Table of Contents
TogglePreface

This manual is compiled by Guangzhou Lain Intelligent System Development Co., Ltd. (KITOZER brand) in accordance with national and industry standards including the *Technical Specification for Fire Trace Tube Extinguishing Devices* (CECS 345:2013), the *Code for Construction and Acceptance of Gas Fire Extinguishing Systems* (GB 50263), and *Fire Trace Tube Extinguishing Devices* (GA 1167-2014). It applies to the installation, wiring, commissioning, acceptance, maintenance, and servicing of the full range of fire detection tube gas fire suppression systems manufactured by our company.
The fire detection tube gas fire suppression system (also known as the fire trace tube extinguishing device) is a new type of independent automatic fire suppression system that integrates fire detection, automatic activation, and precision extinguishing into one unit. It requires no external power supply or traditional fire alarm controller, and relies on its own stored pressure to achieve round-the-clock fire monitoring and automatic fire suppression. It is particularly suitable for confined spaces, sealed cabinets, and the interior of electrical equipment where traditional fire suppression systems are difficult to cover.
This manual covers the full lifecycle technical essentials of the product, and is intended to provide comprehensive, authoritative, and operable technical guidance for construction personnel, operation and maintenance managers, and fire acceptance inspectors. Please read this manual carefully before commencing construction and strictly follow the standardized procedures to ensure installation quality and system operational reliability.
Chapter 1: Product Introduction

1.1 Product Definition
The fire detection tube gas fire suppression system, formally designated as the fire trace tube temperature-sensing self-activation extinguishing device, is a structurally simple, cost-effective, and highly reliable independent automatic fire suppression system. It consists of a pressure vessel charged with fire extinguishing agent, a container valve, fire detection tubes (fire trace tubes), and associated accessories. It requires no external power supply, no traditional smoke or heat detectors, and no complex control equipment or cabling. Relying on the fire detection tube’s own temperature-sensing rupture characteristics and the system’s internal stored pressure, it achieves automatic fire detection and automatic extinguishing agent release.
The fire detection tube is the core component of the system. It is a high-technology non-metallic composite flexible tubing that combines long-term leak resistance, high flexibility, and precise temperature sensitivity. Within the set temperature range, it softens upon heating and ruptures, serving both to discharge the extinguishing medium and to transmit the fire activation signal.
1.2 Product Development History
Fire detection tube extinguishing technology originated in Europe in the 1990s, initially applied to local fire protection for military equipment and precision instruments. It was introduced to the Chinese market in the early 21st century and, thanks to its flexible installation, no-power-supply requirements, and precise extinguishing advantages, was rapidly promoted and applied in electrical cabinets, telecommunications base stations, data rooms, CNC machine tools, and other fields.
In 2013, the China Association for Engineering Construction Standardization issued the *Technical Specification for Fire Trace Tube Extinguishing Devices* (CECS 345:2013), marking the formal inclusion of fire detection tube extinguishing technology into China’s engineering construction standard system. In 2014, the Ministry of Public Security issued the industry standard *Fire Trace Tube Extinguishing Devices* (GA 1167-2014), providing comprehensive regulations on product classification, technical requirements, test methods, and inspection rules.
Guangzhou Lain Intelligent System Development Co., Ltd., as one of the earliest domestic enterprises engaged in the R&D and production of fire detection tube gas fire suppression systems, has formed a complete product matrix covering both direct-type and indirect-type series, and multiple extinguishing agent types including heptafluoropropane, perfluorohexanone, and carbon dioxide, through years of technical iteration. These products are widely applied in data centers, power grids, rail transit, petrochemical, and other industries.
1.3 Core Product Value
Early suppression, minimal loss: The fire detection tube can be arranged close to potential fire sources, enabling detection and suppression activation at the incipient stage of a fire, minimizing fire damage.
No power required, independent operation: Driven entirely by mechanical and physical principles, it requires no external power supply or alarm host, and remains fully functional during power outages — particularly suitable for unattended scenarios.
Flexible installation, strong adaptability: The fire detection tube can be bent and cut to length, allowing it to reach narrow spaces inside equipment and cable trays, solving the protection blind spots of traditional fire suppression systems.
Precision extinguishing, targeted discharge: The fire detection tube ruptures at the point of highest temperature, and the extinguishing agent is released directly at the fire source, achieving high agent utilization and significantly improved extinguishing efficiency.
Simple maintenance, low cost: The system has a simple structure with few moving parts. Daily maintenance only requires periodic inspection of the pressure gauge and tubing appearance, with operating costs far lower than traditional gas fire suppression systems.
Safe and environmentally friendly, good compatibility: Commonly uses clean gas extinguishing agents such as heptafluoropropane and perfluorohexanone, leaving no residue after discharge and causing no secondary damage to electrical equipment or precision instruments.
1.4 Product Applicable Standards
This product strictly adheres to the following national and industry standards for production and inspection:
- *Fire Trace Tube Extinguishing Devices* — GA 1167-2014
- *Technical Specification for Fire Trace Tube Extinguishing Devices* — CECS 345:2013
- *Code for Design of Gas Fire Extinguishing Systems* — GB 50370
- *Code for Construction and Acceptance of Gas Fire Extinguishing Systems* — GB 50263
- *Safety Technical Regulation for Gas Cylinders* — TSG 23-2021
- *Code for Fire Protection Design of Buildings* — GB 50016-2014 (2018 Edition)
- *Standard for Fire Protection Design of Fossil Fuel Power Plants and Substations* — GB 50229-2019
Chapter 2: Product Composition

The fire detection tube gas fire suppression system consists of six major assemblies: the extinguishing agent storage assembly, the fire detection tube assembly, the discharge tube assembly (indirect type only), the signal feedback assembly, the terminal detection assembly, and installation accessories.
2.1 Extinguishing Agent Storage Assembly
The extinguishing agent storage assembly is the agent storage and power source unit of the system, mainly comprising the following components:
2.1.1 Extinguishing Agent Storage Container
- Manufactured from high-quality seamless steel cylinders subjected to quench and tempering treatment, with anti-corrosion treatment on the inner wall and red warning paint sprayed on the outer wall.
- Design service life of 20 years, with periodic inspection intervals in accordance with the *Safety Technical Regulation for Gas Cylinders*.
- Volume specifications cover 2L, 4L, 6L, 10L, 15L, 20L, 30L, and 40L models, corresponding to different extinguishing agent charge quantities.
- The top is equipped with a standard cylinder neck thread for mounting the container valve; the bottom is fitted with a flat base for upright placement or fixed installation via a dedicated mounting bracket.
2.1.2 Container Valve (Cylinder Head Valve)
The container valve is the core valve controlling the storage and release of the extinguishing agent, integrating multiple functions:
- Charging port: Used for charging the extinguishing agent and pressurizing nitrogen; sealed with a plug after charging.
- Actuation chamber: Connected to the fire detection tube; senses pressure changes in the fire detection tube and triggers valve opening.
- Safety relief device: Built-in safety rupture disc; automatically relieves pressure when the internal cylinder pressure exceeds the safety threshold, preventing overpressure explosion of the cylinder.
- Pressure gauge port: For mounting the container pressure gauge to monitor the stored pressure in the container in real time.
- High-pressure ball valve: Controls the connection between the fire detection tube and the container valve; can be closed during installation, commissioning, and maintenance to allow removal of the fire detection tube without discharging the extinguishing agent.
- Outlet port: Connects to the fire detection tube for direct-type systems, or to the discharge tube for indirect-type systems.
The container valve is precision-machined from brass or stainless steel, with reliable sealing performance and an actuation response time of ≤1 second.
2.1.3 Extinguishing Agent and Pressurizing Gas
- Extinguishing agent: Depending on the product type, clean gas extinguishing agents such as heptafluoropropane (HFC-227ea), perfluorohexanone (FK-5-1-12), or carbon dioxide (CO₂) are charged.
- Pressurizing gas: High-purity nitrogen is used as the pressurizing medium to keep the extinguishing agent in a liquid or high-pressure gaseous state at ambient temperature, ensuring discharge power.
- Charging ratio: Strictly implemented in accordance with national standards; the maximum charging ratio for heptafluoropropane shall not exceed 1.12 kg/L, and for carbon dioxide shall not exceed 0.6 kg/L, ensuring safe use at various ambient temperatures.
2.1.4 Container Pressure Gauge
- Mounted on the side of the container valve for direct visual indication of the pressure inside the extinguishing agent storage container.
- The dial is marked with green, yellow, and red zones: green indicates the normal working pressure range, yellow is the high-pressure warning zone, and red is the low-pressure undercharge zone.
- The pressure gauge accuracy class is not less than 2.5, the range matches the system working pressure, and a damping structure is incorporated to prevent pressure fluctuation from damaging the movement.
2.2 Fire Detection Tube Assembly
The fire detection tube (fire trace tube) is the fire detection and activation trigger component of the system, and in direct-type systems also serves as the extinguishing agent discharge line.
2.2.1 Fire Detection Tube Body
- Material: Extruded from high-performance polymer composite material; the inner layer is a gas-tight layer and the outer layer is a temperature-resistant and abrasion-resistant protective layer.
- Appearance: Standard color is bright red with high visibility.
- Specifications:
- Heptafluoropropane / perfluorohexanone systems: outer diameter 6mm, inner diameter 4mm
- Carbon dioxide systems: outer diameter 8mm, inner diameter 6mm
- Temperature sensitivity: Standard actuation temperature is 170°C ±10°C; different actuation temperature ratings of 110°C, 140°C, and 200°C can be customized according to the operating environment.
- Physical characteristics: Minimum bending radius not less than 80mm; service life at normal working pressure not less than 5 years.
- Delivery condition: Supplied in coils, standard length 100 meters per coil; can be cut to length on site as required.
2.2.2 Fire Detection Tube Specialized Fittings
Fire detection tubes are connected using compression-type (ferrule) specialized fittings to ensure sealing reliability under high pressure:
- Straight coupling: Used for extension connections between two sections of fire detection tube.
- Tee coupling: Used for branch splitting of the fire detection tube; branch outlets should be installed horizontally.
- Terminal fitting: Used for end plugging of the fire detection tube or for connecting a pressure gauge or signal feedback device.
- Wall-penetrating sleeve: Used when the fire detection tube passes through walls or cabinet partitions to prevent abrasion of the tube wall.
- Fitting material: Nickel-plated brass or stainless steel, corrosion-resistant and high-strength.
2.3 Discharge Tube Assembly (Indirect Type Only)
Indirect-type fire detection tube systems require a dedicated extinguishing agent discharge line to deliver the agent to the protected area and release it uniformly through nozzles.
2.3.1 Discharge Tube
- Material: Typically copper tube or stainless steel tube with good corrosion resistance and pressure-bearing capacity.
- Specifications: Common outer diameters of 6mm, 8mm, 10mm, and 12mm, selected based on system flow rate and delivery distance.
- Connection method: Compression-type (ferrule) fittings for convenient installation and reliable sealing.
2.3.2 Nozzles
- Function: To discharge the extinguishing agent uniformly into the protected area at the designed flow rate and atomization angle.
- Types: Classified by protection scenario into total flooding nozzles, local application nozzles, and directional discharge nozzles.
- Material: Precision-machined brass or stainless steel; orifice sizes are flow-calibrated to ensure consistent discharge characteristics.
- Configuration: Each indirect-type system is configured with the corresponding quantity and model of nozzles based on the protected area volume and structure.
2.4 Signal Feedback Assembly
The signal feedback assembly converts the system activation status into electrical signals and uploads them to the fire alarm system or triggers local audible and visual alarms.
2.4.1 Pressure Switch
- Installed in the fire detection tube line; senses the pressure drop signal in the fire detection tube.
- When the fire detection tube ruptures and the pressure drops to the set threshold, the internal contacts actuate and output a switch-type signal.
- Contact rating: DC24V/1A, capable of directly driving an audible/visual alarm or connecting to a fire alarm controller input module.
- Protection rating: IP65, suitable for various indoor and outdoor environments.
2.4.2 Audible and Visual Alarm
- Upon receiving the pressure switch signal, emits dual audible and visual alarm indications.
- Sound pressure level: ≥85dB (measured 1m directly in front).
- Light source: High-brightness red LED strobe.
- Operating voltage: DC24V, powered by the fire alarm power supply or a dedicated backup battery.
2.5 Terminal Detection Assembly
2.5.1 Terminal Pressure Gauge
- Installed at the end of the fire detection tube for direct visual inspection of the pressurization pressure inside the fire detection tube during routine inspections.
- The installation position should be outside the protected area or at a location convenient for personnel observation, allowing the pressure to be read without opening the cabinet door.
- Range is typically 0–2.5MPa, accuracy class 2.5, with pressure indication marker.
2.5.2 Check Valve
- Installed ahead of the terminal pressure gauge and pressure switch to prevent backflow of gas during pressure testing or charging operations.
- Low forward opening pressure and reliable reverse sealing, ensuring system pressure stability.
2.6 Installation Accessories
- Tube clips: For securing the fire detection tube and discharge tube; nylon or stainless steel material; spacing not greater than 500mm (fire detection tube) and 1500mm (discharge tube).
- Cylinder bracket: For securing the extinguishing agent storage container to prevent tipping; fitted with cushioning pads.
- Cable ties, labels, warning signs: For tubing organization, identification, and safety warnings.
- Seals, PTFE tape: For auxiliary sealing of threaded connections.
Chapter 3: Product Classification
Fire detection tube gas fire suppression systems can be classified by multiple dimensions, including discharge method, extinguishing agent type, charge capacity, and application scenario.
3.1 Classification by Extinguishing Agent Discharge Method
3.1.1 Direct-Type Fire Detection Tube Extinguishing Device (Model Prefix: Z)
In direct-type systems, the fire detection tube simultaneously performs four functions: fire detection, system activation, extinguishing agent delivery, and extinguishing agent discharge.
Operating principle: The fire detection tube is connected directly to the container valve outlet, and the tube line is charged with nitrogen at the set pressure. When a fire occurs, the fire detection tube ruptures at the point of highest temperature due to heat, the pressure inside the tube drops instantaneously, triggering the container valve to open. The extinguishing agent flows out of the cylinder, through the fire detection tube, and is discharged directly at the fire source from the rupture opening.
Technical features:
- Simplest structure, fewest components, and most convenient installation.
- Extinguishing agent is discharged with precision from the rupture opening, providing point-to-point extinguishing with extremely high agent utilization.
- Suitable for protecting relatively independent electrical cabinets, control cabinets, and small equipment interiors.
- Maximum single fire detection tube length typically does not exceed 25–35 meters, depending on product specifications.
3.1.2 Indirect-Type Fire Detection Tube Extinguishing Device (Model Prefix: J)
In indirect-type systems, the fire detection tube performs only the fire detection and system activation functions, while the extinguishing agent is discharged through a dedicated discharge line and nozzles.
Operating principle: The fire detection tube is connected to the actuation chamber of the container valve, and the discharge tube is connected to the extinguishing agent outlet of the container valve. When a fire occurs, the fire detection tube ruptures due to heat, the actuation chamber pressure drops, the container valve opens, and the extinguishing agent is delivered through the discharge tube to the protected area, where it is uniformly discharged through the nozzles.
Technical features:
- The extinguishing agent is discharged through a dedicated line and nozzles, enabling total flooding extinguishment for larger protected spaces.
- The fire detection tube is used for detection only, with a smaller diameter and more flexible routing, allowing it to reach inside complex structures.
- Suitable for relatively enclosed small protected areas, cabinet groups, and equipment rooms.
- Maximum protected volume per system can reach tens of cubic meters.
3.2 Classification by Extinguishing Agent Type
3.2.1 Heptafluoropropane Fire Detection Tube Extinguishing Device
Heptafluoropropane (HFC-227ea) is currently the most widely used clean gas extinguishing agent.
Characteristics:
- Colorless, odorless, non-conductive, no secondary contamination.
- High extinguishing efficiency, low extinguishing concentration, typically 7%–10%.
- Good chemical stability, long storage life at ambient temperature.
- No ozone depletion potential (ODP = 0), environmentally compliant.
- Suitable for occupied areas with high safety.
Applicable scenarios: Data rooms, telecommunications base stations, electrical control cabinets, precision instrument rooms, archives, etc.
3.2.2 Perfluorohexanone Fire Detection Tube Extinguishing Device
Perfluorohexanone (FK-5-1-12) is a new generation of environmentally friendly clean extinguishing agent.
Characteristics:
- Liquid at ambient temperature, safer for charging and transportation.
- Extremely low extinguishing concentration, approximately 4%–6%, with extremely high extinguishing efficiency.
- Excellent environmental performance, very low GWP value, short atmospheric lifetime.
- Good insulation properties, no damage to electronic equipment.
- Extremely low toxicity, suitable for occupied areas.
Applicable scenarios: High-end data centers, precision CNC machine tools, medical equipment, museum artifact storage rooms, and other locations with high environmental and safety requirements.
3.2.3 Carbon Dioxide Fire Detection Tube Extinguishing Device
Carbon dioxide (CO₂) is a traditional gas extinguishing agent.
Characteristics:
- Extinguishes fire through suffocation and cooling effects.
- Fully vaporizes after discharge, leaving zero residue.
- Low cost and readily available raw materials.
- Suffocation hazard to humans; must not be used in occupied areas.
- Relatively high extinguishing concentration, typically requiring 30%–50%.
Applicable scenarios: Unattended electrical distribution rooms, cable tunnels, warehouse storage areas, flammable liquid storage zones, etc.
3.3 Classification by Charge Capacity
By the volume of the extinguishing agent storage container and charge quantity, common specifications are as follows:
| Container Volume | Heptafluoropropane Charge | Carbon Dioxide Charge | Typical Application |
|---|---|---|---|
| 2L | 2kg | 1.2kg | Small electrical cabinets, switch cabinets |
| 4L | 4kg | 2.4kg | Standard distribution cabinets, control cabinets |
| 6L | 6kg | 3.6kg | Large power cabinets, UPS cabinets |
| 10L | 10kg | 6kg | Multi-cabinet combinations, small equipment rooms |
| 15L | 15kg | 9kg | Small protected areas, cabinet groups |
| 20L | 20kg | 12kg | Medium protected spaces |
| 30L | 30kg | 18kg | Local application in larger spaces |
| 40L | 40kg | 24kg | Large-area total flooding applications |
3.4 Classification by Actuation Temperature
Based on the static burst temperature of the fire detection tube, multiple ratings are available to suit different ambient temperature conditions:
- 110°C rating: Suitable for precision equipment interiors with low ambient temperature and sensitivity to temperature rise.
- 140°C rating: Suitable for general electrical equipment and conventional environments.
- 170°C rating: Standard rating, suitable for most industrial and civil scenarios; the most commonly used specification.
- 200°C rating: Suitable for high-temperature environment equipment, such as near heating furnaces and high-temperature air ducts.
3.5 Classification by Application Scenario
- Cabinet-specific type: Optimized for standard electrical cabinets and control cabinets; primarily direct-type with simple installation.
- Data room-specific type: Optimized for data cabinets and server racks; commonly uses indirect-type or combinations of multiple direct-type units.
- Power-specific type: Designed for high/low voltage switchgear, transformers, and cable trays; high-temperature resistant and electromagnetic interference resistant.
- Machine tool-specific type: Designed for CNC machine tools and machining centers; oil-resistant and vibration-resistant.
- Vehicle-mounted type: Designed for vehicle engine compartments and battery compartments; vibration-resistant and temperature-change resistant.
Chapter 4: Product List
4.1 Direct-Type Fire Detection Tube Extinguishing Device — Standard Configuration List
Using model TH-Z-Q-6/2.5/170 (direct-type, heptafluoropropane, 6kg, 2.5MPa, 170°C) as an example:
| No. | Component Name | Specification/Model | Unit | Qty | Remarks |
|---|---|---|---|---|---|
| 1 | Extinguishing agent storage cylinder | 6L, seamless steel cylinder | pcs | 1 | Includes base |
| 2 | Container valve | Z-type direct-type cylinder head valve | pcs | 1 | Integrated safety relief, pressure gauge port, ball valve |
| 3 | Heptafluoropropane extinguishing agent | HFC-227ea, high purity | kg | 6 | Includes pressurizing nitrogen |
| 4 | Container pressure gauge | 0–6MPa, class 2.5 | pcs | 1 | For container valve |
| 5 | Fire detection tube | Φ6×4mm, 170°C rating | m | 25 | Standard length, adjustable |
| 6 | Fire detection tube tee coupling | Φ6 compression-type tee | pcs | 1 | Side branch for pressure gauge |
| 7 | Fire detection tube terminal fitting | Φ6 compression-type terminal | pcs | 1 | End plugging |
| 8 | Terminal pressure gauge | 0–2.5MPa, class 2.5 | pcs | 1 | For fire detection tube end |
| 9 | Check valve | Φ6 compression-type | pcs | 1 | Ahead of pressure gauge |
| 10 | Pressure switch | 0.1–1.0MPa adjustable, DC24V | pcs | 1 | Signal feedback |
| 11 | Audible and visual alarm | DC24V, 85dB | pcs | 1 | Local alarm |
| 12 | Cylinder mounting bracket | For 6L cylinder | set | 1 | Includes clamps, bolts |
| 13 | Fire detection tube clip | Φ6 tube clip | pcs | 50 | Approx. 2 pcs per meter |
| 14 | Wall-penetrating sleeve | Φ8 sleeve | pcs | 2 | For passing through cabinet panel |
| 15 | Dedicated installation tools | Tube cutter, wrench | set | 1 | Returnable or optional |
| 16 | Product certificate of conformity | / | copy | 1 | / |
| 17 | User manual | / | copy | 1 | / |
| 18 | Inspection report | / | copy | 1 | Photocopy |
4.2 Indirect-Type Fire Detection Tube Extinguishing Device — Standard Configuration List
Using model TH-J-Q-10/2.5/170 (indirect-type, heptafluoropropane, 10kg, 2.5MPa, 170°C) as an example:
| No. | Component Name | Specification/Model | Unit | Qty | Remarks |
|---|---|---|---|---|---|
| 1 | Extinguishing agent storage cylinder | 10L, seamless steel cylinder | pcs | 1 | Includes base |
| 2 | Container valve | J-type indirect-type cylinder head valve | pcs | 1 | Integrated actuation chamber, safety relief, pressure gauge port |
| 3 | Heptafluoropropane extinguishing agent | HFC-227ea, high purity | kg | 10 | Includes pressurizing nitrogen |
| 4 | Container pressure gauge | 0–6MPa, class 2.5 | pcs | 1 | For container valve |
| 5 | Fire detection tube | Φ6×4mm, 170°C rating | m | 20 | For detection |
| 6 | Discharge tube | Φ8 copper tube | m | 10 | For extinguishing agent delivery |
| 7 | Discharge nozzle | Total flooding type | pcs | 2 | Configured as required |
| 8 | Fire detection tube tee coupling | Φ6 compression-type tee | pcs | 1 | / |
| 9 | Discharge tube tee coupling | Φ8 compression-type tee | pcs | 1 | Line branching |
| 10 | Terminal pressure gauge | 0–2.5MPa, class 2.5 | pcs | 1 | / |
| 11 | Check valve | Φ6 compression-type | pcs | 1 | / |
| 12 | Pressure switch | 0.1–1.0MPa adjustable | pcs | 1 | / |
| 13 | Audible and visual alarm | DC24V, 85dB | pcs | 1 | / |
| 14 | Cylinder mounting bracket | For 10L cylinder | set | 1 | / |
| 15 | Fire detection tube clip | Φ6 tube clip | pcs | 40 | / |
| 16 | Discharge tube clip | Φ8 tube clip | pcs | 10 | / |
| 17 | Wall-penetrating sleeve | Matching specification | pcs | 4 | / |
| 18 | Dedicated installation tools | Tube cutter, tube bender, wrench | set | 1 | / |
| 19 | Product certificate, manual, inspection report | / | set | 1 | / |
4.3 Optional Component List
- Backup power module: DC24V battery pack, providing backup power for the audible/visual alarm and pressure switch; alarm remains functional during power outages.
- Fire alarm input module: For connecting the pressure switch signal to the fire linkage control system.
- Remote monitoring module: Uses IoT module to upload system pressure status and alarm information in real time for cloud-based monitoring.
- Manual activation button: Adds an electromagnetic activation device for manual emergency activation.
- Extended fire detection tube: Fire detection tube exceeding the standard length, billed per meter.
- Extended discharge tube: Discharge tube exceeding the standard length, billed per meter.
- Multiple nozzle specifications: Customized nozzles with different discharge angles and flow rates according to the protected area structure.
- Explosion-proof accessories: Explosion-proof pressure switch and audible/visual alarm, suitable for flammable and explosive hazardous environments.
- High-temperature fire detection tube: 140°C, 200°C, and other actuation temperature ratings.
4.4 Unpacking and Acceptance Key Points
- Upon arrival, unpack promptly and verify each component’s model, specification, and quantity against the packing list.
- Inspect the cylinder exterior to confirm no dents, scratches, or corrosion; coating intact; nameplate legible.
- Check that all port plugs on the container valve are intact, with no looseness or signs of leakage.
- Check that the fire detection tube packaging is intact and the tube material has no crushing, kinking, or scratching.
- Check whether the pressure gauge pointer is in the green zone and whether there has been any pressure loss during transportation.
- Verify that technical documents including the product certificate of conformity, inspection report, and manual are complete.
- If any items are missing, damaged, or do not match the specified model, contact the supplier immediately. Non-conforming products are strictly prohibited from being installed on site.
Chapter 5: Product Principles
5.1 Core Physical Principles
The operation of the fire detection tube gas fire suppression system is based on two core physical principles: the thermal softening rupture characteristics of polymer materials and the pressure-differential-driven valve opening principle.
5.1.1 Temperature-Sensing Rupture Principle of the Fire Detection Tube
The fire detection tube is made of a specially formulated polymer material that exhibits good mechanical strength and elasticity at ambient temperature, capable of withstanding internal pressurization without leakage or deformation. When the ambient temperature rises to the actuation temperature range of the fire detection tube, the molecular chain movement of the polymer material intensifies, the material gradually softens, and its mechanical strength drops sharply.
When the temperature at any point along the fire detection tube reaches the actuation temperature, the tube wall strength at that location can no longer withstand the internal gas pressure. The tube wall ruptures, forming a burst opening, and the high-pressure gas inside rapidly discharges, causing the internal pressure to drop to ambient pressure within an extremely short time.
The burst opening always occurs at the point of highest temperature — that is, at the location of the fire source — which ensures that the extinguishing agent can be precisely discharged at the fire source. The actuation temperature of the fire detection tube exhibits good consistency and repeatability, is unaffected by electromagnetic interference and dust, and represents a purely physical temperature-sensing detection method.
5.1.2 Pressure-Differential Activation Principle of the Container Valve
The container valve internally contains two chambers — the actuation chamber and the extinguishing agent chamber — separated by a piston or diaphragm structure. In the normal stand-by state, the actuation chamber is pressurized through the fire detection tube to the same pressure or a proportional pressure as the extinguishing agent chamber. The forces on both sides of the piston are balanced, the valve remains in the closed position, and the extinguishing agent is sealed within the cylinder.
When the fire detection tube ruptures, the pressure in the actuation chamber is released instantaneously, causing a sudden pressure drop and creating a large pressure differential across the piston. The high pressure on the extinguishing agent chamber side rapidly drives the piston to move, the valve opens, and the extinguishing agent flows out at high speed under its own pressure, entering the fire detection tube (direct type) or discharge tube (indirect type), and is ultimately discharged into the protected area to extinguish the fire.
The entire activation process relies entirely on mechanical structure and pressure differential, requiring no electrical components. The response time is typically less than 1 second, providing extremely high reliability.
5.2 Direct-Type System Operating Sequence
5.2.1 Stand-by State
- The cylinder is charged with extinguishing agent and pressurizing nitrogen at a pressure of 2.5MPa (20°C).
- The container valve is in the closed position; the high-pressure ball valve is in the open position.
- The fire detection tube is filled with nitrogen at a pressure consistent with the cylinder pressure.
- The terminal pressure gauge pointer indicates the normal pressure value, and the system is in the alert state.
5.2.2 Detection and Activation
- A fire occurs in the protected area, and the local temperature rises rapidly.
- When the temperature at the corresponding location of the fire detection tube reaches approximately 170°C, the tube wall softens and ruptures.
- The high-pressure nitrogen inside the fire detection tube rapidly discharges through the burst opening, causing a sudden pressure drop in the tube.
- The actuation chamber pressure of the container valve drops simultaneously, the piston becomes unbalanced, and the valve opens instantaneously.
5.2.3 Extinguishing Process
- The extinguishing agent in the cylinder, driven by the high-pressure nitrogen, enters the fire detection tube through the container valve outlet.
- The extinguishing agent flows at high speed along the fire detection tube and is directionally discharged from the burst opening onto the fire source.
- The extinguishing agent rapidly vaporizes, extinguishing the fire through chemical suppression and physical cooling effects.
- The burst opening of the fire detection tube serves as the agent discharge port, directly facing the fire source for extremely high extinguishing efficiency.
5.2.4 Signal Feedback
- Simultaneously with the pressure drop in the fire detection tube, the pressure switch detects the pressure change and the contacts actuate.
- The audible and visual alarm is energized, emitting audible and visual alarm signals.
- If connected to the fire alarm system, the alarm signal is simultaneously uploaded to the fire alarm controller.
5.3 Indirect-Type System Operating Sequence
5.3.1 Stand-by State
- The cylinder is charged with extinguishing agent and pressurizing nitrogen.
- The actuation chamber of the container valve is pressurized through the fire detection tube; the extinguishing agent chamber outlet is sealed, and the agent is contained.
- The discharge tube and nozzles are unpressurized and open to atmosphere.
- The system is in the alert state, with the fire detection tube continuously monitoring the ambient temperature.
5.3.2 Detection and Activation
- A fire occurs, the ambient temperature rises, and the fire detection tube ruptures at the point of highest temperature.
- The actuation chamber pressure is relieved, the container valve piston actuates, and the main valve opens.
- The extinguishing agent flows out of the cylinder and enters the discharge line.
5.3.3 Extinguishing Process
- The extinguishing agent is delivered through the discharge tube to each nozzle.
- The nozzles atomize the extinguishing agent and discharge it uniformly into the entire protected space.
- The extinguishing agent concentration in the protected area rises rapidly, and the flame is extinguished upon reaching the extinguishing concentration.
- For total flooding applications, a certain soaking (immersion) time must be maintained to ensure thorough extinguishment.
5.3.4 Signal Feedback
- As with the direct-type system, the pressure switch actuates to trigger the audible/visual alarm and signal upload.
- Some indirect-type systems may also have an agent discharge pressure switch installed on the discharge line for dual confirmation of the discharge status.
5.4 Extinguishing Agent Fire Suppression Mechanisms
5.4.1 Heptafluoropropane Suppression Mechanism
Heptafluoropropane primarily extinguishes fire through chemical inhibition, accompanied by a certain degree of physical cooling.
- Heptafluoropropane decomposes upon heating to produce fluorine-containing free radicals, which combine with active free radicals (H·, OH·, etc.) in the combustion reaction, interrupting the chain reaction of combustion.
- The vaporization of heptafluoropropane absorbs a large amount of heat, lowering the flame temperature and the temperature of the protected area.
- Rapid fire extinguishing speed; visible flames are typically extinguished within seconds.
5.4.2 Perfluorohexanone Suppression Mechanism
Perfluorohexanone primarily acts through physical cooling, supplemented by chemical inhibition.
- Perfluorohexanone is liquid at ambient temperature and rapidly vaporizes after discharge, absorbing a large amount of heat and quickly reducing the fire site temperature.
- The active groups produced by its decomposition participate in the combustion reaction, inhibiting the chain reaction.
- Extremely high extinguishing efficiency; it is currently one of the clean gas extinguishing agents with the lowest extinguishing concentration.
5.4.3 Carbon Dioxide Suppression Mechanism
Carbon dioxide extinguishes fire primarily through suffocation and cooling effects.
- Carbon dioxide rapidly vaporizes upon release, diluting the oxygen concentration in the protected area. When the oxygen concentration falls below the critical value required to sustain combustion, the flame is extinguished.
- The expansion of liquid carbon dioxide upon vaporization causes a sharp volume increase and absorbs a large amount of heat, producing a cooling effect.
- Carbon dioxide has good insulation properties and is suitable for electrical fires, but poses a suffocation hazard to humans.
5.5 System Response Time Characteristics
- Detection response time: The time from the generation of the fire source to the rupture of the fire detection tube, depending on the fire source power and the distance to the fire detection tube; typically several seconds to tens of seconds.
- Valve opening time: The time from fire detection tube rupture to full opening of the container valve; ≤1 second.
- Extinguishing agent discharge time: The time from valve opening to the basic completion of agent discharge; typically 10–60 seconds, depending on system specifications.
- Extinguishing time: The time from the start of agent discharge to complete flame extinction; typically ≤20 seconds.
Overall, the fire detection tube system can complete the entire detection-activation-extinguishing process within an extremely short time after a fire occurs, truly achieving “early detection, early suppression” and minimizing fire losses.
Chapter 6: Product Technical Parameters
6.1 Heptafluoropropane Fire Detection Tube Extinguishing Device — Technical Parameters
6.1.1 Direct-Type Series
| Parameter | TH-Z-Q-2/2.5 | TH-Z-Q-3/2.5 | TH-Z-Q-6/2.5 | TH-Z-Q-10/2.5 | TH-Z-Q-15/2.5 |
|---|---|---|---|---|---|
| Extinguishing agent type | Heptafluoropropane | Heptafluoropropane | Heptafluoropropane | Heptafluoropropane | Heptafluoropropane |
| Extinguishing agent charge | 2kg | 3kg | 6kg | 10kg | 15kg |
| Storage container volume | 2L | 3L | 6L | 10L | 15L |
| Nominal working pressure (20°C) | 2.5MPa | 2.5MPa | 2.5MPa | 2.5MPa | 2.5MPa |
| Maximum working pressure (50°C) | 4.2MPa | 4.2MPa | 4.2MPa | 4.2MPa | 4.2MPa |
| Safety relief pressure | 5.6±0.28MPa | 5.6±0.28MPa | 5.6±0.28MPa | 5.6±0.28MPa | 5.6±0.28MPa |
| Fire detection tube specification | Φ6×4mm | Φ6×4mm | Φ6×4mm | Φ6×4mm | Φ6×4mm |
| Fire detection tube actuation temperature | 170±10°C | 170±10°C | 170±10°C | 170±10°C | 170±10°C |
| Maximum fire detection tube length | 15m | 20m | 25m | 30m | 35m |
| Minimum bending radius | ≥80mm | ≥80mm | ≥80mm | ≥80mm | ≥80mm |
| Operating ambient temperature | 0°C~50°C | 0°C~50°C | 0°C~50°C | 0°C~50°C | 0°C~50°C |
| Extinguishing agent discharge time | ≤10s | ≤15s | ≤20s | ≤30s | ≤40s |
| Extinguishing time | ≤20s | ≤20s | ≤20s | ≤20s | ≤20s |
| Activation method | Temperature-sensing automatic | Temperature-sensing automatic | Temperature-sensing automatic | Temperature-sensing automatic | Temperature-sensing automatic |
| Signal output | Passive switch contact | Passive switch contact | Passive switch contact | Passive switch contact | Passive switch contact |
| Container design life | 20 years | 20 years | 20 years | 20 years | 20 years |
| Fire detection tube service life | ≥5 years | ≥5 years | ≥5 years | ≥5 years | ≥5 years |
| Maximum protected volume per cabinet | 1m³ | 2m³ | 4m³ | 7m³ | 10m³ |
6.1.2 Indirect-Type Series
| Parameter | TH-J-Q-6/2.5 | TH-J-Q-10/2.5 | TH-J-Q-20/2.5 | TH-J-Q-30/2.5 | TH-J-Q-40/2.5 |
|---|---|---|---|---|---|
| Extinguishing agent type | Heptafluoropropane | Heptafluoropropane | Heptafluoropropane | Heptafluoropropane | Heptafluoropropane |
| Extinguishing agent charge | 6kg | 10kg | 20kg | 30kg | 40kg |
| Storage container volume | 6L | 10L | 20L | 30L | 40L |
| Nominal working pressure (20°C) | 2.5MPa | 2.5MPa | 2.5MPa | 2.5MPa | 2.5MPa |
| Maximum working pressure (50°C) | 4.2MPa | 4.2MPa | 4.2MPa | 4.2MPa | 4.2MPa |
| Fire detection tube specification | Φ6×4mm | Φ6×4mm | Φ6×4mm | Φ6×4mm | Φ6×4mm |
| Maximum fire detection tube length | 25m | 30m | 35m | 35m | 35m |
| Discharge tube specification | Φ8mm | Φ10mm | Φ12mm | Φ14mm | Φ16mm |
| Number of nozzles | 1–2 pcs | 2–3 pcs | 3–5 pcs | 5–8 pcs | 8–12 pcs |
| Maximum total flooding protected volume | 5m³ | 10m³ | 20m³ | 30m³ | 40m³ |
| Maximum local application protected area | 2m² | 4m² | 8m² | 12m² | 16m² |
| Discharge time | ≤20s | ≤30s | ≤45s | ≤60s | ≤60s |
| Soaking time | ≥10min | ≥10min | ≥10min | ≥10min | ≥10min |
| Operating ambient temperature | 0°C~50°C | 0°C~50°C | 0°C~50°C | 0°C~50°C | 0°C~50°C |
6.2 Perfluorohexanone Fire Detection Tube Extinguishing Device — Technical Parameters
| Parameter | TH-Z-F-3/1.6 | TH-Z-F-6/1.6 | TH-J-F-10/1.6 | TH-J-F-20/1.6 |
|---|---|---|---|---|
| Extinguishing agent type | Perfluorohexanone | Perfluorohexanone | Perfluorohexanone | Perfluorohexanone |
| Extinguishing agent charge | 3kg | 6kg | 10kg | 20kg |
| Storage container volume | 4L | 8L | 12L | 25L |
| Nominal working pressure (20°C) | 1.6MPa | 1.6MPa | 1.6MPa | 1.6MPa |
| Maximum working pressure (50°C) | 2.5MPa | 2.5MPa | 2.5MPa | 2.5MPa |
| Fire detection tube actuation temperature | 170±10°C | 170±10°C | 170±10°C | 170±10°C |
| Maximum fire detection tube length | 20m | 25m | 30m | 35m |
| Operating ambient temperature | 0°C~50°C | 0°C~50°C | 0°C~50°C | 0°C~50°C |
| Extinguishing concentration | ~5% | ~5% | ~5% | ~5% |
| Discharge time | ≤15s | ≤25s | ≤35s | ≤50s |
| Environmental characteristics | ODP=0, extremely low GWP | ODP=0, extremely low GWP | ODP=0, extremely low GWP | ODP=0, extremely low GWP |
6.3 Carbon Dioxide Fire Detection Tube Extinguishing Device — Technical Parameters
| Parameter | TH-Z-C-3/5.7 | TH-Z-C-6/5.7 | TH-J-C-10/5.7 | TH-J-C-25/5.7 |
|---|---|---|---|---|
| Extinguishing agent type | Carbon dioxide | Carbon dioxide | Carbon dioxide | Carbon dioxide |
| Extinguishing agent charge | 3kg | 6kg | 10kg | 25kg |
| Storage container volume | 5L | 10L | 16.7L | 40L |
| Nominal working pressure (20°C) | 5.7MPa | 5.7MPa | 5.7MPa | 5.7MPa |
| Fire detection tube specification | Φ8×6mm | Φ8×6mm | Φ8×6mm | Φ8×6mm |
| Fire detection tube actuation temperature | 170±10°C | 170±10°C | 170±10°C | 170±10°C |
| Maximum fire detection tube length | 20m | 25m | 30m | 35m |
| Operating ambient temperature | 0°C~50°C | 0°C~50°C | 0°C~50°C | 0°C~50°C |
| Extinguishing concentration | 34% | 34% | 34% | 34% |
| Discharge time | ≤20s | ≤30s | ≤45s | ≤60s |
6.4 Fire Detection Tube — Technical Parameters
| Parameter | For Heptafluoropropane/Perfluorohexanone | For Carbon Dioxide | Unit |
|---|---|---|---|
| Outer diameter | 6.0±0.2 | 8.0±0.2 | mm |
| Inner diameter | 4.0±0.1 | 6.0±0.1 | mm |
| Wall thickness | 1.0 | 1.0 | mm |
| Standard actuation temperature | 170±10 | 170±10 | °C |
| Ambient temperature burst pressure | ≥6.0 | ≥8.0 | MPa |
| Working pressure | 2.5 | 5.7 | MPa |
| Minimum bending radius | ≥80 | ≥100 | mm |
| Weight per unit length | ~25 | ~35 | g/m |
| Standard coil length | 100 | 100 | m |
| Applicable temperature range | -20~80 | -20~80 | °C |
| Service life | ≥5 | ≥5 | years |
6.5 Electrical Components — Technical Parameters
6.5.1 Pressure Switch
- Working pressure range: 0~2.5MPa
- Adjustable actuation pressure range: 0.1~1.0MPa
- Contact form: 1 set of changeover contacts (normally open / normally closed)
- Contact rating: DC24V/1A, AC220V/0.5A
- Mechanical life: ≥100,000 cycles
- Connection port: Φ6mm compression-type fitting
- Protection rating: IP65
- Operating ambient temperature: -10°C~60°C
6.5.2 Audible and Visual Alarm
- Operating voltage: DC24V±10%
- Operating current: ≤150mA
- Sound pressure level: ≥85dB (A-weighted, 1m directly in front)
- Light source: Red LED strobe
- Strobe frequency: approximately 1Hz
- Tone: Fire alarm tone
- Protection rating: IP54
- Operating ambient temperature: -10°C~55°C
- Mounting method: Wall-mounted
6.6 Material and Environmental Adaptability Parameters
- Cylinder material: HP295 seamless gas cylinder specialty steel
- Valve material: HPb59-1 brass / 304 stainless steel
- Fire detection tube material: Specialty polymer composite
- Discharge tube material: T2 copper tube / 304 stainless steel tube
- Seal material: Nitrile rubber / fluororubber
- Ambient humidity: ≤95%RH, non-condensing
- Salt spray resistance: ≥48 hours (no corrosion of coating)
- Vibration resistance: Compliant with GB/T 2423.10 requirements
- Electromagnetic interference resistance: Compliant with GB/T 17626 requirements
7.1 Core Functions
7.1.1 Automatic Fire Detection Function
The fire detector tube system employs linear heat-sensing detection principles. The entire length of the fire detector tube serves as a detector, leaving no detection blind spots. Compared with traditional point-type heat detectors, it offers the following advantages:
- Long detection range — a single fire detector tube can cover dozens of meters.
- Can be installed close to heat sources for faster detection response.
- Flexible routing adapts to complex internal equipment structures.
- Pure physical principle — unaffected by electromagnetic interference, dust, or oil fumes.
- No power supply required — detection function remains operative during power outages.
7.1.2 Automatic Fire Suppression Activation Function
Detection and activation are integrated. The moment the fire detector tube bursts, the system activates simultaneously — no signal conversion or logic judgment is required in between, ensuring extremely fast response.
- Activation response time ≤ 1 second, far faster than traditional alarm + linkage modes.
- Pure mechanical activation with extremely high reliability — no failures caused by electrical circuit faults.
- No external power supply needed — power outages do not affect activation.
- No manual operation required — truly fully automatic unattended fire suppression.
7.1.3 Precision Extinguishing Agent Discharge Function
In direct-type systems, the extinguishing agent is discharged directly from the burst opening directly above the fire source, achieving targeted fire suppression.
- High extinguishing agent utilization efficiency with minimal consumption, reducing fire suppression costs.
- Non-fire areas are not affected by the extinguishing agent, minimizing secondary damage.
- For equipment with multiple dispersed protection points, independent systems can be configured separately without mutual interference.
7.1.4 Fire Alarm Signal Output Function
The system comes standard with a pressure switch and audible-visual alarm device, enabling on-site alarm and remote signal transmission.
- On-site audible-visual alarm alerts personnel for timely response.
- Passive dry contact signal output for easy integration with various fire alarm systems.
- Alarm and fire suppression trigger simultaneously, ensuring fire information is communicated promptly.
7.1.5 Status Monitoring Function
- The cylinder pressure gauge provides real-time monitoring of extinguishing agent storage pressure.
- The terminal pressure gauge provides real-time monitoring of the fire detector tube pressurization status.
- Daily inspections require no specialized tools — visual inspection is sufficient to determine system status.
- Optional IoT remote monitoring module enables 24-hour online monitoring.
7.2 Product Features
7.2.1 High Reliability
- The system core is a purely mechanical structure with minimal moving parts and extremely low failure rates.
- No power supply, no mainboard, no software — immune to electronic failures such as system crashes or program errors.
- All critical components undergo rigorous high/low temperature, vibration, and aging tests for stable performance.
- Under normal maintenance conditions, the system’s trouble-free operating life can exceed 5 years.
7.2.2 Installation Convenience
- No extensive piping required, no heavy construction equipment needed — short installation period.
- Fire detector tube is flexible and can be cut to length — strong on-site adaptability.
- The cylinder is compact and lightweight — wall-mountable or floor-standing with flexible installation options.
- No modification of existing building structures required — ideal for retrofitting existing projects.
7.2.3 Economic Practicality
- Equipment procurement costs are far lower than traditional piped gas fire suppression systems.
- Simple installation with low labor costs.
- Minimal routine maintenance workload and low operation/maintenance costs.
- Low extinguishing agent consumption — low refill costs after discharge.
- Localized fire suppression minimizes fire losses — significant overall economic benefits.
7.2.4 Safety and Environmental Friendliness
- Uses clean agent extinguishing media — no residue after discharge, no secondary damage to equipment.
- Both HFC-227ea (heptafluoropropane) and Novec 1230 (perfluorohexanone) meet environmental requirements with zero ozone depletion potential.
- The system operates sealed — no environmental impact under leak-free conditions.
- Activation temperature settings are reasonable — no false activation from normal temperature rises.
7.2.5 Scenario Adaptability
- Applicable across scales from 0.1 m³ small electrical enclosures to equipment rooms of dozens of cubic meters.
- Adaptable to indoor, outdoor, vehicle-mounted, underground, and various other environments.
- Customized solutions available for high-temperature, high-humidity, high-dust, and strong electromagnetic environments.
- Can be integrated with other fire protection systems to create a multi-layer protection framework.
7.3 Comparison with Traditional Fire Protection Systems
| Comparison Item | Fire Detector Tube Gas System | Traditional Piped Gas System | Dry Powder Extinguisher | Aerosol Extinguishing Device |
|---|---|---|---|---|
| Power Dependency | None required | Required | None required | Required |
| Fire Detection | Built-in linear detection | Requires separate detectors | Manual discovery | Requires separate detectors |
| Response Speed | Extremely fast (seconds) | Slow (alarm + linkage required) | Slow (manual) | Relatively fast |
| Installation Difficulty | Simple | Complex | Simple | Moderate |
| Space Occupancy | Small | Large | Small | Moderate |
| Suppression Precision | Point-to-point precise | Total flooding | Manual aiming | Total flooding |
| Maintenance Cost | Low | High | Moderate | Moderate |
| Secondary Pollution | None | None | Yes | Residue present |
| Applicable Scenarios | Confined spaces, inside cabinets | Large protected areas | General emergency use | Small-to-medium spaces |
The fire detector tube gas fire suppression system, with its unique technical advantages, is widely applied across industries for localized fire protection, particularly in confined, sealed, and complex spaces where traditional fire protection systems cannot effectively cover.
8.1 Data Centers and Communications Industry
8.1.1 Server Cabinet Interiors
Server cabinets in data centers contain dense equipment with high heat generation and numerous cables, making them high-risk areas for electrical fires. Traditional gas suppression systems protect the entire computer room but cannot rapidly extinguish fires in individual cabinets.
- Install direct-type fire detector tube systems inside each server cabinet, positioned close to servers and power supply modules.
- When a fire occurs in an individual cabinet, the corresponding system activates immediately with precision suppression, without affecting normal operation of other cabinets.
- Avoids whole-computer-room shutdown caused by localized fires, significantly reducing business interruption losses.
8.1.2 Network Switch Cabinets
Network equipment such as switches and routers is high-value with strong business interdependence — fires can cause large-scale network outages.
- Configure dedicated fire detector tube extinguishing devices for core switch cabinets.
- Fire detector tubes are routed above equipment and along cable trays for complete coverage of ignition-prone points.
- No residue after discharge — equipment can quickly resume operation after cleaning.
8.1.3 Communication Base Stations
Outdoor communication base stations and 5G base stations are often unattended, with power supply and transmission equipment vulnerable to fires from lightning strikes or overloads.
- Install fire detector tube extinguishing devices inside base station cabinets for 24-hour automatic monitoring.
- No external power required — functions normally even when base station power is interrupted.
- Compact size — installed inside the cabinet without occupying additional space.
8.1.4 UPS Power Cabinets and Battery Rooms
UPS power supplies and battery banks are the power backbone of data centers and also high-risk fire areas.
- Configure direct-type fire detector tube systems inside UPS cabinets to protect power modules and capacitors.
- Battery rooms use indirect-type fire detector tube systems for total flooding protection.
- Fast response effectively curbs fire spread from battery thermal runaway.
8.2 Power and Electrical Grid Industry
8.2.1 High/Low Voltage Switchgear
High/low voltage switchgear contains numerous live components such as busbars, circuit breakers, and contactors, which are prone to arc fires caused by short circuits or poor contact.
- Configure independent direct-type fire detector tube systems in each switchgear cabinet.
- Fire detector tubes are routed above busbars and circuit breakers for close-range detection.
- Fast suppression capable of extinguishing fires at the arc initiation stage, preventing accident escalation.
8.2.2 Transformer Localized Protection
Oil-immersed and dry-type transformers are core substation equipment with high fire risk.
- Configure fire detector tube systems for localized ignition-prone points such as transformer terminal boxes and cooling fan control cabinets.
- Fire detector tubes are routed above dry-type transformer windings to monitor overheating hazards.
- Serves as a complement to the main fire protection system for early warning and suppression.
8.2.3 Cable Trenches and Cable Basements
Cable trenches and cable basements contain dense cabling where fires are highly concealed and spread rapidly.
- Fire detector tubes are routed along cable trays for linear temperature monitoring.
- Multiple direct-type systems provide segmented protection — a fire in one segment does not affect others.
- More sensitive than traditional heat-sensing cables while also providing fire suppression capability.
8.2.4 Ring Main Units and Compact Substations
Outdoor ring main units and compact substations are widely distributed, unattended, and difficult to maintain.
- Fire detector tube extinguishing devices are integrated inside cabinets for fully automatic operation.
- Adaptable to outdoor temperature variations with stable, reliable performance.
- Significantly reduces on-site inspection frequency and lowers maintenance costs.
8.3 Industrial Manufacturing Industry
8.3.1 CNC Machine Tools and Machining Centers
CNC machine tools contain electrical, hydraulic, and lubrication systems internally. The cutting process generates high-temperature sparks, creating high fire risk.
- Install direct-type fire detector tube systems inside machine electrical cabinets and control cabinets.
- Indirect-type systems can be configured above machining areas for cutting oil fire protection.
- Vibration-resistant and oil-resistant — adapted to harsh industrial environments.
8.3.2 Automated Production Lines
Automated production lines have numerous, widely dispersed electrical control cabinets that traditional fire protection cannot fully cover.
- Each electrical control cabinet is independently equipped with a fire detector tube extinguishing device.
- Installation can be completed without stopping production lines.
- A fault in one cabinet does not affect the entire line — rapid production recovery.
8.3.3 Wind Turbine Generators
Wind turbines are located at height with frequency converters, transformers, gearboxes, and other equipment in the nacelle — making fire rescue extremely difficult.
- Fire detector tube fire suppression systems are configured in zones around critical nacelle components.
- Vibration-resistant and temperature-tolerant — suitable for harsh outdoor environments.
- Automatic fire suppression without on-site personnel — maximum equipment protection.
8.3.4 Coating Production Lines and Paint Spray Booths
Coating operations involve flammable and explosive solvent vapors, creating extremely high fire risk.
- Use explosion-proof fire detector tube extinguishing devices.
- Localized protection for key areas such as spray booths and paint mixing rooms.
- Fast response effectively suppresses flash fires.
8.4 Transportation Industry
8.4.1 New Energy Vehicle Battery Compartments
Thermal runaway in new energy vehicle power batteries is a major safety hazard — traditional vehicle fire extinguishers are inadequate.
- Dedicated fire detector tube systems are installed inside battery packs or battery compartments.
- Early detection and activation at the onset of thermal runaway curbs fire development.
- Compact and lightweight — does not occupy excessive vehicle space.
8.4.2 Bus Engine Compartments
Bus engine compartments have high temperatures and heavy oil contamination, making them prone to spontaneous combustion.
- Fire detector tube extinguishing devices are installed in engine compartments with multi-point detection.
- Automatic activation during vehicle operation without driver intervention.
- Minimal engine damage after discharge — reduced repair costs.
8.4.3 Subway and Light Rail Electrical Cabinets
Subway trains and light rail vehicles contain numerous electrical cabinets in confined spaces.
- Fire detector tube extinguishing devices are installed in various control cabinets and traction cabinets.
- Excellent vibration resistance suitable for vehicle operating environments.
- Independently operated — independent of vehicle control systems.
8.5 Buildings and Public Facilities
8.5.1 Elevator Control Cabinets
Elevator control cabinets are installed beside hoistways or in machine rooms and are prone to fires from electrical faults.
- Install direct-type fire detector tube systems inside control cabinets.
- 24-hour automatic monitoring — functions normally unattended.
- No corrosive effect on circuit boards after discharge — elevators can quickly resume operation.
8.5.2 Building Weak Current Shafts and Service Ducts
Building weak current and power shafts contain dense vertical cabling where fires can spread rapidly along the vertical direction.
- Fire detector tube extinguishing devices are installed in service ducts at each floor level.
- Fire detector tubes are routed along vertical cables for full-height coverage.
- Early suppression prevents vertical fire spread and major losses.
8.5.3 Archives and Cultural Relics Storage Rooms
Archives and cultural relics are irreplaceable and require extremely high extinguishing agent cleanliness.
- Use Novec 1230 (perfluorohexanone) indirect-type fire detector tube systems for total flooding protection.
- No residue and no contamination after discharge — harmless to paper, textiles, and metal artifacts.
- Individual archive cabinets can be precisely protected without affecting other collections.
8.5.4 Kitchen Equipment Protection
Commercial kitchen exhaust hoods and grease ducts accumulate oil deposits, making them prone to duct fires.
- High-temperature type fire detector tube systems are installed inside exhaust hoods.
- Rapid detection and suppression of wok fires or duct fires.
- Serves as a supplement to kitchen automatic fire suppression systems or standalone use in small kitchens.
8.6 Other Typical Application Scenarios
- Medical equipment: Protection inside control cabinets of large medical devices such as CT scanners and MRI systems.
- Laboratories: Localized fire protection for precision analytical instruments and fume hoods.
- Self-service equipment: Internal protection of ATM machines, vending machines, and EV charging piles.
- Storage racking: Localized protection of aisle spaces in automated high-bay warehouses.
- Photovoltaic power stations: Fire protection inside combiner boxes and inverter enclosures.
- Military equipment: Fire protection for various military vehicles, shelters, and weapon systems.
9.1 Pre-Installation Preparation
9.1.1 Technical Preparation
- Familiarize yourself with construction drawings and design documents; clarify protection zone divisions, equipment layout, and piping routes.
- Carefully read this manual and product certificates; understand product models, specifications, and technical parameters.
- Provide technical briefing to construction personnel regarding installation procedures, quality standards, and safety precautions.
- Verify on-site conditions — confirm protection zone structure, dimensions, and openings match the design.
- Prepare construction plan and schedule; assign personnel responsibilities.
9.1.2 Materials and Tool Preparation
- Check all equipment and accessories against the packing list; confirm models, quantities, and exterior integrity.
- Prepare installation tools:
| Tool Category | Tools |
|---|---|
| Pipe-fitting tools | Tube cutter, tube bender, flaring tool, wrench set, torque wrench |
| Measuring tools | Tape measure, spirit level, pressure gauge calibrator |
| Power tools | Electric drill, impact drill, screwdriver set |
| Leak detection tools | Soapy water, spray bottle |
| Miscellaneous | Cable ties, marking pen, gloves, safety protective equipment |
- Prepare auxiliary materials: expansion anchors, self-tapping screws, sealant, PTFE tape, anti-rust paint, etc.
9.1.3 On-Site Condition Verification
- Civil construction of the protection zone is complete; walls and ceiling are ready for installation.
- Protected equipment is installed or installation positions are reserved.
- Cylinder installation position is level and solid with adequate working space.
- No flammable or explosive materials on site; construction environment meets safety requirements.
- If hot work (welding/cutting) is required, obtain hot work permits per regulations.
9.2 Extinguishing Agent Cylinder Assembly Installation
9.2.1 Installation Position Requirements
- The cylinder assembly should be installed near but outside the protection zone for ease of operation and maintenance, away from direct sunlight.
- Installation environment temperature should be within 0°C–50°C; avoid proximity to heat sources.
- The cylinder assembly must be installed upright with a tilt angle not exceeding 5°.
- Maintain at least 0.5 m of working space around the cylinder assembly for inspection and replacement.
- Installation position should avoid mechanical impact; install protective guards where necessary.
- Outdoor installations require rain and sun protection measures.
9.2.2 Bracket Installation
- Determine bracket fixing points based on cylinder assembly height and installation position; mark the locations.
- Drill holes with an electric drill, insert expansion anchors, and secure the bracket base.
- Adjust bracket verticality and levelness; tighten fixing bolts.
- The bracket must be firmly connected to the wall or floor with adequate load-bearing capacity.
- Metal brackets should receive anti-corrosion treatment; welded areas coated with anti-rust paint.
9.2.3 Cylinder Installation
- Place the cylinder levelly on the bracket base; adjust position so the nameplate faces the operating side.
- Install the holding clamp with cushioning pads on the inner side to avoid scratching the cylinder coating.
- Tighten clamp bolts with moderate force, ensuring the cylinder is securely fixed without wobbling.
- Check cylinder verticality; use shims at the base for adjustment if necessary.
- After installation, never move or strike the cylinder arbitrarily.
9.2.4 Container Valve Accessory Installation
- Remove protective plugs from all container valve ports, taking care to protect sealing surfaces.
- Install the container pressure gauge:
- Check that the gauge connection sealing washer is intact.
- Thread the pressure gauge into the gauge port and tighten moderately with a wrench.
- Observe the gauge needle to confirm pressure is in the green normal zone.
- Confirm the high-pressure ball valve is in the closed position in preparation for subsequent fire detector tube installation.
9.3 Direct-Type Fire Detector Tube Installation
9.3.1 Fire Detector Tube Routing Design Principles
- Fire detector tubes should be routed above or diagonally above the protected object, at a distance of no more than 1 m from the protected surface.
- Fire detector tubes must not be in direct contact with surfaces exceeding 80°C; thermal insulation measures are required where proximity is unavoidable.
- Fire detector tube paths should be as straight as possible with minimal unnecessary bending.
- Fire detector tubes should avoid sharp edges, high-temperature components, and positions susceptible to mechanical damage.
- When fire detector tubes pass through cabinet partitions or walls, protective conduits must be installed.
- The total length of a single fire detector tube must not exceed the maximum allowable length for the corresponding model.
- Tee fitting branch outlets should be installed horizontally — never facing downward or upward vertically.
9.3.2 Pipe Measurement and Cutting
- Measure required fire detector tube length based on the designed route, accounting for bending radii and fitting allowances.
- Use a dedicated tube cutter to cut the fire detector tube; the cut must be smooth with no burrs, crushing, or deformation.
- The cut end face should be perpendicular to the tube axis with a tilt not exceeding 10% of the tube diameter.
- Dress the cut end face with a specialized tool to remove internal edge burrs.
- Cut sections in installation sequence order and mark them to avoid confusion.
9.3.3 Pipe Connection Procedure
Compression fitting connection steps:
1. Slide the compression nut onto the fire detector tube, then slide on the compression ferrule (note orientation).
2. Insert the fire detector tube into the fitting body fully to the bottom, ensuring proper seating.
3. Hand-tighten the compression nut, then hold the fitting body with one wrench and tighten the nut with another.
4. Tightening torque should conform to product technical requirements — typically 15–20 N·m; do not over-tighten or under-tighten.
5. After initial installation, mark the position to facilitate future loosening checks.
Tee fitting installation:
- The main fire detector tube passes through both ends of the tee.
- The branch port connects to the pressure gauge or signal feedback line.
- Ensure the branch outlet is horizontally oriented.
- Before all connections, clean the tube ends and fitting interiors — free of dust and oil.
9.3.4 Pipe Fixing
- Fire detector tubes are secured with dedicated pipe clips at intervals not exceeding 500 mm.
- Pipe clips should be fixed to sturdy structural members — never directly to cables or pipes.
- Additional fixing points should be added on both sides of bends, within 100 mm of the bend.
- A fixing point should be provided on each side of fittings within 100 mm.
- During fixing, the fire detector tube should rest naturally and smoothly — no forced stretching or twisting.
- Clip tension should be moderate — secure enough for firm holding without flattening the fire detector tube.
9.3.5 Wall and Panel Penetration Treatment
- When the fire detector tube passes through cabinet side panels, walls, or floor slabs, dedicated protective conduits must be installed.
- The protective conduit inner diameter should be at least 2 mm larger than the fire detector tube outer diameter; length should match the wall/panel thickness.
- Both ends of the conduit should be chamfered to prevent cutting the fire detector tube.
- Gaps between the conduit and the opening should be filled with fire-stop sealing material.
- The fire detector tube should pass centered through the conduit without rubbing against the inner wall.
9.3.6 Terminal Component Installation
- Install the check valve and terminal pressure gauge in sequence at the end of the fire detector tube.
- The terminal pressure gauge should be installed outside the protection zone or in a position convenient for observation, at approximately 1.5 m height.
- The gauge dial should face the inspection direction for easy reading.
- The signal feedback branch should be fitted with a pressure switch, connected securely with reliable sealing.
- The extreme end of the fire detector tube is sealed with a terminal plug — no leak points permitted.
9.4 Indirect System Discharge Pipe and Nozzle Installation
9.4.1 Discharge Pipe Installation Requirements
- Discharge piping should be routed per design drawings with reasonable routing — horizontal and vertical alignment.
- Pipe connections use compression-type fittings with reliable sealing.
- Horizontal pipes should have a slight slope toward the drain point or cylinder side.
- Pipe fixing uses dedicated pipe clamps with spacing not exceeding 1.5 m.
- Additional support brackets should be added at bends and fittings.
- Pipes passing through walls or floor slabs should have protective conduits with fire-stop sealing of gaps.
- After installation, pipes should be purged to ensure interior cleanliness — free of debris.
9.4.2 Nozzle Installation Requirements
- Nozzle models, specifications, and quantities must conform to design requirements.
- Nozzle installation positions and discharge directions should be determined per design to ensure uniform agent distribution.
- For total flooding applications, nozzles should be evenly distributed at the top of the protection zone, discharging downward.
- For local application, nozzles should be aimed at the protected object at design-specified distances.
- Nozzles must be securely installed with unobstructed orifices; protective caps must not be removed before installation.
- Nozzles must not be obstructed — ensure unobstructed discharge paths.
9.5 Audible-Visual Alarm Device Installation
- The audible-visual alarm should be installed at a conspicuous location near the protection zone entrance, at approximately 2.2–2.5 m height.
- Wall-mounted installation with expansion anchors — securely fixed without loosening.
- The alarm front face should face the main personnel access direction for easy visibility and audibility.
- Alarms for multiple protection zones should have clear identification labels distinguishing their respective areas.
- Outdoor installations should use waterproof models with added rain shields.
9.6 Installation Quality Inspection
After installation is complete, a comprehensive installation quality inspection should be performed, covering:
| Inspection Item | Inspection Content |
|---|---|
| Cylinder assembly | Correct position, securely fixed, verticality compliant, nameplate clear and facing outward |
| Valve components | All ports connected properly, ball valve operates smoothly, pressure gauge indicates correctly |
| Fire detector tube routing | Reasonable routing, firmly fixed, spacing compliant, no crushing or twisting, protected at wall penetrations |
| Fitting connections | All fittings firmly connected, compression ferrules properly seated, no signs of loosening |
| Discharge piping | Tidy routing, brackets secure, slope compliant |
| Nozzle installation | Correct model and quantity, accurate direction, unobstructed, not shielded |
| Terminal components | Pressure gauge positioned for easy observation, pressure switch correctly connected |
| Labels and signage | System identification and warning labels complete, clear, and correct |
Only after all inspections pass may the system proceed to the wiring and commissioning stages.
The electrical wiring of the fire detector tube gas fire suppression system primarily involves the pressure switch, audible-visual alarm device, and linkage wiring with the fire alarm system. The system’s core suppression function does not depend on the electrical system, but alarm and signal feedback functions require correct wiring.
10.1 Pre-Wiring Preparation
10.1.1 Technical Preparation
- Familiarize yourself with electrical schematic and wiring diagrams; clarify terminal definitions for each component.
- Confirm power supply parameters — voltage level and capacity meet equipment requirements.
- Understand the interface type and signal requirements of the fire alarm system being connected to.
- Provide safety briefing to wiring personnel regarding live-work safety regulations.
10.1.2 Materials and Tool Preparation
Cables:
| Cable Type | Specification | Application |
|---|---|---|
| Signal cable | RVVP 2×1.0 mm² shielded control cable | Signal transmission |
| Power cable | BV 2×1.5 mm² power cable | Power supply |
| — | — | Conductor size determined by transmission distance and load |
Auxiliary materials: terminal blocks, wire number sleeves, cable ties, insulating tape, flexible conduit, cable trays, etc.
Tools: wire strippers, crimping tools, multimeter, soldering iron, screwdriver set, voltage tester, etc.
Test instruments: megohmmeter, multimeter, signal generator, etc.
10.1.3 Safety Precautions
- Confirm power is disconnected before wiring — never wire live circuits.
- Cable installation should comply with electrical construction codes; keep power and signal cables segregated.
- All connections must be properly insulated — no exposed bare metal.
- Shielded cable screens should be grounded at one end only to avoid ground loops.
- Wiring in explosion-proof areas must comply with explosion-proof code requirements.
10.2 Pressure Switch Wiring
10.2.1 Pressure Switch Terminal Description
Standard pressure switches typically provide three terminal groups:
| Terminal | Description |
|---|---|
| Common (COM) | Common contact |
| Normally Open (NO) | Open in normal state; closes upon activation |
| Normally Closed (NC) | Closed in normal state; opens upon activation |
In the normal standby state of the fire detector tube system, the internal tube pressure is normal and the pressure switch contacts maintain their initial state. When the fire detector tube bursts and pressure drops to the activation value, the contacts switch.
10.2.2 Basic Wiring Methods
Driving the audible-visual alarm:
Power supply positive → Pressure switch common (COM) Pressure switch normally open (NO) → Audible-visual alarm positive Audible-visual alarm negative → Power supply negative
Principle: In the normal state, the switch is open and the alarm does not operate. After the fire detector tube bursts, the switch closes and the alarm receives power to activate.
Connecting to the fire alarm controller:
Fire alarm controller input module signal line → Pressure switch NO and COM terminals Passive contact method used — monitoring voltage provided by the controller Module set to normally-open monitoring mode — alarm signal fed back upon activation
10.2.3 Wiring Workmanship Requirements
- Cable stripping length should be moderate — approximately 5–8 mm — with no broken wire strands.
- Terminal connections should use crimping or soldering for firm connections with low contact resistance.
- Stranded copper wires should be tinned or terminated with cold-pressed ferrules before connecting to terminals.
- Terminal screws should be tightened securely — no loosening — wires must not pull out under tension test.
- Both ends of each wire should be fitted with wire number sleeves with clear markings for maintenance.
- Pressure switch wiring points should be waterproofed — outdoor installations require junction boxes.
10.3 Audible-Visual Alarm Wiring
10.3.1 Power Supply Wiring
- Operating voltage: DC24V, range DC20V–DC28V.
- Connect power supply positive to the alarm “+” terminal and negative to the “−” terminal — polarity must not be reversed.
- Power can be sourced from the fire alarm linkage power supply or a dedicated backup power supply.
- Power circuits should be protected by independent fuses or miniature circuit breakers.
- For long-distance transmission, calculate line loss to ensure terminal voltage meets requirements.
10.3.2 Signal Trigger Wiring
- Passive trigger type: Power on/off directly controlled by the pressure switch contacts — see wiring in Section 10.2.2.
- Active trigger type: Trigger terminal receives DC24V signal voltage; alarm activates upon triggering.
- When multiple alarms are connected in parallel, calculate total current to ensure adequate power supply capacity.
- Multiple alarms in the same protection zone should trigger synchronously.
10.3.3 Addressable Alarm Wiring
For addressable audible-visual alarm devices connected to the fire alarm system bus:
- Connect to the two-wire bus with correct polarity.
- Set the address code per the instruction manual.
- Linkage logic is programmed in the controller — alarms are linked upon receiving the corresponding pressure switch signal.
10.4 Linkage Wiring with Fire Alarm System
10.4.1 Signal Integration Methods
The fire detector tube system provides a passive dry contact signal to the fire alarm system through two primary methods:
Method 1: Connection to input module
- Pressure switch normally-open contacts connect to the fire alarm system’s supervisory input module.
- The module monitors contact status in real time and reports a fire alarm upon activation.
- Advantage: Strong system independence, no mutual interference, faults do not propagate.
- Application: Most common method, suitable for most projects.
Method 2: Connection to fire damper/fan linkage circuits
- Pressure switch contacts are wired in series into the control circuits of related linked equipment.
- Upon system activation, directly links the closing of fire dampers, starting of exhaust fans, etc.
- Note: Verify contact capacity; add intermediate relays where necessary.
10.4.2 Linkage Logic Design
- The fire detector tube system activation signal is transmitted to the fire control room as a fire alarm signal.
- Can link the closing of fire dampers and ventilation/air-conditioning systems in the protection zone.
- Can link the disconnection of non-fire power supplies in the protection zone.
- Can link emergency lighting and evacuation signage activation.
- Multiple fire detector tube systems can display alarm locations by zone for rapid fire location.
10.4.3 Wiring Precautions
- Equipotential grounding should be established between the fire detector tube system and the fire alarm system.
- Signal circuits should maintain adequate separation from power circuits to avoid electromagnetic interference.
- Long-distance transmission should use shielded cables with the shield grounded at the control room end.
- After wiring completion, measure insulation resistance between conductors — should be greater than 20 MΩ.
- All wiring should be documented in drawings with clear, accurate terminal numbers.
10.5 Optional Accessory Wiring
10.5.1 Manual Activation Button Wiring
For systems with optional solenoid activation function, a manual activation button can be added:
- The manual button’s normally-open contacts are wired in series into the solenoid valve power circuit.
- Pressing the button energizes the solenoid valve for manual forced activation.
- The manual button should be installed outside the protection zone with a protective cover to prevent accidental operation.
- Critical locations may use dual buttons requiring simultaneous pressing for activation.
10.5.2 IoT Monitoring Module Wiring
- The pressure switch signal connects to the monitoring module’s acquisition input.
- Optional pressure sensor can be installed for real-time system pressure monitoring.
- The module connects to Ethernet or 4G networks for data upload to the cloud platform.
- Module power: DC24V or built-in battery power.
- Enables features such as mobile app alarm push notifications and historical data queries.
10.6 Cable Routing and Protection
- Cable installation should comply with the requirements of “Code for Construction and Acceptance of Fire Alarm System” (GB 50166).
- Indoor cables can be routed through conduits, cable trays, or trays; outdoor cables must be protected with steel conduits.
- Cables must not have intermediate splices within conduit runs — splices must be made in junction boxes.
- Cable bends and entry/exit points should have service slack — avoid over-tensioning.
- All metal conduits and trays must be reliably grounded.
- After cable installation, labeling should be provided indicating purpose and destination.
10.7 Wiring Quality Inspection
After wiring is complete, perform the following inspections and tests:
| Inspection Item | Content |
|---|---|
| Continuity check | Use a multimeter to test continuity of each circuit; confirm correct wiring, no short circuits or open circuits |
| Insulation test | Use a 500V megohmmeter to measure line-to-ground insulation resistance; should be ≥ 20 MΩ |
| Polarity check | Confirm DC power and bus polarity correct — no reverse connections |
| Label check | Wire numbers clear, accurate, and complete — consistent with drawings |
| Workmanship check | Wiring neat, firm, and presentable — good insulation, no exposed copper |
| Protection check | Conduits, cable trays, and junction boxes properly installed with complete protective measures |
The system may proceed to commissioning only after wiring inspection passes.
After system installation and wiring are complete, standardized commissioning must be performed to verify system functions are normal and sealing performance is sound before the system is placed into service. Commissioning must be strictly performed per this procedure to ensure personnel and equipment safety.
11.1 Pre-Commissioning Preparation
11.1.1 Commissioning Condition Confirmation
- System installation is fully complete with installation quality inspection approved.
- All wiring is complete with wiring inspection approved.
- The protection zone is essentially enclosed with openings treated per requirements.
- The commissioning area is cleared and unauthorized personnel evacuated.
- Commissioning tools and instruments are fully prepared and in good condition.
- Commissioning plan is prepared with clear personnel assignments and safety measures.
11.1.2 Commissioning Tools and Instruments
| Tool/Instrument | Purpose |
|---|---|
| Dedicated charging device: nitrogen cylinder, pressure reducing valve, charging fitting | Pressurization |
| High-precision pressure gauge | Calibration of system pressure gauges |
| Soapy water and spray bottle | Leak detection (air tightness) |
| Stopwatch | Timing |
| Multimeter | Electrical testing |
| Thermometer | Environment temperature measurement |
| Personal protective equipment: gloves, safety goggles | Personnel safety |
11.1.3 Safety Precautions
- Commissioning personnel must be professionally trained and familiar with system principles and operating procedures.
- Smoking and open flames are strictly prohibited at the commissioning site; emergency fire extinguishing equipment should be available.
- During charging operations, personnel should stand to the side — never directly in front of fitting outlets.
- Do not exceed specified pressures during pressure testing — strictly controlled within prescribed limits.
- If abnormal leakage or unusual sounds are detected, stop immediately, relieve pressure, then inspect.
- Maintain records throughout commissioning and complete the commissioning log.
11.2 Fire Detector Tube Air Tightness Test
This is the most critical step in commissioning — ensuring the fire detector tube circuit is leak-free and the system can maintain pressure reliably over the long term.
11.2.1 Test Preparation
- Confirm the high-pressure ball valve on the container valve is in the closed position (critically important — prevents accidental extinguishing agent discharge).
- Remove the terminal pressure gauge from its position, retaining the check valve.
- Connect the dedicated charging fitting to the check valve port; connect the nitrogen cylinder and pressure reducing valve.
- Inspect all connections to confirm secure fitting.
11.2.2 Pressurization
- Slowly open the nitrogen cylinder valve and adjust the pressure reducing valve to control the charging rate.
- Slowly charge nitrogen into the fire detector tube with gradual pressure increase.
- Pressurize to the specified test pressure:
| System Type | Test Pressure |
|---|---|
| HFC-227ea / Novec 1230 systems | 1.2–1.5 MPa (or per manufacturer’s specification) |
| CO₂ systems | Per manufacturer’s specified pressure |
- Perform staged inspections during pressurization — observe for any abnormalities.
- After reaching test pressure, close the gas supply valve and maintain pressure.
11.2.3 Leak Inspection
- Apply soapy water to check all fittings, tees, and valve connections point by point.
- Inspect the fire detector tube body for bulging or seepage.
- Inspect wall-penetration conduit locations for damage or leakage.
- Observation time at each point on the fire detector tube: no less than 10 minutes per meter.
- Monitor the pressure gauge throughout and record pressure changes.
- If bubbles appear, mark the leak point, relieve pressure, and rectify.
11.2.4 Pressure Hold Test
- After initial inspection shows no obvious leaks, proceed with the pressure hold test.
- Hold duration: typically 24 hours, or per code requirements.
- Allowable pressure drop: ≤ 5% of test pressure, without affecting normal system function.
- If pressure drop exceeds the limit, perform comprehensive leak detection and rectification until passing.
- After the hold test passes, slowly relieve pressure to normal operating pressure.
11.2.5 Component Restoration
- Remove the charging fitting.
- Reinstall the terminal pressure gauge and tighten securely.
- Confirm the terminal pressure gauge indicates normally and matches the cylinder pressure.
- Wipe soapy water residue from the tube surfaces to prevent corrosion.
11.3 Container Valve Opening Function Test
11.3.1 Simulated Activation Test
Verify the container valve activation function without discharging extinguishing agent:
1. Close the high-pressure ball valve and disconnect the fire detector tube from the container valve.
2. Connect a test pressure gauge and charging device to the container valve activation chamber port.
3. Slowly reduce the activation chamber pressure and observe whether the valve opens at the set differential pressure.
4. Record the pressure differential at opening — should conform to product technical requirements.
5. After testing, restore the activation chamber pressure — the valve closes.
Note: This test must be performed by qualified personnel. Before testing, confirm the extinguishing agent outlet is sealed to prevent accidental agent discharge.
11.3.2 Actual Activation Verification
For critical projects, actual discharge testing may be performed using empty cylinders:
- Replace with a test cylinder charged with compressed air or nitrogen.
- Connect the fire detector tube and discharge piping.
- Use localized heating to burst the fire detector tube, triggering system activation.
- Observe whether the valve opens, gas discharges, and the pressure switch activates correctly.
- Record the time from heating to discharge to verify response speed.
11.4 Electrical Function Commissioning
11.4.1 Pressure Switch Activation Test
- During the air tightness test, observe pressure switch operation.
- Slowly relieve pressure — when pressure drops to the activation value, the pressure switch should reliably switch.
- Use a multimeter to measure contact continuity changes, confirming accurate activation.
- Slowly restore pressure — contacts should reset when pressure recovers.
- Record activation and reset pressures — should conform to product parameters.
11.4.2 Audible-Visual Alarm Test
- Apply power to the alarm and manually simulate a trigger signal.
- Check that the audible-visual alarm activates normally — loud sound and proper flashing.
- Measure sound pressure level — should be no less than 85 dB at 1 m directly in front.
- Check alarm light brightness and flash frequency per design requirements.
- Multiple alarms should activate synchronously without delay.
11.4.3 Linkage Function Test
- Simulate pressure switch activation and check whether the fire alarm controller receives the alarm signal.
- Verify alarm address and location display are accurate.
- Test linkage logic: confirm fire dampers, fans, and non-fire power supplies operate per preset logic.
- Check that the graphical display device in the fire control room correctly shows the alarm location.
- Test remote monitoring function (if fitted) — confirm alarm information uploads correctly.
11.5 Overall System Functional Verification
11.5.1 Status Confirmation
| Component | Required Status |
|---|---|
| Container valve main valve | Closed (standby state) |
| High-pressure ball valve | Open (system in service) |
| Charging valve | Sealed properly |
| Container pressure gauge | Needle in green zone — pressure normal |
| Terminal pressure gauge | Indicates normally — no obvious pressure drop |
| All piping | Securely fixed — no loosening or damage |
| Electrical system | Energized and in standby mode |
11.5.2 Simulated Fire Test
Where conditions permit, a small-scale simulated fire test may be performed:
1. Select a safe location within the protection zone and place a small combustible item (e.g., alcohol-soaked cotton).
2. Ignite the combustible item and observe system response.
3. Record detection time, activation time, and suppression time.
4. Verify alarm signals are emitted normally.
5. Ventilate and clean the site after the test.
Note: This test must ensure safety, with fire prevention measures in place, and be performed under the guidance of qualified personnel.
11.6 Commissioning Completion Work
- Clean up the commissioning site; collect tools and surplus materials.
- Apply system identification and warning labels:
- Cylinder: system name and number label.
- Protection zone entrance: “Gas Fire Suppression” warning sign.
- Manual activation button: “Anti-accidental Operation” protective cover and operating instructions.
- Compile commissioning records and complete the commissioning report.
- Provide initial operating training to the owner’s operation and maintenance personnel.
- After commissioning passes, the system formally enters the quasi-operational state.
12.1 Installation and Construction Precautions
- Installation qualification requirement: Installation of the fire detector tube fire suppression system should be undertaken by units with appropriate fire protection engineering construction qualifications; construction personnel should be professionally trained.
- Product protection: Equipment should be properly stored upon delivery — protected from sun and rain; the fire detector tube must not be compressed, kinked, or scratched.
- Tube cutting: Only dedicated tube cutters may be used to cut the fire detector tube — scissors, ordinary pliers, and similar tools are strictly prohibited to avoid tube-end deformation or cracking.
- Fitting connections: Compression fittings must be installed per standard procedures, ensuring the ferrule correctly seats into the tube wall with appropriate tightening torque — neither leaking nor over-tightened to the point of cracking.
- Bending radius: The minimum bending radius must be maintained when bending the fire detector tube — sharp bends and hard kinks are strictly prohibited as they can damage the tube wall and create leak hazards.
- Heat source isolation: The fire detector tube must not be placed directly against surfaces above 80°C; thermal insulation measures are required where proximity is unavoidable.
- Mechanical protection: The fire detector tube should avoid positions susceptible to impact and friction; penetrations through openings must have protective sleeves to prevent mechanical damage.
- Construction sequence: Install the cylinder assembly and main piping first, then connect the fire detector tube and terminal components, and finally perform electrical wiring and commissioning.
- No work under pressure: Before disassembling or assembling any piping or components at any time, confirm the relevant section has been depressurized — working under pressure is strictly prohibited.
- Finished work protection: After installation, protect the completed work to prevent damage from subsequent decoration or other trade activities.
12.2 Commissioning and Operation Precautions
- Personnel training: Commissioning and operating personnel must be familiar with system principles, operating procedures, and safety regulations; operation without proper qualification is prohibited.
- High-pressure ball valve operation:
- When installing or servicing the fire detector tube, the high-pressure ball valve must be closed first to prevent accidental extinguishing agent discharge.
- During normal system operation, the high-pressure ball valve must remain fully open and be marked.
- Randomly opening or closing the ball valve during system operation is prohibited.
- Charging safety:
- Charging should be done with gradual pressure increase — rapid pressurization that impacts the piping is prohibited.
- Test pressure must not exceed specified values to prevent overpressure damage to the fire detector tube.
- Charging fittings must be securely connected; personnel should stay clear of the direct front of fittings.
- Pressure relief: Pressure relief should be performed slowly to avoid sudden pressure drops that impact components.
- Discharge testing: When performing actual discharge tests, personnel must evacuate the protection zone to prevent extinguishing agent frostbite or asphyxiation.
- Pressure calibration: System pressure gauges should be calibrated periodically to ensure accurate readings.
- Environment temperature: System operating environment temperature should be within 0°C–50°C; temperature control measures or special specification products should be used outside this range.
- No unauthorized modifications: After the system is placed into service, arbitrarily adding or removing components, changing pipe routing, or adjusting pressure switch set points is strictly prohibited.
Dedicated Management: The user unit shall designate a dedicated person responsible for the daily management and maintenance of the system. Management personnel shall be trained and familiar with system performance and operating procedures.
Inspection System: Establish a regular inspection system, maintain inspection records, and promptly address any abnormalities detected.
Warning Signs: Clear gas fire suppression warning signs shall be posted at the entrance of the protected area, indicating the system type and precautions.
Personnel Evacuation: When personnel are working in the protected area, ensure they are familiar with the system characteristics and evacuation routes. Personnel shall not remain in carbon dioxide system protected areas for extended periods.
Hot Work Management: When hot work is performed in the protected area, reliable fire prevention measures shall be taken. If necessary, the system may be temporarily disabled and restored after completion of the work.
Discharge Delay: Indirect-type total flooding system protected areas shall be equipped with delayed discharge and audible/visual pre-alarm to ensure personnel have adequate time to evacuate.
Ventilation Requirements: After system discharge, the protected area must be thoroughly ventilated before personnel enter.
Documentation Management: Establish a system technical archive, retaining product data, installation records, commissioning reports, maintenance records, etc.
Extinguishing Agent Safety:
- Heptafluoropropane (HFC-227ea): Essentially harmless to humans at normal usage concentrations, but has anesthetic effects at high concentrations. Avoid prolonged exposure.
- Perfluorohexanone: Extremely low toxicity and good safety profile, but direct contact and inhalation should still be avoided.
- Carbon Dioxide: Poses a suffocation hazard. Do not enter the protected area immediately after discharge; ventilation and gas displacement are mandatory.
High-Pressure Safety: System cylinders are high-pressure vessels. Impact, heating, and unauthorized disassembly are strictly prohibited.
Frostbite Risk: Rapid discharge of extinguishing agent produces low temperatures; direct contact may cause frostbite.
Noise Protection: The instantaneous discharge produces significant noise; close proximity may cause hearing damage.
Emergency Handling: In the event of accidental discharge, immediately evacuate personnel, activate ventilation, and only enter for inspection after the gas has fully dispersed.
Maintenance Safety: System maintenance shall be performed by qualified professionals. System must be fully depressurized before any component disassembly, and it must be confirmed that no pressure remains.
Cylinder Transport: Extinguishing agent cylinders are pressure vessels. Transport shall comply with dangerous goods transport regulations, with cylinders kept upright, securely fastened, and protected against impact.
Fire Trace Tube Storage:
- Store in a cool, dry place away from direct sunlight.
- Keep away from heat sources and corrosive gases.
- Store in coiled form; do not stack heavy items on top or bend sharply.
- Recommended storage temperature range: -10°C to 40°C.
Component Storage: Precision components such as valves, pressure gauges, and fittings shall be stored in their original packaging, protected from moisture, dust, and impact.
Shelf Life: Products are guaranteed for a shelf life of 1 year under specified storage conditions.
Pre-Installation Inspection: Products stored for extended periods shall be inspected for appearance and pressure before use, and only installed after confirming normal condition.
- It is strictly prohibited to hang or bind any items on the system piping.
- It is strictly prohibited to disassemble key components such as container valves and safety relief devices without authorization.
- It is strictly prohibited to test fire trace tubes with open flames or high-temperature objects (except during professional testing).
- It is strictly prohibited to apply paint or coatings to fire trace tubes, which may affect temperature sensing performance.
- It is strictly prohibited to store large quantities of combustible materials in the protected area beyond the designed protection capacity.
- It is strictly prohibited to arbitrarily seal off or enlarge openings in the protected area, which would affect extinguishing concentration retention.
- It is strictly prohibited to use the system pressure gauge for any other purpose.
- It is strictly prohibited to loosen any fitting or valve component without first depressurizing the system.
The fire trace tube gas fire suppression system has a simple structure and high reliability, but proper maintenance is essential to ensure long-term stable operation and readiness. The user unit shall establish a comprehensive maintenance system with regular inspections and servicing.
13.1 General Maintenance Principles
Responsible Party: The user unit is responsible for system maintenance and shall designate full-time or part-time management personnel for routine work.
Qualification Requirements: Professional repair and refilling work shall be performed by qualified fire protection technical service organizations or the manufacturer.
Inspection Frequency: Routine inspections shall be conducted at least once per month, quarterly inspections once per quarter, annual inspections once per year, and periodic inspections as required by regulations.
Record Keeping: All maintenance work shall be properly documented and archived for reference.
System Status: During maintenance, measures shall be taken to ensure system safety, and the system shall be promptly restored to normal operation after maintenance is completed.
13.2 Monthly Inspection
A routine inspection shall be conducted monthly, covering the following:
13.2.1 Cylinder Assembly Inspection
Check the cylinder exterior for:
- Impact deformation, corrosion, or coating peeling
Check cylinder mounting:
- Whether brackets and clamps are secure and free from loosening
Check container valve:
- For damage or leakage; ensure all port plugs are intact
Check container pressure gauge:
- Needle should be within the green normal zone
- Compare with previous records for significant pressure drops
- Check for gauge damage, water ingress, or blurred dial
Check nameplate and markings: confirm they are legible and complete.
13.2.2 Piping Inspection
Check the fire trace tube:
- Whether fixation is secure and tube clips are intact
- Surface for damage, cracking, or aging
- For signs of pinching, pulling, or heat damage
- Whether routing has been altered or obstructed
Check the discharge pipe (indirect type): for deformation, corrosion, or loosening.
Check nozzles: for blockage, damage, or displacement.
Check fittings: for signs of leakage at all connection points.
13.2.3 Terminal Component Inspection
Check the terminal pressure gauge: pressure indication normal, dial clear.
Check the pressure switch: exterior intact, wiring secure.
Check the audible/visual alarm: exterior intact, indicator lights normal.
Check wall penetration sleeves: intact, no displacement, sealing intact.
13.2.4 Electrical and Interlock Inspection
Check power supply: voltage normal, indicator lights normal.
Check terminal blocks: no loosening, oxidation, or detachment.
Test audible/visual alarm: manual test function normal.
Check interlock status: fire alarm control panel displays normally, no fault signals.
13.2.5 Environmental Inspection
Check the protected area: whether structure has changed or openings have increased.
Check combustibles: whether significant quantities of new combustible materials have been introduced.
Check ambient temperature: whether it remains within the permissible range.
Check warning signs: whether intact and legible.
If problems are found during monthly inspections, address simple issues immediately, and report complex issues promptly with a request for professional assistance.
13.3 Quarterly Inspection
A more comprehensive inspection shall be conducted quarterly, adding the following to the monthly inspection items:
13.3.1 In-Depth Visual Inspection
- Carefully inspect the full length of the fire trace tube, focusing on bends, connections, and wall penetration points.
- Check for signs of rodent gnawing or chemical corrosion.
- Tighten all discharge pipe brackets and mounting clamps.
- Inspect nozzle orifices, clean dust and debris to ensure unobstructed flow.
13.3.2 Seal Integrity Spot Check
- Apply soapy water to critical connection points for spot leak testing.
- Observe terminal pressure gauge readings, compare with historical data, and analyze pressure trends.
- Investigate and resolve any significant pressure drops.
13.3.3 Electrical Function Tests
- Thoroughly inspect all terminal connections and tighten loose screws.
- Measure supply voltage to confirm it is within the normal range.
- Simulate test of pressure switch and alarm interlock functions.
- Check backup power supply (if fitted) charge level and functionality.
13.3.4 Protected Area Inspection
- Verify the purpose of the protected area and check for changes in combustible loading.
- Inspect door, window, and penetration sealing conditions.
- Check ventilation system and fire damper operational status.
- Verify evacuation routes and exits are unobstructed.
13.4 Annual Inspection and Maintenance
A comprehensive inspection and maintenance shall be conducted annually, which may be combined with the annual fire protection inspection.
13.4.1 Extinguishing Agent Inventory Check
Heptafluoropropane and Perfluorohexanone Systems:
- Check storage pressure via the container pressure gauge
- Pressure within the normal range qualifies as acceptable
- If pressure is below the lower limit, investigate the cause and replenish the charge
Carbon Dioxide Systems:
- Use the weighing method to check agent charge quantity
- Compare actual weight against the rated charge weight
- If loss exceeds 10%, replenish the charge
- Check nitrogen supercharge pressure; replenish if insufficient
13.4.2 Fire Trace Tube Full Inspection
- Inspect the full length of the fire trace tube for aging, cracking, discoloration, or hardening.
- Check all connection points and re-tighten where necessary.
- For fire trace tubes in service for 3 years or more, it is recommended to sample test with burst testing to verify activation temperature.
- Fire trace tubes in service for 5 years should be completely replaced.
13.4.3 Valve and Component Overhaul
- Check the mobility of moving parts on the container valve; lubricate where necessary.
- Inspect safety relief devices to confirm they are intact and functional.
- Calibrate pressure gauges; replace any that fail.
- Check pressure switch activation values; recalibrate where necessary.
- Clean all optical components and electrical contacts.
13.4.4 System Functional Testing
- Conduct an air tightness (leak) test on the fire trace tube, holding pressure and checking for leaks.
- Conduct full electrical system functional testing, including alarm, interlock, and signal transmission.
- Conduct a simulated activation test to verify valve actuation reliability.
- Simulated discharge testing may be conducted for critical locations.
13.4.5 Cylinder Periodic Inspection
Per the requirements of the Safety Technical Regulation for Gas Cylinders (TSG 23-2021):
- Seamless steel gas cylinders shall undergo periodic inspection every 3 years.
- Inspection shall be conducted by organizations qualified for gas cylinder inspection.
- Cylinders may only continue in service after passing inspection.
- Cylinders that have reached their design service life shall be scrapped and replaced.
13.5 Common Repair Items
13.5.1 Fire Trace Tube Leak Repair
Minor connection leakage: Close the high-pressure ball valve, depressurize the system, then re-tighten the fitting or replace the sealing ring.
Tube wall damage and leakage:
- If damage is near the tube end, cut off the damaged section and re-terminate the fitting.
- If damage is in the middle section, install a straight coupling to join the two sections.
- If damage is severe or there are multiple damaged areas, replace the entire fire trace tube.
After any repair, an air tightness test must be performed, and the system may only be returned to service after passing.
13.5.2 Extinguishing Agent Refill
- After system discharge or when pressure is insufficient, the extinguishing agent shall be replenished promptly.
- Refilling must be performed by qualified personnel in facilities with appropriate equipment.
- Inspect the cylinder before refilling; only proceed when confirmed acceptable.
- Fill quantity and pressure must strictly comply with product technical specifications; overfilling is strictly prohibited.
- After refilling, perform a leak test to confirm no leakage.
13.5.3 Valve Repair
- When container valves develop internal leakage, external leakage, or sluggish operation, professional repair is required.
- Minor faults may be addressed by on-site disassembly, cleaning, and replacement of seals.
- Major faults require removal for factory repair or replacement with a new valve.
- After repair, seal integrity and actuation performance tests must be performed.
13.5.4 Electrical Component Repair
Pressure switch fault: Check the pneumatic path and electrical circuit; replace damaged switch elements.
Audible/visual alarm fault: Check power supply and bulb/LED; replace damaged components.
Wiring fault: Re-crimp terminals and repair damaged cables.
Module fault: Check program and wiring; replace faulty modules.
13.6 Component Replacement Principles
- Replacement components shall be genuine original factory parts or certified products of equivalent specifications.
- Fire trace tubes must be replaced with products of identical material, specification, and activation temperature.
- Seals shall be replaced with new parts of the same material and specification.
- Safety relief devices must not be changed to different specifications; they must match the original design.
- After replacement of key components, corresponding functional tests shall be performed.
- All replacements shall be recorded in the maintenance archive.
13.7 Maintenance Safety Code
- Before performing any maintenance work, the system must be depressurized and confirmed to have zero pressure.
- When disassembling high-pressure components, personnel shall avoid standing in line with the outlet direction to prevent injury from residual pressure.
- When filling or venting extinguishing agents, ensure adequate ventilation to prevent asphyxiation and frostbite.
- Maintenance tools shall be dedicated for their purpose, and operating procedures shall be followed to avoid damaging precision components.
- Open flames are strictly prohibited at maintenance sites; fire extinguishing equipment shall be available.
- After maintenance is completed, a full inspection must confirm everything is correct before the system is returned to operation.
14.1 Abnormal Pressure Issues
Problem 1: Container pressure gauge reading low, below the green zone
*Possible causes:*
- Ambient temperature drop, reducing gas pressure with temperature.
- Minor system leakage causing slow pressure loss over time.
- Pressure gauge fault resulting in inaccurate indication.
- Insufficient extinguishing agent charge.
*Troubleshooting and solutions:*
- Measure ambient temperature and calculate against the temperature-pressure curve; if within normal deviation range, this is normal.
- Apply soapy water to check all container valve connections and gauge fittings for leaks.
- Compare terminal pressure gauge and container pressure gauge readings to determine if the gauge is faulty.
- If the gauge is faulty, replace with a gauge of the same specification.
- If leakage is confirmed, locate and repair the leak point, then refill to the specified pressure.
- For CO2 systems, check by weighing to determine if refilling is required.
Problem 2: Fire trace tube terminal pressure gauge pressure drops rapidly
*Possible causes:*
- Leakage at fire trace tube connections.
- Micro-damage or pinholes in the fire trace tube wall.
- Leakage from the terminal pressure gauge or check valve.
- High-pressure ball valve not sealing properly.
*Troubleshooting and solutions:*
- Close the high-pressure ball valve and observe the terminal pressure gauge:
- If pressure stops dropping, the leak is on the upstream side (container valve side).
- If pressure continues dropping, the leak is on the fire trace tube side.
- Apply soapy water to all connections and tube wall on the trace tube side to locate the leak and mark it.
- For fitting leaks, depressurize, re-tighten, or replace the fitting.
- For tube wall damage, repair or replace per section 13.5.1.
- For terminal pressure gauge leakage, replace the gauge or sealing ring.
- For internal ball valve leakage, overhaul or replace the container valve.
Problem 3: System pressure too high, needle entering the yellow zone
*Possible causes:*
- Ambient temperature too high, causing pressure rise.
- Extinguishing agent overcharged.
- Pressurization set too high during filling.
*Troubleshooting and solutions:*
- Confirm whether ambient temperature is within the allowable range; take cooling measures if temperatures are excessive.
- Verify filling records to confirm whether overcharging occurred.
- If slightly overpressure and the reading drops back after temperature normalizes, continue monitoring.
- If pressure remains high and approaches the safety relief pressure, contact professionals for appropriate venting.
- Never arbitrarily vent pressure yourself to prevent accidental discharge.
14.2 False Activation and Failure-to-Activate Issues
Problem 4: System false discharge — self-activation with no fire
*Possible causes:*
- Abnormal ambient temperature rise; local temperature reached the fire trace tube activation temperature.
- Fire trace tube located near high-temperature equipment, subjected to prolonged heat exposure and aging, bursting prematurely.
- Mechanical damage to the fire trace tube, thinning the wall, leading to rupture under normal pressure.
- System overpressure causing abnormal trace tube burst.
- Fire trace tube quality defect or reaching end of service life.
*Troubleshooting and solutions:*
- Survey the site, locate the burst point and identify the cause.
- Check for high-temperature heat sources near the burst point to confirm whether temperatures exceeded limits.
- Check for signs of mechanical damage.
- Verify system pressure records to confirm whether overpressure occurred.
- Replace the damaged fire trace tube and refill the extinguishing agent.
- Implement corrective measures based on the cause: relocate heat sources, add heat shielding, adjust tube routing, or switch to a high-temperature-rated trace tube.
Problem 5: System does not activate after a fire
*Possible causes:*
- High-pressure ball valve in the closed position, disconnecting the trace tube from the container valve.
- Trace tube pressure fully leaked, insufficient differential pressure to activate the valve.
- Container valve piston sticking, preventing normal actuation.
- Fire trace tube shielded, preventing heat from reaching the tube wall.
- Fire too small in scale; temperature did not reach the activation temperature.
*Troubleshooting and solutions:*
- First check whether the high-pressure ball valve is in the open position and ensure normal operating state.
- Check trace tube pressure; if low, first find and fix leaks, then restore pressure.
- Check container valve actuation mobility; repair or replace if sticking.
- Check trace tube layout; remove obstructions to ensure direct heat sensing.
- For very small low-temperature fires, non-activation is normal; trace tubes are designed for fires of a certain scale.
- Conduct regular simulated tests to verify system activation reliability.
Problem 6: Pressure switch does not activate; no alarm signal
*Possible causes:*
- Pressure switch setpoint not properly adjusted; activation pressure set too low.
- Pressure switch pneumatic path blocked, preventing pressure transmission.
- Pressure switch contacts burned out or mechanical sticking.
- Wiring loose or disconnected.
- Audible/visual alarm or interlock circuit fault.
*Troubleshooting and solutions:*
- Check wiring to confirm circuit continuity and secure terminals.
- Slowly vent pressure to test the pressure switch activation point and adjust to the appropriate pressure setting.
- Check pneumatic path connections and clear blockages.
- Use a multimeter to test contacts and confirm normal open/close operation.
- If the pressure switch is damaged, replace with the same model.
- Test the alarm and interlock circuits separately to locate the fault point.
14.3 Fire Extinguishing Performance Issues
Problem 7: Incomplete extinguishment; fire re-ignition
*Possible causes:*
- Insufficient extinguishing agent quantity; extinguishing concentration not achieved.
- Protected area openings too large, agent escapes quickly, immersion time cannot be maintained.
- Nozzle arrangement unreasonable; blind spots exist in the extinguishing coverage.
- Deep-seated fires or concealed fire sources that agent cannot easily reach.
- Trace tube burst location off-set, causing incorrect agent discharge direction.
*Troubleshooting and solutions:*
- Recalculate protected area volume and agent requirements; add cylinders or upsize as needed.
- Seal unnecessary openings and install automatic closing devices.
- Optimize nozzle arrangement, adjust direction and angle, and eliminate blind spots.
- For deep-seated fires, extend immersion time appropriately or combine with other extinguishing methods.
- Optimize trace tube layout to ensure bursting directly above the most likely fire location.
- For critical locations, consider multiple systems for layered protection.
Problem 8: Agent discharge time too short or too long
*Possible causes:*
- Nozzle orifice diameter too large or too small.
- Fill pressure higher or lower than specified.
- Excessive resistance in the discharge piping.
- Agent charge quantity does not match specification.
*Troubleshooting and solutions:*
- Check nozzle model and specification to confirm they match the design.
- Check system pressure and adjust to the specified value.
- Inspect discharge piping for blockages or kinks and ensure unobstructed flow.
- Verify agent charge quantity and correct deviations.
- Discharge time should fall within the product parameter range; either extreme affects extinguishing effectiveness.
14.4 Appearance and Structural Issues
Problem 9: Cracking or aging on fire trace tube surface
*Possible causes:*
- Extended service life, reaching end of design life.
- Prolonged exposure to high-temperature environments accelerating aging.
- Contact with oils, chemicals, or corrosive substances.
- Direct sunlight exposure causing ultraviolet degradation.
*Troubleshooting and solutions:*
- Check service life; trace tubes approaching or exceeding 5 years should be replaced.
- For minor cracking with normal pressure, increase observation frequency and shorten inspection intervals.
- For severe cracking or signs of leakage, replace immediately.
- Analyze the cause of aging and implement heat shielding, oil protection, and sun-shading measures.
- In harsh environments, select specialty fire trace tubes with enhanced temperature and oil resistance.
Problem 10: Cylinder surface corrosion
*Possible causes:*
- Humid installation environment or presence of corrosive gases.
- Damaged surface coating not repaired promptly.
- Special environments such as coastal or chemical plant areas.
*Troubleshooting and solutions:*
- For minor pitting, remove rust and apply anti-corrosion paint.
- For extensive corrosion or corrosion depth exceeding limits, have the cylinder sent for inspection to determine acceptability.
- Improve the installation environment with ventilation and anti-corrosion measures.
- In severely corrosive environments, select stainless steel cylinders or externally coated corrosion-protected cylinders.
14.5 Electrical Issues
Problem 11: Audible/visual alarm not sounding or lighting
*Possible causes:*
- Power supply failure; no power.
- Wiring loose or disconnected.
- Pressure switch not activated or contacts making poor contact.
- Internal speaker or LED in the alarm device damaged.
- Fuse blown.
*Troubleshooting and solutions:*
- Use a multimeter to measure supply voltage and confirm power is normal.
- Check the fuse and replace with the same rating if blown.
- Check terminal connections and re-tighten.
- Short the pressure switch contacts to test whether the alarm operates, isolating the fault segment.
- If the alarm unit itself is damaged, replace with a new unit.
Problem 12: Fire alarm control panel receiving false alarm signal
*Possible causes:*
- Pressure switch false activation.
- Line interference causing module false reporting.
- Module parameter settings incorrect.
- Loose wiring causing poor contact.
*Troubleshooting and solutions:*
- Check system pressure on site to confirm whether there is an actual pressure drop.
- Check pressure switch status to confirm whether it activated falsely.
- Check line shielding and grounding to eliminate interference.
- Check module parameters and sensitivity settings.
- Tighten terminal connections to ensure good contact.
- For frequent false alarms, replace the pressure switch or module.
14.6 Common Installation and Construction Issues
Problem 13: Leakage at fire trace tube connections
*Cause analysis:*
- Tube end cut unevenly, with burrs or beveled edges.
- Compression ferrule installed in the wrong direction or not tightened.
- Torque insufficient, or over-tightened causing the tube end to split.
- Trace tube outer diameter out of tolerance, not matching the fitting.
*Solutions:*
- Depressurize, disassemble the fitting, and re-cut the tube end to ensure a flat, perpendicular surface.
- Correctly install the compression ferrule, ensuring tight contact with the tube wall.
- Tighten to the specified torque — neither too loose nor too tight.
- Confirm the trace tube and fitting specifications match.
- Replace connections that leak repeatedly with new parts.
Problem 14: Fire trace tube mounting clips falling off
*Cause analysis:*
- Mounting surface not secure.
- Screws loosened.
- Clamp specification mismatch.
- External pulling force on the trace tube.
*Solutions:*
- Replace with a more secure mounting surface or use a more reliable fixing method.
- Tighten screws; add spring washers where necessary to prevent loosening.
- Replace with matching specification clamps.
- Organize the piping to eliminate external pulling forces.
- Increase the number of fixing points at critical locations.
Q1: Does the fire trace tube system require electrical power? Will it still work during a power outage?
A: The core fire suppression function of the fire trace tube system requires no electrical power whatsoever, operating on purely mechanical principles. Even in a complete power failure, fire detection and automatic extinguishing functions are completely unaffected. Only optional auxiliary features such as audible/visual alarms and signal transmission require power; during a power outage, alarm signals may not be transmitted, but the fire suppression itself remains unaffected. This is also a key reason why the fire trace tube system is particularly well-suited for unattended locations and sites with high power outage risk.
Q2: What is the service life of the fire trace tube? Must it be replaced when it expires?
A: Under normal operating environment and maintenance conditions, the design service life of the fire trace tube is 5 years. After reaching the service life limit, the polymer material gradually ages and temperature sensing characteristics and mechanical performance may decline. To ensure system reliability, complete replacement is recommended upon expiry. For trace tubes in good environments with regular inspection confirming good condition, service time may be appropriately extended, but inspection frequency should be increased and performance testing conducted annually. For trace tubes in harsh environments or showing obvious signs of aging, replace them promptly — do not operate beyond the service life.
Q3: After the system discharges once, is refilling troublesome? Is the cost high?
A: After system discharge, the main requirements are replacing the fire trace tube and refilling the extinguishing agent. The process is not complicated and can be completed on site by qualified technical personnel. In terms of cost, it is significantly lower than traditional pipe-network gas suppression systems: firstly, less agent is required; secondly, only the section of trace tube that burst needs replacement — other components are reusable. Typically, the recharging cost of a 6kg heptafluoropropane system is far lower than a traditional system of equivalent protection capacity.
Q4: What types of fires can the fire trace tube system extinguish?
A: The fire trace tube gas fire suppression system is suitable for extinguishing the following fire types:
- Electrical fires: fires in energized equipment such as distribution cabinets, control cabinets, transformers, and cables.
- Liquid fires: fires in combustible liquids such as diesel, lubricating oil, and cutting fluid.
- Solid surface fires: fires on solid surfaces such as wood, plastics, and textiles.
- Gas fires where the gas supply can be shut off before extinguishing.
Not suitable for extinguishing:
- Chemical fires containing oxidizing agents (e.g., nitrocellulose, gunpowder).
- Active metal fires (e.g., potassium, sodium, magnesium).
- Metal hydride fires.
- Fires involving self-decomposing chemical substances.
Q5: How do I choose between direct type and indirect type? What scenarios is each suitable for?
A: Selection principles:
Direct type: Suitable for protecting individual cabinets, small equipment interiors, and other relatively independent small spaces. Advantages include simple structure, easy installation, low cost, and precise extinguishing. Disadvantages include limited protection range and restricted trace tube length.
Indirect type: Suitable for protecting a relatively enclosed small room, a group of cabinets, or larger equipment rooms. Advantages include larger protection coverage and total flooding capability with flexible nozzle placement. Disadvantages include slightly more complex structure and somewhat higher cost.
In simple terms: choose the direct type for single cabinet protection; choose the indirect type for multi-cabinet or small-space overall protection.
Q6: How do I choose among heptafluoropropane, perfluorohexanone, and carbon dioxide?
A: Each of the three extinguishing agents has its own characteristics. Selection recommendations:
Heptafluoropropane (HFC-227ea): Balanced overall performance, high extinguishing efficiency, mid-range price, safe for equipment. It is currently the most widely used mainstream choice, suitable for most electrical equipment, data rooms, and archive rooms.
Perfluorohexanone: Best environmental performance, lowest toxicity, lowest extinguishing concentration, and safer ambient-temperature liquid storage. Suitable for high-end locations with strict environmental requirements, occupied spaces, and particularly precision equipment. Relatively higher cost.
Carbon dioxide: The lowest cost option, no residue after extinguishment, but presents an asphyxiation hazard and cannot be used in occupied spaces. Suitable for unattended warehouses, cable tunnels, and flammable liquid areas.
Q7: Does the fire trace tube system require fire acceptance inspection? Does it comply with regulations?
A: The fire trace tube extinguishing system has clear national and industry standards, including the industry product standard GA 1167-2014 and the engineering construction standard CECS 345:2013, making it a compliant fire protection product. Upon completion of the project, acceptance inspection should be conducted per the applicable regulations, and the system may only be put into service after passing acceptance. For specific acceptance requirements and procedures, refer to Chapter 16 of this manual and the relevant standards.
Q8: Is one direct-type system per cabinet sufficient? How do I determine the quantity?
A: Single cabinet configuration must be determined based on cabinet volume, combustible loading, and fire risk level. For conventional electrical control cabinets:
| Cabinet Volume | Recommended Configuration |
|---|---|
| Up to 0.5 m³ | 2kg heptafluoropropane, direct type |
| 0.5-1 m³ | 3kg heptafluoropropane, direct type |
| 1-2 m³ | 6kg heptafluoropropane, direct type |
| Larger cabinets | Multiple systems or indirect type |
Accurate design should be calculated by qualified professionals based on the specific conditions of the protected object. Do not simply apply volume-based calculations; factors such as combustible type, openings, and ventilation conditions must also be considered.
Q9: Will the fire trace tube burst accidentally? Will high summer temperatures cause false activation?
A: Under normal use conditions, false activation will not occur. The activation temperature of the standard trace tube is 170°C ± 10°C, far above normal summer ambient temperatures. Even at cabinet internal temperatures of 50-60°C in summer, there remains a substantial margin below the activation temperature. The activation temperature of the trace tube is strictly calibrated and will only burst when the set temperature range is reached. However, if the trace tube is directly attached to a component surface generating significant heat, prolonged exposure to high temperatures will accelerate aging and may lower the effective activation temperature. Therefore, regulations require that the trace tube should not be in direct contact with surfaces above 80°C.
Q10: Does the system require on-site staffing? Is the maintenance workload heavy?
A: The system operates fully automatically and does not require dedicated on-site personnel. Daily maintenance workload is very low — mainly a monthly visual check of the pressure gauge to confirm normal pressure and inspect for pipe damage. A slightly more comprehensive check is done quarterly, with a full annual maintenance. Compared to traditional fire protection systems, maintenance workload and cost are significantly lower, making it particularly suitable for distributed, remote, and unattended locations.
Q11: When the fire trace tube bursts, does the entire tube shatter? Will debris damage equipment?
A: No. The fire trace tube is a flexible polymer tube. When it bursts, it simply opens a rupture at the highest temperature point, and the internal gas escapes through that opening. The tube itself does not shatter, and no fragments are produced. The extinguishing agent is discharged smoothly from the opening without causing mechanical damage to surrounding equipment. This is another aspect of the fire trace tube system’s safety.
Q12: Can the system be retrofitted to existing equipment? Will it damage the original equipment?
A: It is highly suitable for retrofit upgrades. The fire trace tube system offers flexible installation without extensive construction work or modification of existing equipment structure. Simply secure the trace tube at appropriate locations inside the cabinet and mount the cylinder beside or inside the cabinet. There is almost no impact on existing equipment, and installation does not require prolonged shutdown, making it an ideal solution for fire protection retrofits of in-service equipment.
Q13: After system activation, will electronic equipment inside cabinets be damaged?
A: No. Heptafluoropropane and perfluorohexanone are both clean gas extinguishing agents with excellent dielectric properties. They fully vaporize after discharge, leaving no residue, and do not corrode circuit boards or cause short circuits. They are very safe for electronic equipment. As long as the agent quantity is designed per code, no damage will occur to equipment. By comparison, water and dry powder extinguishing methods cause significantly greater damage to electronic equipment.
Q14: How long can the fire trace tube be? What is the maximum protection area?
A: The maximum trace tube length depends on the system type and extinguishing agent:
| System Type | Maximum Tube Length |
|---|---|
| Direct type with heptafluoropropane | Typically 25-35m |
| Direct type with carbon dioxide | Typically 25-30m |
| Indirect type (detection only) | Up to 35-40m |
Protection coverage:
- Direct type: Point-to-point local protection; protection area is limited but highly precise.
- Indirect type total flooding: A single system can protect up to several tens of cubic meters.
- Larger spaces can be protected using multiple systems in combination.
Q15: Can the system operate in winter low-temperature environments? What is the minimum temperature?
A: The standard fire trace tube system operating environment temperature range is 0°C to 50°C. Indoor environments generally meet this requirement in winter. For outdoor or unheated locations where winter temperatures drop below 0°C, note the following:
- Ambient temperatures that are too low will reduce system storage pressure, potentially affecting discharge performance.
- The trace tube itself has good low-temperature performance, but extremely low temperatures make it brittle and reduce mechanical performance.
- For locations that truly require low-temperature operation, select low-temperature-rated products or implement insulation measures.
- For the specific minimum operating temperature, consult the manufacturer and select based on actual site conditions.
Q16: Is there an explosion-proof version? Can it be used in flammable/explosive locations?
A: Yes, explosion-proof versions are available. For flammable/explosive hazardous environments such as petrochemical plants, coal mines, and paint spray booths, explosion-proof pressure switches, explosion-proof audible/visual alarms, and other electrical components can be selected, with explosion-proof ratings up to Exd II CT6. The fire trace tube itself is a purely mechanical, passive component that does not generate electrical sparks and is intrinsically safe. However, system design and installation must comply with explosion-proof code requirements and be performed by qualified professionals.
Q17: Do the cylinders require annual inspection? How often are they inspected?
A: Extinguishing agent cylinders are pressure vessels. Per the Safety Technical Regulation for Gas Cylinders, seamless steel gas cylinders undergo periodic inspection every 3 years, performed by organizations qualified for gas cylinder inspection. Inspection items include visual inspection, wall thickness measurement, hydrostatic testing, and pneumatic leak testing. Cylinders that pass inspection may continue in service; those that fail shall be scrapped. In addition to cylinder periodic inspections, the system itself should receive an annual inspection and maintenance.
Q18: In a fire, which comes first — the trace tube burst or the smoke detector alarm?
A: Under typical conditions, the fire trace tube responds faster. Because the trace tube can be placed directly near the fire source and senses temperature rise at close range, while smoke detectors are usually installed on the ceiling and require smoke to spread to a certain concentration before alarming. For fires inside electrical cabinets, smoke must escape the cabinet and reach the smoke detector, which takes time, while the trace tube is already inside the cabinet and activates as soon as temperature rises. In actual testing, the trace tube typically detects a fire tens of seconds to several minutes earlier than traditional smoke detectors, achieving true early suppression.
16.1 General Acceptance Principles
Acceptance of the fire trace tube extinguishing device is the final stage of engineering quality control. Acceptance work shall be strictly performed in accordance with national codes and design documents to ensure reliable system function and qualified quality.
16.1.1 Acceptance Organization
Acceptance is organized by the construction entity, with participation from the design unit, construction unit, supervision unit, and fire protection technical service organization.
Fire protection supervisory authorities may be invited for oversight or filing purposes as needed.
Acceptance personnel shall possess appropriate professional knowledge and qualifications.
16.1.2 Acceptance Basis
- Technical Specification for Fire Trace Tube Extinguishing Devices, CECS 345:2013
- Code for Construction and Acceptance of Gas Fire Extinguishing Systems, GB 50263
- Fire Trace Tube Extinguishing Equipment, GA 1167-2014
- Approved construction drawing design documents and design change records
- Product factory certificates, inspection reports, and instruction manuals
- Construction records, commissioning records, and concealed work acceptance records
16.1.3 Technical Documents to be Submitted Prior to Acceptance
The construction entity shall submit the following technical materials for acceptance review:
- Acceptance application report
- Construction drawing design documents and design change written records
- Equipment factory inspection reports, product certificates, and operation and maintenance manuals
- Cylinder inspection reports and filling records
- Construction records (including concealed work acceptance records)
- Commissioning records and commissioning reports
- Incoming inspection records for system components and materials
- Management personnel registration forms and training records
16.2 Appearance and Installation Quality Acceptance
16.2.1 Cylinder Assembly Acceptance
- Quantity, model, specification, and markings of extinguishing agent storage containers shall comply with design requirements.
- Cylinder exterior shows no obvious damage or corrosion; coating intact; nameplate legible.
- Installation location correct; fixation secure; verticality deviation not exceeding 5‰.
- Operating space meets requirements for ease of operation and maintenance.
- Container valve components complete, correctly installed, and free from damage.
- Pressure gauge indicates normally within the green working zone.
- High-pressure ball valve in open position with clear indication marking.
16.2.2 Piping Acceptance
- Model, specification, and length of fire trace tube and discharge piping comply with design requirements.
- Piping layout reasonable, plumb and level, securely fixed.
- Fire trace tube clip spacing ≤ 500mm; discharge pipe clip spacing ≤ 1500mm.
- Piping bends natural, minimum bend radius conforms to requirements; no sharp kinks or flattening.
- Wall/floor penetrations fitted with sleeves and properly sealed.
- All connections secure with no signs of leakage.
- Three-way branch outlets installed horizontally per code requirements.
- Distance from trace tube to protected object ≤ 1m; not in direct contact with surfaces above 80°C.
16.2.3 Nozzle Acceptance (Indirect Type)
- Nozzle model, specification, and quantity comply with design requirements.
- Nozzle installation position and discharge direction correct.
- Nozzles free from damage, blockage, and obstruction.
- Nozzles securely fixed with clean orifices.
16.2.4 Terminal Component Acceptance
- Terminal pressure gauge installed in a position convenient for viewing, indicating normally.
- Pressure switch correctly installed with secure wiring.
- Audible/visual alarm installed in a conspicuous position, functioning normally.
- Check valves, safety valves, and other components complete with correct installation direction.
16.2.5 Labeling and Warning Acceptance
- All system component labels clear and correct.
- Conspicuous gas fire suppression warning signs installed at protected area entrances.
- Manual operating devices equipped with operation instructions and anti-inadvertent-actuation measures.
- Piping fitted with medium flow direction indicators.
16.3 Performance and Function Acceptance
16.3.1 Pressure Checks
- Heptafluoropropane and perfluorohexanone systems: Check pressure in each storage container individually; must comply with design requirements and product technical parameters.
- Carbon dioxide systems: Conduct weighing spot checks on 20% of total count; charge quantity deviation not exceeding ±5%. If fewer than 5 cylinders, inspect all.
- Fire trace tube pressure check: Terminal pressure gauge reading normal, no significant leakage.
16.3.2 Air Tightness Test
- The fire trace tube system shall undergo an air tightness test: hold pressure for 24 hours with pressure drop not exceeding 5% of test pressure.
- Alternatively, use the soapy water bubble detection method; no bubbles may form at any connection or along the piping.
- Review construction and commissioning records; the air tightness test must have passed.
16.3.3 Simulated Activation Test
- Simulated activation tests shall be conducted by sampling; sample ratio not less than 5% of total count, and no fewer than 2 units.
- Test method: close the high-pressure ball valve, slowly vent pressure on the trace tube side, and observe whether the container valve activates normally.
- Acceptance criteria: valve actuation responsive and reliable; pressure switch activates normally; audible/visual alarm activates normally.
- Where interlock functions are installed, interlock signals shall be correctly output.
16.3.4 Simulated Discharge Test
- Indirect-type fire trace tube systems shall undergo a simulated discharge test.
- The test shall use nitrogen or compressed air as the simulated medium, with fill pressure consistent with the working pressure of the extinguishing agent.
- Use a heating method to burst the fire trace tube, triggering system discharge.
- Acceptance criteria:
- Trace tube burst location correct and activation reliable
- Container valve opens normally with smooth discharge
- All nozzles discharge evenly with no blockage
- Pressure signals and alarm signals normal
The simulated discharge test shall comply with the relevant provisions of GB 50263.
16.3.5 Electrical Function Acceptance
- Pressure switch actuation accurate; contacts open and close normally.
- Audible/visual alarm sound pressure level ≥ 85dB; strobe functions normally.
- Interlock with the fire alarm system correct; signal transmission accurate.
- Wiring neat, labeling clear, insulation acceptable.
- Backup power supply (if fitted) changeover function normal.
16.4 Protected Area Acceptance
- Division, area, and volume of the protected area comply with design requirements.
- Enclosure structural strength and allowable pressure relief time comply with code requirements.
- Openings in the protected area arranged correctly, with automatic closing devices fitted or compensation accounted for.
- Evacuation routes and exits unobstructed; emergency lighting and evacuation signage functional.
- Ventilation system configured correctly and capable of automatic shutdown during extinguishing.
- No obstructions in the protected area that would impair extinguishing effectiveness.
- Pressure relief openings installed per code requirements (for total flooding systems).
16.5 Acceptance Determination Rules
16.5.1 Qualified Determination
The acceptance shall only be determined as qualified when all acceptance items pass, system functions operate normally, and documentation is complete.
16.5.2 Unqualified Handling
- If general items fail, rectify within a specified period and re-inspect.
- If main control items fail, corrections are mandatory until passing.
- If serious quality hazards exist that cannot be rectified, the acceptance shall be determined as unqualified.
- If re-inspection still fails, the acceptance shall not be approved.
16.5.3 Acceptance Records and Reports
- Acceptance records shall be completed during the process, with signature confirmation from all participating units.
- After passing acceptance, a formal acceptance report shall be issued.
- Acceptance documentation shall be archived by the construction entity for long-term retention.
16.6 Post-Acceptance Work
Upon passing acceptance, the system is officially put into service.
- The construction unit shall hand over the complete set of technical documentation to the user unit.
- Training on operation and routine maintenance shall be provided to user unit management personnel.
- Warranty period and after-sales service arrangements shall be clearly defined.
- The acceptance-qualified label shall be affixed in a conspicuous location on the system.
I. Search Keyword Categories
1. Core Primary Keywords
Fire trace tube gas fire suppression, fire trace tube extinguishing device, trace tube-type extinguishing device, fire trace tube automatic fire suppression system, data room fire trace tube fire protection
2. High-Conversion Long-Tail Keywords
Fire trace tube gas fire suppression installation, fire trace tube wiring and commissioning, fire trace tube installation manual, trace tube extinguishing device installation code, data room gas fire suppression fire trace tube, fire trace tube heptafluoropropane extinguishing device, direct-type fire trace tube extinguishing device, indirect-type fire trace tube extinguishing system, electrical cabinet fire trace tube extinguishing, cabinet automatic fire suppression device
3. Industry Traffic Keywords
Gas fire suppression system, data room gas fire extinguishing, cabinet-type gas fire extinguishing device, automatic fire detection and suppression system, temperature-sensing self-activating extinguishing device, electrical room fire suppression, data center fire protection solution, electrical cabinet fire extinguishing, machine tool automatic fire suppression, charging pile fire suppression system
4. Brand-Specific Keywords
Lain fire trace tube, Guangdong Lain fire protection, Lain smart data room fire protection, Guangzhou fire trace tube manufacturer, Lain fire trace tube extinguishing device, Lain gas fire suppression system
5. Drop-down / Related Search Keywords
Fire trace tube working principle, fire trace tube technical parameters, fire trace tube service life, fire trace tube acceptance standard, fire trace tube maintenance, fire trace tube common faults, fire trace tube installation video, fire trace tube price per set, fire trace tube manufacturer, fire trace tube code and standard
II. SEO Optimization Tag System
1. Core Page Optimization Tags
Page theme: Fire trace tube gas fire suppression installation, wiring, and commissioning manual
Core positioning: Professional full-process technical guide for fire trace tube gas fire suppression systems
Target audience: Fire protection engineering contractors, data room operations personnel, electrical engineers, property management personnel
2. Title Tag
Fire Trace Tube Gas Fire Suppression Installation Wiring Commissioning Manual_Trace Tube Extinguishing Device Technical Parameters_Guangdong Lain Smart Data Room Equipment Co., Ltd.
3. Meta Keywords
Fire trace tube gas fire suppression, trace tube-type extinguishing device, fire trace tube installation and commissioning, data room gas fire extinguishing, heptafluoropropane fire trace tube, direct-type fire trace tube, indirect-type fire trace tube, electrical cabinet automatic fire suppression, Lain fire protection, fire trace tube manual
4. Meta Description
Guangdong Lain Smart Data Room Equipment Co., Ltd. provides a complete technical manual for fire trace tube gas fire suppression systems, covering product introduction, composition, classification, working principles, technical parameters, installation codes, wiring methods, commissioning procedures, maintenance, common faults, and acceptance standards — a full-process guide applicable to data rooms, electrical rooms, electrical cabinets, and more. Service hotline: +86 13538869979
5. H1 Tag
Fire Trace Tube Gas Fire Suppression Installation Wiring Commissioning Manual
6. H2 Tags
Product Introduction, Product Composition, Product Classification, Product List, Product Principles, Product Technical Parameters, Product Functions and Features, Product Application Scenarios, Product Installation, Product Wiring, Product Commissioning, Product Precautions, Product Maintenance and Repair, Product Common Problems and Solutions, Product FAQ, Product Acceptance
7. Internal Link Optimization Tags (Anchors)
Core anchor texts:
- Fire trace tube gas fire suppression
- Trace tube-type extinguishing device
- Heptafluoropropane extinguishing system
- Data room gas fire suppression
Long-tail anchor texts:
- Fire trace tube installation and wiring method
- Trace tube extinguishing device commissioning code
- Direct-type fire trace tube working principle
- Indirect-type fire trace tube technical parameters
- Electrical cabinet automatic fire suppression solution
Related anchor texts:
- Data room fire protection solution
- Gas fire extinguishing system construction and acceptance
- Fire protection equipment maintenance
- Data center fire safety
- Electrical room fire protection design
Manufacturer: Guangdong Lain Smart Data Room Equipment Co., Ltd.
Service Hotline: +86 13538869979 (WeChat same number)
Technical Support: +86 13538869979
Company Address: Zhongrun Industrial Park, No. 5 Huashan Road, Shilou Town, Panyu District, Guangzhou
Official Website: https://gdlain.com
This document is copyrighted by Guangdong Lain Smart Data Room Equipment Co., Ltd. and is protected by national copyright law.
No individual or organization may reproduce, redistribute, excerpt, or alter all or part of this document in any form without the written authorization of the company. Where reprinting or citation is required, the source must be acknowledged and the complete copyright information retained.
The contents of this document are subject to update without prior notice; the latest version shall prevail. Product technical parameters and specifications are subject to change; the actual product shall govern. The company reserves the right of final interpretation.
The technical content in this document is compiled based on current national and industry standards and is provided for engineering reference only. Specific projects shall be designed and constructed by qualified professionals based on actual conditions. The company accepts no liability for losses resulting from improper use of this document.