called an ODF unit), installed in a 19-inch rack to terminate backbone fiber cables and distribute patch cords. When the 24/48-core backbone cable from the carrier’s fiber distribution frame enters the data hall, each strand must be fusion-spliced to a pigtail and broken out to a standard SC adapter so patch cords can run to switch optical modules. KTR-FB24SC does exactly this: a 2U steel enclosure, cable enters from the rear, pigtails are spliced in the splice tray, and 24 SC adapters on the front face are ready for patch cords.

“Fully loaded” means all 24 SC adapters are pre-installed at shipment — no field snapping. Each front adapter maps to one internal pigtail: a 24-core cable spliced to 24 SC pigtails, one-to-one. The box is folded from 1.2 mm cold-rolled steel, black powder-coated, on a sliding tray that pulls out for rear splicing. Two splice trays (12 cores each) hold the splices; pigtails are routed in loops of ≥30 mm bend radius through the management ring, ending at the front adapters.

KTR-FB24SC is available in single-mode (blue OS2 adapter) or multimode (aqua OM3/OM4) — specify when ordering. The front panel includes cable managers and a label strip for port numbering. Rack ears and cage nuts mount directly to 19-inch square rails. Rear cable entry has a fiber-protection boot to prevent excessive bend.

2. Key Features

24-port SC loaded

  • 24 SC adapters pre-installed.
  • SM blue or MM aqua options.
  • One-to-one pigtail mapping.

Sliding tray

  • Whole front pulls out for work.
  • 2 splice trays (12 cores each).
  • Bend-radius management ring.

Cold-rolled steel

  • 1.2 mm sheet.
  • Black powder coat.
  • 2U, 19-inch.

Labeling & management

  • Front label strip.
  • Cable managers.
  • Rear entry boot.

3. Specifications

Item KTR-FB24SC
Configuration 24-port SC
Height 2U (19-inch rack)
Adapters SC simplex (24 loaded)
Fiber type OS2 SM / OM3/OM4 MM
Splice trays 2 (12 cores each)
Material 1.2 mm cold-rolled steel, black
Cable entry Rear, with boot
Bend radius ≥30 mm
Mount 19-inch square rails
Operating temp -10~60℃

4. Reference Prices

KTR-FB24SC 24-port SC loaded box (SM, adapters + trays): Reference USD 39~63 / unit (ref. CNY 280~450 at ~7.2)

KTR-FB24SC 24-port SC loaded box (OM4 aqua): Reference USD 49~76 / unit (ref. CNY 350~550 at ~7.2)

Reference only; priced by SM/MM and adapter type. Cable and pigtails sold separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Backbone cable termination ODF.
  • Switch optical module patch field.
  • Vertical riser cable distribution.
  • Data hall fiber patch panel.
  • Enterprise/campus aggregation.

6. Installation & Maintenance

Installation

  • Bolt box to rack rails with M6.
  • Backbone enters through rear entry.
  • Anchor strength member to ground stud.
  • Strip jacket; fusion-splice 24 cores to SC pigtails.
  • Place splices in trays, close lids.
  • Route pigtails through managers, ≥30 mm bend.
  • Plug pigtails into front SC adapters.
  • Label each port.
  • Test every core with power meter.

Maintenance

  • Cap unused ports.
  • Clean adapter faces periodically.
  • Check bolts and ground.
  • Replace faded labels.
  • Blow dust inside.

7. FAQ

  • Q: 24 SC vs 24 LC?
    A: LC doubles density (one duplex LC in the SC footprint). Choose LC for new high-density halls; SC if you have existing SC cords/modules.
  • Q: Loaded vs unloaded price?
    A: Loaded costs 100~200 CNY more but saves on-site adapter snapping. Projects should buy loaded.
  • Q: How many splices per tray?
    A: 12 per tray; 2 trays in the 24-port box = 24 cores; 48-port box uses 4.
  • Q: Does the box need grounding?
    A: Yes. Bond the cable’s strength member and armor to the box stud, then to the rack ground bar.

8. Trend & Selection

Fiber boxes trend to higher density (48/96/144 ports) and modular MPO pre-termination, but the 24-port SC loaded box remains the workhorse of small/medium halls — 2U per box, 24-core per cable, simple to install and intuitive to maintain. Select: loaded saves labor; SM/MM per link design; sliding tray for splicing; tray count matches cores; clear port labels. The box is the cable’s terminus — good termination makes patching and maintenance painless.

9. Delivery & Service

KITOZER supplies 24-port SC loaded boxes matched to backbone core count and port plan, with SC adapters, splice trays and mounting hardware. We provide the fiber system drawing and port label list. Warranty covers adapters and enclosure replacement.

10. Additional Notes

The most common mistake: pigtails bent too sharply. Contractors coil pigtails in 180° loops under 10 mm radius; micro-bend loss pushes the link over budget. Route pigtails through managers at ≥30 mm bend radius.

Another pitfall: unsecured strength member. Cable enters, jacket stripped, but the strength member left floating — a tug pulls the whole cable back and breaks the splices. Clamp the strength member to the box stud and leave 1~2 m service slack.

Selection summary: 2U 24-port SC loaded; SM/MM as needed; sliding tray; 2 splice trays; ≥30 mm bend; grounded strength member. The box looks like a tin can, but 24 fibers inside each carry a link — termination cannot be sloppy.