Table of Contents
ToggleForeword

This manual has been compiled by Guangzhou Lain Intelligent System Development Co., Ltd. in accordance with national and industry standards including GB 50174-2017 *Code for Design of Data Centers*, GB 50009-2012 *Load Code for the Design of Building Structures*, GB 50017-2017 *Standard for Design of Steel Structures*, and YD/T 2319-2011 *Technical Requirements and Test Methods for Network Racks Used for Data Equipment*. It provides full-process guidance for the installation, wiring, commissioning, acceptance inspection, operation and maintenance, and fault diagnosis of the company’s full range of rack load-bearing base products.
This manual covers the key technical points across the entire product lifecycle, aiming to provide a standardized operating basis for data center construction units, construction contractors, and operation and maintenance units, ensuring the safe and reliable operation of the rack load-bearing base system. It effectively addresses core issues such as insufficient data center floor load-bearing capacity, rack levelness deviation, seismic reinforcement, cable management, and electrostatic protection. All operating personnel must read this manual carefully and strictly comply with it. Improper operation may result in structural failure, equipment damage, personal injury, and other safety accidents.
Manual version: V2.6.202607, Release date: July 15, 2026. Our company reserves the right to update and revise the contents of this manual. Any technical upgrades or specification changes will be announced separately, without individual notification.
Chapter 1 Product Introduction

1.1 Product Definition
A rack load-bearing base, also known as a rack load distribution frame, equipment pedestal, or rack load-bearing foundation base, is a dedicated load-bearing structural component installed between the data center floor and the bottom of a rack. Its core function is to evenly distribute the concentrated load of the rack and its internal equipment over a larger floor slab area, reducing the load per unit area of the floor slab, and bringing the data center floor slab load into compliance with national code requirements. At the same time, it achieves composite functions including precise rack leveling, seismic reinforcement, bottom-side cable routing, electrostatic discharge, and moisture/humidity isolation. It is a core foundational component of the load-bearing reinforcement system for modern data centers, telecommunication equipment rooms, secure computer rooms, and industrial control rooms.
1.2 Product Development Background
With the rapid development of the digital economy, the power density of data center racks has continued to rise, escalating rapidly from the traditional 2–3 kW/cabinet to 8–15 kW/cabinet. High-density liquid-cooled racks have even exceeded 50 kW/cabinet, with the corresponding fully loaded weight of a single rack growing from 800 kg to over 3,500 kg — far exceeding the design live load standard values of most existing building floor slabs. A large number of existing data centers were constructed in earlier years with floor slab design loads of only 4.0–6.0 kN/m², which cannot meet the deployment requirements of high-density racks. Direct deployment poses safety risks of floor slab cracking, structural settlement, and even collapse.
At the same time, the requirements for rack installation precision, seismic performance, cable management, and electrostatic protection in data center construction have been continuously raised. Traditional direct floor-mounted installation methods can no longer meet the requirements of the latest codes such as GB 50174-2017. Against this background, the rack load-bearing base has emerged as a low-cost, high-efficiency, modular load-bearing reinforcement solution. Without requiring large-scale modification of the building structure, it can rapidly enhance the data center’s load-bearing capacity while incorporating multiple auxiliary functions. It has become a standard configuration for data center construction and renovation.
1.3 Product Development History
The development of rack load-bearing base technology has roughly gone through three stages:
First Generation: Fixed Cement Equipment Pedestals — Early data centers used brick-built or concrete-cast fixed pedestals, which could only achieve an elevation function. Load distribution was poor, height could not be adjusted, construction periods were long, and removal was difficult. These have now been largely phased out.
Second Generation: Simple Steel Base Frames — Made by welding ordinary channel steel and angle steel, these achieved modular production and on-site assembly, with basic load distribution and height adjustment capabilities. However, the structural design had not undergone rigorous mechanical verification, anti-corrosion performance was poor, there was no standardized seismic or grounding design, and safety margins were insufficient.
Third Generation: Standardized Intelligent Load-Bearing Bases — The current main product series of our company, featuring structural design optimized through finite element analysis, high-precision CNC processing technology, and integration of load distribution, three-dimensional adjustment, seismic damping, equipotential grounding, cable management, and waterproof/moisture-proof functions. Some high-end models integrate IoT functions such as intelligent level monitoring and settlement warning, fully complying with the latest national codes and suitable for various high-standard data center scenarios.
1.4 Product Applicable Standards
Our company’s rack load-bearing base products strictly comply with the following standards for design, production, and inspection:
- GB 50174-2017 *Code for Design of Data Centers*
- GB 50009-2012 *Load Code for the Design of Building Structures* (2012 Edition)
- GB 50017-2017 *Standard for Design of Steel Structures*
- GB/T 18663.4-2022 *Mechanical Structures for Electronic Equipment — Tests for Metric and Inch Series — Part 4: Bump, Shock and Vibration Tests for Cabinets and Subracks*
- GB/T 3047.2-2022 *Basic Dimensions Series for Panels, Racks and Cabinets with 20mm Increments in Height*
- YD/T 2319-2011 *Technical Requirements and Test Methods for Network Racks Used for Data Equipment*
- YD 5059-2005 *Code for Seismic Design of Telecommunication Equipment Installation*
- GB 50367-2013 *Code for Design of Strengthening Concrete Structures*
- GB/T 9799-2011 *Metallic and Other Inorganic Coatings — Electrodeposited Coatings of Zinc with Supplementary Treatments on Iron or Steel*
- GB 50169-2016 *Code for Construction and Acceptance of Earthing Installation for Electrical Equipment Installation Engineering*
1.5 Product Core Values
Structural Safety Value: Through optimized load distribution structures, the concentrated load of the rack is equivalently distributed, reducing the per-unit-area load on the floor slab by 30%–70%, eliminating the risk of floor slab cracking and settlement, and ensuring building structural safety.
Economic Cost Value: Compared with traditional data center load-bearing reinforcement solutions such as carbon fiber reinforcement, concrete thickening, and I-beam raised access floors, the cost is reduced by 40%–60%, the construction period is shortened by over 70%, and the product is recyclable and reusable.
Installation Efficiency Value: The modular assembly design requires no on-site welding or hot work. Two people can complete the installation of a single base, greatly shortening the construction period and reducing the impact on normal data center operations.
Operation and Maintenance Convenience Value: Sufficient cable routing space is reserved at the bottom, facilitating the laying and maintenance of power and signal cables. The adjustable height design accommodates raised access floors of different thicknesses. Standardized interfaces facilitate future rack expansion and layout adjustment.
Compliance and Acceptance Value: Fully compliant with various national codes and acceptance standards for data centers and telecommunication equipment rooms, helping projects pass fire protection, lightning protection, seismic, and structural safety special inspections.
Chapter 2 Product Composition

2.1 Main Load-Bearing Frame System
The main load-bearing frame is the core load-bearing component of the rack load-bearing base, directly supporting the entire rack load and distributing it.
- Main Load-Bearing Cross Beams: Made of high-quality carbon structural steel cold-rolled profiles or hot-rolled steel sections, with different specifications selected according to load-bearing grade. These are the primary load transfer path. The surface is treated with rust removal, phosphating, electrostatic powder coating, or hot-dip galvanizing, providing excellent anti-corrosion performance.
- Longitudinal Secondary Beams: Connected perpendicularly to the main cross beams, forming a grid-type load-bearing structure that further distributes the load, enhances overall rigidity, and prevents single-point stress deformation.
- Border Perimeter Beams: Form the outer contour of the base, fixing the overall dimensions, and serving as the mounting substrate for side sealing plates and cable routing holes.
- Corner Connectors: Made of high-strength cast steel parts or thick steel plate bent parts, achieving right-angle connections between cross beams and longitudinal beams. These are critical structural load-bearing nodes, designed with reinforcement ribs to ensure corner torsional and shear strength.
2.2 Support and Leveling System
The support and leveling system provides the connection between the base and the floor, while also serving the functions of height adjustment, level calibration, and load transfer.
- Main Support Feet: Distributed at the four corners of the base and at main cross beam node positions, made of high-strength carbon steel. The upper portion connects to the frame via threads, and the lower portion is fitted with a load-bearing base plate to increase the contact area with the floor.
- Height Adjustment Screws: Trapezoidal thread design with self-locking function. The adjustment range covers 100 mm–500 mm, with adjustment accuracy up to ±0.5 mm. Equipped with lock nuts, the position is locked after adjustment to prevent displacement under long-term loading.
- Load-Bearing Foot Pads: Installed at the bottom of the support feet, made of high-strength nylon or rubber composite material. They increase the friction coefficient to prevent slipping, while also providing cushioning and vibration damping, protecting the floor surface, and isolating moisture.
- Auxiliary Support Columns: For large-size, high-load-bearing models, auxiliary support points are added inside the frame to further reduce the load per support point and enhance overall stability.
2.3 Rack Connection and Fixing System
Used to achieve a reliable connection between the base and the bottom of the rack, ensuring that the rack and base form an integrated unit to prevent displacement and tipping.
- Rack Mounting Holes: Precisely machined to standard 19-inch rack mounting hole spacing, compatible with mainstream domestic and international rack brands. Some models support stepless hole position adjustment to accommodate non-standard dimension racks.
- Fixing Bolt Assemblies: Equipped with M10/M12 high-strength bolts, complete with flat washers and spring washers, ensuring a secure connection with anti-loosening capability.
- Insulating Gaskets: Installed between the rack and base contact surfaces to achieve electrical insulation, preventing electrochemical corrosion between dissimilar metals and interrupting stray current conduction paths.
- Anti-Slip Textured Surface: The top surface of the base features raised textured patterns to increase the friction coefficient with the rack bottom, preventing horizontal sliding of the rack even if bolts become slightly loose.
2.4 Seismic Reinforcement System
Complies with the seismic code requirements of YD 5059-2005, ensuring that racks do not tip over or shift under seismic conditions.
- Lateral Seismic Connectors: Used for horizontal connection between adjacent bases, making an entire row of bases form an integrated load-bearing unit and improving lateral displacement resistance.
- Diagonal Tie Rods: Provided on high seismic grade models. The upper end connects to the upper part of the rack, and the lower end is fixed to the floor or the base, forming a triangular stable structure to resist horizontal seismic forces.
- Damping Vibration Isolators: Some high-end models incorporate high-attenuation rubber damping layers that absorb seismic energy through elastic deformation, reducing vibration acceleration transmissibility and protecting sensitive internal equipment.
- Floor Anchoring Assemblies: Including chemical anchor bolts and expansion bolts, securing the base firmly to the concrete floor to prevent overall sliding.
2.5 Grounding and Electrostatic Protection System
Ensures electrical safety, discharges static electricity, and eliminates potential differences.
- Grounding Terminal Bar: A dedicated grounding terminal is reserved on the base frame, made of brass with tin-plated contact surfaces to ensure excellent electrical conductivity.
- Equipotential Bonding Connectors: When multiple bases are installed in a row, copper braided straps are used for cross-connection, bringing all bases to the same potential and eliminating potential differences.
- Grounding Connection Cables: Supplied with multi-strand copper core yellow-green dual-color grounding cables. The cable cross-sectional area is configured according to the load-bearing grade and code requirements, ensuring reliable grounding current discharge.
2.6 Cable Management System
Utilizes the internal space of the base for the laying and management of power and signal cables in the data center.
- Bottom Cable Routing Channel: The hollow internal space of the base serves as a natural cable routing channel, accommodating power cables, fiber optic cables, and signal control cables, achieving concealed cabling for underfloor air supply data centers.
- Cable Pass-Through Holes: Standard-size cable pass-through holes are pre-drilled on the top surface of the base, equipped with rubber grommets to prevent cables from being cut through their insulation by metal edges.
- Cable Fixing Brackets: Optional cable tie-down brackets can be installed inside the base for securing and organizing laid cables, preventing messy cable accumulation that could obstruct airflow.
- Cable Entry Openings: Openable cable entry openings are reserved on the side surfaces of the base, facilitating cable introduction from the side and accommodating different data center cabling methods.
2.7 Enclosure and Decorative System
Enhances product aesthetics while providing a certain degree of protective function.
- Side Sealing Plates: Made of bent thin steel plates, installed on the four sides of the base to conceal internal structures and cables, enhancing overall aesthetics while preventing rodents and insects from entering.
- Decorative Cover Plates: Cover connection nodes, adjustment screws, and other areas to enhance overall appearance.
- Identification Labels and Nameplates: Product nameplates, warning labels, and grounding identification for operation and maintenance recognition.
2.8 Optional Functional Components
Optional expansion functional components selected based on user requirements:
- Waterproof Cofferdam Assembly: A water-retaining lip is installed around the perimeter of the base to prevent accumulated floor water from entering the bottom of the rack. Suitable for data center areas prone to water leakage.
- Temperature and Humidity Sensors: Sensors installed inside the base for real-time monitoring of the temperature and humidity of the bottom space, with data uploaded through the IoT platform and warning alerts triggered under abnormal conditions.
- Settlement Monitoring Module: High-precision displacement sensors for long-term monitoring of base settlement. An automatic alarm is triggered when the settlement exceeds the threshold, providing early warning of structural safety risks.
- Ventilation and Heat Dissipation Assembly: Ventilation openings and airflow guide plates are added at the bottom, working with the underfloor air supply air conditioning system to optimize airflow organization beneath the racks.
Chapter 3 Product Classification
3.1 Classification by Load-Bearing Grade
3.1.1 Light Duty Load-Bearing Bases (L Series)
- Rated Static Load: 800 kg–1200 kg
- Applicable Scenarios: Standard network racks, distribution racks, small server racks. Suitable for data centers with good floor slab load conditions where only elevation, leveling, and cable routing functions are required.
- Structural Features: 1.5–2.0 mm cold-rolled steel plate bent frame, four-point support, lightweight structure, easy installation.
- Representative Models: LA-L6060, LA-L6080, LA-L6100
3.1.2 Medium Duty Load-Bearing Bases (M Series)
- Rated Static Load: 1200 kg–2000 kg
- Applicable Scenarios: Standard 42U server racks at full load, small UPS cabinets, battery cabinets. Suitable for load-bearing reinforcement scenarios with data center floor slab loads of 6–8 kN/m².
- Structural Features: 2.5–3.0 mm thick steel plate or No. 8 channel steel frame, six to eight support points, reinforced main cross beam design, good load distribution effect.
- Representative Models: LA-M6080, LA-M6100, LA-M8080, LA-M8100
3.1.3 Heavy Duty Load-Bearing Bases (H Series)
- Rated Static Load: 2000 kg–3500 kg
- Applicable Scenarios: High-density server racks, high-power UPS main cabinets, large-capacity battery cabinets, precision air conditioning indoor units. Core load-bearing reinforcement scenarios where data center floor slab load is insufficient.
- Structural Features: No. 10–16 hot-rolled steel sections or welded frames of steel plate 4 mm and above, multi-point support, internal secondary beams forming a grid-type load distribution structure, excellent load distribution capability.
- Representative Models: LA-H8100, LA-H8120, LA-H1010, LA-H1012
3.1.4 Ultra-Heavy Duty Load-Bearing Bases (UH Series)
- Rated Static Load: 3500 kg–8000 kg
- Applicable Scenarios: Immersion liquid-cooled racks, large UPS systems, energy storage battery clusters, heavy industrial control cabinets, and other ultra-heavy equipment. Special reinforcement scenarios with severely insufficient floor slab load.
- Structural Features: H-beam main frame with I-beam secondary beams, dense support point layout, capable of distributing concentrated loads over a multiple-fold larger area. Custom span-beam structures can be provided when necessary to transfer loads directly to the building’s main structural beams.
- Representative Models: LA-UH1012, LA-UH1212, LA-UH1215
3.2 Classification by Structural Form
3.2.1 Individual Independent Bases
Each rack corresponds to a single base, with bases independent of one another, allowing individual installation and individual adjustment.
- Advantages: Flexible layout, adaptable to scattered rack deployment, individual adjustment does not affect other racks, convenient for later position adjustments.
- Disadvantages: Slightly weaker overall integrity when installed in a row, relatively longer installation labor hours.
- Applicable: Scattered racks, new racks added in renovation projects, non-standard layout data centers.
3.2.2 Row-Connected Modular Bases
Modular design; multiple bases can be connected via connectors to form an integrated row structure.
- Advantages: Good overall rigidity, uniform load distribution, easy to maintain row levelness, excellent seismic performance, high installation efficiency.
- Disadvantages: Layout adjustment is relatively troublesome; connectors must be removed for disassembly.
- Applicable: New data center row rack deployment, standardized data center modules.
3.2.3 Integral Welded Bases
Factory-welded as one piece; positioned and installed directly on site.
- Advantages: Highest structural strength, best overall integrity, precision calibrated before leaving the factory, fast on-site installation.
- Disadvantages: Large transport volume, higher cost, dimensions not adjustable.
- Applicable: Ultra-high load-bearing requirements, standardized size batch projects.
3.2.4 Assembled Bases
Fully bolted connection, shipped as loose parts, assembled on site.
- Advantages: Small transport volume, low logistics cost, no hot work required on site, suitable for renovation of existing data centers.
- Disadvantages: Longer installation labor hours, certain skill requirements for installation personnel.
- Applicable: Long-distance transport projects, data centers without lifting equipment, renovation projects.
3.3 Classification by Functional Characteristics
3.3.1 Standard Load-Bearing Type
Takes load distribution and level adjustment as the core functions, meeting basic data center load-bearing reinforcement needs with the highest cost-effectiveness.
- Core Configuration: Main frame + support leveling feet + fixing connectors + grounding terminal.
- Applicable: The vast majority of conventional data center scenarios.
3.3.2 Seismic Reinforced Type
Strengthened seismic design based on the standard type, meeting the seismic requirements of data centers in high-intensity seismic zones.
- Core Configuration: All standard type configurations + damping vibration isolators + lateral reinforcement connectors + floor anchoring assemblies + optional diagonal tie rods.
- Seismic Grade: Capable of meeting seismic fortification intensity of 8 degrees and above.
- Applicable: High seismic intensity regions, critical data centers, core equipment rooms.
3.3.3 Waterproof and Moisture-Proof Type
Designed for humid environments such as basements, low-lying areas, and data centers prone to water leakage.
- Core Configuration: All standard type configurations + waterproof cofferdam + sealing rubber strips + moisture-proof anti-corrosion coating + elevated design.
- Protection Level: Capable of withstanding up to 100 mm of accumulated floor water at the bottom.
- Applicable: Underground data centers, data centers in humid southern regions, data center areas beneath water pipes.
3.3.4 Intelligent Monitoring Type
Integrates IoT sensors for real-time monitoring of base operating status.
- Core Configuration: All standard type configurations + settlement sensors + horizontal inclination sensors + temperature and humidity sensors + data transmission module.
- Functions: Real-time monitoring of settlement, inclination, temperature, and humidity, with automatic alarms under abnormal conditions.
- Applicable: Core data centers, unattended equipment rooms, and high-importance data center areas.
3.3.5 Ventilation and Heat Dissipation Type
Optimized for underfloor air supply air conditioning systems to improve cold air utilization efficiency.
- Core Configuration: All standard type configurations + airflow guide ventilation structure + airflow volume adjustment plates + sealing components.
- Function: Reduces cold air leakage, improves rack inlet air efficiency, and lowers PUE.
- Applicable: Underfloor air supply precision air conditioning data centers, high-density rack data centers.
3.4 Classification by Material
3.4.1 Cold-Rolled Steel Plate Bases
Made of high-quality carbon structural cold-rolled steel plate, formed by CNC bending and welding.
- Features: High processing precision, smooth surface, aesthetically pleasing, capable of complex structures, moderate cost.
- Surface Treatment: Electrostatic powder coating, standard data center colors available including RAL7035 and RAL9005.
- Applicable: The vast majority of indoor data center scenarios.
3.4.2 Hot-Rolled Steel Section Bases
Made by welding hot-rolled steel sections such as channel steel, I-beams, and H-beams.
- Features: High structural strength, strong load-bearing capability, good rigidity, suitable for high-load scenarios.
- Surface Treatment: Rust removal followed by epoxy zinc-rich primer + topcoat, or hot-dip galvanizing.
- Applicable: Heavy and ultra-heavy load-bearing scenarios.
3.4.3 Stainless Steel Bases
Made of 304 or 316 stainless steel.
- Features: Excellent anti-corrosion performance, high cleanliness, aesthetically pleasing and easy to clean.
- Applicable: Cleanroom data centers, food and pharmaceutical industry computer rooms, high-corrosion environment equipment rooms.
3.4.4 Aluminum Alloy Bases
Made by assembling aluminum alloy profiles.
- Features: Light weight, corrosion-resistant, easy to install, no magnetic interference.
- Applicable: Lightweight requirement scenarios, data centers with special electromagnetic requirements.
3.5 Classification by Compatible Rack Dimensions
Common specifications corresponding to standard rack width and depth:
| Base Size (W×D) | Compatible Rack |
|---|---|
| 600×600 mm | Small network racks, floor-standing wall cabinets |
| 600×800 mm | Standard network racks, shallow-depth server racks |
| 600×1000 mm | Standard 19-inch server racks — most commonly used specification |
| 600×1200 mm | Deep-depth server racks, cabling cabinets |
| 800×800 mm | Wide network racks, small UPS cabinets |
| 800×1000 mm | Wide server racks, medium UPS cabinets |
| 800×1200 mm | High-density server racks, large UPS cabinets |
| 1000×1000 mm | Battery cabinets, precision air conditioning units, heavy equipment |
| 1000×1200 mm | Large-capacity battery cabinets, high-power UPS systems |
| 1200×1200 mm | Ultra-heavy equipment, liquid-cooled racks |
Non-standard sizes can be custom-manufactured according to user requirements.
Chapter 4 Product List
4.1 Standard Configuration List (Example: Model LA-M6100)
| No. | Component Name | Specification / Model | Qty. | Material | Remarks |
|---|---|---|---|---|---|
| 1 | Main load-bearing cross beam | 600 mm, 3.0 mm thick | 2 pcs | Q235B cold-rolled steel plate | Front and rear main cross beams |
| 2 | Longitudinal secondary beam | 1000 mm, 2.5 mm thick | 3 pcs | Q235B cold-rolled steel plate | Including center reinforcement beam |
| 3 | Corner connector seat | 80×80×50 mm | 4 pcs | Cast steel | With reinforcement ribs |
| 4 | Main support leveling foot | M16×150 mm | 6 pcs | 45# steel | With lock nut and load-bearing base plate |
| 5 | Rack fixing bolt assembly | M12×30 mm | 8 sets | Grade 8.8 carbon steel | Including flat washer, spring washer, nut |
| 6 | Floor anchoring bolt | M10×100 mm expansion bolt | 6 sets | Galvanized carbon steel | For floor fixing |
| 7 | Grounding terminal | M8 brass terminal | 2 pcs | H62 brass | Tin-plated |
| 8 | Grounding connection cable | 6 mm² yellow-green dual-color, 1 m length | 1 pc | Multi-strand copper core | With copper lug |
| 9 | Equipotential bonding strap | 20×2 mm copper bar, 100 mm | 4 pcs | T2 copper | For cabinet row connection |
| 10 | Insulating gasket | 120×120×3 mm | 4 pcs | Epoxy resin | Rack contact surface |
| 11 | Anti-slip rubber pad | Φ80×5 mm | 6 pcs | Nitrile rubber | At support foot bottom |
| 12 | Side sealing plate | Corresponding dimensions, 1.5 mm thick | 4 pcs | Q235B cold-rolled steel plate | Powder coated |
| 13 | Cable pass-through hole grommet | Φ50 mm | 2 pcs | Rubber | Top surface cable routing holes |
| 14 | Product nameplate | 80×50 mm | 1 pc | Aluminum | Engraved with product information |
| 15 | Installation manual | A4 version | 1 copy | Paper | Including certificate of conformity |
| 16 | Special wrench | 14–17 double-ended | 1 pc | Carbon steel | Installation tool |
4.2 Configuration Differences by Series
| Configuration Item | L Series Light | M Series Medium | H Series Heavy | UH Series Ultra-Heavy |
|---|---|---|---|---|
| Plate thickness | 1.5–2.0 mm | 2.5–3.0 mm | 4.0–6.0 mm / steel section | 8 mm and above / H-beam |
| Number of support points | 4 points | 6–8 points | 8–12 points | 12–16 points |
| Adjustment screw specification | M12 | M16 | M20 | M24 |
| Standard grounding cable | 4 mm² | 6 mm² | 10 mm² | 16 mm² |
| Side sealing plates | Optional | Standard | Standard | Standard |
| Seismic connectors | Optional | Optional | Standard | Standard |
| Floor anchoring assembly | Optional | Standard | Standard | Standard |
| Installation tools | Simple wrench | Special wrench set | Special wrench set | Special tool set |
4.3 Optional Accessories List
| No. | Accessory Name | Compatible Models | Function Description |
|---|---|---|---|
| 1 | Lateral seismic tie rod | All series | Enhances horizontal seismic resistance; recommended for seismic intensity of 8 degrees and above |
| 2 | Damping vibration isolator | M/H/UH series | Built-in rubber damping, reduces vibration transmissibility |
| 3 | Waterproof retaining lip | All series | 30 mm raised water-retaining structure around base perimeter |
| 4 | Cable management rack | All series | Internal cable tie-down and fixing bracket |
| 5 | Settlement monitoring sensor | All series | High-precision displacement monitoring, supports data upload |
| 6 | Inclination sensor | All series | Monitors base horizontal inclination, alarms on abnormality |
| 7 | Temperature and humidity sensor | All series | Monitors bottom space environment |
| 8 | Ventilation airflow guide plate | All series | Optimizes underfloor air supply airflow organization |
| 9 | Cabinet row connection kit | All series | Fixing assembly for connecting multiple bases |
| 10 | Stainless steel upgrade kit | All series | All fasteners replaced with 304 stainless steel |
| 11 | Hot-dip galvanizing upgrade | All series | Surface treatment upgraded to hot-dip galvanizing for stronger corrosion protection |
| 12 | Custom hole opening service | All series | Custom cable routing holes and mounting holes per requirements |
4.4 Technical Documentation List Included with Shipment
- Product Certificate of Conformity: Including product model, factory serial number, date of manufacture, inspector signature, and conformity mark.
- Factory Inspection Report: Including dimensional accuracy inspection, load test sampling records, surface quality inspection, and grounding continuity inspection.
- Installation and Operating Manual: This manual, providing detailed guidance on installation, wiring, commissioning, and maintenance.
- Material Certification Documents: Main steel material test reports, galvanized layer/powder coating thickness test reports.
- Third-Party Test Reports (optional): Load-bearing test, seismic test, and anti-corrosion test reports issued by authorized organizations.
- Warranty Card: Stating warranty period, warranty scope, and service contact information.
4.5 Receiving Inspection and Inventory Instructions
- Upon product arrival, inventory each component quantity and specification against the packing list, and inspect the appearance for shipping damage.
- If missing parts, damage, or specification discrepancies are found, please contact our sales personnel within 3 working days of arrival.
- Store all components and technical documents properly. Do not remove packaging arbitrarily before installation to prevent component loss.
- Consumable parts and standard parts are shipped with a 105% spare ratio; no additional purchase is required within the normal installation loss range.
Chapter 5 Product Principles
5.1 Load Distribution Mechanical Principle
The core working principle of the rack load-bearing base is based on the mechanical principle of equivalent uniform distribution of concentrated loads. The load-bearing capacity of a floor slab structure is typically expressed by the “uniformly distributed live load” (unit: kN/m²) as the design indicator. A rack applies its entire weight to the floor through four feet as concentrated loads. These four extremely small contact points generate enormous local stress far exceeding the floor slab’s uniformly distributed load design value, easily causing local cracking, deformation, or even failure of the floor slab.
The rack load-bearing base, through a frame structure with adequate rigidity, receives the concentrated load from the rack feet, transfers and disperses it through a grid structure composed of main beams and secondary beams, and ultimately distributes the load evenly over a larger floor slab area through multiple support feet. According to Saint-Venant’s principle, the load gradually becomes uniformly distributed during the dispersion process, and the pressure per unit area acting on the floor slab is greatly reduced, bringing the floor slab load-bearing value down to within the allowable design range.
Load Distribution Effect Calculation Formulas:
Load Distribution Factor = Effective load-bearing area of base / Total contact area of rack feet
>
Actual floor surface load = Total rack weight × Safety factor / Effective load-bearing area of base
Example — Standard 600×1000 mm base carrying a 1500 kg rack:
- Total contact area of rack feet: approximately 4 × 0.01 m² = 0.04 m²
- Effective load-bearing area of base: approximately 0.6 × 1.0 = 0.6 m²
- Load distribution factor: approximately 15×, meaning the per-unit-area load on the floor slab is reduced to 1/15 of direct placement — an extremely significant effect.
5.2 Structural Load Transfer Path
The complete load transfer chain is:
Equipment inside rack → Rack cabinet frame → Rack feet → Base top load-bearing plate → Base main cross beams → Base secondary beams → Support leveling feet → Building floor slab → Building beams/columns → Building foundation
Each link has undergone mechanical verification to ensure that strength, stiffness, and stability meet requirements:
- Top load-bearing plate: Bears the local compressive stress of the rack feet; must satisfy local compressive strength requirements without denting deformation.
- Main cross beams: Bending members; bending strength, shear strength, and deflection deformation must be verified. Maximum deflection controlled within L/1000.
- Secondary beams: Auxiliary bending members that further distribute the load and enhance overall rigidity.
- Support feet: Axially loaded compression members; compressive strength and stability verified to prevent buckling.
- Connection nodes: Bolt shear and weld strength verified; node strength not lower than the strength of the components themselves.
5.3 Height Adjustment and Level Calibration Principle
Height adjustment is achieved using the screw transmission principle. The support foot consists of a screw and nut sleeve assembly. The screw is fixedly connected to the base frame, and the nut sleeve connects to the load-bearing base plate. When the nut sleeve is rotated, the thread engagement length of the screw changes through thread transmission, thereby achieving adjustment of the base height at a single point.
The trapezoidal thread has self-locking characteristics, meaning it will not rotate or shift by itself under axial load, ensuring the adjusted height remains stable. With the accompanying lock nut, tightening the lock nut after adjustment forms a dual anti-loosening mechanism, completely eliminating height creep under long-term loading.
By individually adjusting the heights of the four corners and each support point, the levelness of the base top surface can be precisely calibrated, offsetting the effects of floor unevenness and ensuring the rack is in a completely level state after installation, avoiding equipment sliding, door deformation, hard disk vibration, and other problems caused by rack inclination.
5.4 Seismic Working Principle
The seismic design of the rack load-bearing base is based on the combination of “resistance” and “energy dissipation”:
- Rigid Resistance: Through the high-strength frame structure, reliable floor anchoring, firm connection between the cabinet and the base, and integral row connection between bases, a rigid integrated unit is formed. Structural strength is relied upon to resist seismic forces, preventing rack tipping and sliding.
- Damping Energy Dissipation: High-end models incorporate rubber damping layers or spring dampers at support locations. When an earthquake occurs, the damping material undergoes elastic deformation, absorbing and dissipating part of the seismic energy, reducing the acceleration transmitted to the rack, minimizing the impact force on internal equipment, and protecting precision electronic components from damage.
- Displacement Limitation Protection: Lateral limiting structures are provided to control the horizontal displacement of the rack within a safe range, preventing excessive displacement that could cause cable strain and equipment collision.
5.5 Equipotential Grounding Principle
A large number of electronic devices exist in data centers. Static electricity, induced currents, and leakage currents can cause interference or damage to equipment. At the same time, potential differences between different metal components may produce electrical sparks, creating safety hazards.
The rack load-bearing base is reliably connected to the data center’s equipotential grounding system through dedicated grounding terminals, and the metal frame of the base becomes part of the equipotential system. Multiple bases are cross-connected using copper braided straps, ensuring all bases and racks are at the same potential, eliminating potential differences. When static electricity is generated on a rack or a minor leakage current occurs, the current can be rapidly discharged through the path of base → grounding cable → grounding busbar → grounding grid, ensuring the safety of equipment and personnel.
At the same time, the design of insulating gaskets between the base and the rack achieves potential isolation between rack grounding and base grounding, satisfying the zoned grounding requirements of certain special equipment rooms and avoiding ground loop currents.
5.6 Waterproof and Moisture-Proof Principle
Waterproof-type bases achieve waterproof and moisture-proof functions through multiple layers of protection:
- Physical Elevation: The base raises the rack bottom 100–300 mm above the floor, keeping the rack out of the range of accumulated floor water immersion.
- Water-Retaining Cofferdam: Raised water-retaining lips are installed around the perimeter of the base top surface, forming a cofferdam structure. Even if water spills onto the base, it will not flow into the interior of the rack.
- Sealing Treatment: Sealing rubber strips are installed at all assembly gaps to prevent moisture and humidity from entering through the gaps.
- Anti-Corrosion Coating: Metal surfaces use multi-layer anti-corrosion treatment to resist rusting in humid environments.
- Bottom Isolation: Support foot pads are made of water-barrier materials, blocking capillary water from penetrating upward through the floor.
5.7 Intelligent Monitoring Working Principle
Intelligent-type bases integrate multiple sensors and IoT modules:
- Settlement Monitoring: High-precision laser displacement sensors or strain-type sensors are used for real-time monitoring of the vertical displacement at each support point of the base, providing long-term tracking of settlement conditions. An alarm is triggered when cumulative settlement or differential settlement exceeds the threshold.
- Inclination Monitoring: Dual-axis inclination sensors detect the inclination angles of the base in the X and Y directions in real time, determining changes in level status.
- Data Transmission: Data is uploaded to the environment monitoring system or cloud platform via RS485 or wireless LoRa/WiFi.
- Warning Function: Multi-level threshold settings supported. Abnormal conditions notify operation and maintenance personnel through audible/visual alarms, SMS, platform messages, and other means.
Chapter 6 Product Technical Parameters
6.1 Core Performance Parameter Table by Series
| Parameter Item | L Series Light | M Series Medium | H Series Heavy | UH Series Ultra-Heavy |
|---|---|---|---|---|
| Rated static load | 800–1200 kg | 1200–2000 kg | 2000–3500 kg | 3500–8000 kg |
| Rated dynamic load | 600–900 kg | 900–1500 kg | 1500–2600 kg | 2600–6000 kg |
| Safety factor | ≥1.5× | ≥1.6× | ≥1.8× | ≥2.0× |
| Ultimate failure load | ≥2.25× rated | ≥2.4× rated | ≥2.7× rated | ≥3.0× rated |
| Maximum deflection at rated load | ≤1.0 mm/m | ≤0.8 mm/m | ≤0.6 mm/m | ≤0.5 mm/m |
| Height adjustment range | 100–200 mm | 150–350 mm | 200–450 mm | 300–500 mm |
| Level adjustment accuracy | ±0.5 mm | ±0.5 mm | ±0.3 mm | ±0.2 mm |
| Standard number of support points | 4 points | 6–8 points | 8–12 points | 12–16 points |
| Seismic fortification intensity | 6 degrees | 7 degrees | 8 degrees | 9 degrees |
| Grounding resistance requirement | ≤4 Ω | ≤1 Ω | ≤1 Ω | ≤1 Ω |
| Design service life | ≥20 years | ≥25 years | ≥30 years | ≥30 years |
6.2 Structural Dimension Parameters
6.2.1 Standard Width Series (Unit: mm)
- Standard width specifications: 600, 800, 1000, 1200
- Width tolerance: ±1.0 mm
6.2.2 Standard Depth Series (Unit: mm)
- Standard depth specifications: 600, 800, 1000, 1200, 1500
- Depth tolerance: ±1.0 mm
6.2.3 Height Parameters (Unit: mm)
- Minimum installation height (excluding foot pads): 100 (L) / 150 (M) / 200 (H) / 300 (UH)
- Maximum installation height (excluding foot pads): 200 (L) / 350 (M) / 450 (H) / 500 (UH)
- Height adjustment step: 0.5 mm
- Adjustment per turn: 3 mm
6.2.4 Mounting Hole Parameters
- Rack mounting hole spacing: Compatible with standard 19-inch rack hole spacing (465 mm width-direction hole spacing)
- Hole position adjustment allowance: ±20 mm
- Mounting hole diameter: Φ13 mm (for M12 bolts)
- Floor fixing hole diameter: Φ14 mm (for M12 expansion bolts)
6.3 Material and Surface Treatment Parameters
6.3.1 Main Structural Materials
| Component | Material |
|---|---|
| Frame main material | Q235B high-quality carbon structural steel |
| Screw material | 45# high-quality carbon structural steel, quenched and tempered |
| Nut material | 45# steel, trapezoidal thread |
| Connection bolts | Grade 8.8 high-strength carbon steel bolts |
| Grounding terminal | H62 brass, tin-plated surface |
| Insulating gasket | Epoxy resin plate, insulation resistance ≥10¹² Ω |
6.3.2 Surface Treatment Parameters
Electrostatic Powder Coating Type:
- Pre-treatment: Degreasing → Acid pickling → Phosphating → Passivation
- Coating thickness: 60–80 μm
- Adhesion: ≥Grade 1 (cross-cut test)
- Impact resistance: ≥50 kg·cm
- Salt spray test: ≥480 hours without red rust
- Standard colors: RAL7035 light gray, RAL9005 black. Other colors available on request.
Hot-Dip Galvanized Type:
- Zinc layer thickness: ≥85 μm
- Zinc layer adhesion: No peeling or blistering
- Salt spray test: ≥1000 hours without red rust
- Applicable environments: Humid, high-corrosion, outdoor/semi-outdoor scenarios
6.4 Electrical Performance Parameters
| Parameter | Value |
|---|---|
| Frame continuity resistance | ≤0.1 Ω |
| Grounding terminal continuity resistance | ≤0.05 Ω |
| Insulating gasket withstand voltage | ≥2000 V |
| Static discharge time | ≤0.1 s |
| Compatible grounding cable cross-section | 4–16 mm² |
6.5 Environmental Adaptability Parameters
| Parameter | Value |
|---|---|
| Operating ambient temperature | -20 °C ~ +60 °C |
| Storage ambient temperature | -40 °C ~ +80 °C |
| Relative humidity | ≤95% (non-condensing) |
| Altitude | ≤3000 m (derating required above 3000 m) |
| Corrosion protection grade | Indoor C3 grade; hot-dip galvanized type up to C4 grade |
| Flammability rating | Metal components non-combustible; non-metal components V-0 grade |
6.6 Detailed Parameter Tables by Model
6.6.1 L Series Model Parameters
| Model | Dimensions (W×D×H) mm | Rated Static Load (kg) | Support Points | Self-Weight (kg) | Compatible Rack |
|---|---|---|---|---|---|
| LA-L6060 | 600×600×100–200 | 800 | 4 | 12 | 600×600 network rack |
| LA-L6080 | 600×800×100–200 | 1000 | 4 | 15 | 600×800 network rack |
| LA-L6100 | 600×1000×100–200 | 1200 | 6 | 18 | 600×1000 standard rack |
6.6.2 M Series Model Parameters
| Model | Dimensions (W×D×H) mm | Rated Static Load (kg) | Support Points | Self-Weight (kg) | Compatible Rack |
|---|---|---|---|---|---|
| LA-M6080 | 600×800×150–350 | 1200 | 6 | 22 | 600×800 server rack |
| LA-M6100 | 600×1000×150–350 | 1600 | 6 | 28 | 600×1000 standard server rack |
| LA-M6120 | 600×1200×150–350 | 1800 | 8 | 35 | 600×1200 deep rack |
| LA-M8080 | 800×800×150–350 | 1500 | 6 | 26 | 800 wide small UPS cabinet |
| LA-M8100 | 800×1000×150–350 | 2000 | 8 | 32 | 800 wide server rack/UPS |
6.6.3 H Series Model Parameters
| Model | Dimensions (W×D×H) mm | Rated Static Load (kg) | Support Points | Self-Weight (kg) | Compatible Rack |
|---|---|---|---|---|---|
| LA-H8100 | 800×1000×200–450 | 2500 | 8 | 55 | High-density server/medium UPS |
| LA-H8120 | 800×1200×200–450 | 3000 | 10 | 68 | Large UPS/battery cabinet |
| LA-H1010 | 1000×1000×200–450 | 3000 | 9 | 65 | Battery cabinet/precision air conditioning |
| LA-H1012 | 1000×1200×200–450 | 3500 | 12 | 82 | Large-capacity battery cabinet/high-power UPS |
6.6.4 UH Series Model Parameters
| Model | Dimensions (W×D×H) mm | Rated Static Load (kg) | Support Points | Self-Weight (kg) | Compatible Equipment |
|---|---|---|---|---|---|
| LA-UH1012 | 1000×1200×300–500 | 4500 | 12 | 120 | Liquid-cooled rack/large energy storage |
| LA-UH1212 | 1200×1200×300–500 | 6000 | 16 | 150 | Ultra-heavy equipment |
| LA-UH1215 | 1200×1500×300–500 | 8000 | 16 | 185 | Extra-large power equipment |
6.7 Custom Parameter Description
The above are standard model parameters. Products with any size, load capacity, and height can be customized according to user requirements.
Special environments (such as high altitude, strong corrosion, low temperature) can be accommodated with customized models.
Special functional requirements such as explosion-proofing, shielding, and improved waterproof ratings can be specifically designed.
Delivery times for customized products will be extended accordingly based on complexity. Please consult a sales engineer for specifics.
Chapter 7: Product Functions and Features
7.1 Core Load-Bearing and Reinforcement Functions
7.1.1 Efficient Load Distribution
The grid-type mechanical structure design disperses the concentrated load of the cabinet over an area several times its size, effectively reducing the pressure per unit area on the floor slab by 30%-70%, enabling floor slabs that previously did not meet load-bearing requirements to meet safe deployment standards. Optimized through finite element analysis by professional structural engineers, each model undergoes rigorous load-bearing tests and verification, ensuring uniform load distribution without stress concentration points.
7.1.2 Sufficient Safety Margin
The entire product series maintains a safety factor of no less than 1.5 times, with heavy-duty and above products reaching 1.8-2.0 times, significantly higher than the industry standard of 1.2 times. Considering additional loads from equipment expansion, maintenance personnel stepping on the structure, and handling impacts, ample safety redundancy is reserved to ensure no risk of structural deformation under long-term full-load operation.
7.1.3 Low Deflection Control
Structural deflection under rated load is strictly controlled. For heavy-duty products, deflection is ≤0.6mm/m, far below the allowable values specified in steel structure codes. This prevents cabinet tilting or uneven equipment stress caused by base deformation, protecting sensitive components like internal hard drives and fans from additional stress.
7.2 Three-Dimensional Adjustability Features
7.2.1 Wide Height Adjustment Range
The height adjustment range covers 100mm to 500mm, suitable for various raised floor thicknesses (300mm, 350mm, 400mm, etc.), and allows flexible adjustment of the cabinet installation height based on the specific conditions of the machine room floor. The wide adjustment range eliminates the need for customizing different height specifications; one model can adapt to multiple scenarios.
7.2.2 High-Precision Leveling
Individual adjustment points allow for precise leveling with accuracy up to ±0.2~0.5mm. Used with a laser level, extremely high installation flatness can be achieved. This effectively compensates for uneven floors and differential settlement of floor slabs, ensuring cabinet verticality and levelness meet high-standard machine room requirements, preventing issues like doors not closing properly or equipment slide rails jamming.
7.2.3 Self-Locking Stable Structure
The trapezoidal thread design features a self-locking function. Combined with the double locking of the lock nut, the height remains stable and reliable after adjustment, with no automatic sinking or displacement under long-term load. Stability is several times better than standard bolt adjustment, eliminating the risk of gradual tilting over time.
7.3 Seismic Protection Features
7.3.1 Multi-Intensity Seismic Adaptation
Full coverage from seismic intensity 6 to 9. Corresponding product grades can be selected based on the project’s location seismic intensity. Designed strictly according to YD 5059-2005 “Code for Seismic Design of Communication Equipment Installation”, products are verified through seismic tests conducted by authoritative institutions, ensuring cabinets do not topple, shift, or suffer structural damage during earthquakes.
7.3.2 Integrated Seismic System
The entire row of bases is connected into a single unit using bay coupling connectors, enabling collaborative force distribution and significantly enhancing seismic performance compared to individual independent bases. Combined with chemical anchor bolts for ground fixing, secure connections between cabinets and bases, and upper diagonal bracing reinforcement, a complete upper-lower integrated seismic protection system is formed.
7.3.3 Damping and Shock Absorption Protection
High-end models feature a built-in high-damping rubber shock absorption layer, effectively absorbing vibration energy and reducing vibration acceleration transmission rates. This not only withstands earthquakes but also attenuates continuous micro-vibrations generated by machine room equipment like air conditioners and water pumps, reducing failures caused by micro-vibrations such as hard drive bad sectors and loose equipment connectors, thereby extending equipment lifespan.
7.4 Electrical Safety and Static Protection Features
7.4.1 Standardized Equipotential Grounding
Dedicated grounding terminals are pre-installed, offering low resistance and reliable conduction paths. Convenient equipotential cross-bonding is possible when multiple cabinets are installed side-by-side, ensuring the entire cabinet group is at the same potential, eliminating static discharge and signal interference issues caused by potential differences.
7.4.2 Optional Insulation Isolation
Insulating gaskets are configured between the cabinet and the base to achieve electrical isolation, meeting special grounding requirements such as zoned grounding or ground loop suppression. This also prevents electrochemical corrosion caused by contact between different metal materials, extending service life.
7.4.3 Rapid Static Discharge
The metal frame exhibits excellent overall electrical conductivity. Static electricity generated by the cabinet can be quickly discharged through the base to the grounding system, preventing static accumulation from damaging electronic components and ensuring stable equipment operation.
7.5 Cable Management and Maintenance Convenience Features
7.5.1 Concealed Bottom Cabling
The hollow interior of the base serves as a natural cable routing channel, accommodating power cables, network cables, fiber optic cables, etc., enabling concealed wiring that keeps the machine room tidy and aesthetically pleasing while preventing cables from being stepped on or crushed, thus extending cable life.
7.5.2 Flexible Cable Openings
Cable openings can be pre-reserved on both the top and side surfaces, accommodating different cabinet wiring methods like bottom exit or side exit. Rubber grommets are provided to protect cable insulation from being cut by sharp metal edges, eliminating risks of leakage and short circuits.
7.5.3 Removable Maintenance Design
Side covers are fixed with buckles or screws, allowing easy removal for convenient inspection, repair, or expansion of bottom cables at a later stage. Maintenance can be performed without moving the cabinet, significantly reducing maintenance difficulty and downtime risks.
7.6 Installation Convenience Features
7.6.1 Modular Assembly Design
Standard products utilize a bolted assembly structure, shipped as components and assembled on-site without requiring hot work welding. This is particularly suitable for renovation projects of existing machine rooms, avoiding fire risks associated with hot work. Components are highly standardized with good interchangeability.
7.6.2 High Installation Efficiency
Two people can complete the installation. Skilled workers can install a single base in just 15-30 minutes. Installing a whole row is even more efficient. Compared to traditional concrete pedestals or welded load distribution frames, the construction period is reduced by over 70%, enabling rapid delivery and use.
7.6.3 Reusable
All connections use bolts, allowing for easy disassembly, relocation, and reuse. This adapts to needs such as phased machine room construction or layout adjustments, reducing secondary construction costs and aligning with the concept of green data centers.
7.7 Anti-Corrosion and Durability Features
7.7.1 Multi-Layer Anti-Corrosion Treatment
Strict pre-treatment processes plus high-quality surface coatings. Indoor powder-coated type achieves salt spray test resistance ≥480 hours; hot-dip galvanized type ≥1000 hours, effectively withstanding humid, sulfiding, and corrosive gas environments in machine rooms, ensuring a 20-30 year service life.
7.7.2 Bottom Moisture Protection Design
Support foot pads isolate the base from direct ground contact, blocking capillary water rise and preventing bottom corrosion. The base body is elevated to stay out of areas prone to ground water accumulation and moisture, reducing corrosion risk.
7.8 Aesthetics and Environmental Adaptation Features
7.8.1 Standardized Appearance Design
Smooth surfaces, uniform seams, colors consistent with standard cabinets, resulting in a coordinated and aesthetically pleasing overall appearance. Side covers conceal internal structures and cables, providing a clean and unified visual effect for the machine room.
7.8.2 Full Series Color Customization
Full RAL color customization is available, matching cabinets of any brand or customized according to the machine room’s overall decoration style, meeting the visual requirements of high-end machine rooms.
7.9 Intelligent Expansion Features
7.9.1 Real-Time Status Monitoring
Optional sensors for settlement, inclination, temperature, and humidity can be integrated into the machine room’s environment and power monitoring system (DCIM/BMS), enabling 24-hour continuous monitoring of the base’s operational status, shifting from passive inspection to proactive alerting.
7.9.2 Intelligent Abnormal Alarm
Multi-level threshold settings trigger automatic alarms when settlement or inclination exceeds limits, identifying potential structural safety hazards early and preventing accidents. Data is traceable, facilitating analysis of long-term trends in the machine room floor slab.
7.10 Economic and Environmental Features
7.10.1 Low Comprehensive Cost
Compared to building structural reinforcement solutions, the cost is only 30%-50%, with faster construction and less damage to the building. It also avoids complex approval procedures for structural modifications.
7.10.2 Green and Recyclable
All components are metal, making the product 100% recyclable at the end of its service life, reducing construction waste and aligning with the development direction of green buildings and low-carbon data centers.
Chapter 8: Product Application Scenarios
8.1 Data Center Machine Rooms
8.1.1 Telecom Operator Data Centers
The three major telecom operators and third-party IDC data centers are the primary application scenarios for cabinet load-bearing bases. These machine rooms feature a high number and density of cabinets, high power per cabinet, and significant pressure on floor slab load capacity, with strict requirements for installation standards, seismic resistance, and grounding. Standard and seismic-reinforced bases are widely used for server cabinets, network cabinets, and storage cabinets in IDC facilities, effectively addressing insufficient floor load capacity while enhancing overall standardization.
8.1.2 Enterprise Data Centers
Enterprise data centers built by finance, securities, energy, and transportation industries have extremely high requirements for reliability and security, typically constructed according to Class A machine room standards. These scenarios often select heavy-duty or above bases with intelligent monitoring features to ensure the absolute safety and reliability of core business system infrastructure. Some financial machine rooms may also require stainless steel material or special anti-corrosion treatment.
8.1.3 Edge Data Centers
Edge data centers and small machine rooms distributed across various locations often utilize renovated existing buildings with varying structural conditions. Most floor slabs cannot meet the load requirements of cabinets. Modular, easy-to-install load-bearing bases are the optimal choice for renovation projects, enabling rapid machine room upgrades without extensive civil construction.
8.1.4 Liquid-Cooled Data Centers
High-density data centers utilizing cold plate or immersion liquid cooling technologies can have single-cabinet weights reaching 3-5 tons, far exceeding standard machine room load capacities. Ultra-heavy-duty load-bearing bases combined with load distribution frame structures effectively distribute the load, meeting the deployment requirements of liquid-cooled cabinets. They are essential infrastructure for liquid-cooled data centers.
8.2 Telecommunication Machine Rooms
8.2.1 Core Switch Machine Rooms
Core machine rooms and transmission rooms of telecom operators deploy a large number of switching, transmission, and power equipment. Equipment weights are significant, and seismic requirements are high. The telecommunications industry standard YD/T 2319 explicitly requires mounting bases for raised floor machine rooms. Our products fully comply with telecommunications industry standards and are widely used in various telecommunication machine rooms.
8.2.2 Base Station Machine Rooms
5G base station support rooms and edge computing rooms are characterized by small spaces and heavy equipment. Some are prefabricated buildings or simple structures with limited load capacity. Compact, lightweight load-bearing bases effectively distribute equipment loads while providing waterproof and moisture-resistant capabilities suitable for the complex environment of base station rooms.
8.2.3 Access Network Machine Rooms
Widely distributed access network rooms and optical cross-connect rooms have varying construction standards and flexible equipment placement. Individual load-bearing bases offer flexible installation and can be easily adjusted according to equipment positions, adapting to the diverse needs of access network rooms.
8.3 Electric Power and Industrial Control Machine Rooms
8.3.1 Substation Control Rooms
Relay protection rooms and control rooms in power grid substations and converter stations deploy numerous protection panels, control cabinets, and communication panels with high requirements for equipment stability and seismic resistance. Load-bearing bases enable precise equipment leveling, enhance seismic capacity, and facilitate bottom cable routing. They are widely used in power grid construction and renovation projects.
8.3.2 Industrial Automation Control Rooms
Factory DCS control rooms and PLC cabinet rooms have relatively complex environments with certain vibration and corrosion factors. Industrial-grade load-bearing bases offer superior vibration resistance and anti-corrosion performance, protecting industrial control equipment for stable operation and preventing production accidents.
8.3.3 New Energy Control Rooms
Control rooms and energy storage battery compartments for photovoltaic, wind power, and energy storage stations involve heavy equipment and harsh outdoor or semi-outdoor environmental conditions. Waterproof and anti-corrosion load-bearing bases can withstand harsh environments, ensuring reliable operation of control equipment at new energy stations.
8.4 Special Function Machine Rooms
8.4.1 Secure/Confidential Machine Rooms
Secure machine rooms for government agencies, military, and classified units have special requirements for shielding, grounding, and structural safety. Customizable shielded and equipotential-optimized load-bearing bases are available to meet standards related to confidentiality assessment and classified protection.
8.4.2 Cleanroom Machine Rooms
Cleanrooms in the biopharmaceutical, semiconductor, and precision manufacturing industries have high demands for cleanliness, dust prevention, and easy cleaning. Load-bearing bases made of stainless steel or with high surface quality, featuring no sanitary dead corners, easy cleaning, and no dust generation, meet cleanroom class requirements.
8.4.3 Disaster Recovery Machine Rooms
Disaster recovery centers and emergency command machine rooms typically require high seismic resistance and high reliability to ensure equipment can still operate normally during disasters. Seismic-reinforced bases combined with a complete anchoring system significantly enhance the disaster resilience of these facilities.
8.5 Machine Room Renovation and Upgrade Scenarios
8.5.1 Old Machine Room Load Capacity Upgrade
Early-built machine rooms face significant weight increases as equipment is upgraded, leaving original floor slabs structurally inadequate. Using load-bearing bases for reinforcement avoids damaging the building structure, has a short construction period, and allows for phased upgrades without affecting business operations, making it the preferred solution for old machine room renovations.
8.5.2 Machine Room Layout Adjustment
When expanding or repositioning cabinets, existing reinforcement structures cannot be reused. Modular load-bearing bases can be easily disassembled, relocated, and reused, significantly reducing renovation costs and flexibly adapting to layout changes.
8.5.3 Raised Floor Replacement and Modification
When replacing or adjusting the height of raised floors in machine rooms, load-bearing bases can be simultaneously height-adjusted to suit the new floor system, preventing mismatches between cabinet height and the floor.
8.6 Other Application Scenarios
8.6.1 Precision Equipment Foundations
Heavy equipment such as precision air conditioners, UPS mainframes, battery banks, and precision instruments can all use appropriately sized load-bearing bases as installation foundations, providing leveling, vibration damping, and load distribution functions, replacing traditional concrete foundations with faster construction and better adjustability.
8.6.2 Display Cabinets and Operating Consoles
Monitoring center large-screen bases, command console foundations, and display cabinets can also utilize customized load-bearing bases to achieve height adjustment, horizontal leveling, and concealed cable routing, enhancing overall project quality.
8.6.3 Outdoor Cabinet Foundations
Outdoor integrated cabinets and smart streetlight support cabinets can use waterproof load-bearing bases as foundations, elevating equipment to prevent rainwater immersion, while providing secure fixing to withstand wind forces and adapt to complex outdoor environments.
Chapter 9: Product Installation
9.1 Pre-Installation Preparation Work
9.1.1 Technical Preparation
- Familiarize with construction drawings, this manual, and relevant technical specifications; clarify installation position, elevation, and arrangement pattern.
- Verify that the product model, specification, and quantity match the design drawings.
- Conduct technical and safety briefings for installation personnel, clarifying key operation points and safety precautions.
- Confirm the machine room building structure data, understand floor slab structure, load-bearing capacity, and beam/column positions, ensuring reasonable support point locations.
9.1.2 Site Condition Preparation
- Machine room floor construction completed, concrete strength meets design requirements, surface is basically level.
- Machine room decoration, ceiling, and wall construction basically completed, free from large amounts of dust and standing water.
- Temporary power on-site connected, lighting meets construction requirements.
- Clear debris from the installation area floor and keep the site tidy.
- For renovation projects, ensure protection of equipment already in service to avoid affecting operating equipment during construction.
9.1.3 Tool Preparation
| Tool Name | Specification | Purpose |
|---|---|---|
| Laser Level | Accuracy ±0.2mm/m | Leveling calibration, elevation measurement |
| Impact Drill | With Φ14 drill bit | Drilling holes in floor for expansion bolts |
| Torque Wrench | 0-100N·m | Tightening bolts, controlling torque |
| Adjustable Wrench | 12 inch, 10 inch | General bolt tightening |
| Socket Wrench Set | M10, M12, M16, M20 | Tightening corresponding bolt sizes |
| Steel Tape Measure | 5m | Dimension measurement, positioning, layout marking |
| Ink Line (Chalk Line) | / | Snap lines for positioning |
| Angle Grinder | / | Grinding floor protrusions, trimming holes |
| Vacuum Cleaner | / | Cleaning drilling dust |
| Rubber Mallet | / | Gently tapping to adjust position |
| Feeler Gauge | 1-10mm | Checking gaps |
| Multimeter | / | Ground continuity test |
| Earth Resistance Tester | / | Ground resistance test |
9.1.4 Material Preparation
- Inventory and verify the product body and all accessories are complete.
- Auxiliary materials: expansion bolts (if exceeding standard quantity included), copper braided grounding straps, conductive paste, anti-rust paint, sealant, etc.
- Safety protective equipment: safety helmets, gloves, safety goggles, protective footwear, etc.
9.2 On-Site Survey and Layout Positioning
9.2.1 Floor Condition Inspection
- Floor Flatness Check: Use a 2m straightedge and feeler gauge; flatness should be ≤3mm/2m. Grinding or leveling is required if out of range.
- Floor Strength Check: Concrete floor strength should be not less than C20. Floors with dusting or loose texture require hardening treatment first.
- Hollow Area Check: Tap the floor to check for hollow areas. Areas with significant hollow areas are not suitable as support points.
- Verify No Pipes Below: Before drilling, confirm there are no embedded water pipes, electrical conduits, or fiber optic cables beneath the floor to avoid accidents.
9.2.2 Layout Positioning
- Determine the cabinet arrangement baseline according to construction drawings, typically based on machine room columns or walls.
- Use an ink line to snap the installation position boundary lines for the bases, ensuring neat arrangement with straightness deviation ≤2mm/m.
- Mark the floor fixing point positions for each support foot, ensuring accurate points.
- For whole-row installation, first snap the entire row’s baseline, then position each unit individually to ensure overall alignment.
9.2.3 Elevation Datum Setting
- Determine the design elevation of the base top surface based on the raised floor height or design elevation.
- Mark the elevation datum line on walls or columns as a reference for installation leveling.
- Calculate the approximate adjustment height for each support foot and pre-adjust to near the design elevation to improve installation efficiency.
9.3 Base Frame Assembly
9.3.1 Loose Parts Assembly Process (Assembled Products)
1. Remove all parts from packaging, categorize and arrange them, verify quantities.
2. Initially connect the two main beams and two longitudinal beams using corner connectors to form a rectangular outer frame.
3. Install intermediate secondary beams, fix according to drawing positions, do not fully tighten bolts yet.
4. Adjust the frame diagonal dimensions; diagonal deviation ≤2mm to ensure a standard rectangle.
5. Tighten all connecting bolts sequentially in a diagonal pattern, reaching design torque values.
6. Install nut seats for the support feet and initially screw in the adjustment spindles.
7. Check the overall frame dimensions, hole positions for correctness, and check for any deformation.
9.3.2 Assembly Quality Requirements
- Frame Dimensional Deviation: ±1.5mm
- Frame Diagonal Deviation: ≤2mm
- Frame Flatness: ≤1mm (when freely placed on a flat surface)
- Bolt Tightening Torque: M8 bolts 20N·m, M10 bolts 35N·m, M12 bolts 50N·m, M16 bolts 80N·m
- All bolts must be equipped with flat washers and spring washers for reliable loosening prevention.
9.3.3 One-Piece Product Inspection
For products welded and shipped as a single piece, after on-site unpacking, check:
- For deformation, weld cracks, or coating damage during transportation.
- Whether support feet are adjustable freely without jamming.
- Whether installation holes match the drawings.
- If minor coating damage is present, repair on-site with the supplied touch-up paint.
9.4 Base Positioning and Initial Leveling
9.4.1 Base Positioning
- Transport the assembled base to the marked installation position.
- Align the edges, adjust front/back/left/right positions so the base edges coincide with the ink lines.
- Control position deviation within ±1mm.
9.4.2 Initial Leveling
- Rotate the adjustment nuts on each support foot to raise the base completely off the ground.
- Using a laser level, first adjust the height of the four corners so their elevations are basically consistent.
- Then adjust the intermediate support feet so they just touch the ground and bear load.
- After initial leveling, overall levelness should be controlled within 2mm/m. Fine adjustment occurs after fixing.
- Ensure all support feet bear load evenly with no suspended or empty feet.
9.4.3 Elevation Recheck
- Use a level or leveling instrument with a staff gauge to recheck the top surface elevation of the base.
- Deviation from design elevation should be controlled within ±2mm.
- Elevation difference between adjacent bases ≤1mm, ensuring consistent height across the entire row.
9.5 Ground Anchoring and Fixing
9.5.1 Drilling Operation
- Mark drilling positions on the floor through the base’s floor fixing holes.
- Move the base aside. Use an impact drill to drill holes at the marked positions. Hole diameter depends on the expansion bolt specification; hole depth must meet expansion bolt installation requirements (typically M12 bolt hole depth 110mm).
- Drill holes perpendicular to the floor; inclination ≤2°.
- After drilling, clean dust from the holes using a vacuum cleaner to ensure they are clean and free of loose particles.
- If rebar is encountered, adjust the hole position appropriately. It is strictly forbidden to cut structural rebar.
9.5.2 Expansion Bolt Installation
- Insert expansion bolts into the holes, ensuring they are fully seated.
- Gently tap the bolt head with a hammer to drive the expansion sleeve fully into the hole until flush with the floor surface.
- Initially tighten the nut to expand the sleeve and firmly engage with the hole wall.
- Chemical anchor installation must follow product instructions; after injecting the agent, allow it to cure undisturbed; do not touch during the curing period.
9.5.3 Base Fixing
- Reposition the base, aligning the fixing holes with the expansion bolts.
- Fit flat washers and spring washers, then thread on the nuts.
- Tighten the nuts progressively in a diagonal sequence; M12 expansion bolt tightening torque is 50N·m.
- Monitor levelness continuously during tightening to avoid tilting the base.
9.6 Precise Leveling and Calibration
9.6.1 Fine Leveling
- After fixing is complete, perform fine adjustment using a high-precision level.
- Place the level on the top surface of the base in both longitudinal and transverse directions, read deviation values.
- Fine-tune the height of each support foot, adjusting and measuring until levelness meets requirements.
- Standard machine room requirement: levelness ≤1mm/m. High-precision machine room requirement: ≤0.5mm/m.
9.6.2 Locking and Securing
- Once levelness meets requirements, tighten all support foot lock nuts to lock the height.
- Recheck levelness to confirm the locking process did not cause changes.
- All adjustment points must be locked and secure without looseness.
9.6.3 Whole Row Consistency Calibration
- For whole-row installations, after individually leveling each unit, calibrate the straightness and elevation consistency of the entire row.
- Pull a string line to check the front straightness; deviation ≤2mm for the entire row.
- Height difference at seams between adjacent bases ≤0.5mm; seam gap uniform and ≤1mm.
- Install bay coupling connectors to securely connect adjacent bases.
9.7 Cabinet Installation and Positioning
9.7.1 Pre-Installation Preparation
- Recheck that the base top dimensions and holes match the cabinet bottom.
- Apply insulating gaskets at specified positions on the base top surface.
- Clean debris and dust from the base top surface.
9.7.2 Cabinet Hoisting/Transport Positioning
- Use a hydraulic pallet truck or dedicated cabinet moving cart for transport; manually tipping cabinets over is strictly prohibited.
- The tilting angle of the cabinet during transport must not exceed 15° to prevent internal equipment displacement or damage.
- Slowly place the cabinet onto the base, aligning the mounting holes.
- Adjust the cabinet position so all holes are perfectly aligned.
9.7.3 Cabinet Fixing
- Insert fixing bolts from below the base upward through the cabinet’s bottom mounting holes.
- Fit flat washers and spring washers, thread on the nuts.
- Tighten sequentially in a diagonal pattern; M12 bolt tightening torque is 45N·m.
- After fixing, check the cabinet verticality; deviation ≤1.5mm/m.
9.8 Accessory Installation
9.8.1 Side Cover Installation
- Align the side cover with the mounting slots or screw holes.
- Fix with the provided screws, ensuring smooth seams and uniform gaps.
- For locations requiring cable entry, either open the corresponding hole on the side cover or temporarily omit installation.
- After installation, check the appearance for flatness, no warping or deformation.
9.8.2 Cable Opening Treatment
- Knock out the pre-cut cable opening blanks as per actual cabling needs.
- Install rubber grommets to ensure cables are not damaged when passing through.
- Keep unused openings sealed to prevent dust, rodents, and insects from entering.
9.8.3 Labeling
- Affix the product nameplate at a prominent position on the front of the base.
- Affix the grounding label near the grounding terminal.
- Affix warning labels where necessary.
9.9 Installation Quality Self-Inspection
After installation is complete, conduct a step-by-step self-inspection according to the following items:
| Inspection Item | Acceptance Criteria |
|---|---|
| Position Accuracy | Deviation from drawing position ≤5mm |
| Levelness | ≤1mm/m |
| Elevation Deviation | ±2mm |
| Verticality (after cabinet installation) | ≤1.5mm/m |
| Bolt Tightening | All bolts reach specified torque, none missed |
| Ground Continuity | Base and grounding system well connected |
| Appearance Quality | Coating undamaged, accessories complete, appearance clean |
| Safety Check | No sharp burrs, no loose parts |
After passing self-inspection, fill out installation records and submit for acceptance.
Chapter 10: Product Wiring
10.1 Wiring Overview
Wiring for cabinet load-bearing bases primarily refers to grounding system wiring. Bases with intelligent monitoring functions also include sensor power supply and signal wiring. A proper grounding system is crucial for ensuring electrical safety, static protection, and equipment anti-interference, and must strictly follow specifications.
10.2 Grounding System Design Requirements
10.2.1 Grounding Standard Basis
Implement requirements from GB 50169-2016 “Code for Construction and Acceptance of Grounding Devices of Electrical Equipment Installation Engineering” and GB 50174-2017 “Code for Design of Data Centers”:
| Grounding Type | Resistance Requirement |
|---|---|
| Machine Room Safety Protection Grounding | ≤4Ω |
| AC Working Grounding | ≤4Ω |
| DC Working Grounding | Based on system requirements, typically ≤1Ω |
| Lightning Protection Grounding | ≤10Ω |
| Combined Grounding System | Ground resistance ≤1Ω |
10.2.2 Grounding Architecture
Utilize equipotential grounding method; base grounding connects to the machine room’s equipotential grounding grid:
- Each base is equipped with at least 2 grounding terminal points.
- Adjacent bases are cross-bonded using copper braided straps to form an equipotential unit.
- Each row of bases must have at least 2 reliable connection points to the machine room grounding busbar.
- Grounding conductors use multi-strand copper core yellow-green dual-color wires, with cross-sectional area meeting current carrying capacity requirements.
10.2.3 Grounding Conductor Size Selection
| Base Rated Load Capacity | Minimum Ground Wire Cross-Sectional Area | Cross-Bonding Copper Braided Strap Specification |
|---|---|---|
| ≤1500kg | 4mm² | 20×2mm |
| 1500-3000kg | 6mm² | 30×3mm |
| ≥3000kg | 10mm² | 40×4mm |
10.3 Grounding Wiring Construction Process
10.3.1 Construction Preparation
- Prepare grounding wires, copper braided straps, copper lugs, bolts, conductive paste, etc.
- Prepare crimping tools, wire strippers, wrenches, multimeters, etc.
- Confirm the location of the machine room grounding busbar and plan the grounding wire path.
10.3.2 Equipotential Cross-Bonding Between Bases
1. Cut copper braided strap to the appropriate length and crimp wiring terminals on both ends.
2. Connect both ends of the strap to the grounding terminals of adjacent bases.
3. Clean contact surfaces; apply a small amount of conductive paste to reduce contact resistance.
4. Tighten with bolts, ensuring spring washers are compressed flat, guaranteeing reliable contact.
5. Cross-bond bases in the row sequentially to form a continuous equipotential band.
10.3.3 Grounding Down Conductor Connection
1. Select at least 2 grounding points per row of bases, usually at both ends.
2. Cut the grounding down conductor; crimp a copper lug on one end and connect it to the base grounding terminal.
3. Route the other end along the floor or cable tray to the machine room grounding busbar.
4. Grounding down conductors should be laid straight and securely fixed to avoid being stepped on or crushed.
5. Use dedicated grounding bolts for connection to the grounding busbar.
10.3.4 Cabinet and Base Grounding Treatment
- If using the insulating gasket isolation scheme, the cabinet ground is connected separately and does not conduct through the base.
- If no insulation requirement exists, direct contact between cabinet and base is sufficient; cabinet grounding can be discharged through the base.
- Multiple grounding paths with different potentials between the cabinet and base are strictly prohibited to prevent ground loops.
10.4 Wiring for Intelligent Monitoring Bases
10.4.1 Sensor Wiring
- Signal wires for settlement, inclination, and temperature/humidity sensors should use shielded cables.
- Connect power supply positive/negative and signal positive/negative according to the sensor wiring diagram.
- Shield layer should be grounded at a single point, typically at the acquisition end.
- All connections should be properly insulated to prevent short circuits.
10.4.2 Data Transmission Wiring
- When using the RS485 bus method, use RVSP 2×1.0mm² shielded twisted pair wire.
- Connect devices in a daisy-chain (hand-in-hand) topology; avoid star wiring.
- Connect 120Ω terminating resistors at both ends of the bus.
- Connect to the DCIM (Environment and Power Monitoring System) acquisition host.
10.4.3 Power Supply Wiring
- Sensor power supply is typically DC 12V or DC 24V, provided by the machine room DC power supply system.
- Install fuse protection on the power supply line.
- Ensure correct polarity (positive/negative) connections; reverse connection is strictly prohibited as it may damage equipment.
- Confirm voltage level matches equipment requirements before wiring.
10.5 Wiring Quality Requirements
- All electrical connections must be firm, reliable, and have low contact resistance.
- Wiring terminals must be tightly crimped with no looseness, strand breakage.
- Bolt connection contact surfaces must be flat, clean, and provide good conductivity.
- Cable identification should be clear; apply cable number ferrules at both ends indicating the circuit number.
- Wiring should be neat and aesthetically pleasing, secured with ties, and properly strain-relieved.
- Separate strong current (power) and weak current (signal) cables; spacing ≥50mm to avoid interference.
- All exposed conductors must not be left exposed; ensure proper insulation protection.
10.6 Grounding Test
After wiring is complete, grounding tests must be performed:
| Test Item | Method | Acceptance Criteria |
|---|---|---|
| Continuity Test | Measure resistance between base and grounding busbar with multimeter resistance mode | ≤0.5Ω |
| Ground Resistance Test | Measure system ground resistance using a ground resistance tester | Meet design requirements (typically ≤1Ω) |
| Equipotential Test | Measure potential difference between different bases, and between base and cabinet | ≤0.1V |
| Insulation Test | Measure insulation resistance between cabinet and base (if insulation isolation required) | ≥1MΩ |
After passing the tests, fill out the grounding test record as part of the acceptance documentation.
10.7 Wiring Safety Precautions
- Wiring operations must be performed with power disconnected; live work is strictly prohibited.
- Pay attention to tool safety during wire stripping and crimping to prevent cuts.
- Grounding wires must not be connected in series; each point must be directly connected or reliably cross-bonded.
- It is strictly prohibited to connect grounding wires to non-dedicated grounding bodies such as water pipes or heating pipes.
- The grounding system is a safety guarantee; do not arbitrarily remove or disconnect it.
- Pay attention to electrostatic protection when working on intelligent equipment wiring to prevent static damage to sensors.
Chapter 11: Product Commissioning
11.1 Commissioning Overview
Commissioning of the cabinet load-bearing base is a critical step after installation and before formal operation. Through a series of tests and adjustments, it ensures that all performance indicators of the base meet design requirements, safeguarding the subsequent safe operation of cabinets and equipment. Commissioning is divided into two phases: immediate post-installation commissioning and comprehensive commissioning before full-load operation.
11.2 Post-Installation Immediate Commissioning
11.2.1 Geometric Accuracy Check
- Levelness Recheck: Use a frame level with an accuracy of 0.02mm/m to measure in both longitudinal and transverse directions on the base top surface, confirming levelness ≤1mm/m. If not up to standard, fine-tune the support feet again.
- Elevation Recheck: Use a level to re-measure the top surface elevation, confirming deviation from the design value is within ±2mm.
- Verticality Recheck: After cabinet installation, use a magnetic plumb bob or theodolite to measure the cabinet’s front and side verticality, deviation ≤1.5mm/m.
- Straightness Recheck: Pull a steel wire along the front of the entire row of cabinets, measure straightness deviation ≤3mm for the entire row.
11.2.2 Structural Tightness Check
- Use a torque wrench to spot-check all connecting bolts according to specified torque values, including frame connection bolts, cabinet fixing bolts, and ground anchor bolts, ensuring all reach design torque values.
- Check if all lock nuts are fully tightened by attempting to turn them by hand; confirm no looseness.
- Shake the base and cabinet by hand to check overall stability; there should be no obvious shaking or abnormal noise.
- Check if the bay coupling connectors are tight and there is no relative displacement between adjacent bases.
11.2.3 Grounding System Check
- Complete ground resistance and continuity tests as required in Chapter 10, confirming compliance.
- Check all grounding connection points for looseness and oxidation, ensuring long-term reliability.
- Test the conductivity between the cabinet metal casing and the grounding system, confirming a complete grounding path.
11.2.4 Functional Component Check
- Side covers installed securely, easy to open and remove, with uniform gaps.
- Cable opening grommets installed correctly without falling off.
- Labels and nameplates affixed firmly and aligned properly.
- For waterproof bases, check that sealing strips fit well with no gaps.
11.3 Load Testing (Important Item)
11.3.1 Purpose of Load Testing
Simulate actual service loads to verify the deformation, settlement, and stability of the base under rated load, confirming structural safety and avoiding problems after formal loading.
11.3.2 Loading Method
- Sandbag Loading: Use standard counterweight sandbags, uniformly stacked on the base top surface, total weight reaching the rated load.
- Standard Weight Loading: Use standard weights if conditions allow, providing higher accuracy.
- Step Loading: Load progressively in 3-5 stages, observing after each stage, finally loading to 1.0 times the rated load.
- Load should be uniformly distributed, simulating the actual stress state of the cabinet, avoiding concentrated stacking.
11.3.3 Observation Items
| Observation Item | Acceptance Criteria |
|---|---|
| Deflection Observation | Measure deflection change at the mid-span position before and after loading; relative deflection ≤1/1000 of span |
| Settlement Observation | Set settlement observation points next to each support; measure elevation changes before and after loading; settle uniformly, differential settlement ≤0.5mm |
| Structural Deformation Observation | Check for obvious frame deformation, weld cracks, bolt deformation |
| Levelness Change | Re-measure levelness after loading; change ≤0.3mm/m |
11.3.4 Post-Unloading Inspection
1. After static loading at full load for 24 hours, unload in stages.
2. After complete unloading, re-measure deflection and levelness; should essentially recover, residual deformation ≤0.1mm.
3. Check all connection points for looseness or deformation.
4. If abnormal deformation, irreversible deformation, bolt deformation, or other issues occur, prohibit putting into service and contact the manufacturer for analysis and resolution.
11.4 Seismic Performance Commissioning
11.4.1 Anchor Force Spot Check
- Conduct pull-out force spot checks on ground anchor bolts, sampling ratio 5% and no less than 2 bolts. Pull-out force should meet design values with no pull-out or loosening.
11.4.2 Lateral Push Test
- If conditions permit, conduct a simple lateral push test. Apply a horizontal force to the side of the cabinet (1/10 of the rated weight), observe the base displacement. After unloading, the base should return to its original position without permanent displacement, and connecting parts should have no deformation.
11.5 Intelligent Monitoring System Commissioning
11.5.1 Sensor Calibration
- Settlement Sensor Zeroing: Set the zero point based on the current state.
- Inclination Sensor Calibration: Calibrate the zero point while in a level state, correcting installation tilt.
- Temperature/Humidity Sensor: Compare with a standard thermometer/hygrometer; error should be within the allowable range.
11.5.2 Communication Check
- Check if communication between sensors and the data collector is normal and data is uploaded.
- Test integration with the DCIM platform, confirming data displays correctly.
- Test communication stability for 24 consecutive hours with no packet loss or disconnection.
11.5.3 Alarm Function Check
- Simulate overload/over-limit states to test if the alarm function triggers correctly.
- Check all alarm channels such as audible/visual alarm, platform alarm, SMS alarm, etc., for normal operation.
- Verify the rationality of alarm threshold settings; adjust to appropriate values.
11.6 Commissioning Records and Conclusions
- All commissioning items must be truthfully recorded in the commissioning log, including test data, environmental conditions, testing personnel, and testing time.
- Only after all commissioning items pass can the product be officially put into service, with a commissioning acceptance conclusion issued.
- Any non-compliant items must be rectified and re-commissioned until all pass.
- Commissioning records are an important part of the acceptance documentation and should be archived for future reference.
Chapter 12: Product Precautions
12.1 Transportation and Storage Precautions
- Products must be firmly secured during transportation to avoid collision and extrusion, preventing frame deformation and coating damage.
- Components should be packaged separately; bolts and small parts should be bagged to prevent loss.
- The storage area should be dry and well-ventilated, avoiding open-air stacking to prevent moisture and rust.
- When stacking, place wooden pallets underneath, keeping the product at least 100mm off the ground; stacking height should not exceed 2 meters to avoid bending deformation.
- Periodically inspect during storage; handle any rust or deformation promptly.
- Apply anti-rust oil to spindles and threaded parts for protection; avoid contact with mud and sand during storage.
12.2 Installation and Construction Precautions
- Installers must be trained and familiar with the product structure and installation methods, strictly operating according to the manual.
- Safety helmets and protective footwear are mandatory when entering the construction site; safety belts are required when working at heights.
- When using power tools such as impact drills and angle grinders, comply with operating procedures and wear safety goggles.
- Before drilling, confirm there are no pipes beneath the floor; blindly drilling is strictly prohibited.
- Hot work operations (if on-site welding is required) must have a hot work permit, fire extinguishing equipment, and dedicated supervision.
- When multiple people are moving bases or cabinets, ensure unified command and coordinated action to prevent crushing injuries.
- Protect the finished machine room fit-out during installation, avoiding contamination or damage to floors and walls.
- Clean up the site at the end of each workday to keep the machine room tidy.
- It is strictly prohibited to arbitrarily modify the product structure or cut/weld primary load-bearing components. If changes are needed, contact the manufacturer for confirmation.
12.3 Service Load Precautions
- Strictly prohibit using the product beyond its rated load; the total actual use weight must not exceed the product’s rated static load value.
- Loads should be distributed as evenly as possible, avoiding severe eccentric loading; eccentricity must not exceed 1/6 of the base width.
- It is forbidden to apply impact loads to the base; dropping heavy objects onto the base from heights is strictly prohibited.
- Equipment should be placed smoothly onto racks, avoiding sudden pushes or drops that create impact.
- For future equipment expansion, recalculate the total weight; if overloaded, upgrade to a higher load capacity base.
- Persons are prohibited from standing or stepping on the base frame, especially at mid-span positions.
12.4 Environmental Usage Precautions
- Indoor standard models are strictly prohibited from outdoor open-air use.
- Avoid out-of-specification use in strongly corrosive, high humidity, or high-temperature extreme environments; select the appropriate model for special environments.
- Keep the machine room dry to avoid long-term water immersion of the base.
- Avoid contact with corrosive liquids such as acids and alkalis; promptly clean and dry any accidental spills.
- Keep away from heat sources to avoid high-temperature exposure causing coating peeling and material property degradation.
12.5 Maintenance and Operation Precautions
- During routine maintenance, be careful not to arbitrarily loosen primary load-bearing bolts.
- Adjust levelness incrementally; avoid excessive single adjustments that cause cabinet tilting.
- When maintaining the grounding system, ensure power is disconnected to prevent electric shock.
- Before servicing intelligent components, disconnect the power supply first.
- When removing side covers, store them properly to avoid deformation and paint damage.
- It is strictly prohibited to perform welding operations on the base to prevent high temperatures from damaging internal cables or causing fire.
12.6 Electrical Safety Precautions
- The base must be reliably grounded. Do not power on cabinet equipment before grounding is completed.
- Power cables laid at the bottom of the base must be intact and undamaged. Cables with damaged insulation are strictly prohibited from being laid inside the base.
- Strong current and weak current cables should be laid in separate zones to avoid interference caused by mixed laying.
- Regularly inspect cable conditions to prevent rodents from biting through cables and causing short circuits.
- Strictly prohibit unauthorized wiring or temporary connections inside the base.
12.7 Seismic-Related Precautions
- Floor anchoring bolts must be installed as per design requirements. It is strictly forbidden to skip installation for convenience.
- Seismic tie rods, connectors, and other seismic components must not be removed arbitrarily.
- After an earthquake, a comprehensive inspection of the base must be conducted. Use may only be resumed after confirming no structural damage.
- In high seismic intensity areas, regularly check anchoring bolts for loosening.
12.8 Modification and Expansion Precautions
- When relocating cabinets, first unload internal equipment, then move the cabinet and base.
- After reinstallation, re-leveling, re-fixing, and re-testing of grounding must be performed.
- When adding new cabinets, use original manufacturer-provided connection hardware to ensure reliable connections.
- When changing the purpose of use or placing heavier equipment, the load-bearing capacity must be recalculated, and the base replaced if necessary.
12.9 Special Scenario Precautions
- Raised Floor Computer Rooms: The base height should match the raised floor. The top surface of the base should be 1-2mm slightly higher than the floor surface. The floor must not bear cabinet weight.
- Anti-Static Floor Computer Rooms: Pay attention to the positional relationship between the base and floor supports to avoid conflicts. Adjust support point positions if necessary.
- Underfloor Air Supply (Cold Aisle): The base perimeter should be properly sealed to reduce cold air leakage and improve cooling efficiency.
- Computer Rooms with Anti-Static Requirements: Ensure the grounding system meets anti-static requirements. The base surface must not have insulating paint layers that impede static dissipation.
13.1 Routine Maintenance System
Establish a regular maintenance system, incorporating the cabinet load-bearing base into the routine inspection scope of the computer room to ensure long-term reliable operation.
- Daily Inspection: Visual appearance check for obvious abnormalities.
- Monthly Inspection: Check fasteners, appearance, and grounding.
- Quarterly Maintenance: Re-measure levelness, comprehensive tightening, cleaning and dust removal.
- Annual Comprehensive Overhaul: Full performance testing, anti-corrosion inspection, settlement observation.
13.2 Routine Inspection Content
13.2.1 Daily Inspection (Regular Patrol by Operations Personnel)
- Visually observe the base for obvious overall deformation or tilting.
- Observe the ground for signs of settlement or cracking.
- Check if side sealing panels are intact, detached, or damaged.
- Check for water accumulation or debris accumulation at the bottom.
- Listen for abnormal friction sounds or noises.
13.2.2 Monthly Inspection
- Spot-check key connecting bolts for looseness; use a wrench to test tightening.
- Check grounding connection points for looseness or corrosion.
- Check support feet for corrosion or deformation.
- Clean debris around the base, maintain ventilation and dryness.
- Check the operating status of intelligent monitoring equipment.
13.2.3 Quarterly Maintenance
- Comprehensively inspect all visible bolts; retighten according to specified torque.
- Use a level to re-measure base levelness; make minor adjustments if changes are found.
- Clean dust and debris inside the base.
- Check surface coating for peeling or corrosion; promptly touch up paint for minor damage.
- Inspect cables for damage or signs of rodent bites.
- Spot-test grounding resistance to confirm the grounding system is in good condition.
13.2.4 Annual Comprehensive Overhaul
- Comprehensive Structural Inspection: Check the frame for deformation, welds for cracks, and connectors for deformation.
- Comprehensive Levelness & Elevation Re-measurement: Record data and compare with historical data to analyze settlement trends.
- Comprehensive Bolt Tightening: Including concealed areas.
- Anti-Corrosion Inspection: Comprehensively check coating condition; remove rust and repaint corroded areas.
- Grounding System Comprehensive Testing: Full test of grounding resistance and continuity resistance.
- Intelligent Monitoring System Comprehensive Calibration: Functional testing.
- Bottom Cable Comprehensive Inspection and Organization: Arrange and tidy cables.
- Issue Annual Overhaul Report: Evaluate operating status and provide maintenance recommendations.
13.3 Common Maintenance Operation Methods
13.3.1 Level Adjustment
1. Prepare a level and wrenches of appropriate specifications.
2. First, measure to determine the direction and amount of tilt.
3. Slightly loosen the lock nut.
4. Rotate the adjustment nut to adjust height – lower the high side, raise the low side.
5. Adjust and measure simultaneously, approaching the target gradually to avoid overshooting.
6. After adjustment meets standards, retighten the lock nut.
7. During adjustment, observe equipment inside the cabinet to avoid excessive tilting causing equipment displacement.
13.3.2 Bolt Tightening Maintenance
- Use a torque wrench to tighten according to specified torque.
- Tighten in a diagonal sequence to avoid uneven stress.
- Promptly replace stripped or damaged bolts with high-strength bolts of the same specification.
- Apply anti-rust agent to corroded bolts; replace severely corroded ones.
13.3.3 Coating Repair
1. Use sandpaper to grind corroded or peeled areas until bare metal is exposed.
2. Clean dust and oil stains.
3. Apply anti-rust primer, and after drying, apply topcoat.
4. Minor damage can be repaired with matching touch-up paint pens.
5. For large-area coating damage, it is recommended to return to the factory or seek professional treatment.
13.3.4 Grounding System Maintenance
- If grounding terminals are oxidized, sand the contact surfaces and retighten.
- Replace damaged or aged grounding wires promptly.
- Replace copper braided straps if strands are broken or corroded.
- Focus on inspecting the grounding system before the rainy season each year.
13.4 Common Fault Repair
13.4.1 Support Foot Thread Jamming
- Causes: Dirt, corrosion, or insufficient lubrication in threads.
- Repair Method: Clean debris from threads, apply anti-rust lubricating oil, and repeatedly rotate to break in. If severely corroded and cannot be adjusted, replace the support foot assembly.
13.4.2 Local Coating Corrosion
- Causes: Damaged coating or humid environment.
- Repair Method: Remove rust, touch up paint, improve environmental ventilation, locate and eliminate moisture sources.
13.4.3 Bolt Loosening
- Causes: Long-term vibration, thermal expansion/contraction, insufficient initial tightening.
- Repair Method: Retighten to specified torque, replace failed spring washers, and apply thread-locking compound to critical areas.
13.4.4 Side Sealing Panel Deformation or Detachment
- Causes: Impact or improper installation.
- Repair Method: For minor deformation, correct and reinstall. For severe deformation, replace with new side sealing panels.
13.5 Wear Parts and Replacement Cycles
| Wear Part Name | Recommended Replacement Cycle | Remarks |
|---|---|---|
| Rubber Foot Pads | 5-8 years | Replace when aging, cracking, or flattened |
| Rubber Cable Grommets | 8-10 years | Replace when aging or cracking |
| Spring Washers | Replace after every disassembly | Ensure anti-loosening effectiveness |
| Grounding Bonding Strap | 10 years | Replace earlier if severely corroded |
| Sensor Battery (Wireless Type) | 2-3 years | Replace when battery runs low |
13.6 Maintenance Safety Precautions
- When performing maintenance work, ensure the surrounding environment is safe. Set up warning signs if necessary.
- Before adjusting base height, assess the impact on equipment inside the cabinet. Remove heavy equipment if necessary.
- Electrical-related maintenance must be performed with power disconnected.
- When working at height, use a ladder. Stepping on cabinets or the base is prohibited.
- Ensure ventilation during rust removal and painting operations. Wear protective equipment.
- If major issues are discovered, such as structural abnormalities, severe deformation, or abnormal settlement, report immediately to superiors, stop using the equipment, and promptly contact the manufacturer for professional handling.
13.7 Manufacturer After-Sales Service
- Product warranty period: 18 months from factory shipment or 12 months after installation acceptance, whichever comes first.
- Quality issues not caused by human factors within the warranty period will be repaired or replaced free of charge.
- Outside the warranty period, lifetime maintenance service is provided at cost price.
- Services include technical consultation, on-site troubleshooting, and regular follow-up visits.
- Service Hotline: +86 13538869979 (also WeChat ID)
- Technical Support: +86 13538869979
14.1 Installation Problems
Problem 1: Uneven ground makes base leveling difficult
- Possible Causes: Poor ground flatness, excessive height differences.
- Solutions:
- Grind down local protrusions smoothly using an angle grinder.
- Level local depressions using epoxy mortar.
- Use the base’s height adjustment range to compensate; as long as the total deviation is within the adjustment range, leveling can be achieved step-by-step.
- If the height difference is excessive, add flat, anti-rust metal shims under the support feet. Shim count must not exceed 3 pieces.
Problem 2: Drilling meets rebar, unable to install expansion bolts
- Possible Causes: Drilling position hits floor slab reinforcement.
- Solutions:
- Slightly offset the drilling position to avoid rebar, keeping the offset within allowable limits.
- Cutting structural main reinforcement is strictly prohibited.
- If the base fixing holes do not align after offsetting, enlarge or re-drill holes in the base.
- For critical load-bearing areas, use chemical anchor bolts or grouted rebar for reinforcement.
Problem 3: Significant diagonal deviation after base frame assembly
- Possible Causes: Bolts tightened before alignment during assembly, or component deformation during transport.
- Solutions:
- Loosen all connecting bolts, adjust the frame to a rectangle (diagonal deviation ≤ 2mm), then progressively tighten.
- Inspect components for deformation; slight deformation can be corrected, severe deformation requires contacting the manufacturer for replacement.
- Tighten bolts in a diagonal cross sequence to avoid tilting from one-sided tightening.
Problem 4: Cabinet bottom holes do not align with the base
- Possible Causes: Non-standard cabinet hole positions, or base hole position deviation.
- Solutions:
- Confirm cabinet hole dimensions; most cabinet holes have some adjustment allowance.
- For minor deviations, fine-tune cabinet position for alignment.
- For larger deviations, re-drill holes in the base according to actual positions.
- For custom products, provide cabinet hole layout drawings in advance to ensure a match.
14.2 Structural Performance Problems
Problem 5: Excessive deflection, slight sag after full load
- Possible Causes: Load near upper limit, or excessive local load.
- Solutions:
- First, verify total weight is not overloaded. If overloaded, must reduce load or replace with a higher capacity model.
- Check if load distribution is even; place heavy equipment above column positions if possible.
- If within allowable deflection range, this is normal elastic deformation and does not affect safe use.
- If deflection exceeds standards, add auxiliary support points at the bottom for reinforcement.
Problem 6: Abnormal noise from the base
- Possible Causes: Loose bolts, or component friction.
- Solutions:
- Comprehensively check all connecting bolts; retighten any that are loose.
- Check if support feet are evenly loaded; “ghost feet” (not in full contact) can cause noise during load changes.
- For friction noise between metal contact surfaces, apply a small amount of grease.
- Check for deformation causing friction; correct or replace deformed parts.
Problem 7: Tilting occurs after a period of use
- Possible Causes: Ground settlement, or loose bolts.
- Solutions:
- First, check and tighten all bolts.
- Re-measure levelness and re-level based on the tilt amount.
- Check for obvious ground settlement; uniform settlement can be compensated by height adjustment.
- If uneven settlement is severe, assess ground structural safety, and take reinforcement measures if necessary.
14.3 Anti-Corrosion and Appearance Problems
Problem 8: Localized rust spots appear
- Possible Causes: Damaged coating, or humid environment.
- Solutions:
- Remove rust with sandpaper, clean the area, then apply anti-rust primer and topcoat.
- Locate moisture sources, improve ventilation, and prevent water accumulation.
- In coastal or highly corrosive environments, recommend hot-dip galvanized products.
- Conduct regular inspections, detect and address early to prevent rust from spreading.
Problem 9: Surface coating scratches or peeling
- Possible Causes: Collisions or scrapes during handling and installation.
- Solutions:
- Use matching touch-up paint for minor scratches.
- Return to factory for repainting for large-area peeling.
- Provide proper protection during installation and handling to avoid impacts.
14.4 Grounding and Electrical Problems
Problem 10: Grounding resistance does not meet standards
- Possible Causes: High resistance of the grounding grid itself, or poor contact at connection points.
- Solutions:
- Check all connection points, sand contact surfaces, retighten, apply conductive paste.
- Check if the grounding wire is too thin or too long; replace with compliant grounding wire.
- Increase the number of grounding down conductors, using multi-point connections.
- If the overall grounding grid of the computer room is substandard, the grounding grid needs renovation.
Problem 11: Potential difference exists between cabinet and base
- Possible Causes: Poor contact, or connection to different grounding grids.
- Solutions:
- Clean contact surfaces to ensure good metal contact.
- Add dedicated grounding bonding wire connecting the cabinet and base grounding terminals directly.
- If intentional insulation design exists, this is normal; ensure each has reliable independent grounding.
- Avoid excessive potential difference between two grounding grids to prevent ESD damage to equipment.
14.5 Intelligent Monitoring Problems
Problem 12: Sensor data not uploading
- Possible Causes: Wiring fault, power fault, equipment failure.
- Solutions:
- Check if power supply is normal and voltage meets requirements.
- Check communication lines for continuity and loose connections.
- Restart the acquisition equipment and observe if it recovers.
- For hardware failures, contact the manufacturer for repair or replacement.
Problem 13: Large data deviation, inaccurate readings
- Possible Causes: Sensor zero drift, or loose installation.
- Solutions:
- Check if sensor installation is secure and has not shifted.
- Re-calibrate the zero point.
- Compare with manual measurements and correct deviation.
- Replace sensor if damaged.
14.6 Other Common Problems
Problem 14: Rodents or debris inside the base
- Possible Causes: Poor sealing, or missing side sealing panels.
- Solutions:
- Clean debris and rodent traces; implement rodent control measures.
- Install all side sealing panels; seal gaps that are too large.
- Implement fire-resistant sealing for cable entry/exit holes.
- Implement overall rodent prevention measures in the computer room.
Problem 15: Water accumulation at the bottom
- Possible Causes: Leaks in the computer room, condensation water.
- Solutions:
- Locate water source and repair leak points.
- Clean accumulated water, wipe the base dry to prevent corrosion.
- Use waterproof base types in areas frequently prone to water accumulation.
- Provide drainage slope or drainage measures at the bottom.
Q1: Are the cabinet load-bearing base and load distribution frame the same?
A: Essentially both are load-bearing reinforcement components for computer rooms, with similar functions but slightly different connotations. A load distribution frame typically refers to a larger-area, overall load-bearing frame shared by multiple cabinets, spreading load over a larger area. A cabinet load-bearing base generally corresponds to one unit per cabinet, offering higher modularity and more flexible installation. Our product combines the advantages of both – usable independently for a single unit, or connectable into a full row as a load distribution frame.
Q2: How to choose an appropriate load capacity base?
A: First, calculate the total fully-loaded cabinet weight, including cabinet self-weight, all internal equipment, PDU, cables, etc. Then multiply by a safety factor of 1.2-1.5 times, and select a model whose rated static load exceeds this value. If future expansion is planned, it is recommended to reserve margin and choose a higher grade model directly.
Q3: Can a load-bearing base alone solve insufficient floor load capacity?
A: In most conventional scenarios, the base effectively reduces the pressure per unit area on the floor after load distribution, meeting safety requirements. However, if the floor slab itself is insufficient in thickness or strength, or the equipment is extremely heavy, professional structural calculations are still required, possibly combined with other reinforcement solutions like floor slab strengthening or load transfer to main beams. It is recommended to provide building structural drawings for professional engineer evaluation.
Q4: What height should the base be?
A: Mainly based on the height of the raised floor. The top surface of the base should be level with or slightly higher (1-2mm) than the top surface of the floor, ensuring the cabinet weight is fully borne by the base and not the floor. Common raised floor heights are 300mm, 350mm, and 400mm. Select a base model with an adjustment range covering the required height.
Q5: Is it necessary to fix the base with expansion bolts?
A: For general lightweight, low-load scenarios without seismic requirements, leaving expansion bolts out is possible, relying on self-weight and friction for stability. However, according to specifications and seismic design requirements, floor anchoring is mandatory, especially for heavy equipment, high seismic grades, and high center-of-gravity equipment. Expansion bolts must be installed to prevent sliding and tipping.
Q6: Does the base need grounding? Is grounding optional?
A: Grounding is mandatory. As a metal component in direct contact with the cabinet, the base is a critical part of the grounding system. Reliable grounding dissipates static electricity, ensures leakage safety, and shields against electromagnetic interference. Not grounding poses risks of ESD damage to equipment and electric shock hazards, and fails to meet electrical acceptance specifications.
Q7: Can holes be drilled or modifications be made to the base?
A: Small-scale openings on the sides or top in non-primary load-bearing areas, such as cable routing holes, are acceptable if structural safety is not compromised. However, cutting primary load-bearing components such as main beams or main supports is strictly prohibited, as is large-area removal of frame material. If uncertain about structural impact, consult manufacturer’s technical personnel.
Q8: What is the service life of the base?
A: Under normal indoor computer room conditions, the design service life is 20-30 years. The actual lifespan depends on environmental conditions, maintenance, and load levels. In dry environments with good maintenance and no load overload, over 30 years is achievable. Humid and corrosive environments will shorten service life.
Q9: During computer room renovation, can a base be installed without moving the cabinet?
A: Normally, the cabinet needs to be lifted to insert and install the base underneath. If shutdown and relocation are not possible due to constraints, specialized lifting equipment can be used to synchronously lift the cabinet to a certain height, slide the base into position, and then slowly lower the cabinet. This operation requires professional personnel and specialized tools. Do not attempt it yourself to avoid safety accidents.
Q10: Can a seismic base actually withstand earthquakes?
A: Seismic bases are designed according to the corresponding seismic fortification intensity. Under design-basis earthquakes, they ensure cabinets do not tip over, slide, or suffer structural failure, protecting the equipment. However, absolute safety cannot be guaranteed during extreme earthquakes exceeding the design fortification intensity, which is common to all building structures. Seismic performance relies on a complete system including floor anchoring and upper-structure reinforcement.
Q11: Are bases compatible with different brands of cabinets?
A: Standard 19-inch cabinets have generally universal bottom mounting hole patterns. Our standard bases are compatible with the vast majority of mainstream cabinet brands. For a few special brands or non-standard sized cabinets, hole positions can be customized based on provided bottom drawings for a perfect fit.
Q12: Can the base be used with anti-static floors?
A: Absolutely, this is the most common usage scenario. The base is installed on the building floor beneath the raised floor, with the top surface level with the floor, and the floor cut out around the cabinet location. The base itself can also serve as an ESD dissipation path, connecting to the anti-static grounding system.
Q13: Will installing a base affect the performance of underfloor air conditioning?
A: If installed improperly, air leakage through gaps around the base can affect cooling efficiency. With proper perimeter sealing and ventilation/air guiding design, the base can actually help guide airflow into the cabinet, improving cooling efficiency. We offer specialized ventilated bases optimized for underfloor air supply scenarios.
Q14: Is the intelligent monitoring feature necessary?
A: For general computer rooms, regular manual inspections suffice. For core data centers, unattended sites, or highly critical computer rooms, intelligent monitoring provides 24/7 status tracking, detecting potential issues like settlement or tilting early to prevent major accidents – this is very valuable.
Q15: What is the warranty period? What if problems arise?
A: Warranty period is 18 months from factory shipment or 12 months from acceptance, whichever comes first. Quality issues within the warranty period are repaired or replaced free of charge. Beyond warranty, lifetime cost-price repair service is available. For issues, call the service hotline +86 13538869979; technical staff will guide troubleshooting or arrange on-site service if necessary.
Q16: Can third-party test reports be provided?
A: Yes. Our products have authoritative third-party test reports including load-bearing capacity tests, seismic performance tests, and anti-corrosion tests, which can be provided with shipments. Special project requirements can also be accommodated through witnessed sampling and testing.
Q17: What information is needed for custom products?
A: Customization requires: overall dimensions (width × depth × height range), rated load requirement, installation environment conditions, special functional requirements, hole layout drawings (if any special requirements), surface treatment and color requirements. Technical engineers will provide a solution and drawings for confirmation based on your needs.
Q18: What is the typical delivery time?
A: Standard models are stocked and can ship within 1-3 days. For bulk orders or custom products, delivery time typically ranges from 7-20 days depending on quantity and complexity. Confirm specific delivery times with sales staff before ordering.
16.1 Acceptance Basis
- GB 50174-2017 “Data Center Design Specification”
- GB 50300-2013 “Unified Standard for Construction Quality Acceptance of Building Engineering”
- YD/T 2319-2011 “Technical Requirements and Test Methods for Data Equipment Network Cabinets”
- YD 5059-2005 “Code for Seismic Design of Communication Equipment Installation”
- GB 50169-2016 “Code for Construction and Acceptance of Grounding Connection Works for Electrical Equipment Installation”
- Construction design drawings, technical disclosure documents
- This product manual and manufacturer’s technical standards
- Product supply contract and technical agreement
16.2 Acceptance Organization and Procedure
16.2.1 Acceptance Organization
Organized by the construction unit, with participation from the supervision unit, construction unit, and equipment manufacturer. Third-party testing institutions may be invited for important projects.
16.2.2 Acceptance Procedure
1. Construction Unit Self-Inspection: After construction completion, the construction unit self-inspects item by item against acceptance standards, rectifies non-conforming items, and submits an acceptance application after passing self-inspection.
2. Documentation Review: The acceptance team first reviews completed project documents. On-site acceptance proceeds only after documents are complete and qualified.
3. On-Site Physical Acceptance: Inspect and record item by item according to acceptance items.
4. Problem Rectification: Issues found during acceptance must be rectified within a specified period, followed by re-inspection.
5. Signing Acceptance Documents: After all items pass, all parties sign the acceptance documents.
16.3 Acceptance Documentation Checklist
The following documents must be submitted before acceptance:
- Product factory certificate, factory inspection report
- Main material material certificates, third-party test reports (if any)
- Installation technical records, commissioning records
- Grounding resistance test records
- Concealed works acceptance records (if any)
- Design change, technical consultation documents
- As-built drawings
- Product manual, warranty card
16.4 On-Site Acceptance Items and Standards
16.4.1 Appearance and Specification Acceptance
| Inspection Item | Quality Standard | Inspection Method |
|---|---|---|
| Product Model/Spec | Consistent with design drawings and contract | Verify nameplate, drawings |
| Appearance Quality | Uniform coating, no peeling, no rust, no obvious deformation | Visual inspection |
| Component Completeness | All parts present, no missing or damaged | Count against list |
| Labels and Nameplates | Nameplate and labels complete, clear, correctly placed | Visual inspection |
16.4.2 Installation Position and Dimension Acceptance
| Inspection Item | Allowable Deviation | Inspection Method |
|---|---|---|
| Base Plan Position | ±5mm | Steel tape measure, compare with baseline |
| Top Surface Elevation | ±2mm | Level instrument measurement |
| Top Surface Levelness | ≤1mm/m | Level measurement |
| Overall Row Straightness | ≤3mm/total length | Pull wire measurement |
| Adjacent Base Joint Height Difference | ≤0.5mm | Feeler gauge, straight edge |
| Adjacent Base Joint Gap Width | ≤1mm and uniform | Feeler gauge measurement |
| Cabinet Verticality (after installation) | ≤1.5mm/m | Plumb bob or theodolite |
16.4.3 Structure and Fastening Acceptance
| Inspection Item | Quality Standard | Inspection Method |
|---|---|---|
| Bolt Tightening | 100% fastened, torque meets requirements, no omissions | Torque wrench spot check, ratio ≥10% |
| Spring Washers | All compressed flat, effective anti-loosening | Visual spot check |
| Floor Anchoring | Bolt quantity and specification meet design, securely installed | Visual inspection, pull-out spot check |
| Cabinet Connection | Connectors complete, securely fastened | Visual inspection, manual pry test |
| Structural Deformation | No obvious deformation, no weld cracks | Visual inspection, straight edge measurement |
16.4.4 Grounding System Acceptance
| Inspection Item | Quality Standard | Inspection Method |
|---|---|---|
| Grounding Connection | Reliable connection, complete terminals, standard bonding | Visual inspection |
| Ground Wire Specification | Wire diameter meets design requirements | Caliper measurement, specification check |
| Grounding Resistance | ≤1Ω (integrated grounding) or meets design value | Ground resistance tester measurement |
| Continuity Resistance | Between base and grounding busbar ≤0.5Ω | Multimeter, micro-ohmmeter |
| Identification | Clear grounding identification | Visual inspection |
16.4.5 Functional Acceptance
- Height Adjustment Function: Flexible adjustment, reliable locking.
- Side Panel Assembly/Disassembly: Convenient disassembly, secure installation.
- Cable Routing Function: Neat cable holes, complete grommets.
- Intelligent Monitoring Function (if applicable): Accurate data, normal alarms, stable communication.
16.4.6 Load Test Acceptance (Optional for Important Projects)
For important projects or high-load projects, on-site load testing may be performed:
- Load to 1.0 times rated load, hold for 24 hours.
- No permanent structural deformation, no weld cracks, no bolt deformation.
- Maximum deflection ≤ L/1000.
- Basically recovers after unloading, minimal residual deformation.
- No new cracks or obvious settlement on the ground.
16.5 Acceptance Judgment Rules
- All main control items pass, and the pass rate for general items is ≥90%, the project can be judged as qualified.
- If any main control item fails, the project is judged as unqualified and must be rectified and re-inspected.
- If the non-conforming rate of general items exceeds 10%, rectification and re-inspection are required.
- If standards still cannot be met after rectification, acceptance will not be granted.
16.6 Acceptance Document Signing
After qualified acceptance, all parties jointly sign the “Cabinet Load-Bearing Base Installation Acceptance Record,” including:
- Project name, number
- Acceptance date, location
- Acceptance scope, quantity
- Results of each inspection item
- Existing issues and rectification suggestions
- Acceptance conclusion
- Signatures and seals of representatives
Multiple copies of acceptance documents are created, archived separately by each party, and form part of the completed project documentation.
16.7 Handling of Failed Acceptance
- Issues found during acceptance result in a rectification notice, specifying content and deadline.
- After the construction unit completes rectification as required, re-inspection is applied for.
- If re-inspection still fails, handle according to contract terms.
- Serious quality issues involving structural safety must be completely rectified. Use of the equipment is strictly prohibited without rectification.
17.1 Keyword Classification System
17.1.1 Core Primary Keywords
- Cabinet Load-Bearing Base
- Cabinet Load Distribution Frame
- Computer Room Load-Bearing Reinforcement
- Cabinet Base
- Load-Bearing Distribution Frame
17.1.2 High-Conversion Long-Tail Keywords
- Cabinet load-bearing base manufacturer
- Computer room cabinet load-bearing base price
- Server cabinet load-bearing base customization
- Data center load distribution frame manufacturer
- High-density cabinet load-bearing reinforcement solutions
- Liquid-cooled cabinet load-bearing base specifications
- Seismic cabinet base installation
- Adjustable cabinet load-bearing base
- Load-bearing base for old computer room renovation
- Raised floor equipment pier manufacturer
17.1.3 Industry Traffic Keywords
- What to do if computer room floor load capacity is insufficient
- Data center cabinet load-bearing standards
- Cabinet base height specifications
- Communication room equipment base installation specifications
- Computer room load distribution frame design specifications
- Cabinet load-bearing reinforcement construction plan
- Equipment load distribution frame manufacturing standards
- Computer room load-bearing reinforcement acceptance standards
- Cabinet base grounding requirements
- Steel structure load-bearing base technical parameters
17.1.4 Brand-Specific Keywords
- KITOZER Cabinet Load-Bearing Base
- KITOZER Load Distribution Frame
- KITOZER Computer Room Load-Bearing Reinforcement
- LA Series Cabinet Base
- KITOZER Smart Computer Room Equipment
17.1.5 Dropdown/Related Search Keywords
- Cabinet load-bearing base installation method
- Cabinet load-bearing base dimensions and specifications
- What material is used for cabinet load-bearing base
- Cabinet load distribution frame pictures
- Price of computer room load distribution frame per square meter
- Load-bearing base wiring tutorial
- Cabinet base commissioning steps
- Load distribution frame acceptance standards
- Cabinet base maintenance methods
- Load-bearing base common faults
17.2 SEO Optimization Tag System
17.2.1 Page Core Optimization Tags
- Page Topic Positioning: Professional cabinet load-bearing base and computer room load distribution frame products with installation solutions, covering product introduction, technical parameters, installation wiring, and commissioning acceptance full-process technical guidance.
- Core Value Positioning: National standard quality, high load capacity, adjustable leveling, seismic reinforcement, one-stop computer room load-bearing solution service provider.
- Target Audience Positioning: Computer room construction units, weak current engineering contractors, system integrators, data center operations, decoration/construction companies.
17.2.2 Title Tag
Cabinet Load-Bearing Base_Load Distribution Frame_Cabinet Load-Bearing Reinforcement Manufacturer – Guangzhou Lain Intelligent System Development Co., Ltd.
17.2.3 Meta Keywords
cabinet load-bearing base, load distribution frame, computer room load-bearing reinforcement, cabinet base, load-bearing distribution frame, server cabinet base, data center distribution frame, seismic cabinet base, adjustable load-bearing base, computer room renovation reinforcement
17.2.4 Meta Description
Guangzhou Lain Intelligent System Development specializes in manufacturing cabinet load-bearing bases and computer room load distribution frames, offering a full range of light/medium/heavy/extra-heavy load-bearing reinforcement products compatible with server cabinets, UPS cabinets, battery cabinets, and liquid-cooled cabinets. Features include 3D adjustability, seismic reinforcement, and equipotential grounding. One-stop installation, wiring, and commissioning services. Compliant with GB50174 national standards, helping your computer room pass load-bearing acceptance smoothly. Service Hotline: +86 13538869979
17.2.5 H1 Tag
Cabinet Load-Bearing Base Installation, Wiring, and Commissioning Manual
17.2.6 H2 Tags
- Product Introduction
- Product Composition
- Product Classification
- Product List
- Product Principle
- Product Technical Parameters
- Product Functions and Features
- Product Application Scenarios
- Product Installation
- Product Wiring
- Product Commissioning
- Product Precautions
- Product Maintenance and Repair
- Product Common Problems and Solutions
- Product QA
- Product Acceptance
17.3 Internal Link Optimization Tags (Natural Anchor Text Integration)
17.3.1 Core Anchor Text
- Cabinet Load-Bearing Base
- Computer Room Load-Bearing Reinforcement
- Load Distribution Frame
- Cabinet Base
17.3.2 Long-Tail Anchor Text
- Heavy-Duty Cabinet Load-Bearing Base
- Seismic Load Distribution Frame
- Computer Room Floor Load-Bearing Reinforcement
- Adjustable Cabinet Base
- Liquid-Cooled Cabinet Load Distribution Frame
17.3.3 Related Anchor Text
- Shielded Cabinet
- Micro-Module Cold Aisle Containment
- Computer Room Noise Reduction
- Precision Air Conditioner Base
- Battery Rack
18.1 Copyright Statement
The copyright of this document belongs to Guangzhou Lain Intelligent System Development Co., Ltd. and is protected by the Copyright Law of the People’s Republic of China. Without written authorization from the company, no unit or individual may reproduce, reprint, adapt, excerpt, translate, disseminate, or use all or part of this document for commercial purposes in any form.
When authorized to reprint or quote, the source must be credited as “Guangzhou Lain Intelligent System Development Co., Ltd.” and the content must not be distorted or altered. Violators of the above statement will be held legally liable by the company.
The content of this manual is subject to periodic updates with product technology upgrades without prior notice. The latest version is based on the official website https://gdlain.com.
18.2 Manufacturer Information
- Manufacturer: Guangzhou Lain Intelligent System Development Co., Ltd.
- Service Hotline: +86 13538869979 (also WeChat ID)
- Technical Support: +86 13538869979
- Address: Zhongrun Industrial Park, No. 5 Huashan Road, Shilou Town, Panyu District, Guangzhou, China
- Official Website: https://gdlain.com
Document Version: V2.6.202607
Release Date: July 15, 2026