ToggleKITOZER KTR-B2200D 2V200Ah Deep-Cycle VRLA Battery
Brand: KITOZER Series: KTR-B2200D Category: Power Distribution / Battery Backup
battery2V200Ahdeep cycleVRLAvalve-regulatedKTR-B2200D
1. Overview
KITOZER KTR-B2200D is a 2V200Ah deep-cycle VRLA (valve-regulated lead-acid) battery — the energy core of UPS, DC control and telecom standby systems. VRLA cells are sealed: electrolyte does not flow or spill under normal use; a one-way safety valve on top vents excess internal pressure while keeping outside air out, so cells can be mounted in any orientation without watering.
A 2V cell means each block is rated 2 V; a 48 V system needs 24 cells in series, a 220 V DC panel needs 108. Compared with 12 V blocks, 2 V cells offer larger capacity, lower internal resistance and higher discharge current — better for large UPS and DC panels. 200 Ah means, at the 10-hour rate (20 A down to cutoff), the cell delivers 200 Ah. “Deep-cycle” means it can be repeatedly discharged to 80% DoD without major life loss, suiting sites with frequent outages.
KTR-B2200D uses AGM absorbed-glass-mat separators that hold the electrolyte immobilized; pasted positive plates and Pb-Ca negative grids reduce gassing. Design float life is 12 years at 25℃. Tinned-copper terminals cut contact resistance. ABS flame-retardant case; top safety valve is maintenance-free. Recommended ambient is 20~25℃; every 10℃ rise halves life. Cells are series/parallel-arranged on racks, inter-cell links torqued to spec, and the string end voltage feeds the UPS or DC panel.
2. Key Features
2 V large cell
- 2 V / 200 Ah, low resistance.
- For large UPS and DC panels.
- Series to system voltage.
Deep-cycle
- Frequent 80% DoD OK.
- AGM separator.
- Tolerates frequent outages.
Sealed VRLA
- No spill, no watering.
- One-way safety valve.
- Any-orientation mount.
Long life
- 12-year float at 25℃.
- Pb-Ca grids.
- Flame-retardant ABS.
3. Specifications
| Item | KTR-B2200D |
|---|---|
| Rated voltage | 2 V |
| Rated capacity (10hr) | 200 Ah |
| Float design life (25℃) | 12 years |
| Float charge voltage | 2.27~2.30 V/cell |
| Equalize charge | 2.30~2.35 V/cell |
| Discharge cutoff | 1.80 V/cell (10hr) |
| Self-discharge | ≤3%/month (25℃) |
| Terminal | Tinned copper, M8 bolt |
| Operating temp | -15~50℃ (recommend 20~25℃) |
| Case | ABS flame retardant |
| Weight | ~13.5 kg/cell |
4. Reference Prices
KTR-B2200D 2V200Ah VRLA cell (single, with link): Reference USD 53~81 / cell (ref. CNY 380~580 at ~7.2)
KTR-B2200D 48V string (24 cells + rack): Reference USD 1,319~2,014 / string (ref. CNY 9,500~14,500 at ~7.2)
Reference only; priced by cell count, rack, links. Freight by weight. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- [‘
- Data-center UPS standby.
- DC control switchgear.
- Telecom -48V battery plant.
- Off-grid PV storage.
- Emergency lighting and fire backup.
‘, ‘
‘, ‘
‘, ‘
‘, ‘
‘]
6. Installation & Maintenance
Installation
- [‘
- Count cells by system voltage (48V=24).
- Level rack in battery room.
- Place cells by number.
- Torque links (M8 ~12 N·m).
- String ends to UPS/DC panel.
- Measure OCV per cell; spread ≤0.05 V.
- Full-charge before load.
- Leave ventilation gap between cells.
‘, ‘
‘, ‘
‘, ‘
‘, ‘
‘, ‘
‘, ‘
‘, ‘
‘]
Maintenance
- [‘
- Measure per-cell and string voltage monthly.
- Conduct a capacity discharge test yearly.
- Inspect links for corrosion/looseness.
- Keep battery room at 25℃.
- Wipe case dust with a damp cloth.
‘, ‘
‘, ‘
‘, ‘
‘, ‘
‘]
7. FAQ
- [‘
- Q: When to replace?
A: 12-year float at 25℃, but high temp and frequent cycling shorten it. Do a capacity test every 6~8 years; replace when below 80%. - Q: Can I mix new and old cells?
A: No. Different internal resistance/capacity in series means the old cell dies first and reverses, dragging the whole string down. Install and replace the string together. - Q: Why climate-control the battery room?
A: Lead-acid life is temperature-sensitive: every 10℃ rise halves life. Keep the room at 25℃ or the 12-year design life drops to 5~6 years. - Q: How soon to recharge after discharge?
A: Within 24 h. Long under-charging sulfates the plates and permanently loses capacity.
‘, ‘
‘, ‘
‘, ‘
‘]
8. Trend & Selection
[“
UPS batteries evolve from VRLA to Li-ion, but VRLA remains mainstream in traditional halls thanks to safety, maturity and cost. 2 V large cells beat 12 V blocks in high-power applications. Select: size by backup time; cell count by system voltage; keep 25℃; torque links; annual capacity test. The battery string is the UPS’s last line — when mains fails, it decides how long servers survive.
“]
9. Delivery & Service
[‘
KITOZER supplies KTR-B2200D strings sized to UPS backup time and system voltage, with cells, links and rack. We provide the layout drawing and torque spec. Warranty covers sub-capacity cells.
‘]
10. Additional Notes
[‘
A common mistake: not torquing links. Tightening by hand with an ordinary wrench leaves high contact resistance; during high-current discharge the terminals overheat and melt. M8 links need a torque wrench to 12 N·m, re-tightened after 3 months.
‘, ‘
Another pitfall: no AC in the battery room. The hall is air-conditioned but the separate battery room is not; summer temperatures exceed 40℃ and battery life halves. Climate-control the battery room to 25℃.
‘, ‘
Selection summary: 2V200Ah; deep-cycle AGM; 12-year float; series to 48/220 V; 12 N·m links; 25℃ room. Batteries are passive — charging at rest, discharging in crisis; their health decides UPS reliability.
‘]