ToggleKITOZER KTR-TH12 Data Center Temperature & Humidity Sensor (RS485 Modbus)
Brand: KITOZER Series: KTR-TH12 Category: Environmental Monitoring / Telemetry
temp/humidity sensorRS485Modbusdata center monitoringwall-mountKTR-TH12
1. Overview
KITOZER KTR-TH12 is a temperature and humidity sensor that feeds the data-center environmental monitoring system. Servers are sensitive to ambient conditions: high temperature triggers thermal throttling or shutdown; low humidity builds static charge that damages chips; high humidity causes condensation and shorts. ASHRAE recommends 18~27℃ inlet air and 40~60% RH. The monitoring system deploys sensors across the hall, samples data and pushes it to the platform; on threshold breach it links to the AC and triggers alarms.
KTR-TH12 uses a digital industrial-grade SHT sensor element: temperature -20~60℃ at ±0.5℃, humidity 0~100% RH at ±3% RH. It is wall-mount in a white ABS case with a front LED display showing live T and RH. Output is RS485 Modbus-RTU, 9600/19200 bps selectable, up to 32 sensors on one RS485 bus, daisy-chained with shielded twisted pair to the host’s 485 port.
Power is DC 12~24 V wide-range, shared on a two-core shielded cable (power+signal) or fed independently. Field-wiring terminals simplify install. Mount in the cold aisle at rack-inlet height ~1.5 m — the ASHRAE reference point representing server inlet. KTR-TH12 also supports threshold settings: when T or RH crosses limits, the sensor pushes an alarm flag via Modbus; the platform receives it and triggers SMS and audible/visual alerts.
2. Key Features
[‘
Industrial accuracy
- T ±0.5℃, RH ±3%.
- Digital SHT probe, no calibration.
- -20~60℃ range.
‘, ‘
RS485 Modbus-RTU
- Standard Modbus.
- Up to 32 sensors per bus.
- 9600/19200 bps.
‘, ‘
LED local display
- Live T/RH on front.
- At-a-glance walk-round.
- White ABS wall case.
‘, ‘
Wide-range power
- DC 12~24V.
- 2-wire power+signal.
- Threshold alarm push.
‘]
3. Specifications
| Item | KTR-TH12 |
|---|---|
| Temperature range | -20~60℃ |
| Temperature accuracy | ±0.5℃ |
| Humidity range | 0~100%RH |
| Humidity accuracy | ±3%RH |
| Interface | RS485 |
| Protocol | Modbus-RTU |
| Baud rate | 9600 / 19200 |
| Nodes/bus | ≤32 |
| Power | DC 12~24V |
| Display | LED digital |
| Mount | Wall-mount |
| Case | White ABS |
4. Reference Prices
KTR-TH12 T/H sensor (RS485, LED, no adapter): Reference USD 17~31 / unit (ref. CNY 120~220 at ~7.2)
‘, ‘
KTR-TH12 T/H sensor (RS485 + audible alarm, with adapter): Reference USD 31~53 / unit (ref. CNY 220~380 at ~7.2)
‘, ‘
Reference only; priced by adapter/alarm. Bulk (10+) on request. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
‘]
5. Applications
- [‘
- Cold-aisle T/H monitoring.
- IDC environmental monitoring.
- Battery room and power room sensors.
- Lab and archive climate control.
- Unmanned telecom sites.
‘, ‘
‘, ‘
‘, ‘
‘, ‘
‘]
6. Installation & Maintenance
Installation
- [‘
- Pick points per monitoring plan.
- Wall-mount at 1.5 m in cold aisle.
- Avoid AC outlets and heat sources.
- Daisy-chain RS485 sensors.
- Install 120 Ω terminator at bus end.
- Power DC 12~24V.
- Dip-switch a unique address per sensor.
- Host scans and registers devices.
‘, ‘
‘, ‘
‘, ‘
‘, ‘
‘, ‘
‘, ‘
‘, ‘
‘]
Maintenance
- [‘
- Compare against a reference meter quarterly.
- Wipe case dust with dry cloth.
- Inspect RS485 terminals.
- Check terminator yearly.
- Replace probe if drift >±1℃.
‘, ‘
‘, ‘
‘, ‘
‘, ‘
‘]
7. FAQ
- [‘
- Q: How far can RS485 run?
A: Up to 1200 m at 19200 bps. Beyond that, add a 485 repeater or fiber. - Q: Can addresses conflict?
A: Yes — each sensor needs a unique dip-switch address (1~32). Duplicate addresses corrupt the bus. Assign per the site plan and record. - Q: Why is the reading high?
A: If the sensor is near an AC outlet or in direct sun, it reads wrong. Mount in the cold-aisle inlet, away from blast and heat. - Q: Need on-site calibration?
A: SHT probes are factory-calibrated; no field trim needed. If systematic offset appears, correct the zero via Modbus register.
‘, ‘
‘, ‘
‘, ‘
‘]
8. Trend & Selection
[‘
Environmental monitoring extends from wired RS485 to wireless LoRa/NB-IoT, but RS485 Modbus remains mainstream for stability, noise immunity and cost. Sensors evolve from single T/H to multi-parameter (T/H + leak + smoke + current). KTR-TH12 is the basic T/H node — the sensory nerve of the BMS. Select: standard RS485 Modbus; unique addresses; 120 Ω terminator; cold-aisle inlet mount; threshold alarm linkage. T and RH are the most basic, most critical hall parameters — well-placed sensors give the AC tuning its reference.
‘]
9. Delivery & Service
[‘
KITOZER supplies KTR-TH12 sensors per the floor plan and rack layout, with wall bracket and terminals. We provide the point layout and address table. Warranty covers accuracy comparison and defect replacement.
‘]
10. Additional Notes
[‘
A common mistake: mounting in the hot aisle. Installers put the sensor at the rear exhaust, so it reads exhaust temp instead of inlet temp — the AC tunes to the wrong number. Mount in the cold aisle inlet.
‘, ‘
Another pitfall: star-wired RS485. Treating RS485 like Ethernet with home-runs to the host causes reflection and unstable comms. Daisy-chain the bus and add the end terminator.
‘, “
Selection summary: RS485 Modbus-RTU; ±0.5℃/±3%RH; LED; wall at 1.5 m; daisy-chain; unique address. The sensor is the BMS’s eye — correct points make AC group-control and alarms meaningful.
“]