Modular UPS Installation, Wiring and Commissioning Manual

Manufacturer: Guangzhou Lain Intelligent System Development Co., Ltd.

Service Hotline: +86 13538869979 (WeChat same number)

Technical Support: +86 13538869979

Company Address: Zhongrun Industrial Park, No. 5 Huashan Road, Shilou Town, Panyu District, Guangzhou

Official Website: https://gdlain.com

Table of Contents

Preface

In today’s rapidly developing digital economy, core scenarios such as data centers, telecommunication equipment rooms, industrial automation systems, and precision medical equipment have imposed extremely stringent requirements on the continuity, stability, and power quality of power supply. As the core equipment of the power assurance system, the Uninterruptible Power Supply (UPS) is undergoing a generational upgrade in its technical architecture and product form — from traditional tower-type integrated design to modular, intelligent, and green solutions.

Modular UPS, with its core advantages of “configuration on demand, elastic expansion, online maintenance, and N+X redundancy,” has completely solved the industry pain points of traditional tower-type UPS, such as fixed capacity, difficult expansion, maintenance downtime, and high risk of single-point failure. It has become the mainstream choice for a new generation ofequipment room power infrastructure. Guangzhou Lain Intelligent System Development Co., Ltd. hasdeeply cultivated the field of equipment room power for many years. Its self-developed full series of modular UPS products adopt advanced three-level inverter technology and fully digital DSP control architecture, covering the full power range from 20kVA to 1200kVA, and are widely adapted to various medium and large equipment rooms, data centers, industrial control, and critical business scenarios.

This manual is the official technical guidance document for the Lain series modular UPS. It systematically covers the full lifecycle technical content including product principles, structural parameters, installation and wiring, commissioning and operation, maintenance, fault troubleshooting, and acceptance standards. It aims to provide comprehensive, rigorous, and implementable technical guidance for equipment installation engineers, operation and maintenance management personnel, and system integrators. Relevant personnel should read this manual carefully before equipment installation, commissioning, and operation, and strictly follow the operating specifications and safety requirements therein to ensure safe and stable equipment operation.

The content of this manual will be continuously updated according to product technology iteration. The final interpretation right belongs to Guangzhou Lain Intelligent System Development Co., Ltd. If you encounter any product technical questions or after-sales needs, please contact our technical support team at any time.

Chapter 1 Product Introduction

1.1 Definition and Technical Positioning of Modular UPS

Modular UPS (Modular Uninterruptible Power Supply) is an online double-conversion uninterruptible power supply system designed with a modular architecture. It integrates the core power and functional components of traditional UPS — rectifier, inverter, static bypass switch, charging circuit, control unit, etc. — into independent, pluggable standard power modules. Multiple power modules are installed in parallel within a standardized cabinet frame, and together with a centralized bypass module, system monitoring module, power distribution unit, and battery bank, they form a complete uninterruptible power supply system.

Unlike the traditional tower-type UPS design logic of “integrated whole machine, fixed capacity, non-splittable,” modular UPS follows the design philosophy of “standardization, pluggability, distribution, and redundancy.” Each power module is an independent power unit with complete rectifier-inverter functionality. There is no master-slave distinction among modules; they achieve autonomous current sharing and coordinated operation through high-speed digital communication. When a single module fails, it automatically exits the system without affecting the normal power supply of the remaining modules. Module replacement and expansion support hot-swap operation without interrupting load power supply, truly achieving “online maintenance and lossless expansion.”

From a technology generation perspective, modular UPS is a typical representative of the third generation of UPS technology: The first generation of line-frequency tower UPS relied on bulky line-frequency transformers, which were large in size and low in efficiency. The second generation of high-frequency tower UPS eliminated line-frequency transformers, improving efficiency and power density, but still maintained a fixed whole-machine architecture. The third generation of modular UPS further achieves architectural decoupling on the basis of high-frequency technology, elevating availability, flexibility, and operation and maintenance efficiency to a new level. It is the preferred technical route for high-end equipment room power assurance.

1.2 Industry Development Background of Modular UPS

With the rapid expansion of cloud computing, big data, 5G communications, industrial internet, and other industries, the construction scale of global data centers and critical infrastructure continues to grow. The power assurance system faces three core challenges:

Uncertainty of business growth: Enterprise IT loads grow dynamically with business development. The traditional UPS model of one-time full-capacity planning leads to waste of early investment and idle resources. If the initial configuration capacity is insufficient, later expansion faces problems such as downtime renovation and complex construction.

Rigid demand for high availability: Core scenarios such as finance, securities, medical, and telecommunications operators require power supply availability to reach 99.999% or even higher. Traditional tower-type UPS has single-point failure risks in rectifiers, inverters, control boards, etc. The 1+1 parallel solution has problems of high cost and complex parallel logic.

Operation and maintenance efficiency and cost pressure: Traditional UPS fault repair requires professional engineers to disassemble and repair on-site. The fault location and repair cycle is long, and the repair process often requires switching to bypass or even shutdown, bringing risks to business continuity. At the same time, the full lifecycle operation and maintenance cost of equipment remains high.

The emergence of modular UPS was precisely to systematically solve the above pain points. Since 2010, modular UPS has rapidly proliferated in the global data center field, and the domestic market penetration rate has increased year by year. According to industry statistics, in 2025, modular UPS adoption in new medium and large data center construction projects in China has exceeded 75%, becoming the mainstream power supply solution. At the technical level, modular UPS is continuously evolving toward higher power density, higher efficiency, smarter battery management, and more complete digital monitoring and cloud operation and maintenance.

1.3 Overview of Lain Modular UPS Products

The LA-M series modular UPS launched by Guangzhou Lain Intelligent System Development Co., Ltd. is a full series of online double-conversion modular UPS products deeply optimized for domestic equipment room application environments. The products adopt three-level IGBT inverter topology and fully digital DSP parallel control technology. Single module power covers five specifications: 10kVA, 20kVA, 30kVA, 50kVA, and 100kVA. A single cabinet supports up to 10 modules in parallel, and the system capacity can be smoothly expanded from 10kVA to 1200kVA, fully covering all scenarios from small equipment rooms to large cloud data centers.

The Lain modular UPS adopts N+X redundant architecture design, supports module hot-swap, with single module replacement time ≤5 minutes, and system availability as high as 99.999%. The whole machine efficiency can reach up to 96%, and in ECO economic mode, efficiency exceeds 99%, meeting the energy-saving requirements of green data centers. It is equipped with a 10.1-inch color touch screen display, supporting bilingual Chinese-English interface, integrating rich communication interfaces and intelligent monitoring functions, enabling comprehensive local and remote operation and maintenance management.

Products strictly comply with GB/T 7260.3-2003 “Uninterruptible power supply equipment – Part 3: Methods of specifying performance and test requirements,” YD/T 1970-2009 “Uninterruptible power supply (UPS) for telecommunications,” and other national and industry standards, and have passed CE, CCC and other authoritative certifications. They are equipped with comprehensive multiple protection mechanisms including overvoltage, undervoltage, overcurrent, short circuit, overtemperature, and battery reverse connection, ensuring equipment and load safety.

1.4 Core Differences Between Modular UPS and Traditional Tower-Type UPS

Comparison Dimension Modular UPS Traditional Tower-Type UPS
Architecture Form Cabinet + pluggable power modules, distributed architecture Integrated whole machine, centralized architecture
Capacity Configuration Configured on demand, gradual expansion, supports N+X redundancy Fixed capacity, one-time planning, 1+1 parallel requires two complete machines
Expansion Method Online hot-swap add modules, no shutdown required Requires shutdown renovation, replace whole machine or add parallel equipment
Fault Impact Single module failure automatically exits, does not affect system power supply Core component failure of whole machine requires bypass switching or shutdown
Maintenance Method Module hot-swap replacement, online maintenance, can be operated by general engineers Requires professional personnel to disassemble and repair, long maintenance cycle, often requires shutdown
Availability Level N+X redundancy, availability ≥99.999% Single machine availability about 99.9%, 1+1 parallel about 99.99%
Investment Model Phased investment, low initial investment, gradual expansion with business growth One-time full investment, high early resource idle rate
Floor Area High power density, saves equipment room space Large single machine volume, larger footprint required for reserved expansion space
Spare Parts Management Universal power modules, low spare parts inventory cost Different models have non-universal spare parts, high spare parts inventory pressure

1.5 Core Value of Lain Modular UPS

Extreme availability, eliminating single-point failures: Adopting N+X parallel redundant design. When any power module fails, the system automatically isolates it, and the remaining modules bear the full load with zero power supply interruption. Both bypass modules and monitoring modules support redundant configuration, comprehensively eliminating system single-point failure risks and meeting Tier III and Tier IV data center availability requirements.

Elastic expansion, protecting early investment: Users can configure the corresponding number of power modules according to current load. When business grows later, capacity expansion can be completed by simply adding modules without replacing the whole machine, significantly reducing initial investment costs, achieving “add as needed, upgrade smoothly.”

Minimal maintenance, reducing downtime risk: Both power modules and monitoring modules support hot-swap. Faulty modules can be replaced online without switching to bypass or interrupting the load. Module standardization is high, replacement operation is simple, and ordinary maintenance personnel can complete it after simple training, greatly shortening fault repair time (MTTR).

High efficiency and energy saving, reducing operating costs: Adopting three-level inverter technology and optimized magnetic component design, the whole machine full-load efficiency is as high as 96%. Supports intelligent sleep function — automatically sleeps some modules at low load to improve system operating efficiency. In ECO mode, efficiency can reach above 99%, significantly reducing long-term operating electricity costs.

Intelligent management, improving maintenance efficiency: Integrated full-featured monitoring system, real-time collection of system operating parameters, supporting fault alarms, historical records, intelligent battery management, remote monitoring, and other functions. Supports multiple communication protocols such as SNMP, Modbus, RS485, and can seamlessly integrate into the equipment room environment monitoring system, achieving unattended operation and maintenance.

Chapter 2 Product Composition

The Lain LA-M series modular UPS system consists of six core parts: cabinet system, power module units, centralized bypass module, system monitoring module, input/output power distribution unit, and cooling ventilation system. An external battery bank is connected to form a complete uninterruptible power supply system. Each part adopts standardized, modular design with clear division of labor and coordinated operation, jointly ensuring the stable and reliable operation of the system.

2.1 Cabinet System

The cabinet is the physical load-bearing frame of the modular UPS. It is formed from high-strength cold-rolled steel plate, with electrostatic powder coating on the surface, providing excellent structural strength, corrosion resistance, and electromagnetic shielding capability. The cabinet adopts a standard 19-inch rack-mount design with standardized module slots reserved internally, supporting pluggable installation of power modules, bypass modules, and monitoring modules.

2.1.1 Cabinet Structure Composition

Rack main frame: Made of 2.0mm high-quality cold-rolled steel plate, formed by nine-fold profile welded construction, with overall load-bearing capacity ≥1500kg, ensuring stable structure without deformation when fully loaded with modules. The frame surface is galvanized for rust prevention, with external powder coating, color is standard equipment room gray (RAL7035).

Module slot compartment: Located in the middle of the cabinet, this is the installation area for power modules. It is equipped with guide rails, electrical connectors, and positioning pins internally. Each slot corresponds to one power module installation position. The slot backplane integrates busbars and communication buses — after module insertion, electrical and communication connections are automatically completed without additional wiring. The number of slots varies by cabinet model: 5-slot, 8-slot, 10-slot specifications, etc.

Top distribution compartment: Located in the upper part of the cabinet, integrating input busbars, bypass busbars, output busbars, terminal blocks, circuit breakers, and other distribution components. It is responsible for power distribution and circuit connection of utility input, bypass input, and system output. On some models, the output distribution unit is integrated here, allowing direct connection of load circuits.

Bottom cable entry compartment: Located in the lower part of the cabinet, with top and bottom cable entry openings, supporting both top-entry and bottom-entry wiring methods. It is equipped with grounding copper busbar and cable fixing brackets internally, facilitating the introduction, fixing, and grounding connection of input and output cables.

Front door and side doors: The front door adopts a perforated mesh design with opening rate ≥70%, ensuring ventilation and heat dissipation, and is equipped with a safety door lock. Side doors are removable steel plate doors, facilitating internal inspection and wiring operations.

Base and leveling feet: The cabinet bottom is equipped with heavy-duty adjustable leveling feet and a support base, with adjustable height of ±20mm, used for horizontal leveling on uneven floors. Some models can be optionally equipped with universal casters for easy equipment transportation and positioning.

2.1.2 Cabinet Busbar System

The cabinet integrates three independent copper busbar systems internally, all made of high-purity T2 copper bar with tin-plated surface treatment, providing excellent electrical conductivity and low temperature rise:

DC busbar: Connects the DC output terminals of each power module with the battery bank interface, realizing parallel transmission of DC power and the battery charge/discharge circuit.

AC output busbar: Collects the inverter output of each power module, and after passing through the bypass switch, delivers it to the output distribution terminals.

Bypass busbar: Independently transmits bypass utility power. When the inverter system fails or is overloaded, it switches to supply the load through the static switch.

2.2 Power Module Unit

The power module is the core power conversion unit of the modular UPS. It integrates all core components including rectifier, inverter, DC-DC charging circuit, drive circuit, DSP control board, and cooling fan — making it a complete independent UPS unit. Each power module can independently complete the AC-DC-AC double conversion process. When multiple modules operate in parallel, they jointly share the load power.

The Lain modular UPS power module is a standard rack-mount pluggable structure, with a handle, fixing screws, and status indicator lights on the front. Electrical connections are automatically completed after insertion into the cabinet slot. Modules adopt masterless parallel technology — all modules are equal in status, communicating in real-time through high-speed CAN bus, autonomously achieving current sharing control.

2.2.1 Internal Composition of Power Module

Input rectifier and PFC unit: Uses three-phase full-bridge rectification + Active Power Factor Correction (APFC) circuit to convert input three-phase AC power into stable DC power, while improving input power factor to above 0.99, reducing input harmonic current and reducing pollution to the power grid. Adopts three-level Boost PFC topology, reducing device stress and improving conversion efficiency.

DC busbar and filtering unit: Consists of high-capacity electrolytic capacitors and film capacitors forming the DC filtering circuit, smoothing the rectified DC voltage to provide stable DC power for the downstream inverter. It also has buffer energy storage function, maintaining DC bus voltage stability at the instant of utility interruption.

DC-DC charging unit: An independent bidirectional DC-DC conversion circuit responsible for stepping down the DC bus voltage to charge the battery bank, supporting three-stage charging management of constant current, constant voltage, and float charging. During battery discharge, it boosts the battery voltage to the DC bus voltage, ensuring stable inverter input.

Three-level inverter unit: Uses IGBT three-level inverter topology with SPWM sinusoidal pulse width modulation technology to invert DC power into pure sinusoidal AC power. Compared with traditional two-level topology, the three-level topology has lower output harmonics, smaller dv/dt, simpler filtering, while improving overall machine efficiency and reliability.

Output filtering unit: Composed of LC filter circuits, filtering high-frequency harmonics from the inverter output, making the output voltage waveform a standard sine wave with total harmonic distortion (THD) ≤3% (linear load), meeting the power quality requirements of precision loads.

DSP digital control unit: Centered on a high-performance 32-bit digital signal processor (DSP), integrating AD sampling, logic control, drive output, communication interfaces, and other functions. It collects module voltage, current, temperature, and other parameters in real-time, completes fully digital closed-loop control of rectification, inversion, and charging, and simultaneously implements communication interaction with the system monitoring module and other power modules.

Protection and detection unit: Integrates voltage, current, temperature sensors and multiple protection circuits, achieving comprehensive protection including input overvoltage/undervoltage, output overcurrent/short circuit, module overtemperature, and DC bus overvoltage. When faults occur, it acts quickly to protect the module itself and load safety, and reports fault information.

Cooling unit: Uses intelligent temperature-controlled fans that automatically adjust fan speed according to module load rate and temperature, balancing heat dissipation effectiveness with noise reduction and energy saving. Adopts front-air-inlet, rear-air-outlet airflow design, matching the cabinet’s overall airflow path to ensure heat dissipation efficiency.

2.2.2 Power Module Status Indication

Each power module is equipped with three-color status indicator lights on the front, visually displaying module operating status:

Light Status Meaning
Green solid Module operating normally, inverter output normal
Green flashing Module standby or sleep state
Yellow solid Module bypass operation or alarm state
Red solid Module fault, has exited the system
Red flashing Module serious fault, requires immediate replacement

2.3 Centralized Bypass Module

The centralized bypass module is the bypass power supply and switching core of the modular UPS system. It is responsible for seamlessly switching the load to bypass utility power in scenarios such as inverter system failure, overload, and maintenance, ensuring power supply continuity. The bypass module is independent of power modules, adopting a centralized design — one system is configured with one bypass module, or two for redundant configuration.

2.3.1 Bypass Module Composition

Static bypass switch: Composed of two groups of reverse-parallel high-power silicon controlled rectifiers (SCR), this is the core actuating device for bypass switching. It has microsecond-level switching speed, achieving zero-interruption switching between inverter and bypass, with switching time ≤2ms, ensuring the load is unaffected by the switching.

Maintenance bypass switch: A manual isolating switch used during equipment inspection and maintenance to directly switch the load to utility bypass while completely isolating the UPS internal circuits, ensuring the safety of maintenance personnel. The maintenance bypass switch is equipped with mechanical interlock and position indication to prevent misoperation.

Bypass control unit: An independent bypass control board responsible for detecting bypass voltage, frequency, and phase, synchronizing and tracking with the inverter output, and controlling the smooth switching of the static switch. It also has bypass overcurrent and short circuit protection functions.

Input circuit breaker: A dedicated circuit breaker for bypass power input, with overload and short circuit protection functions. It automatically disconnects upon faults, protecting the bypass circuit and load safety.

2.3.2 Bypass Operating Modes

Normal inverter mode: The static bypass switch is open, and the load is powered by the power module inverter output. The bypass module is in hot standby state, tracking the inverter output voltage phase in real-time.

Automatic bypass mode: When inverter system failure, output overload exceeding inverter capability, module temperature too high, etc. occur, the system automatically controls the static switch to conduct, and the load seamlessly switches to bypass utility power supply. After the fault is eliminated, it automatically switches back to inverter mode.

Manual bypass mode: Through monitoring panel operation, the system can be manually switched to bypass power supply mode for scenarios such as module replacement and system maintenance.

Maintenance bypass mode: Close the maintenance bypass switch, and the load is directly powered by utility power. All UPS internal circuits are completely isolated from the load, allowing safe equipment inspection, module replacement, and other operations.

2.4 System Monitoring Module

The system monitoring module is the “brain” of the entire modular UPS system, responsible for full-system operating status monitoring, logic control, human-machine interaction, communication management, and fault alarms. The monitoring module adopts an independent modular design, supporting hot-swap and redundant configuration — a single-point failure does not affect system power output.

2.4.1 Monitoring Module Composition

Main control unit: Uses a high-performance ARM processor running an embedded operating system, responsible for system-level logic control, data processing, and scheduling management. It collects operating data from each power module, bypass module, and battery bank for unified analysis and processing.

Human-machine interaction unit: Equipped with a 10.1-inch color LCD touch screen display with resolution 1024×600, supporting bilingual Chinese-English interface. The display can show system input/output parameters, load rate, battery status, module operating status, alarm information, etc. in real-time, and supports touch operation for parameter settings, function configuration, and system control.

Status indication and operation buttons: The cabinet panel is equipped with system-level status indicator lights (utility, inverter, bypass, battery, fault) and an emergency power off (EPO) button, allowing users to quickly understand system status and perform emergency operations.

Communication interface unit: Integrates rich communication interfaces including RS232, RS485, dry contact interfaces, and USB interface. Optional SNMP network card, WiFi module, and 4G communication module are available for remote network monitoring and SMS alarm functions.

Data storage unit: Built-in large-capacity storage chip capable of storing ≥10,000 historical alarm records and operating data, supporting fault tracing and data analysis. Supports USB drive export of operating logs and fault records.

Battery management unit: An independent battery management (BMS) function that monitors the battery bank total voltage, charge/discharge current, and battery temperature in real-time, implementing intelligent charging management, battery low voltage alarm, battery capacity prediction, and periodic automatic battery testing functions.

2.4.2 Monitoring System Main Functions

Real-time monitoring: Input voltage/current/frequency, output voltage/current/frequency/power/load rate, battery voltage/current/temperature/remaining capacity, each module’s operating status and temperature, etc.

System control: Power on, power off, inverter start/stop, bypass switching, battery test, parameter settings, etc.

Alarm management: Hierarchical alarm mechanism, supporting audible/visual alarms, screen popup alarms, and remote communication alarms. Alarm types include input abnormality, output abnormality, battery abnormality, module fault, overtemperature, etc.

Battery management: Three-stage intelligent charging, battery temperature compensation, battery low voltage protection, periodic automatic discharge testing, battery life prediction.

Historical records: Stores alarm history, operation history, and operating data, supporting query and export.

Remote monitoring: Supports host computer software, web interface, and mobile APP remote monitoring and management, and supports integration into environment monitoring systems.

2.5 Input/Output Power Distribution Unit

The power distribution unit is responsible for power input distribution and output distribution of the UPS system. It is divided into input distribution and output distribution parts. Depending on the model, it can be integrated inside the UPS cabinet or configured as a separate distribution cabinet.

2.5.1 Input Power Distribution Unit

Main input circuit breaker: Three-phase main input air switch with overload and short circuit protection, used for system total power on/off control and fault protection.

Bypass input circuit breaker: A dedicated circuit breaker for bypass power, independent of the main input, ensuring the bypass power supply circuit is independent and reliable.

Surge protective device (SPD): Class C or Class B+C lightning protection module, suppressing surge voltage and lightning overvoltage from the utility input, protecting UPS internal circuits.

Input EMI filter unit: Suppresses grid conducted interference, improving UPS electromagnetic interference resistance, while reducing the UPS’s own conducted emissions to the grid.

2.5.2 Output Power Distribution Unit

Total output circuit breaker: System output main switch, controlling the on/off of the total load circuit, with overload and short circuit protection.

Branch output circuit breakers: Multiple branch output circuits that can directly connect different load devices. Branch capacity is configured according to requirements, facilitating load management and fault isolation.

Output isolation transformer (optional): Some special scenarios can be configured with an output isolation transformer to achieve electrical isolation, reduce neutral-to-ground voltage, and improve power supply safety and anti-interference capability.

2.6 Cooling Ventilation System

Good heat dissipation is an important guarantee for long-term stable UPS operation. The Lain modular UPS adopts a zoned heat dissipation, intelligent temperature control ventilation cooling system to ensure all components operate within reasonable temperature ranges.

Cabinet overall airflow path: Adopts a horizontal front-inlet, rear-outlet airflow design. Cool air enters through the front door mesh, flows through heat-generating components such as power modules and bypass modules, and is discharged from the rear of the cabinet after carrying away heat. The airflow path is optimized to reduce turbulence and hot air recirculation, improving heat dissipation efficiency.

Module-level heat dissipation: Each power module has its own independent temperature-controlled fan that automatically adjusts speed according to module internal temperature and load rate. At low load and low temperature, it runs at low speed to reduce noise and energy consumption. At high load and high temperature, it runs at high speed to ensure heat dissipation.

Cabinet top exhaust: The cabinet top is equipped with auxiliary exhaust fans to strengthen internal air circulation and avoid heat accumulation at the top. Some high-power models use forced top exhaust design.

Temperature monitoring and protection: Multiple temperature sensors are installed in various positions inside the cabinet, monitoring inlet air temperature, module temperature, busbar temperature, etc. in real-time. When temperature is too high, an alarm is automatically issued. When the overtemperature threshold is exceeded, the system automatically reduces load or switches to bypass protection, preventing component damage from overheating.

2.7 Battery Bank

The battery bank is the energy storage unit of the UPS system. It stores electrical energy when utility power is normal and releases energy during utility interruption to maintain inverter output and ensure continuous load power supply. The Lain modular UPS supports multiple battery types including valve-regulated lead-acid batteries (VRLA), gel batteries, and lithium iron phosphate batteries, with flexible external battery bank configuration.

Battery bank connection method: Batteries are connected in series to form the required DC voltage level. For example, 32 pieces of 12V batteries in series form a 384V system, and 40 pieces in series form a 480V system. Multiple battery banks can be connected in parallel for capacity expansion, increasing backup time.

Battery switch: A dedicated DC circuit breaker is configured as the on/off switch between the battery bank and the UPS host, with overcurrent and short circuit protection, facilitating battery maintenance and fault isolation.

Battery cabinet/rack: Used for placing the battery bank, adopting standard cabinet or open rack design, with load-bearing, ventilation, and corrosion resistance capabilities. It can be placed side by side with the UPS host or independently in a battery room.

Chapter 3 Product Classification

The Lain modular UPS product system is rich and can be classified by multiple dimensions including power level, module specification, application scenario, topology structure, and input/output configuration, meeting the diverse needs of different users.

3.1 Classification by System Power Level

3.1.1 Small Modular UPS (10kVA~60kVA)

Representative models: LA-M10, LA-M20 series

Single module power: 10kVA/10kW, 20kVA/20kW

Number of modules per cabinet: 1~3

System maximum capacity: 60kVA/60kW

Features: Compact size, standard 19-inch rack-mount installation, height 6U~12U. Suitable for small equipment rooms, network cabinets, edge computing nodes, small office equipment rooms, and other scenarios. Easy installation, rapid deployment, can be directly installed in standard server cabinets.

Input/output configuration: Single-phase input/single-phase output, three-phase input/single-phase output optional.

3.1.2 Medium Modular UPS (60kVA~300kVA)

Representative models: LA-M30, LA-M50 series

Single module power: 30kVA/30kW, 50kVA/50kW

Number of modules per cabinet: 1~6

System maximum capacity: 300kVA/300kW

Features: Balances performance and cost, and is the mainstream model in the market. Suitable for medium and large enterprise equipment rooms, county-level operator equipment rooms, hospital medical technology building equipment rooms, industrial central control rooms, and other scenarios. Supports N+1, N+2 redundant configurations with high availability.

Input/output configuration: Mainly three-phase input/three-phase output (three-in, three-out).

3.1.3 Large Modular UPS (300kVA~1200kVA)

Representative models: LA-M100 series

Single module power: 100kVA/100kW

Number of modules per cabinet: 1~10, supports multiple cabinet parallel operation

System maximum capacity: Single cabinet 1000kVA, multiple cabinet parallel maximum 1200kVA

Features: High power, high reliability, high density. Suitable for large data centers, cloud computing centers, provincial operator core equipment rooms, financial data centers, large industrial factory areas, and other scenarios. Supports multiple system parallel operation with horizontally expandable capacity. Full redundant design meets high-level availability requirements.

Input/output configuration: Three-phase input/three-phase output, supports dual utility power input.

3.2 Classification by Power Module Technical Topology

3.2.1 Two-Level Modular UPS

Technical features: Uses traditional two-level IGBT inverter topology, mature technology, relatively low cost. Output harmonics are relatively higher, requiring larger output filters.

Applicable scenarios: Ordinary equipment rooms sensitive to cost, with loads mainly consisting of conventional servers and network equipment.

Representative series: LA-M Basic Edition series.

3.2.2 Three-Level Modular UPS

Technical features: Uses T-type three-level or NPC three-level inverter topology, with low switching losses, high overall machine efficiency, low output harmonics, and low electromagnetic interference. Higher power density, quieter operation.

Applicable scenarios: Mid-to-high-end data centers with high requirements for energy efficiency and power quality, precision equipment rooms, medical equipment rooms, etc.

Representative series: LA-M Pro full series, which is Lain’s main high-end model.

3.3 Classification by Application Scenario and Protection Level

3.3.1 General Equipment Room Modular UPS

Protection level: IP20

Environmental requirements: Indoor constant temperature and humidity equipment room environment, temperature 0~40°C, relative humidity 30%~90% without condensation.

Features: Standard rack-mount design, optimized heat dissipation and electromagnetic compatibility performance, adapted to standard equipment room environments. This is the most commonly used model.

Applications: Various data centers, computer rooms, telecommunication equipment rooms, control rooms, and other indoor standard environments.

3.3.2 Industrial Grade Modular UPS

Protection level: IP30~IP42

Environmental requirements: Wide temperature design, operating temperature -10°C~55°C, adapting to relatively harsh industrial environments with dust, humidity, and high temperature. Has stronger anti-interference and anti-vibration capabilities.

Features: Reinforced structural design, wide temperature component selection, enhanced filtering and protection circuits. Adapts to complex grid environments and harsh physical environments in industrial sites.

Applications: Factory automation production lines, underground mine control rooms, outdoor base station equipment rooms, railway transit route equipment rooms, power substations, etc.

3.3.3 Edge Micro Modular UPS

Protection level: IP20~IP31

Features: Ultra-compact modular design, height only 3U~6U, can be directly installed in edge cabinets, weak current shafts, and outdoor cabinets. Supports wide voltage input, adapting to unstable grid environments. Integrated distribution and monitoring, minimal deployment complexity.

Applications: 5G edge equipment rooms, smart street light base stations, campus weak current rooms, branch network point equipment rooms, and other edge computing scenarios.

3.4 Classification by Battery Configuration Method

3.4.1 External Battery Modular UPS

Features: The battery bank is independent of the UPS host, configured in dedicated battery cabinets or racks. Battery capacity and backup time can be flexibly configured according to requirements, ranging from 15 minutes to several hours.

Advantages: Flexible battery configuration, easy expansion, independent heat dissipation and maintenance, suitable for scenarios requiring longer backup times.

Applicable: The vast majority of medium and large equipment room scenarios.

3.4.2 Built-in Battery Modular UPS

Features: Battery modules are integrated with power modules inside the UPS cabinet, using pluggable battery module design. The whole machine has a high degree of integration, saving space.

Advantages: Rapid deployment, no additional battery cabinet required, neat appearance. Suitable for space-constrained scenarios with short backup time requirements (5~30 minutes).

Applicable: Small equipment rooms, integrated cabinets, edge computing nodes, etc.

3.5 Classification by Redundant Architecture

3.5.1 N+X Redundant Modular UPS

Definition: N is the number of modules required to carry the load, X is the number of redundant modules (X=1, 2, 3…). When any X modules fail, the remaining modules can still carry the full load.

Features: The most mainstream redundant architecture, with high reliability. Redundancy level can be flexibly configured according to requirements. The more modules, the higher the redundancy and the stronger the availability.

Applications: Core equipment rooms with high availability requirements, typically configured with N+1 or N+2 redundancy.

3.5.2 2N Dual-Bus Modular UPS

Definition: Two independent modular UPS systems form a dual-bus power supply architecture, each powering dual-power loads. When one system fails, the other system can bear the full load.

Features: Highest availability, no single point of failure, meeting Tier IV data center requirements. Relatively higher cost.

Applications: Financial core data centers, large cloud data centers, disaster recovery centers, and other extremely high availability requirement scenarios.

Chapter 4 Product List

4.1 Standard Host Cabinet Configuration List (Example: LA-M30 Series 120kVA System)

No. Component Name Specification/Model Qty Unit Remarks
1 UPS host cabinet LA-M30-5 cabinet (600mm×1100mm×2000mm) 1 Unit Includes cabinet frame, busbar system, airflow structure
2 Power module LA-M30-PM (30kVA/30kW) 4 Each 3+1 redundant configuration, includes rectifier, inverter, control
3 Centralized bypass module LA-M30-BM (150A) 1 Each Includes static switch, maintenance bypass, control unit
4 System monitoring module LA-M30-CM 1 Each Includes 10.1-inch touch screen, main control board, communication interfaces
5 Input power distribution unit 3P 250A circuit breaker + surge protector 1 Set Includes main input, bypass input circuit breakers
6 Output power distribution unit 3P 250A total output circuit breaker 1 Set Expandable with branch outputs
7 Cooling system Intelligent temperature-controlled fan set 1 Set Includes module fans, cabinet exhaust fans
8 Cabinet accessories Leveling feet, door locks, keys, mounting screws 1 Set Standard installation accessories
9 Communication cables RS485 communication cable, dry contact connection cable 1 Set Standard included
10 Technical documentation Manual, certificate of conformity, warranty card, test report 1 Set Paper version + electronic version

4.2 Battery Bank Configuration List (30-minute Backup Example)

No. Component Name Specification/Model Qty Unit Remarks
1 Valve-regulated lead-acid battery 12V 100Ah 32 Pieces 384V system, float charge voltage 432V
2 Battery cabinet A32 standard battery cabinet 1 Each Can accommodate 32 pieces of 100Ah batteries
3 Battery rack Steel four-tier battery rack 1 Set Includes insulation pads, fixing components
4 Battery connection cable 25mm² copper core insulated wire 32 Pieces Includes copper lugs, insulating sleeves
5 Battery main switch DC circuit breaker 200A/DC500V 1 Each Battery circuit main protection
6 Battery inspection unit 32-channel battery voltage inspection module 1 Set Optional, monitors individual battery voltage

4.3 Optional Accessories List

No. Accessory Name Function Description Applicable Scenario
1 SNMP network management card Enables Ethernet remote monitoring, supports web access, SNMP protocol Equipment rooms requiring remote network monitoring
2 4G SMS alarm module Fault alarm SMS notification, supports mobile phone status inquiry Unattended equipment rooms, remote sites
3 Battery inspection instrument Real-time monitoring of each battery’s voltage, internal resistance, temperature, accurate battery status assessment Core scenarios with high battery reliability requirements
4 Output isolation transformer Electrical isolation, reduces neutral-to-ground voltage, suppresses common-mode interference Medical equipment, precision instrument equipment rooms
5 Input isolation transformer Grid electrical isolation, improves anti-interference capability Industrial scenarios with harsh grid environments
6 Output branch distribution unit Multiple branch output circuit breakers, directly powers multiple load circuits Scenarios with many load circuits requiring refined distribution
7 Parallel expansion kit Enables multiple UPS cabinet parallel operation, expands system capacity Large data centers requiring high capacity systems
8 Redundant monitoring module Dual monitoring module redundant configuration, eliminates monitoring single-point failure Core equipment rooms with high availability requirements
9 Universal caster kit Installs casters at cabinet bottom for easy equipment movement and positioning Scenarios requiring frequent relocation or position adjustment
10 Temperature sensor kit Multi-point ambient temperature monitoring, linked temperature control and alarms Equipment rooms with strict environmental control

4.4 Included Tools and Documentation List

Special tools: Module insertion/extraction handle, terminal tightening wrench, anti-static wrist strap, multimeter (optional)

Technical documentation:

  • Modular UPS Installation, Wiring and Commissioning Manual (this document)
  • Modular UPS Monitoring Software Operation Manual
  • Product certificate of conformity, factory inspection report
  • Warranty card and after-sales service description
  • Electrical schematic diagrams, wiring diagrams, cabinet dimension drawings

Others: Spare fuses, spare indicator lamps, sealing rubber strips, wire number sleeves, and other consumables

4.5 Unpacking and Acceptance Notes

After equipment arrival, unpacking and acceptance must be conducted with both the receiving party and the supplier present, checking the equipment model, quantity, and accessories one by one against the packing list.

Check the equipment appearance for transportation damage such as collision, deformation, paint peeling, moisture, etc. Check whether the module packaging is intact and free of water ingress traces.

Verify the equipment nameplate information, confirming that the model, specification, and factory serial number match the contract.

If any equipment is found missing, damaged, or with mismatched models, record it immediately, take photos for retention, and contact the supplier for handling.

After acceptance is confirmed without issues, fill in the unpacking acceptance form and both parties sign for confirmation. If the equipment is not to be installed immediately, store it in a dry, ventilated indoor environment free of corrosive gases.

Chapter 5 Product Working Principle

The Lain modular UPS adopts a fully online double-conversion architecture. When utility power is normal, power passes through the dual conversion process of “AC input → rectification → DC bus → inversion → AC output” to supply the load, while simultaneously charging the battery bank. When utility power is interrupted, the battery bank releases energy, which is supplied to the inverter through the DC bus, continuing to power the load, thereby achieving uninterruptible power supply.

5.1 Basic Working Principle of Double Conversion

Online double conversion is the most reliable UPS operating mode. The load is always powered by the inverter. Electrical isolation between the utility power and the load is achieved through power conversion, completely isolating all types of utility power quality problems and providing the load with the purest, most stable sinusoidal power supply.

5.1.1 Normal Utility Mode (Main Path Power Supply)

Rectification stage: After three-phase AC utility power enters, it first passes through EMI filtering and surge protection, then enters the active power factor correction (APFC) rectifier circuit, which converts AC power into stable DC voltage. At the same time, it corrects the input current waveform, making the input power factor approach 1, significantly reducing harmonic current pollution to the power grid.

DC bus stage: The rectified DC power converges into the DC bus, is filtered and regulated by high-capacity capacitors, providing stable DC power for the inverter. At the same time, the DC-DC charging circuit draws power from the DC bus to perform intelligent charging of the battery bank.

Inverter stage: The inverter uses SPWM pulse width modulation technology to invert the DC voltage into high-frequency pulse voltage. After LC low-pass filtering, it outputs a standard, pure sinusoidal AC power. The output voltage is stabilized at the rated value (380V/220V), and the frequency is stabilized at 50Hz, unaffected by utility power fluctuations.

Output stage: The inverter outputs of each power module are paralleled to the output busbar, and after passing through the static bypass switch (inverter side conducting), they are delivered to the output distribution terminals to power the load.

5.1.2 Battery Power Mode (Utility Interruption)

When utility power is interrupted, input voltage exceeds the allowable range, or input frequency is abnormal, the UPS automatically switches to battery power mode. The switching process has zero interruption, and the load is completely unaffected:

The rectifier stops working, and the DC bus voltage is maintained by the battery bank. The battery bank boosts the battery voltage stably to the DC bus rated voltage through the DC-DC boost circuit.

The inverter continues normal operation, inverting DC power into AC power output. Load power supply is completely uninterrupted.

The monitoring system monitors battery voltage and discharge current in real-time, calculating the remaining backup time. When the battery voltage drops to the discharge termination voltage, a low voltage alarm is issued. If utility power has still not recovered, it will automatically shut down to protect the battery.

After utility power returns to normal, the UPS automatically switches back to utility rectifier power supply mode. At the same time, the charger automatically starts, charging the battery bank with constant current and constant voltage until the battery is fully charged, then transitions to float charging state.

5.1.3 Bypass Power Mode

When the UPS inverter system fails, output overload exceeds inverter load capacity, internal temperature is too high, or maintenance is required, the system will seamlessly switch to bypass power mode, with utility power directly powering the load:

The bypass control unit detects the bypass utility voltage, frequency, and phase in real-time, maintaining synchronous tracking with the inverter output.

When switching conditions are met, the static bypass switch (SCR) conducts at microsecond level, while the inverter output is simultaneously turned off, achieving zero-interruption switching with no flicker in load power supply.

After the fault is eliminated or overload is cleared, the system automatically detects that the inverter output is synchronized with the bypass voltage and automatically switches back to inverter mode. It can also be manually switched back to inverter operation.

In maintenance bypass mode, the maintenance bypass isolating switch is manually closed, and the load is directly powered by utility power. At this time, all UPS internal power can be completely disconnected, allowing safe equipment inspection.

5.2 Modular Parallel Current Sharing Principle

When multiple power modules operate in parallel, achieving uniform output current distribution among modules is the core technical challenge of modular UPS systems. Lain modular UPS employs fully digital DSP masterless parallel current sharing technology, achieving precise load current sharing through high-speed communication and digital closed-loop control.

5.2.1 Masterless Parallel Architecture

All power modules in the system have completely equal status; there is no master control module. Each module functions as both a power output unit and a control unit, independently sampling its own output current and voltage, and independently calculating control signals.

Advantages: No single point of failure risk from a master controller; failure of any module does not affect the operation of other modules, resulting in higher system reliability; modules have strong universality and are fully interchangeable.

5.2.2 Current Sharing Control Principle

Each power module communicates in real time with other modules via a high-speed CAN bus, exchanging data such as individual output current, output voltage, and operating status.

The DSP controller of each module dynamically fine-tunes its own output voltage and phase based on the deviation between its own current and the system average current, causing the output current to converge toward the average value.

Dual-loop current sharing control is adopted: the voltage outer loop ensures output voltage stability, while the current inner loop achieves fast current sharing regulation; current sharing accuracy can reach within ±5%, meeting parallel operation requirements.

During module hot-swap, a newly inserted module first performs voltage tracking and phase synchronization, then smoothly integrates into the system after matching the system output, avoiding inrush current; when a module is removed, the current is gradually unloaded before disconnection, without affecting system output stability.

5.3 Static Bypass Switching Principle

The static bypass switch is the core device for achieving seamless switching between inverter and bypass modes. It consists of two sets of high-power thyristors (SCRs) connected in reverse parallel, controlling the inverter path and bypass path respectively.

5.3.1 Synchronous Tracking Mechanism

The bypass control unit collects the voltage amplitude, frequency, and phase of the bypass mains supply in real time, while also collecting the corresponding parameters of the inverter output; through Phase-Locked Loop (PLL) technology, the inverter output frequency and phase are controlled to continuously track the bypass mains, maintaining synchronization between the two in preparation for switching at any time.

Synchronization conditions: Voltage difference ≤ ±5%, frequency difference ≤ ±0.5 Hz, phase difference ≤ ±5°; when conditions are met, the system is in a “same-phase synchronized” state, allowing bumpless switching.

5.3.2 Switching Execution Process

Inverter to Bypass: When a switch to bypass is required, the control circuit first triggers the bypass-side SCR into conduction, while simultaneously shutting off the inverter output; due to synchronization, the switching process introduces minimal current surge, output voltage shows no noticeable fluctuation, switching time ≤ 2 ms, and the load experiences no perceptible disturbance.

Bypass to Inverter: When the inverter recovers and switching back is required, the inverter output voltage is first controlled to synchronize with the bypass, then the inverter-side SCR is triggered into conduction while the bypass-side SCR is turned off, achieving a smooth, seamless transition.

Overload Switching Logic: When the load exceeds the inverter’s capacity (e.g., 150% overload sustained for 10 s), the system automatically switches to bypass; after the overload is cleared, the system automatically switches back to inverter after a delay, avoiding frequent switching.

5.4 Intelligent Battery Management Principle

The battery is a relatively weak link in terms of reliability in a UPS system. An intelligent Battery Management System (BMS) is critical for extending battery life and improving battery reliability.

5.4.1 Three-Stage Charging Management

Constant Current Charging Stage: After battery discharge, charging begins with a constant high current to rapidly replenish capacity; the charging current is automatically set based on battery capacity to avoid overcurrent damage to the battery.

Constant Voltage Charging Stage: When the battery voltage rises to the equalizing charge voltage, charging switches to constant voltage mode, and the charging current gradually decreases; this stage charges the battery to full capacity.

Float Charging Stage: After the battery is fully charged, the system automatically switches to float charge mode, maintaining the battery at full charge with a lower float voltage, compensating for battery self-discharge; this also prevents overcharging and extends battery life.

5.4.2 Temperature Compensation Function

The optimal charging voltage of a battery varies with ambient temperature: when temperature rises, the charging voltage should be appropriately reduced; when temperature drops, it should be appropriately increased. The system detects battery ambient temperature in real time through battery temperature sensors and automatically adjusts the charging voltage. The temperature compensation coefficient is -3 mV/°C/cell, ensuring optimal charging under different temperature conditions.

5.4.3 Battery Testing and Life Management

Scheduled Automatic Testing: Test cycles can be configured (e.g., monthly/quarterly) for automatic battery discharge testing, performing short-duration discharges to detect battery voltage decay rate and assess battery capacity and health status; if mains power is interrupted during the test, the test is immediately terminated and normal discharge is initiated.

Low Voltage Protection: During battery discharge, battery voltage is monitored in real time; when the low voltage alarm threshold is reached, an audible and visual alarm is triggered; when the end-of-discharge voltage is reached, discharge is automatically stopped to prevent damage from deep discharge.

Life Prediction: Based on data such as battery charge/discharge cycles, operating temperature, and internal resistance changes, the remaining battery life is comprehensively assessed, providing early warning for replacement needs.

5.5 System Protection Operating Principle

Lain modular UPS features a comprehensive multi-level protection mechanism covering input, output, battery, module, and system levels, providingcomprehensive protection for equipment and loads.

Protection Type Protection Function Description Action Mechanism
Input Overvoltage Protection Protects downstream circuits when mains voltage is too high Stops rectification when exceeding upper limit, switches to battery supply; alarm if sustained overvoltage
Input Undervoltage Protection Ensures output stability when mains voltage is too low Switches to battery supply when below lower limit; shuts down after battery depletion under sustained undervoltage
Output Overcurrent Protection Protects the inverter when load current is excessive Current-limited output; switches to bypass if sustained overload
Output Short Circuit Protection Protects equipment safety when output terminals are short-circuited Instantaneous current limiting, rapid inverter shutdown, switch to bypass with alarm
DC Bus Overvoltage Protects power devices from excessive DC voltage Activates discharge circuit; module shutdown protection for severe overvoltage
Module Overtemperature Protection Protects power devices when module temperature is excessive Load reduction at high temperature; module exits operation with alarm at overtemperature
Battery Reverse Polarity Protection Protects the circuit when battery terminals are reversed Diode blocking + circuit breaker protection, preventing reverse current from damaging equipment
Battery Overcharge Protection Prevents battery damage from overcharging Stops charging when charge voltage reaches upper limit; constant voltage float charge control
Battery Overdischarge Protection Prevents battery damage from deep discharge Stops discharge and automatically shuts down when discharge reaches end voltage

Chapter 6 Product Technical Parameters

6.1 System General Technical Parameters

Parameter Category Parameter Item LA-M10 Series LA-M30 Series LA-M50 Series LA-M100 Series
System Capacity Rated capacity range 10~60 kVA 30~300 kVA 50~300 kVA 100~1200 kVA
Single module capacity 10 kVA/10 kW 30 kVA/30 kW 50 kVA/50 kW 100 kVA/100 kW
Max modules per cabinet 6 10 6 12
Input Characteristics Rated input voltage 380V/220V 3-phase 4-wire 380V/220V 3-phase 4-wire 380V/220V 3-phase 4-wire 380V/220V 3-phase 4-wire
Input voltage range 138~485V (line voltage) 138~485V (line voltage) 138~485V (line voltage) 120~485V (line voltage)
Rated input frequency 50 Hz 50 Hz 50 Hz 50 Hz
Input frequency range 40~70 Hz 40~70 Hz 40~70 Hz 40~70 Hz
Input power factor ≥0.99 (full load) ≥0.99 (full load) ≥0.99 (full load) ≥0.99 (full load)
Input current THDi ≤3% (full load) ≤3% (full load) ≤3% (full load) ≤2.5% (full load)
Output Characteristics Rated output voltage 380V/220V 3-phase 4-wire 380V/220V 3-phase 4-wire 380V/220V 3-phase 4-wire 380V/220V 3-phase 4-wire
Output voltage regulation ±1% (steady state) ±1% (steady state) ±1% (steady state) ±0.5% (steady state)
Output frequency regulation ±0.1% (battery mode) ±0.1% (battery mode) ±0.1% (battery mode) ±0.05% (battery mode)
Output waveform Pure sine wave Pure sine wave Pure sine wave Pure sine wave
Output harmonic distortion THDu ≤3% (linear load) ≤3% (linear load) ≤3% (linear load) ≤2% (linear load)
Overload capability 110% load continuous; 150% load 60 s; 125% load 10 min 110% load continuous; 150% load 60 s; 125% load 10 min 110% load continuous; 150% load 60 s; 125% load 10 min 110% load continuous; 150% load 120 s; 125% load 15 min
Transfer time 0 ms (mains to battery); ≤2 ms (inverter to bypass) 0 ms (mains to battery); ≤2 ms (inverter to bypass) 0 ms (mains to battery); ≤2 ms (inverter to bypass) 0 ms (mains to battery); ≤1 ms (inverter to bypass)
Efficiency Full load efficiency ≥95% ≥95.5% ≥96% ≥96%
ECO mode efficiency ≥98.5% ≥99% ≥99% ≥99.2%
Half load efficiency ≥94% ≥94.5% ≥95% ≥95.5%
Battery Characteristics DC bus voltage 192V/384V 384V 384V/480V 480V
Battery nominal voltage 12V/cell 12V/cell 12V/cell 12V/cell
Battery cell count options 16/32 cells 32/36/40 cells 32/36/40 cells 40 cells
Charging method 3-stage: constant current + constant voltage + float 3-stage: constant current + constant voltage + float 3-stage: constant current + constant voltage + float 3-stage: constant current + constant voltage + float
Environmental Parameters Operating temperature 0~40°C (rated output); 40~55°C derated 0~40°C (rated output); 40~55°C derated 0~40°C (rated output); 40~55°C derated 0~40°C (rated output); 40~55°C derated
Storage temperature -25~55°C -25~55°C -25~55°C -25~55°C
Relative humidity 20%~90%, non-condensing 20%~90%, non-condensing 20%~90%, non-condensing 20%~90%, non-condensing
Altitude ≤1000 m rated output; derate 10% per 1000 m above 1000 m ≤1000 m rated output; derate 10% per 1000 m above 1000 m ≤1000 m rated output; derate 10% per 1000 m above 1000 m ≤1000 m rated output; derate 10% per 1000 m above 1000 m
Noise level ≤55 dB (1 m distance) ≤58 dB (1 m distance) ≤60 dB (1 m distance) ≤62 dB (1 m distance)
Mechanical Parameters Cabinet dimensions (W×D×H) 600×800×2000 mm 600×1100×2000 mm 600×1100×2000 mm 800×1200×2200 mm
Cabinet weight (empty) Approx. 180 kg Approx. 280 kg Approx. 300 kg Approx. 450 kg
Single module weight Approx. 12 kg Approx. 25 kg Approx. 38 kg Approx. 65 kg
Protection rating IP20 IP20 IP20 IP20

6.2 Power Module Detailed Electrical Parameters (using LA-M30-PM as an example)

Input Parameters

  • Rated input voltage: 3-phase 3-wire 380 VAC
  • Input voltage range: 176~528 VAC (line voltage)
  • Rated input frequency: 50 Hz/60 Hz auto-adaptive
  • Input power factor: ≥0.99 @ 100% load
  • Input current total harmonic distortion: ≤3% @ 100% linear load
  • Inrush current: ≤1.5× rated input current

DC Output Parameters

  • DC bus rated voltage: 384 VDC
  • DC bus voltage range: 320~420 VDC
  • Charging voltage range: 410~440 VDC (adjustable)
  • Maximum charging current: 10 A/module

Output Parameters

  • Rated output capacity: 30 kVA/30 kW
  • Output voltage: 3-phase 4-wire 380V/220V AC
  • Voltage regulation accuracy: ±1%
  • Frequency accuracy: ±0.1% (battery mode)
  • Waveform distortion: THD ≤3% (linear load), THD ≤5% (nonlinear load)
  • Load power factor: 0.9 (leading/lagging)
  • Three-phase unbalance: voltage deviation ≤±2% under 100% unbalanced load

Protection Parameters

  • Output overcurrent protection: 110%~150% current limiting; fast protection above 150%
  • Output short circuit protection: instantaneous short circuit supported; automatic current limiting and bypass transfer
  • Overtemperature protection: alarm at 85°C, shutdown protection at 95°C
  • DC overvoltage protection: trips at 450 VDC
  • DC undervoltage protection: alarm at 300 VDC, shutdown at 280 VDC

6.3 Monitoring and Communication Parameters

  • Display interface: 10.1-inch color LCD touchscreen, resolution 1024×600, bilingual Chinese/English
  • Display content: Input voltage/current/frequency, output voltage/current/power/load percentage, battery voltage/current/capacity, module status, alarm information, operation logs, etc.
  • Standard communication interfaces:
  • RS232 interface: 1 channel, supports host computer communication
  • RS485 interface: 1 channel, supports Modbus-RTU protocol
  • Dry contact interface: 4 inputs, 6 outputs, customizable alarms and control
  • USB interface: 1 channel, supports firmware upgrade and data export
  • Optional communication interfaces:
  • SNMP network card: supports SNMP v1/v2c/v3, web-based remote management
  • 4G module: SMS alarm, remote inquiry
  • Dry contact expansion card: expands additional dry contact count
  • Alarm methods: Local audible/visual alarm, on-screen popup alarm, remote communication alarm, SMS alarm (optional)
  • History records: ≥10,000 alarm records, ≥1,000 operation records, circular storage supported

6.4 Standards and Certifications

  • Compliance standard: GB/T 7260.3-2003 “Uninterruptible Power Systems (UPS) – Part 3: Methods of Specifying the Performance and Test Requirements”
  • Compliance standard: YD/T 1970-2009 “Uninterruptible Power Supply (UPS) for Telecommunications”
  • Safety standard: GB 4943.1-2022 “Safety of Information Technology Equipment – Part 1: General Requirements”
  • Electromagnetic compatibility: GB/T 17626 series EMC standards
  • Product certifications: CCC certification, CE certification
  • Lightning protection standard: GB 50057-2010 “Code for Design Protection of Structures against Lightning” Class C protection

Chapter 7 Product Functions and Features

7.1 High-Reliability Functions

7.1.1 N+X Parallel Redundancy

The system supports N+1, N+2, and other redundancy configurations. When any one or more power modules fail, the system automatically isolates the faulty modules, and the remaining modules continue to carry the full load with zero power interruption. Redundancy levels can be flexibly configured based on load criticality. System availability can reach up to 99.999%, meeting the high-reliability requirements of core business operations.

7.1.2 No Single Point of Failure Design

  • Power modules: Distributed parallel architecture, no single point of failure
  • Bypass module: Supports redundant configuration, dual bypass modules in hot standby
  • Monitoring module: Supports dual monitoring redundancy; failure of a single monitoring unit does not affect power output
  • Bus system: High-current redundant design, reliable connections, low temperature rise
  • Cooling system: Multiple independent cooling fans; failure of a single fan does not affect overall cooling

7.1.3 Comprehensive Protection System

Features more than twenty protection functions including input overvoltage/undervoltage, output overcurrent/short circuit, DC overvoltage/undervoltage, module overtemperature, battery reverse polarity, battery overcharge/overdischarge, etc. Faults are handled in a graded manner: minor faults trigger alarms, while severe faults trigger automatic protection, ensuring absolute safety of equipment and loads.

7.1.4 Industrial-Grade Component Selection

Core power components use internationally leading brand IGBTs, capacitors, and fans; critical components undergo strict screening and high/low temperature burn-in testing; PCBs use immersion gold process for moisture and corrosion resistance; all products undergo 72-hour full-load burn-in testing before shipment to ensure factory reliability.

7.2 Flexible Expansion and Easy Maintenance Functions

7.2.1 Online Hot-Swap

Power modules, monitoring modules, and bypass modules all support hot-swap operation. When replacing a faulty module or adding expansion modules, no shutdown or bypass transfer is required — modules can be inserted or removed directly online without any impact on load power supply. Single module replacement time ≤ 5 minutes, significantly reducing maintenance difficulty and fault repair time.

7.2.2 On-Demand Smooth Expansion

Initial investment can be matched to current load requirements by configuring the appropriate number of modules. As business grows, capacity upgrades only require purchasing additional power modules and inserting them into the cabinet slots — no need to replace the entire system. The expansion process is simple and fast, protecting the user’s initial investment and achieving optimal TCO (Total Cost of Ownership).

7.2.3 Standardized Universal Modules

Modules of the same specification across the full series are fully interchangeable with no special pairing requirements. Spare parts inventory only needs to stock standard power modules, eliminating the need to stock large quantities of different spare parts for different models, significantly reducing spare parts inventory costs and management complexity.

7.2.4 Visualized Operation & Maintenance Interface

10.1-inch color touchscreen with graphical display of system operation topology, module status, and all electrical parameters. In the event of a fault, the faulty module is automatically located with fault codes and troubleshooting guides displayed. Operation is simple and intuitive, allowing regular maintenance personnel to quickly become proficient, reducing dependence on specialized engineers.

7.3 High Efficiency, Energy Saving, and Green Design

7.3.1 Three-Level High-Efficiency Topology

Advanced three-level inverter technology is adopted. Compared to traditional two-level topologies, switching losses are reduced by more than 30%. Full-load efficiency reaches as high as 96%, and half-load efficiency remains above 95%. Long-term operation saves significant electricity costs, reduces PUE, and meets green data center construction requirements.

7.3.2 ECO Economic Operation Mode

ECO energy-saving mode is supported. When mains power quality is good, the load is preferentially supplied directly from mains through the bypass, with the inverter in hot standby. System efficiency can reach over 99% in this mode, significantly reducing losses. When mains is abnormal, the system automatically and seamlessly switches back to inverter mode, balancing both energy savings and reliability.

7.3.3 Intelligent Sleep Function

When system load is low, some power modules automatically enter sleep mode, allowing operating modules to run in a higher-load, more efficient operating range, improving overall system efficiency. Sleeping modules remain in hot standby and can be quickly awakened to resume operation during sudden load increases. Module rotation sleep is supported to prevent certain modules from remaining idle for extended periods, extending module service life.

7.3.4 Intelligent Temperature-Controlled Cooling

Multi-level intelligent temperature-controlled fans automatically adjust fan speed based on load percentage and ambient temperature. At low load and low temperature, fans run at low speed, reducing noise and power consumption. At high load and high temperature, fan speed automatically increases to ensure adequate cooling. Fan start/stop and speed adjustment are smooth and gradual, avoiding frequent on/off cycling and extending fan life.

7.3.5 Green Environmental Design

Input power factor ≥0.99 and input harmonic distortion ≤3%, causing minimal pollution to the power grid without requiring additional harmonic filtering equipment. Compliant with RoHS environmental directives, free of hazardous substances. Products can be dismantled and recycled at the end of their lifecycle, reducing environmental impact.

7.4 Intelligent Management Functions

7.4.1 Intelligent Battery Management

  • Three-stage intelligent charging with automatic charging strategy adjustment based on battery state
  • Temperature-compensated charging to adapt to different ambient temperatures, extending battery life
  • Automatic battery testing for periodic battery health assessment and early warning
  • Real-time calculation of battery State of Charge (SOC) with accurate backup time display
  • Battery internal resistance monitoring (optional) for precise assessment of battery aging

7.4.2 Comprehensive Monitoring and Communication

  • Full-function operation on local touchscreen: parameter settings, status inquiry, and fault diagnosis all available
  • Supports RS232, RS485, SNMP, dry contact, and other communication methods for seamless integration into environment monitoring systems
  • Web-based remote management: view status, configure parameters, and receive alarms via browser
  • Mobile APP and SMS alarm support for monitoring equipment status anytime, anywhere
  • Centralized monitoring of multiple UPS units with unified management, suitable for multi-computer-room, large-scale deployments

7.4.3 Fault Self-Diagnosis and Recording

  • Real-time system self-diagnosis automatically detects fault points with precise location of faulty modules and fault types
  • Dual indication of fault code + text description with troubleshooting guides for rapid problem identification
  • Large-capacity historical storage recording all alarms, operations, and operational data for traceability and analysis
  • Black box function: automatically saves operational data from the period preceding a fault for fault analysis

7.4.4 Parallel Expansion Function

Supports multi-cabinet parallel operation with expansion capability beyond 1200 kVA. Parallel systems also support N+X redundancy with universal modules and flexible expansion. Parallel control uses high-speed fiber-optic communication for high current sharing accuracy and strong reliability.

7.5 Safety Protection Functions

7.5.1 Emergency Power Off (EPO)

The cabinet front panel is equipped with an emergency stop button. In emergency situations (such as fire or electric shock), pressing this button immediately shuts off all UPS output and disconnects internal power, ensuring personnel and equipment safety.

7.5.2 Maintenance Bypass Safety Design

The maintenance bypass switch features mechanical interlocking to prevent misoperation. When the maintenance bypass is closed, the UPS internal circuit is completely electrically isolated from the load, allowing maintenance personnel to perform safe servicing. The panel clearly indicates maintenance bypass status, avoiding live-work risks.

7.5.3 Grounding and Lightning Protection

Comprehensive grounding system design with reliable connections between the chassis, grounding copper bar, and input PE terminal. Standard configuration includes Class C lightning surge protection; Class B lightning protection is available as an option, effectively suppressing lightning strikes and grid surges. Equipment insulation rating is high, and electric shock protection complies with safety standards.

7.5.4 Operation Permission Management

The monitoring system supports multi-level user permissions: regular users can only view status, while administrators can perform parameter settings and system control. This prevents unauthorized personnel from misoperation and ensures system operation security.

Chapter 8 Product Application Scenarios

Lain modular UPS, with its core advantages of high reliability, easy expansion, easy maintenance, and high efficiency, is widely applied across data centers, telecommunications, finance, healthcare, industrial, transportation, energy, and government sectors, providing stable and reliable power protection for various critical loads.

8.1 Data Center Scenarios

8.1.1 Small and Medium Enterprise Data Centers

Scenario characteristics: Load grows gradually with business; limited computer room space; few maintenance personnel; requiring high reliability, easy maintenance, and smooth expandability.

Solution configuration: LA-M30 series modular UPS, 30 kVA per module, initial configuration of 2~3 modules with N+1 redundancy; modules can be added at any time for subsequent business expansion, with maximum expansion to 300 kVA.

Core value: On-demand investment avoids resource waste; hot-swappable modules make maintenance simple and lower the maintenance threshold; high efficiency and energy savings reduce long-term operating costs.

8.1.2 Large Cloud Data Centers

Scenario characteristics: Large capacity requirements; high availability requirements (Tier III/Tier IV); strict PUE requirements; centralized operation and maintenance.

Solution configuration: LA-M100 series large modular UPS, 10 modules per cabinet, multiple cabinets in parallel; 2N dual-bus power supply architecture with fully redundant design.

Core value: Large-capacity parallel expansion capability meets ultra-high power demands; N+X redundancy + 2N architecture achieves availability targets; high-efficiency topology + intelligent sleep reduces PUE; centralized monitoring and management improves O&M efficiency.

8.1.3 Edge Data Centers / Modular Computer Rooms

Scenario characteristics: Dispersed deployment; confined spaces; unattended operation; relatively poor environmental conditions.

Solution configuration: LA-M10/20 series small modular UPS, integrated design that can be directly installed into micro-module cabinets; optional 4G remote monitoring and SMS alarm.

Core value: Compact size, rapid deployment; adapts to wide voltage and wide temperature environments; remote monitoring enables reliable unattended operation.

8.2 Telecommunications Industry Scenarios

8.2.1 Carrier Core Computer Rooms

Scenario characteristics: Core network equipment and switching equipment for telecommunications have extremely high requirements for power supply continuity, operating 24×7 without interruption; large load capacity; high level of standardization in computer rooms.

Solution configuration: LA-M50 series modular UPS in N+2 redundant configuration; dual mains input; supporting battery bank providing 4+ hours of backup power.

Core value: High reliability meeting carrier-grade 99.999% availability requirements; modular design allows expansion and maintenance without business interruption; comprehensive communication interfaces for integration into telecom network management systems.

8.2.2 5G Base Stations and Edge Computer Rooms

Scenario characteristics: Large number of dispersed sites; small equipment room space; complex grid environment; high operation and maintenance costs.

Solution configuration: LA-M10 series miniature modular UPS, rack-mount installation, compact size; wide voltage input adapts to unstable grid; supports remote centralized monitoring.

Core value: Rapid deployment at moderate cost; adapts to complex grid environments; centralized O&M reduces site maintenance costs.

8.2.3 Broadcast and Television Transmission Computer Rooms

Scenario characteristics: Broadcast and TV transmission equipment has high requirements for power supply stability; broadcast incidents have significant consequences; computer rooms are typically located at TV stations and transmitter sites.

Solution configuration: LA-M30 series modular UPS with N+1 redundancy; output isolation transformer configured to improve power quality.

Core value: Zero-interruption switching ensures broadcast security; pure sine wave output protects precision broadcast equipment; reliable and stable, reducing the risk of broadcast interruption.

8.3 Financial Industry Scenarios

8.3.1 Bank Data Centers and Branch Outlets

Scenario characteristics: Core transaction systems and data storage systems cannot be interrupted; business continuity directly affects fund security and customer experience; branch outlets are dispersed, making O&M difficult.

Solution configuration: Data centers use LA-M100 series in 2N dual-bus architecture; branch outlets use LA-M20 series small modular UPS.

Core value: High availability eliminates transaction interruptions; unified equipment models reduce spare parts and O&M costs; remote centralized monitoring improves branch O&M efficiency.

8.3.2 Securities/Futures Trading Computer Rooms

Scenario characteristics: Trading systems have extremely high requirements for power supply stability and power quality; even momentary power interruptions can cause trading anomalies and data loss; strict requirements for neutral-to-earth voltage and harmonics.

Solution configuration: LA-M50 series modular UPS with output isolation transformer, N+2 redundancy; paired with precision power distribution system.

Core value: Pure sine wave, low harmonic output ensures stable operation of trading equipment; millisecond-level switching with zero power flicker; highly redundant architecture eliminates single points of failure.

8.3.3 Insurance/Fund Data Centers

Scenario characteristics: Massive customer data and business systems require continuous operation; high data security and business continuity requirements; high IT equipment density.

Solution configuration: LA-M30/50 series modular UPS, gradually expanding capacity as business grows; paired with intelligent battery management system.

Core value: Smooth expansion matches business development pace; intelligent battery management ensures backup power reliability; high efficiency and energy savings reduce computer room operating costs.

8.4 Healthcare Industry Scenarios

8.4.1 Hospital Information Center (HIS Computer Room)

Scenario characteristics: Hospital information systems, electronic medical records, and billing systems run hospital-wide; interruption affects medical service order; load grows continuously with gradual computer room expansion.

Solution configuration: LA-M30 series modular UPS, N+1 redundancy, 30+ minutes backup power; integrated into hospital environment monitoring system.

Core value: Reliable power supply ensures stable operation of hospital information systems; online expansion does not affect daily medical services; easy maintenance reduces pressure on IT department.

8.4.2 Precision Medical Equipment Computer Rooms

Scenario characteristics: Large medical equipment such as MRI, CT, DSA, and biochemical analyzers are extremely expensive and have very high requirements for power quality and stability; voltage fluctuations and harmonics can affect equipment accuracy or even cause damage.

Solution configuration: LA-M50 series modular UPS with isolation transformer and high-precision filtering; industrial-grade wide temperature design.

Core value: Clean, stable sine wave output protects precision medical equipment; zero-interruption power supply prevents examination interruptions and data loss; comprehensive protection prevents equipment damage.

8.4.3 Operating Rooms and ICU Power Supply Systems

Scenario characteristics: Life support equipment and surgical equipment cannot lose power; power interruption directly endangers patient lives; extremely high requirements for power supply reliability and safety.

Solution configuration: Medical-grade modular UPS with dual redundant configuration, compliant with medical electrical safety standards; isolated output for leakage protection.

Core value: Ultra-high reliability ensures uninterrupted power to life-critical equipment; medical-grade safety design prevents electric shock and interference; rapid maintenance ensures faults do not affect surgical operations.

8.5 Industrial Automation Scenarios

8.5.1 Factory Automation Production Lines

Scenario characteristics: Automated production lines, PLC control systems, and robotic equipment power failures can cause production interruptions, product scrapping, and even equipment damage; industrial sites have complex grid environments with poor dust and temperature conditions.

Solution configuration: Industrial-grade LA-M30 series modular UPS with wide temperature design and enhanced protection; input isolation and lightning protection configured.

Core value: Adapts to harsh industrial environments with strong anti-interference capability; ensures continuous production line operation, reducing downtime losses; easily replaceable modules reduce production stoppage repair time.

8.5.2 Power Substation / Power Plant Control Rooms

Scenario characteristics: Power dispatch, relay protection, and monitoring systems must operate continuously; power supply interruption could cause grid accidents; substations have complex electromagnetic environments and large grid fluctuations.

Solution configuration: Industrial-grade modular UPS with dual input, N+1 redundancy; strong electromagnetic compatibility design; paired with long-duration backup battery banks.

Core value: Strong anti-interference capability adapts to complex electromagnetic environments in substations; wide voltage input adapts to grid fluctuations; high reliability ensures safety of power control systems.

8.5.3 Petrochemical Control Rooms

Scenario characteristics: Chemical production DCS control systems and Safety Instrumented Systems (SIS) cannot lose power; power failure may cause safety incidents; sites may have corrosive gases and high temperatures.

Solution configuration: Corrosion-resistant industrial modular UPS installed in pressurized control rooms; N+2 redundant configuration.

Core value: High reliability ensures safe operation of chemical control systems; corrosion-resistant design adapts to harsh environments; online maintenance does not affect continuous production operation.

8.6 Transportation Industry Scenarios

8.6.1 Rail Transit Control Centers

Scenario characteristics: Subway and high-speed rail signaling systems, dispatch systems, and AFC ticketing systems have extremely high requirements for power supply reliability; power failures can cause operational interruptions affecting public safety.

Solution configuration: LA-M50 series modular UPS with dual redundant sets; compliant with rail transit industry standards.

Core value: High redundancy and reliability prevent operational incidents; smooth, interruption-free switching ensures stable signal system operation; long-life design adapts to long-term rail transit operation requirements.

8.6.2 Airport Terminals and Air Traffic Control Systems

Scenario characteristics: Air traffic control radar, communication navigation, departure systems, and security screening equipment are all critical loads; power interruptions affect flight operations and aviation safety.

Solution configuration: Large modular UPS system with 2N architecture; paired with diesel generators as backup power.

Core value: Ultra-high availability ensures civil aviation operational safety; large-capacity parallel capability meets terminal large-load demands; stable and reliable, compliant with civil aviation industry standards.

8.6.3 Highway Toll Stations and Monitoring Centers

Scenario characteristics: Toll collection systems, monitoring systems, and communication sites are dispersed with varying grid conditions and unattended operation; power failure causes toll collection interruption and surveillance failure.

Solution configuration: Small modular UPS with wide voltage input, supporting remote monitoring and SMS alarm.

Core value: Adapts to dispersed site deployment with unattended operation; stable and reliable with reduced failure probability; remote management reduces on-site O&M costs.

8.7 Government and Public Utility Scenarios

8.7.1 Government Data Centers and E-Government Computer Rooms

Scenario characteristics: E-government systems and government cloud platforms carry large amounts of government services and public data, requiring high reliability and security; must comply with classified protection requirements.

Solution configuration: LA-M30/50 series modular UPS with N+1 redundancy; compliant with Level 3 classified protection power supply requirements.

Core value: High-reliability power supply ensures continuous operation of government services; secure and compliant, meeting classified protection requirements; smooth expansion adapts to e-government cloud development.

8.7.2 Public Security / Emergency Command Centers

Scenario characteristics: Command dispatch systems, video surveillance systems, and communication systems must operate 24×7; power cannot be interrupted during emergency situations.

Solution configuration: Modular UPS with dual-bus architecture, paired with long-duration battery banks and generator coordination.

Core value: Dual-bus architecture eliminates single points of failure, ensuring uninterrupted command system operation; seamless generator transition extends backup time; stable and reliable, prepared for sudden emergency events.

8.7.3 Education and Research Computer Rooms

Scenario characteristics: University data centers, research laboratories, and supercomputing centers have high-value equipment and precious research data; load fluctuations are large; research project cycles are long.

Solution configuration: LA-M50 series modular UPS, configured on demand with gradual expansion; comprehensive protection functions.

Core value: Protects expensive research equipment and experimental data; flexible expansion adapts to research project changes; high efficiency and energy savings reduce university computer room operating costs.

Chapter 9 Product Installation

9.1 Pre-Installation Preparation

9.1.1 Installation Site Survey and Requirements

Before equipment installation, a site survey of the installation location must be conducted to confirm that environmental conditions meet equipment operation requirements, avoiding equipment failure or shortened service life due to environmental issues.

Temperature and Humidity Requirements

  • Operating ambient temperature: 0°C~40°C (rated output); optimal operating temperature 20°C~25°C
  • Storage ambient temperature: -25°C~55°C
  • Relative humidity: 20%~90%, non-condensing; recommended battery environment humidity 30%~60%

Note: Installation location should be away from heaters, air conditioner outlets, and direct sunlight to avoid sudden temperature changes and localized overheating; dehumidification equipment is required in humid areas.

Space and Floor Loading Requirements

  • Front operating space in front of cabinet: ≥1000 mm, to facilitate module insertion/removal and routine operation
  • Rear maintenance space behind cabinet: ≥800 mm, to facilitate wiring and rear access
  • Top clearance above cabinet: ≥500 mm, to ensure ventilation and heat dissipation
  • Floor load-bearing requirement: calculated based on cabinet full-load weight; floor load capacity ≥800 kg/m²; large models require ≥1000 kg/m²

Note: Installation location should avoid main aisle passageways, doorways, and other areas prone to impact; floor must be level with no significant incline.

Ventilation and Heat Dissipation Requirements

  • Installation location must have good ventilation with no obstructions in front of and behind the unit, ensuring smooth air circulation
  • When multiple cabinets are placed side by side, maintain a gap of ≥50 mm between cabinets, or use hot/cold aisle layout
  • Computer room air conditioning supply/return air should match UPS airflow direction to avoid hot air recirculation causing elevated inlet temperatures
  • Computer room ambient temperature should be maintained below 25°C to ensure UPS operates in its optimal efficiency and service life range

Other Environmental Requirements

  • Keep away from corrosive gases, flammable/explosive materials, and strong electromagnetic interference sources
  • Avoid installation in dusty, oily, or high-vibration locations
  • Altitude ≤1000 m; derating required above 1000 m; custom high-altitude models required above 2000 m
  • Installation location should facilitate cable routing and grounding connections, close to mains input and load terminations

9.1.2 Tool and Material Preparation

Before installation, prepare all necessary tools and auxiliary materials to ensure smooth installation:

Installation Tools

  • Handling equipment: forklift, manual hydraulic pallet truck, lifting slings (for large cabinets)
  • Fastening tools: torque wrench, socket wrench set, Phillips/flathead screwdrivers, hex key set
  • Measuring tools: multimeter, clamp meter, phase sequence meter, spirit level, tape measure, ground resistance tester
  • Other tools: wire strippers, crimping pliers, electrician’s knife, heat gun, anti-static wrist strap, insulating gloves, flashlight

Installation Auxiliary Materials

  • Cables: input/output power cables, battery interconnecting cables, control/communication cables, grounding wires
  • Connectors: copper lugs, wire markers, cable ties, insulating tape, heat-shrink tubing, expansion bolts, anti-vibration pads
  • Other: grounding copper bar, fire-stop putty, identification labels, anti-rust paint

9.1.3 Personnel and Safety Preparation

Personnel Requirements

  • Installation personnel must hold a valid electrician’s certificate with qualifications for low-voltage distribution operations
  • Must have received modular UPS installation training and be familiar with product structure and installation procedures
  • At least 2 installation personnel required on site; 3~4 personnel needed for coordinated work on large equipment
  • Designate an on-site supervisor for unified command and standardized operation

Safety Precautions

  • Confirm the on-site mains input is de-energized before installation, and post a “Work in Progress – Do Not Close” warning sign
  • Operators must wear insulating gloves, anti-static wrist straps, and insulating shoes
  • Exercise caution when handling heavy cabinets to prevent crushing or pinching injuries
  • For overhead work (e.g., top wiring), use a ladder with fall protection measures in place
  • Equip the construction site with fire extinguishers and take fire prevention measures
  • Strictly prohibit closing the circuit breaker and energizing before wiring is completed

9.2 Equipment Delivery and Unpacking Inspection

After equipment arrives at the site, inspect the outer packaging for integrity, signs of rain exposure, impact damage, or breakage; immediately record and contact the logistics provider and manufacturer if any anomalies are found.

Unpack in the presence of both supplier and customer personnel, and verify the model and quantity of the main unit, modules, accessories, and technical documentation against the packing list item by item.

Inspect equipment appearance: cabinet paint finish for damage, deformation, or dents; module front panels for integrity; connectors and terminals for damage.

Verify equipment nameplate: model, rated capacity, factory serial number, and date of manufacture should match the contract.

After acceptance, both parties sign the unpacking inspection report; if there are missing or damaged items, take photos for documentation and contact the manufacturer for replacement.

Equipment not immediately installed should be stored in a dry, ventilated indoor location with dust and moisture protection; modules must not be stacked or compressed to prevent damage.

9.3 Cabinet Positioning and Securing

9.3.1 Cabinet Handling and Positioning

Mark cabinet installation reference lines on the floor at the planned location to ensure proper alignment.

Use a forklift or hydraulic pallet truck for handling heavy cabinets; keep cabinets upright during transport — tipping beyond 30° is strictly prohibited to prevent internal component displacement and damage.

Move the cabinet to the predetermined position and roughly align with reference lines; remove cabinet packaging and protective materials.

9.3.2 Leveling and Securing

Adjust the adjustable leveling feet at the cabinet base, using a spirit level to set cabinet levelness and plumbness; horizontal deviation ≤2 mm/m, vertical deviation ≤3 mm/m.

For multiple cabinets configured together, adjust spacing and alignment to ensure cabinet fronts are flush and gaps are uniform.

Where floor anchoring is required, secure the cabinet firmly to the floor using expansion bolts through the mounting holes at the cabinet base; for raised access floor environments, fabricate a load-bearing base and secure the cabinet to the base.

Cabinet grounding: Reliably connect the cabinet grounding terminal to the computer room grounding copper bar using yellow-green two-color copper core wire with a cross-section ≥16 mm².

9.4 Module Installation

9.4.1 Pre-Installation Inspection

Inspect the power modules, bypass modules, and monitoring modules for any external damage or transit-related defects.

Inspect the guide rails and connectors inside the cabinet slots to ensure they are intact, free from deformation, and free of foreign objects.

Operators must wear anti-static wrist straps to discharge static electricity from the human body, preventing electrostatic damage to electronic components.

9.4.2 Module Installation Procedure

1. Open the front door of the cabinet, locate the corresponding module slot, and confirm the slot number.

2. Support the bottom of the module with both hands, align it with the slot guide rails, and push the module smoothly into the slot; keep it level during insertion to avoid tilting.

3. When the module is pushed near the bottom, apply moderate force to ensure the backplane connector is fully seated; stop when a “click” sound is heard or the seated position is felt.

4. Tighten the fixing screws on both sides of the module. Control the torque between 1.2~1.5 N·m to ensure the module is firmly secured with good contact.

5. Install all power modules, bypass modules, and monitoring modules using the same method; there is no special requirement for installation order—both bottom-to-top and top-to-bottom sequences are acceptable.

6. After all modules are installed, check that each module is firmly secured without loosening; confirm the initial status of the module panel indicator lights is normal.

9.4.3 Module Installation Precautions

  • Hot-swapping modules is strictly prohibited (except during initial installation before power-on); hot-swap operations during later maintenance must strictly follow the operating procedures.
  • Use moderate force when inserting modules; never use excessive force or impact, as this may damage connectors and internal components.
  • Modules of different specifications or models must not be mixed; only power modules of the identical model and specification may be used.
  • Unused slots must be fitted with blanking plates to maintain airflow path integrity and prevent dust ingress and safety hazards.

9.5 Grounding System Installation

Proper grounding is the foundation for safe UPS operation, anti-interference, and lightning protection. Installation must strictly comply with applicable specifications.

9.5.1 Grounding Requirements

  • Grounding resistance requirements: UPS system working grounding resistance ≤4 Ω; combined grounding system resistance ≤1 Ω.
  • Grounding conductor specifications: The protective grounding conductor shall be a yellow-green dual-colored stranded copper flexible wire, with cross-section selected according to system capacity:
  • 60 kVA and below: ≥16 mm²
  • 60~200 kVA: ≥25 mm²
  • Above 200 kVA: ≥35 mm²
  • Grounding connection points must be firm and reliable, with anti-rust treatment; using water pipes or heating pipes as grounding electrodes is strictly prohibited.

9.5.2 Grounding Connection Procedure

1. Confirm the location of the equipment room grounding copper busbar and verify that the grounding resistance meets the requirements and has passed testing.

2. Cut the grounding conductor to an appropriate length, crimp copper lugs of matching specification at both ends, and apply tin coating.

3. Connect one end to the grounding terminal at the bottom of the UPS cabinet and tighten the fixing screws to ensure good contact.

4. Connect the other end to the equipment room grounding copper busbar, securing with bolts and spring washers.

5. Supporting equipment such as battery cabinets and output distribution cabinets must also be individually grounded, each with its own dedicated connection to the grounding busbar; series grounding is prohibited.

6. After connection, use a multimeter to test continuity between the cabinet and the grounding copper busbar; resistance approaching zero indicates normal condition.

9.6 Post-Installation Appearance and Structural Inspection

  • Overall inspection: Cabinets are neatly arranged, level and plumb as required, and firmly secured.
  • Module inspection: All modules are installed in place, fixing screws are tightened, and panels are flush.
  • Door inspection: Front and side doors open and close smoothly, door locks function properly, and sealing is intact.
  • Label inspection: Equipment labels and warning signs are clear and complete; cable labels must be completed after subsequent wiring.
  • Environment inspection: Installation site is cleaned up with no debris left behind; clearance around equipment meets requirements.

Wiring is the core of UPS installation. Wiring quality directly affects the safety and reliability of equipment operation. All wiring must be performed by certified electricians, strictly following electrical codes and the requirements of this manual, ensuring correct, firm connections with proper insulation.

10.1 General Wiring Principles and Safety Requirements

  • De-energized operation: All wiring work must be performed with the utility power input disconnected and the battery breaker open. Wiring under power is strictly prohibited; verify the absence of voltage after de-energizing.
  • Correct phase sequence: Three-phase input and output must strictly distinguish phase sequence (L1/L2/L3 or R/S/T), neutral (N), and ground (PE). Incorrect wiring or reversed connections are strictly prohibited.
  • Compliant conductor size: Power cable cross-sections must meet current-carrying capacity requirements, with voltage drop ≤2%; using undersized cables for large loads is strictly prohibited to avoid cable overheating and safety hazards.
  • Firm connections: All wiring terminals must be tightened with torque meeting requirements; stranded conductors must be crimped with copper lugs, and direct insertion into terminals is prohibited.
  • Insulation protection: Exposed live parts must be properly insulated; after wiring, clean up wire clippings and metal debris to prevent short circuits.
  • Clear identification: Both ends of all cables must be fitted with wire number sleeves indicating circuit names and phase sequences, facilitating subsequent maintenance and troubleshooting.
  • Cable routing: Power cables and signal cables must be routed separately to avoid cross-interference; cables should be neatly bundled, straight and level, without obstructing airflow paths or operating components.

10.2 Cable Sizing Calculation

10.2.1 Conductor Sizing Principles

Cable cross-section selection must simultaneously satisfy current-carrying capacity and voltage drop requirements, whichever is larger.

  • Current-carrying capacity: The cable’s long-term allowable current-carrying capacity ≥ maximum operating current of the circuit; derating is required when ambient temperature is higher.
  • Voltage drop: For longer cable runs, calculate the line voltage drop; the full-load voltage drop must be ≤2% of the rated voltage.

10.2.2 Current Calculation Formula

Three-phase circuit rated current calculation formula:

I = S / (√3 × U × cosφ)

Where:

  • I: Rated current (A)
  • S: UPS rated capacity (VA)
  • U: Rated line voltage (V), typically 380 V
  • cosφ: Power factor, typically 0.9~1.0 for modular UPS

Example: 300 kVA UPS, input line voltage 380 V, power factor 0.99

I = 300000 / (1.732 × 380 × 0.99) ≈ 460 A

10.2.3 Common Power Range Cable Cross-Section Reference (Copper-core PVC cable, 35°C ambient)

UPS Capacity Input Cable (Three-Phase) Output Cable (Three-Phase) Battery Cable (DC) Grounding Cable
30 kVA 3×16 mm² + 1×10 mm² 3×16 mm² + 1×10 mm² 25 mm² 16 mm²
60 kVA 3×25 mm² + 1×16 mm² 3×25 mm² + 1×16 mm² 35 mm² 16 mm²
120 kVA 3×50 mm² + 1×25 mm² 3×50 mm² + 1×25 mm² 70 mm² 25 mm²
200 kVA 3×70 mm² + 1×35 mm² 3×70 mm² + 1×35 mm² 95 mm² 25 mm²
300 kVA 3×120 mm² + 1×70 mm² 3×120 mm² + 1×70 mm² 150 mm² 35 mm²
500 kVA 2×(3×95 mm²) 2×(3×95 mm²) 2×120 mm² 50 mm²

Note: When cable length exceeds 50 m, it is recommended to increase the cross-section by one grade; when multiple cables are paralleled, ensure identical length and specifications.

10.3 Utility Input Wiring

10.3.1 Pre-Wiring Confirmation

  • Confirm that the upstream input distribution cabinet breaker is open and verify the absence of voltage.
  • Confirm input voltage, frequency, and phase sequence match the UPS rated input.
  • Confirm input cable specifications and length meet requirements, with properly crimped copper lugs at both ends.

10.3.2 Wiring Procedure

1. Open the top distribution compartment cover or bottom cable entry compartment cover and confirm the input terminal block location; terminal markings: R/L1, S/L2, T/L3, N, PE.

2. Route the input cable through the top or bottom cable entry hole, leaving appropriate length, and strip the insulation at the end.

3. Connect the three-phase live wires R, S, T to the corresponding input terminals according to phase sequence; connect the neutral wire to terminal N; connect the protective ground wire to terminal PE.

4. Tighten the terminal fixing screws with torque meeting the requirements for the corresponding conductor size; ensure the conductor is firmly clamped without loosening, and the exposed portion of the copper lug does not extend beyond the terminal.

5. Bypass input wiring: For independent bypass input circuits, connect to the bypass input terminals using the same method; if the main input and bypass share the same source, they may be connected in parallel before termination.

6. After wiring, organize the cables, secure with cable ties, and install wire number identification; verify phase sequence labels are clear and correct.

10.3.3 Input Wiring Inspection

  • Visual inspection: Connections are firm, insulation is intact, phase sequence labels are clear; no exposed copper conductors or residual metal debris.
  • Continuity inspection: Use a multimeter continuity range to test for short circuits between phases and between phase-to-ground; verify N and PE are not interconnected.
  • Phase sequence inspection: Before power-on, verify phase sequence at the upstream distribution cabinet; recheck with a phase sequence meter at first power-on.

10.4 Load Output Wiring

10.4.1 Wiring Procedure

1. Confirm the output terminal block location; terminal markings: U/L1, V/L2, W/L3, N, PE.

2. Route the output cable through the cabinet cable entry hole and connect to the output terminals accordingly: three-phase live wires per phase sequence, neutral to N, ground to PE.

3. Tighten terminal screws to ensure firm connection; for multiple parallel cables, tighten evenly with consistent tension.

4. Connect the output to the load distribution cabinet or directly to loads; configure output branch breakers according to load circuits.

5. Organize and secure cables, label both ends; label each circuit in the output distribution cabinet with the corresponding load clearly identified.

10.4.2 Output Wiring Precautions

  • The output neutral and input neutral must never be interconnected or shorted; the UPS output is an independent system.
  • The output must never be connected in parallel with other power sources (such as generators or other UPS outputs) unless the system has paralleling capability.
  • Inductive loads and impact loads should be configured on dedicated circuits to avoid affecting other precision loads.
  • For long output cable runs, verify voltage drop and increase conductor size as necessary.

10.5 Battery Bank Wiring

Battery wiring is the most safety-critical aspect of installation. Extreme caution must be exercised, and operating procedures must be strictly followed to prevent short circuits and electric shock.

10.5.1 Battery Bank Connection Principles

  • Batteries are connected in series to increase voltage and in parallel to increase capacity; first connect in series to form strings, then connect strings in parallel for capacity expansion.
  • For series connection, connect positive and negative terminals sequentially: Battery 1 positive → Battery 2 negative → Battery 2 positive → Battery 3 negative… The string ends become the overall positive and negative terminals.
  • For multiple parallel strings, the total voltage of each string must be identical, polarities must correspond, with positive-to-positive and negative-to-negative connections.
  • Battery connecting cables should be as equal in length as possible to ensure uniform current distribution among batteries and strings.

10.5.2 Battery Wiring Procedure

1. Battery installation: Place batteries in sequence in the battery rack/cabinet with consistent polarity orientation; place insulating pads under batteries and provide insulation between layers.

2. Cell connection: Wear insulating gloves and use dedicated connecting cables to connect adjacent battery terminals; tighten connecting screws to the torque specified by the battery manufacturer. Pay strict attention to polarity and avoid short circuits.

3. Main output leads: Route cable from the string ends (overall positive and overall negative) to the input terminals of the battery breaker.

4. UPS-side connection: Connect the other end of the battery cable to the UPS battery terminals, marked “BATTERY +” and “BATTERY −”, ensuring correct polarity; reversed connection is strictly prohibited!

5. Battery switch: Install the battery main breaker between the battery bank and the UPS for convenient on/off control and maintenance.

6. After wiring, organize the battery connecting cables and bundle neatly; measure the total battery bank voltage to confirm normal voltage and correct polarity.

10.5.3 Battery Wiring Safety Precautions

  • During wiring, tools and metal objects must never simultaneously contact the positive and negative terminals to prevent short circuits; metal tools must be insulated.
  • Reversing battery polarity is strictly prohibited! Reversal will instantly destroy the UPS charging circuit, causing equipment damage and safety hazards.
  • The number of series-connected batteries must match the UPS DC voltage rating; adding or omitting batteries is strictly prohibited.
  • Battery terminal connections must be tight; loose connections cause high contact resistance, overheating, and potential fire hazards.
  • When wiring, connect the negative terminal first, then the positive; when disconnecting, remove the positive first, then the negative; avoid tools bridging the positive and negative terminals.

10.6 Control and Communication Wiring

10.6.1 Dry Contact Wiring

  • Dry contact interfaces are located at the rear of the monitoring module, divided into input dry contacts and output dry contacts.
  • Output dry contacts are passive relay contacts that can connect to the alarm collection terminals of an environmental monitoring (DCS/BMS) system for remote alarming; common alarms include utility failure, low battery, system fault, and bypass operation.
  • Input dry contacts can accept external control signals such as remote on/off and emergency shutdown.
  • Use shielded control cables with conductor cross-section of 0.5~1.0 mm²; ground the shield at one end only to avoid interference.

10.6.2 Communication Cable Wiring

  • RS485 communication: Use shielded twisted pair; connect A to A and B to B, ground the shield; communication distance ≤1200 m, can connect to environmental monitoring or building management systems.
  • SNMP network card: Insert into the monitoring module expansion slot and connect network cable to the LAN for network monitoring.
  • USB interface: Can connect a USB drive for data export or connect to a local computer for commissioning.
  • Communication cables must be routed separately from power cables with a clearance of ≥30 cm to avoid electromagnetic interference.

10.6.3 Battery Monitoring Wiring

When a battery monitoring instrument is optional equipment, connect each cell’s voltage sampling wire to the corresponding terminal on the monitoring instrument, ensuring correct polarity (reversal is strictly prohibited); connect the monitoring instrument’s communication cable to the UPS monitoring module for unified battery data monitoring.

10.7 Comprehensive Inspection After Wiring Completion

Before power-on commissioning, a comprehensive inspection must confirm:

Wiring Correctness Inspection

  • Input and output three-phase sequence is correct, no phase reversal or phase loss
  • Neutral and ground connections are correct, N and PE are not interconnected
  • Battery positive and negative connections are correct, no reversal
  • Communication and dry contact wiring correspond correctly

Connection Firmness Inspection

  • All terminal screws are tightened to the required torque
  • Copper lugs are securely crimped, no loosening or broken strands
  • Battery terminal connections are firm, no loosening

Insulation and Short-Circuit Inspection

  • Multimeter testing confirms no short circuit between input/output phases or phase-to-ground
  • Battery positive and negative have no short circuit to ground or between each other
  • No exposed live parts; insulation protection is in place

Cable Routing and Label Inspection

  • Cables are neatly bundled, power and signal cables separated
  • Labels at both ends of all cables are clear and correct
  • Cables do not block airflow paths, door operation, or module insertion/removal

Grounding System Inspection

  • Cabinet, battery cabinet, and distribution cabinet are all reliably grounded
  • Grounding cable cross-sections meet requirements, connections are firm
  • Grounding resistance testing has passed

Commissioning is the critical phase before the UPS is put into service. Step-by-step testing verifies equipment functionality, performance, and wiring correctness, ensuring safe and reliable operation. Commissioning must be performed by qualified technical personnel, strictly following procedures and documenting all results.

11.1 Pre-Commissioning Preparation and Inspection

11.1.1 Required Commissioning Tools

  • Multimeter (true RMS), clamp ammeter, phase sequence meter
  • Oscilloscope (optional, for waveform and transfer time testing)
  • Infrared thermometer (optional, for terminal temperature rise testing)
  • Laptop computer (optional, for commissioning software and data logging)
  • Insulating gloves, screwdrivers, and other standard tools

11.1.2 Final Inspection Before Power-On

1. Confirm all wiring is complete and has passed inspection, with no tools or metal debris left inside the equipment.

2. Confirm all breakers are in the open position: input breaker, output breaker, battery breaker, and maintenance bypass switch.

3. Confirm all power modules, bypass modules, and monitoring modules are installed in place and firmly secured.

4. Confirm cabinet front and rear doors open and close normally, and ventilation openings are unobstructed.

5. Confirm the load-side main breaker is open; no load is connected at this stage.

6. Confirm site ambient temperature and humidity meet operating requirements.

7. Commissioning personnel are familiar with equipment operation and commissioning procedures, with clear division of responsibilities and proper safety protection.

11.2 No-Load Power-On Commissioning

11.2.1 Pre-Energization Preparation

1. Close the upstream utility input breaker and measure input voltage: line voltage 380 V ±10%, phase voltage 220 V ±10%, frequency 50 Hz ±1 Hz.

2. Confirm input phase sequence is correct and three-phase voltages are balanced.

11.2.2 System Power-On Startup

1. Close the UPS main input breaker; the system auxiliary power starts, the monitoring screen lights up, module fans start, and the system enters initialization.

2. Observe the monitoring screen startup process and confirm no error messages; observe module indicator lights, initially in standby status.

3. After initialization, check the monitoring screen home page parameters:

  • Input voltage and frequency are normal, three phases balanced
  • Bypass voltage and frequency are normal
  • DC bus voltage is within the normal range
  • All module statuses display normally without fault alarms

4. If a fault alarm is present, record the fault code, power off immediately, troubleshoot, and only continue after resolving the fault.

11.2.3 Inverter Startup Test

1. Confirm the system has no faults or alarms, and utility and bypass are normal.

2. On the monitoring screen: press the “ON” key, select “Inverter Start,” and confirm the start.

3. Observe system status: the inverter starts gradually, output voltage builds to rated value; confirm output voltage stabilizes at 380 V/220 V, frequency 50 Hz, three phases balanced.

4. Measure output voltage: use a multimeter to measure output line and phase voltages and compare with displayed values; deviation within ±1% is normal.

5. Observe each power module status: all display “Inverter Running” with steady green indicator; no alarms, no abnormal sounds.

11.2.4 Bypass Transfer Test

1. After stable inverter operation, perform a manual bypass transfer test.

2. On the monitoring screen: select “Transfer to Bypass” and confirm the operation.

3. Observe the transfer: output voltage shows no significant fluctuation, system status changes to “Bypass Operation,” and the bypass indicator lights up.

4. Measure bypass output voltage and confirm it is normal and consistent with utility.

5. Transfer back to inverter mode and confirm smooth transfer without abnormality; record output voltage variations during the transfer.

11.2.5 Battery Mode Test

1. With the inverter operating normally, open the utility input breaker to simulate a utility outage.

2. Observe system status: instantaneous transfer to battery-powered mode, output voltage remains stable without interruption; battery indicator lights up.

3. Measure output voltage and confirm voltage and frequency are stable in battery mode.

4. Observe battery discharge current and voltage changes to confirm normal discharge.

5. Close the utility input breaker; the system automatically transfers back to utility-inverter mode and the battery enters charging state; confirm normal charging current.

11.3 Loaded Commissioning

After no-load commissioning passes, progressively connect loads to verify load-carrying capability and current-sharing performance.

11.3.1 Progressive Load Test

1. Confirm the output breaker is open and all load-side branch breakers are open.

2. Close the UPS output main breaker and confirm normal output voltage.

3. Connect a small load first (e.g., server, lighting), approximately 10%~20% load factor.

4. Observe system status: output voltage stable, module currents balanced, no alarms; measure output current and calculate load factor.

5. Progressively increase load to 30%, 50%, 80%, and 100% of rated load; after each level, run stably for 5 minutes and observe operating status.

6. At full load, run for 30 minutes and check:

  • Output voltage stability and three-phase unbalance
  • Individual power module output currents and current-sharing accuracy (≤±5%)
  • Module temperature and fan speed are normal
  • Cabinet, cable terminals show no abnormal heating
  • No abnormal noise or odor

11.3.2 Overload Test (Optional)

Verify overload capability as required:

  • Load at 125% of rated load for 10 minutes; the system should operate normally without transferring to bypass.
  • Load at 150% of rated load for 60 seconds; the system should sustain the load, then automatically transfer to bypass after timeout.
  • Closely monitor equipment status during testing; immediately remove load if any abnormality occurs.

11.3.3 Loaded Transfer Test

1. At 50% load, perform inverter-to-bypass and bypass-to-inverter bidirectional transfer tests, confirming no load interruption or restart during transfer.

2. With load connected, open the utility input to transfer to battery power; confirm stable output and normal load operation.

3. Restore utility and confirm automatic transfer back to utility mode with normal charging.

11.4 Function-Specific Tests

11.4.1 Module Redundancy and Hot-Swap Test

1. Under N+X redundant configuration, simulate a single module fault: manually shut down one power module.

2. Observe system status: remaining modules automatically assume the full load, output voltage remains stable, no load interruption; system issues a module fault alarm.

3. Re-engage the faulted module: start the module, confirm smooth integration into the system, current redistribution, and normal current sharing.

4. Hot-swap test (optional, requires professional operation): In bypass mode or with sufficient load redundancy, remove one module and confirm normal system operation; reinsert the module and confirm automatic integration.

11.4.2 Protection Function Test

  • Input overvoltage/undervoltage protection: Simulate input voltage outside limits; confirm the system transfers to battery power or issues an alarm.
  • Output short-circuit protection: Briefly simulate a short circuit at the output (operate with caution); confirm rapid protection activation, transfer to bypass, and alarm.
  • Overtemperature protection: Simulate the temperature sensor signal; confirm overtemperature alarm and load reduction protection activate.
  • Emergency stop test: Press the EPO emergency stop button; confirm the system immediately shuts down output and issues a shutdown alarm. Reset after testing.

11.4.3 Battery Management Function Test

  • Check charging parameters: float charge voltage, boost charge voltage, and charging current settings are correct.
  • Observe battery charging status: constant current, constant voltage, and float charge stage transitions are correct.
  • Low battery alarm: Discharge to the low battery alarm point; confirm audible and visual alarms activate correctly.
  • Battery test function: Initiate a manual battery test; confirm the test process is normal and results are accurate.

11.4.4 Monitoring and Alarm Function Test

  • Verify all displayed parameters are accurate by comparing with multimeter measurements.
  • Simulate various faults and confirm audible/visual alarms activate with automatic fault log saving.
  • Test dry contact alarms: corresponding alarm output dry contacts operate correctly.
  • Test communication functions: connect to an upper computer or SNMP web interface; confirm remote monitoring is normal with data synchronization.
  • Test historical record queries, parameter settings, permission management, and other functions operate correctly.

11.5 System Integration Commissioning and Optimization

11.5.1 Parameter Optimization Settings

Based on site conditions and user requirements, optimize system parameter settings:

  • Battery parameters: battery count, float charge voltage, boost charge voltage, low voltage alarm value, end-of-discharge voltage.
  • Alarm thresholds: input voltage range, overtemperature threshold, load factor alarm threshold.
  • Function settings: ECO mode on/off, intelligent sleep on/off, automatic battery test cycle.
  • Communication parameters: address, baud rate, alarm enable items.
  • System settings: date/time, language, backlight, etc.

11.5.2 Parallel System Integration Commissioning (Multi-Cabinet Parallel)

1. After all individual unit commissioning passes, proceed with parallel system integration.

2. Connect parallel communication fibers and confirm parallel communication is normal.

3. Start up the parallel system uniformly; confirm normal current sharing among all cabinets with evenly distributed load.

4. Test individual cabinet withdrawal and re-engagement; confirm stable system operation.

5. Verify parallel system bypass synchronization, battery management, and other functional consistency.

11.5.3 Generator Linkage Commissioning (If Applicable)

If a diesel generator is equipped as backup power, linkage commissioning is required:

  • After utility interruption, the UPS transfers to battery power; the generator starts, and once output voltage stabilizes, the UPS automatically transfers to generator input.
  • Test UPS operating stability under generator power, including the effect of input current harmonics on the generator.
  • After utility restoration, confirm automatic transfer back to utility and generator shutdown.

11.6 Commissioning Records and Delivery

1. Fill in the “UPS Commissioning Record Form” item by item during commissioning, documenting all test data, parameter settings, and test results.

2. After commissioning passes, organize the commissioning records and parameter setting tables for user archival.

3. Conduct on-site operational training for user maintenance personnel, covering startup, shutdown, routine inspection, and common alarm handling.

4. Both parties sign the commissioning delivery form, and the equipment enters the trial operation phase.

12.1 Installation Safety Precautions

  • Installation must be performed by certified professional electricians, strictly complying with national electrical safety codes and the requirements of this manual.
  • Equipment installation location must meet environmental requirements; installation in humid, dusty, corrosive, flammable, or explosive environments is strictly prohibited.
  • Exercise personal safety during equipment transportation and positioning; use dedicated handling equipment for heavy equipment to prevent tipping or crushing injuries.
  • The upstream power source must be disconnected before wiring, and voltage absence must be verified before operation; post warning signs to prevent accidental closure.
  • Battery wiring requires insulating gloves and insulated tools; short-circuiting the positive and negative terminals is strictly prohibited, and battery polarity must never be reversed.
  • Grounding must be reliable with grounding resistance meeting requirements; omitting the grounding conductor or substituting the neutral for the ground is strictly prohibited.
  • No open flames or smoking at the installation site; fire-fighting equipment must be available; special attention to fire prevention during battery work to avoid short-circuit sparks igniting hydrogen gas.
  • After installation, conduct a comprehensive inspection to confirm no short circuits, wiring errors, or leftover tools/debris before power-on.

12.2 Commissioning and Operation Precautions

  • First power-on must be performed by factory-authorized technical personnel; unauthorized user power-on commissioning is strictly prohibited.
  • Before power-on, confirm input voltage, frequency, and phase sequence match equipment ratings to avoid phase errors or overvoltage damage.
  • During commissioning, strictly follow procedures step by step; immediately power off and troubleshoot upon any abnormality; never operate a faulted system.
  • Destructive tests such as short-circuit and overload testing require caution with proper protection to avoid equipment and load damage.
  • While equipment is operating, never open the distribution compartment cover or touch live terminals; maintenance operations require de-energizing or transferring to maintenance bypass.
  • The emergency stop button is for emergency situations only (fire, electric shock); normal shutdown must be performed through the screen interface.
  • Keep front and rear ventilation openings clear during operation; never block or cover cabinet vents; avoid placing objects on top of the cabinet.
  • Avoid frequent power cycling; after shutdown, wait at least 30 seconds before restarting to prevent impact damage to components.

12.3 Battery Usage Precautions

  • Batteries are chemical hazardous materials and must be installed and maintained by professionals; disassembling or incinerating batteries is strictly prohibited.
  • Battery rooms/cabinets must be well ventilated to prevent hydrogen accumulation; open flames and smoking are strictly prohibited.
  • Batteries must be protected from overcharging and over-discharging; the UPS has protection parameters pre-set, and modifying the battery low-voltage protection value without authorization is strictly prohibited.
  • Batteries under long-term float charge should undergo discharge testing every 3~6 months to activate the batteries and extend service life.
  • Optimal battery ambient temperature is 20~25°C; excessive temperature significantly shortens battery life, while low temperature reduces capacity.
  • Batteries of different brands, capacities, or ages must never be mixed in series connection.
  • Batteries showing leakage, bulging, or deformation must be removed from service immediately and replaced; replacing the entire battery bank is recommended.
  • Waste batteries must be recycled by qualified entities; indiscriminate disposal polluting the environment is strictly prohibited.

12.4 Routine Operation and Maintenance Precautions

  • Maintenance personnel must be trained and familiar with equipment operation and safety precautions; unauthorized personnel are prohibited from operating the equipment.
  • Routine inspections must strictly follow the inspection schedule with records kept; promptly handle abnormalities and contact factory technical support for major faults.
  • Equipment cleaning requires de-energization and the use of a dry soft cloth; washing equipment with water or liquid cleaners is strictly prohibited; using organic solvents on plastic parts is prohibited.
  • Module insertion/removal requires dedicated tools and anti-static wrist straps; hot-swap operations require confirmation of sufficient system redundancy.
  • Replacement spare parts must be identical original factory parts; non-original substitutes are prohibited to avoid inducing faults.
  • Firmware upgrades must be performed by factory technical personnel; no power interruption during the upgrade process; verify function after upgrade.
  • Periodically inspect wiring terminal and battery terminal tightness to prevent loosening and overheating; high-current circuits should be re-tightened at least once per year.
  • Implement dust, moisture, and rodent prevention measures in the equipment room to prevent dust, humidity, and pests from entering equipment and causing faults.

12.5 Special Scenario Precautions

12.5.1 High-Altitude Areas

  • Above 1000 m altitude, the equipment requires derating: 10% derating for every additional 1000 m.
  • Above 2000 m altitude, it is recommended to select plateau-specific models with enhanced insulation and heat dissipation design.
  • Due to reduced cooling capacity at lower air density, enhance equipment room ventilation and cooling, and lower ambient temperature.

12.5.2 Low/High Temperature Environments

  • When ambient temperature falls below 0°C, battery capacity drops significantly; increase battery configuration or implement insulation measures.
  • When ambient temperature exceeds 40°C, the equipment operates derated; strengthen air conditioning cooling to avoid prolonged high-temperature operation.
  • In environments with rapid temperature changes, prevent condensation, which can degrade insulation and cause short-circuit faults.

12.5.3 Harsh Industrial Environments

  • In dusty environments, regularly clean dust filters and internal dust accumulation to prevent airflow path blockage causing overheating.
  • In corrosive gas environments, select corrosion-resistant models and periodically inspect component corrosion.
  • In strong electromagnetic interference environments, implement proper shielding and grounding; use shielded cables for communication to prevent malfunction from interference.

12.6 Safety Warning Label Descriptions

Safety warning labels on the equipment must be strictly observed. Common label meanings:

  • Electric shock hazard: Indicates high-voltage danger; unauthorized personnel must not open; operations require de-energization.
  • High-temperature warning: Indicates high surface temperature; avoid contact to prevent burns.
  • Battery warning: Indicates chemical energy storage hazard; short-circuiting, disassembly, and incineration are prohibited.
  • Do not close: Posted during equipment maintenance; closing and energizing prohibited.
  • Emergency stop: Press in emergencies to cut output.

Scientific and standardized maintenance is key to ensuring long-term stable UPS operation and extending service life. Establishing a comprehensive preventive maintenance system can significantly reduce fault rates, improve equipment availability, and extend the full lifecycle.

13.1 General Maintenance Principles

  • Prevention first: Adhere to the principle of preventive maintenance first and corrective maintenance second; perform regular maintenance to eliminate hidden hazards in advance.
  • Dedicated responsibility: Assign trained maintenance personnel to be responsible for routine equipment maintenance and establish maintenance records.
  • Safety first: All maintenance operations must comply with safety regulations; de-energize or transfer to maintenance bypass with proper protection.
  • Complete records: Every maintenance and repair must be documented in detail, including time, content, fault symptoms, resolution, and replaced parts.
  • Factory support: For major faults and core component repairs, contact factory technical support; avoid unauthorized disassembly that may worsen the fault.

13.2 Routine Inspection (Daily)

Daily inspections are performed by duty maintenance personnel to quickly assess equipment operating status and detect obvious abnormalities.

Inspection Item Inspection Content and Requirements Normal Status
System status indication Observe panel indicator lights: utility, inverter, battery, fault status Utility and inverter lights steady on, no red fault indicator
Display parameters Check input voltage, output voltage, load factor, battery voltage, temperature and other key parameters Parameters within normal range, no alarms
Fans and noise Listen to equipment operating sound; verify fan operation Fans running smoothly, no abnormal noise or friction
Appearance and environment Check equipment appearance and surrounding environment for odors, abnormal sounds, water leaks Equipment intact, environment clean, temperature normal
Alarm information Check for current and historical alarms No active alarms; historical alarms resolved

Fill in the “UPS Daily Inspection Record Form” and promptly report and resolve any abnormalities.

13.3 Monthly Maintenance

Perform a comprehensive inspection and cleaning monthly, executed by dedicated maintenance personnel.

13.3.1 Electrical Inspection

1. Measure input and output voltage, current; record load factor and compare with historical data to analyze load trends.

2. Measure total battery bank voltage and individual cell voltage (directly readable if a monitoring instrument is installed); record battery voltage and temperature to assess battery condition.

3. Check breaker and switch positions are correct, with no tripping or heating.

4. Use an infrared thermometer to measure key terminal and busbar temperatures for abnormal temperature rise; temperature rise exceeding 40 K requires focused attention.

13.3.2 Appearance and Cleaning

1. Clean the cabinet exterior, display screen, and indicator lights to keep them clean and dust-free.

2. Clean dust from front and rear ventilation openings and dust filters to ensure smooth airflow.

3. Check cabinet door locks, hinges, and leveling feet are intact and secure.

4. Check cable labels are legible and cables show no damage or heat-aging signs.

13.3.3 Functional Checks

1. Test alarm functions: simulate simple alarms and confirm audible/visual alarms operate correctly.

2. Check communication connections: remote monitoring online with normal data synchronization.

3. Verify system time and calibrate clock drift.

4. Export monthly operating data and alarm records for archival backup.

13.4 Quarterly Maintenance

Perform in-depth maintenance quarterly, recommended to be executed by the factory or professional service providers.

13.4.1 Battery Deep Maintenance

1. Perform a battery verification discharge test: discharge to 30%~50% of rated capacity, recording voltage and current changes during discharge to assess actual battery capacity.

2. Measure each cell’s internal resistance and compare with historical data to identify weak cells; cells with internal resistance deviation exceeding 20% must be marked and tracked.

3. Inspect battery terminals and re-tighten to specified torque; clean terminal oxidation and apply conductive grease for oxidation prevention.

4. Clean battery surfaces and battery cabinet dust; inspect batteries for bulging, leakage, or swelling.

13.4.2 Interior Cleaning and Inspection

1. After transferring the equipment to maintenance bypass or de-energizing, open the cabinet side doors and internal covers.

2. Use anti-static brushes and vacuum cleaners to remove dust from module surfaces, airflow paths, and cabinet interior; use ionizing blowers for circuit board dust removal.

3. Inspect internal busbars, capacitors, and power devices for bulging, leakage, discoloration, or odor.

4. Inspect fan operation and clean fan dust; promptly replace fans with bearing noise.

13.4.3 System Functional Verification

1. Perform a utility interruption simulation test to verify battery transfer and power supply are normal.

2. Perform inverter-to-bypass transfer test to verify smooth transfer without interruption.

3. Verify intelligent sleep and ECO mode energy-saving functions operate normally.

4. Check firmware version and assess whether upgrade is needed; perform firmware optimization upgrade if necessary.

13.5 Annual Maintenance

Perform a comprehensive deep maintenance and performance testing annually, equivalent to the equipment’s “annual inspection,” ensuring long-term reliable operation.

13.5.1 Comprehensive Electrical Testing

1. Input/output characteristic testing: Test voltage stability, waveform distortion, and frequency accuracy at different load factors to verify performance specifications.

2. Current-sharing accuracy testing: Test output current deviation among power modules; current-sharing accuracy should be ≤±5%.

3. Protection function verification: Verify all protection thresholds are accurate and protection actions are reliable.

4. Insulation resistance testing: After de-energization, test main circuit insulation resistance to ground; should be ≥2 MΩ.

13.5.2 Mechanical and Structural Maintenance

1. Re-tighten all high-current terminals and busbar connecting screws to specified torque.

2. Check cabinet structure, guide rails, and connectors for loosening, deformation, or oxidation.

3. Perform life assessment on fans, breakers, and other wear parts; perform preventive replacement for parts reaching their lifecycle.

4. Inspect the grounding system and test grounding resistance to ensure reliable grounding.

13.5.3 System Calibration and Optimization

1. Calibrate voltage, current, temperature, and other sampling parameters to ensure accurate display.

2. Optimize system parameter settings based on load changes and operating conditions, such as sleep strategy and charging parameters.

3. Clear historical system data and back up configuration parameters; organize the annual maintenance archive.

4. Assess equipment health status and provide recommendations for next year’s maintenance plan and spare parts replacement schedule.

13.6 Common Component Replacement Methods

13.6.1 Power Module Replacement (Hot-Swap)

1. Prerequisite: The system has sufficient N+X redundancy; remaining modules can carry the full load after single module removal.

2. Confirm the system is operating normally and bypass is available; check current load factor and module count on the monitoring screen to confirm sufficient redundancy.

3. Wear an anti-static wrist strap, locate the faulted module, and loosen the fixing screws on both sides.

4. Hold the module handle and smoothly, slowly pull the module out of the cabinet; observe system status during extraction to ensure normal output.

5. Take out the new module, confirm the model matches and the appearance is intact; align with the slot guide rails and push in smoothly.

6. After pushing to the bottom, confirm the connector is fully seated, then tighten the fixing screws.

7. Observe module startup; after approximately 1~2 minutes, the module automatically integrates into the system and the indicator turns steady green.

8. Check module status on the monitoring screen to confirm normal operation with balanced current distribution.

9. Record the replacement time and module number for archival purposes.

13.6.2 Fan Replacement

  • Cabinet fan replacement: After de-energizing or transferring to maintenance bypass, open the corresponding cover, disconnect the fan power plug, remove the fixing screws, and take out the old fan; install the new fan with correct wiring and firm fixing.
  • Module fan replacement: It is recommended to return the module to the factory for replacement; on-site replacement requires de-energization and opening the module housing to replace the corresponding fan, noting correct wiring polarity.
  • After replacement, power on and test to confirm normal fan operation without abnormal noise.

13.6.3 Battery Replacement

1. Preparation: Open the battery breaker and confirm the battery circuit is de-energized; wear insulating gloves and prepare the new batteries and tools.

2. Removing old batteries: Disconnect the overall positive first, then the overall negative, followed by disconnecting each inter-cell connection cable; carefully remove old batteries and place them in a safe location.

3. Installing new batteries: Place new batteries in order according to polarity, connect inter-cell cables one by one, and tighten terminals securely.

4. Measure total voltage and polarity to confirm correctness before connecting to the battery switch.

5. Close the battery breaker and confirm the UPS recognizes the battery voltage normally and initiates charging.

6. Store old batteries properly and hand them over to a qualified entity for recycling.

7. Record battery replacement time, brand, and quantity; update the battery records.

13.7 Fault Repair Procedure

1. Fault reporting: Upon fault detection, immediately record the fault symptom, fault code, and operating status, and report to the person in charge.

2. Preliminary troubleshooting: Maintenance personnel perform initial troubleshooting based on the fault code and manual guidance to determine fault type and severity.

3. Emergency response: Take emergency measures to protect load power, such as transferring to bypass, engaging redundant modules, or switching to backup power, prioritizing business continuity.

4. Technical support: For faults that cannot be resolved internally, contact factory technical support (+86 13538869979) with the fault symptoms and codes for remote assistance.

5. On-site repair: If remote resolution is not possible, arrange for an engineer to visit; replace faulted components and restore normal operation through commissioning.

6. Fault review: After repair, analyze the root cause, develop preventive measures, and update maintenance records.

13.8 Maintenance Safety Regulations

  • High-voltage hazard! Internal maintenance requires de-energization or transfer to maintenance bypass, with voltage absence verified before operation.
  • Maintenance personnel must wear insulating gloves and anti-static wrist straps, and use insulated tools.
  • Battery maintenance strictly prohibits short-circuiting the positive and negative terminals; take precautions against electric shock and chemical burns when replacing batteries.
  • Capacitors retain charge after de-energization; allow full discharge before contact to prevent electric shock.
  • Module hot-swap operations must follow proper procedures; rough handling that damages connectors or causes arc burns is strictly prohibited.
  • Open flames are prohibited at the maintenance site; fire extinguishers must be available; special attention to fire and explosion prevention during battery operations.
  • Unauthorized disassembly or modification of equipment is strictly prohibited; unauthorized disassembly during the warranty period voids the warranty.

Chapter 14 Common Product Problems and Solutions

14.1 Input-Type Faults

Fault Symptom Possible Cause Troubleshooting Steps Solution
System reports input overvoltage, switches to battery power 1. Utility voltage is indeed too high<br>2. Abnormal input voltage sampling<br>3. Power grid surge impact 1. Measure actual input voltage with a multimeter<br>2. Compare displayed value with measured value<br>3. Check whether upstream grid is stable 1. High voltage is normal protection; auto-recovers after utility power restores<br>2. For long-term overvoltage, recommend installing a voltage stabilizer<br>3. Sampling abnormality requires monitoring board repair/inspection
System reports input undervoltage, frequent switching to battery 1. Low utility voltage<br>2. Large voltage drop on input line<br>3. Input loose connection, poor contact<br>4. Frequent grid fluctuations 1. Measure input voltage and voltage at UPS terminals<br>2. Check whether input wiring terminals are tightened<br>3. Observe grid fluctuation conditions 1. For long-term low voltage, recommend installing a voltage stabilizer or voltage regulator<br>2. Tighten wiring terminals, increase input cable cross-section<br>3. Adjust input voltage range parameters (requires manufacturer guidance)
Input phase loss alarm 1. Phase loss in upstream grid<br>2. Poor contact on one phase of input circuit breaker<br>3. Loose input wiring terminals<br>4. Input fuse blown 1. Measure whether the three-phase output voltage of upstream supply is normal<br>2. Check input circuit breaker on/off status<br>3. Check UPS input terminal voltage 1. Contact power supply bureau to restore three-phase power<br>2. Replace damaged circuit breaker or fuse<br>3. Tighten loose wiring terminals
Input frequency abnormal alarm 1. Utility frequency deviates from range<br>2. Unstable frequency from generator supply<br>3. Frequency sampling fault 1. Measure actual input frequency<br>2. Confirm whether power source is a generator 1. Wait for grid recovery if utility frequency is abnormal<br>2. Adjust generator speed to stabilize frequency<br>3. Inspect/repair monitoring module for sampling fault
Low input power factor, high harmonics 1. Load rate too low<br>2. APFC circuit not working normally<br>3. A power module faulted and exited 1. View current system load rate<br>2. Check whether all power modules are running normally 1. Low load is a normal phenomenon; power factor automatically rises when load increases<br>2. Repair faulty module, restore full module operation

14.2 Output-Type Faults

Fault Symptom Possible Cause Troubleshooting Steps Solution
Output voltage high/low 1. Output voltage calibration deviation<br>2. Severely unbalanced three-phase load<br>3. Abnormal inverter control 1. Measure output phase voltage and line voltage with a multimeter<br>2. Check whether three-phase load currents are balanced<br>3. Observe if there are any alarm messages 1. Deviation within ±1% is normal<br>2. Adjust load distribution to balance three phases as much as possible<br>3. Excessive deviation requires recalibration or module inspection/repair
Large output waveform distortion 1. Non-linear load proportion too high<br>2. Output filter components damaged<br>3. Module fault causing abnormal waveform 1. Confirm load type and proportion<br>2. Measure output waveform with an oscilloscope<br>3. Check operation status of each module 1. Large non-linear load is normal; THD ≤ 5% meets standard<br>2. Install output filter to improve<br>3. Repair faulty module
System frequently switches to bypass 1. Load overload or impact load<br>2. Inverter module fault<br>3. Output short circuit or hidden grounding<br>4. Module over-temperature protection 1. Check load rate and overload records<br>2. Check whether there are module fault alarms<br>3. Measure module temperature<br>4. Check output circuit for grounding or short circuit 1. Reduce load or expand UPS capacity<br>2. Replace faulty power module<br>3. Troubleshoot output circuit, eliminate short circuit/grounding fault<br>4. Improve heat dissipation, clean dust, lower ambient temperature
Unbalanced three-phase output 1. Uneven three-phase load distribution<br>2. Abnormal module on one phase<br>3. Poor contact on one phase of output wiring 1. Check three-phase output currents<br>2. Check whether three-phase output of each module is normal<br>3. Check output terminal temperature rise 1. Adjust load to balance three phases as much as possible<br>2. Repair faulty module<br>3. Tighten output wiring terminals
High neutral-to-ground voltage at output 1. Input neutral-to-ground voltage is inherently high<br>2. Severely unbalanced three-phase load<br>3. Poor system grounding<br>4. Output isolation transformer not configured 1. Measure input neutral-to-ground voltage<br>2. Check whether grounding is reliable<br>3. Check three-phase load balance 1. Improve upstream grid neutral-to-ground voltage<br>2. Balance three-phase load<br>3. Check and reinforce grounding system<br>4. Install output isolation transformer for high-precision applications

14.3 Battery-Type Faults

Fault Symptom Possible Cause Troubleshooting Steps Solution
Low battery voltage alarm, short backup time 1. Long-term utility power outage, battery over-discharged<br>2. Battery aging, capacity degradation<br>3. Charging voltage set too low<br>4. Individual battery cells lagging or failed 1. Check battery discharge history<br>2. Measure total voltage and individual cell voltages<br>3. Check charging voltage settings<br>4. Measure battery internal resistance 1. Auto-charging after utility power restores; alarm clears after full charge<br>2. Replace aging/lagging batteries<br>3. Correctly set charging parameters according to battery specifications
Battery cannot be fully charged 1. Charging current set too low<br>2. Insufficient charging time<br>3. Battery aging with high internal resistance<br>4. Charging circuit fault<br>5. Battery temperature too high 1. Check charging current and charging status<br>2. Confirm whether charging duration is sufficient<br>3. Measure battery internal resistance and temperature 1. Appropriately increase charging current (not exceeding battery allowable value)<br>2. Extend charging time<br>3. Replace aging batteries<br>4. Repair charging module fault
Battery overvoltage alarm 1. Equalize charging voltage set too high<br>2. Abnormal temperature compensation<br>3. Charging control fault 1. Check equalize charging voltage setting value<br>2. Check whether battery temperature sensor is normal<br>3. Compare measured battery voltage with displayed value 1. Correct charging voltage settings according to battery specifications<br>2. Repair or replace temperature sensor<br>3. Inspect/repair charging control circuit
Battery reverse connection alarm 1. Battery positive and negative poles reversed<br>2. Battery sampling wires reversed 1. Immediately disconnect battery switch<br>2. Verify battery polarity and wiring 1. Power off immediately, correct wiring; check whether equipment is damaged<br>2. Strictly prohibit forced energization; retry only after confirming correct wiring
High battery temperature alarm 1. Ambient temperature too high<br>2. Large current battery charge/discharge<br>3. High battery internal resistance causing excessive heat<br>4. Loose battery terminals causing contact heating 1. Check battery room/cabinet temperature<br>2. Check charge/discharge current<br>3. Measure battery surface temperature and terminal temperature<br>4. Check whether battery connections are tightened 1. Strengthen ventilation and cooling, lower ambient temperature<br>2. Large current charge/discharge is a temporary phenomenon; returns to normal after recovery<br>3. Replace aging, heat-generating batteries<br>4. Tighten battery connection terminals

14.4 Module and System-Type Faults

Fault Symptom Possible Cause Troubleshooting Steps Solution
Single power module fault, red light on 1. Module internal overcurrent, overvoltage, over-temperature protection<br>2. Module control board fault<br>3. Power device damage<br>4. Connector poor contact 1. Check fault code, confirm fault type<br>2. Re-insert module to confirm whether it is a contact issue<br>3. Replace with spare module for testing 1. Recoverable faults can be restored by restarting the module<br>2. Poor contact: re-insert and tighten<br>3. Hardware fault: replace faulty module, return to factory for repair
Uneven module current sharing, large current deviation 1. Module output voltage calibration deviation<br>2. Communication abnormality in a module<br>3. Poor bus bar connection contact 1. Check output current values of each module<br>2. Check module communication status<br>3. Recalibrate module output voltage 1. Deviation within ±5% is normal<br>2. Excessive deviation: perform current sharing calibration again<br>3. Repair communication fault, tighten bus bar connections
System communication interrupted, no monitoring data 1. Monitoring module fault<br>2. Communication cable loose or disconnected<br>3. Communication address or baud rate set incorrectly<br>4. Host computer/environment monitoring system fault 1. Check whether local display screen is normal<br>2. Check communication cable connections<br>3. Verify communication parameter settings<br>4. Test communication line continuity 1. If local display is normal, troubleshoot external communication lines and equipment<br>2. Tighten loose communication cables<br>3. Correct communication parameters<br>4. Replace monitoring module if monitoring module is faulty
Fan fault alarm, loud noise 1. Fan dust accumulation, bearing aging<br>2. Fan power supply poor contact<br>3. Fan control circuit fault 1. Observe whether fan is rotating, any abnormal noise<br>2. Clean fan dust<br>3. Check fan wiring 1. Clean dust; replace fan if bearing noise exists<br>2. Re-plug fan power connector<br>3. Repair corresponding circuit board for control fault
System over-temperature alarm 1. Ambient temperature too high<br>2. Dust filter screen or air duct blocked, poor heat dissipation<br>3. Fan fault, insufficient speed<br>4. Load too high, modules generating excessive heat 1. Measure equipment room ambient temperature<br>2. Check if vents and dust filter screen have dust accumulation<br>3. Check fan operation status<br>4. Check current load rate 1. Turn on air conditioner, lower ambient temperature<br>2. Clean dust filter screen and air duct dust<br>3. Replace faulty fan<br>4. Reduce load or expand UPS capacity
Emergency stop alarm, cannot power on 1. EPO button pressed and not reset<br>2. External emergency stop signal triggered<br>3. EPO circuit fault 1. Check EPO button status on panel<br>2. Check external dry contact input 1. Reset EPO button, restore normal status<br>2. Eliminate external trigger signal<br>3. Inspect/repair EPO control circuit

14.5 Bypass-Type Faults

Fault Symptom Possible Cause Troubleshooting Steps Solution
Bypass voltage abnormal alarm 1. Bypass utility power outage or phase loss<br>2. Bypass circuit breaker tripped<br>3. Bypass voltage/frequency out of range 1. Measure bypass input voltage<br>2. Check bypass circuit breaker status<br>3. Verify bypass voltage range settings 1. Restore bypass power supply, close circuit breaker<br>2. Adjust bypass allowable range (caution required)
Bypass out of synchronization, cannot switch to inverter 1. Large deviation in bypass voltage phase and frequency<br>2. Bypass phase sequence error<br>3. Synchronization control circuit fault 1. Measure bypass voltage frequency and phase sequence<br>2. Compare inverter and bypass phase 1. Abnormal bypass power: wait for restoration to normal<br>2. Correct bypass phase sequence wiring<br>3. Inspect/repair bypass control module
Static switch fault alarm 1. Thyristor (SCR) damaged<br>2. Bypass drive circuit fault<br>3. Excessive current burned the switch 1. Test whether bypass transfer function is normal<br>2. Measure static switch components 1. Hardware fault: replace bypass module or static switch<br>2. Avoid frequent switching with large loads
Maintenance bypass cannot close 1. Mechanical interlock not in place<br>2. Incorrect operation sequence<br>3. Switch mechanism jammed 1. Confirm whether operation procedure is correct<br>2. Check interlock mechanism status 1. Strictly follow operation sequence<br>2. Inspect/repair switch mechanism and interlock device

14.6 Monitoring and Display-Type Faults

Fault Symptom Possible Cause Troubleshooting Steps Solution
Display screen black, no display 1. Auxiliary power supply fault<br>2. Display ribbon cable loose<br>3. Monitoring board fault<br>4. System not powered on 1. Confirm whether system is powered on and indicator lights are on<br>2. Check display connection cable<br>3. Measure auxiliary power supply voltage 1. Ensure system is properly powered on<br>2. Re-insert display ribbon cable<br>3. Replace monitoring module if auxiliary power supply or monitoring board is faulty
Displayed data deviates significantly from measured values 1. Sampling calibration offset<br>2. Sampling circuit fault<br>3. Current transformer (CT) damaged 1. Measure key parameters with a multimeter, compare with displayed values<br>2. Compare multiple phase parameters to determine if deviation is widespread 1. Small deviations: correct through calibration<br>2. Sampling hardware fault: inspect/repair monitoring board or module
Keypad/touchscreen unresponsive 1. Screen frozen<br>2. Touch panel damaged<br>3. Keypad ribbon cable loose 1. Try restarting the system<br>2. Check physical condition of keypad/touchscreen 1. System freeze: restart to recover<br>2. Hardware damage: replace display panel or monitoring module
No alarm sound, no audible/visual indication 1. Buzzer damaged<br>2. Alarm muted<br>3. Alarm setting disabled 1. Check alarm mute status<br>2. Test buzzer function 1. Unmute, enable corresponding alarm<br>2. Replace monitoring module if buzzer is damaged
Historical records lost 1. System powered off for extended period<br>2. Memory chip fault<br>3. Records accidentally cleared 1. Confirm whether there was a long power outage<br>2. Check storage function 1. Regularly export and back up historical data<br>2. Replace monitoring module for storage hardware fault

Chapter 15 Product Q&A

15.1 Basic Concept Category

Q1: What is a modular UPS? What is the difference between it and a traditional tower UPS?

A: A modular UPS is an uninterruptible power supply in which core power units such as rectifiers and inverters are made into independent pluggable modules, installed in parallel inside a standard cabinet. Compared with traditional tower UPS, it supports N+X redundancy, online hot-swap maintenance, and on-demand smooth expansion, offering higher availability, simpler operation and maintenance, and more flexible investment. It is the mainstream selection for high-end computer rooms.

Q2: Is the Lain modular UPS an online (double-conversion) type or an offline (standby) type?

A: All Lain series modular UPS units use an online double-conversion architecture. The load is always powered by the inverter, and the utility power is completely isolated from the load, providing the best power quality and the highest power supply reliability. This is different from low-end architectures such as standby (offline) and line-interactive types.

Q3: What does N+1 redundancy mean? Is redundancy mandatory?

A: N is the number of modules required to carry the load, and 1 is one redundant module. For example, if the load requires 3 modules, configuring 4 modules provides 3+1 redundancy. If any one module fails, the remaining 3 can still carry the full load. Redundancy is not mandatory, but for critical loads, at least N+1 redundancy is strongly recommended to eliminate single points of failure and improve availability. For non-critical loads, a non-redundant configuration is also acceptable at lower cost.

Q4: What battery types does the modular UPS support?

A: Standard configuration supports valve-regulated lead-acid (VRLA) batteries, with optional gel batteries. Customized models support lithium iron phosphate (LiFePO4) batteries with a dedicated BMS management system. Different battery types have different charging parameters; please specify at the time of ordering.

Q5: What is the maximum capacity of a single UPS? What if capacity is insufficient?

A: The Lain single-cabinet UPS supports up to 1200kVA. If capacity requirements are greater, multi-cabinet parallel expansion is supported, expandable up to 5000kVA and above, meeting the needs of ultra-large data centers.

15.2 Installation and Selection Category

Q6: How to select the appropriate UPS capacity?

A: First, calculate the total power of all loads (kW), divide by the power factor of 0.9 to obtain the apparent power (kVA); reserve 20%~30% expansion margin, while also considering redundant configuration.

Formula: UPS capacity (kVA) ≥ Total load power (kW) ÷ 0.9 × (1 + margin factor) ÷ redundancy factor

15.5 Operation and Maintenance Category

Q1: What routine maintenance work is required for a modular UPS?

A: Routine operation and maintenance is divided into four levels: daily inspection, weekly inspection, monthly maintenance, and quarterly maintenance, forming a standardized O&M system. Daily inspection focuses on system operation status indicator lights, core parameters on the display screen (input/output voltage, load rate, battery voltage), any alarm messages, and whether fans are operating normally. Record daily operating data and form an O&M log. Weekly inspection focuses on cleaning equipment surfaces and ventilation openings of dust, checking room ambient temperature and humidity, verifying total battery string voltage, and checking cables for looseness or signs of heating. Monthly maintenance requires deep cleaning of dust filter screens, tightening exposed wiring terminals, testing alarm audible/visual functions, exporting monthly operating data for archiving, and conducting a battery status verification. Quarterly maintenance requires internal dust cleaning (with power off), battery internal resistance testing, in-depth fan operation status inspection, sampling verification of protection functions, and comprehensive troubleshooting of potential hidden hazards.

Q2: Do the power modules of a modular UPS need to be replaced periodically? What is the service life?

A: Power modules are semiconductor electronic devices with no fixed mandatory replacement cycle. Under standard operation and maintenance and compliant environmental conditions, the Mean Time Between Failures (MTBF) is ≥ 200,000 hours, and the normal service life can reach 8 to 10 years. There is no need for periodic batch replacement, but operating status should be regularly inspected. If signs of aging such as frequent alarms, parameter drift, or efficiency decline appear, replacement or repair should be performed. It is recommended to increase inspection frequency annually after 6 years of service, focusing on susceptible components such as capacitors, IGBTs, and fans, and to stock identical spare parts in advance to avoid sudden failures affecting continuous load operation.

Q3: What is the normal service life of batteries? How to extend battery life?

A: Valve-regulated lead-acid batteries have a float charge service life of approximately 5–8 years at 25°C ambient temperature; gel batteries approximately 8–10 years; lithium iron phosphate batteries can reach 10–15 years. For every 10°C increase in ambient temperature, battery life is approximately halved, so temperature control is the key to extending life. Core measures to extend battery life include: controlling ambient temperature at 20–25°C to avoid high-temperature operation; avoiding overcharge and over-discharge, strictly implementing three-stage charging management; conducting a verification discharge test every 3 to 6 months to activate battery performance; ensuring tight battery connections to avoid heating from excessive contact resistance; avoiding mixing old and new batteries or different brands; and for stable utility power scenarios, performing a deep discharge every 3 months to prevent battery sulfation.

Q4: If the UPS runs on utility power for a long time without power outages, is periodic discharge required?

A: Yes, periodic discharge testing is required. Lead-acid batteries in long-term float charge condition are prone to plate sulfation, causing capacity decline and internal resistance increase, commonly known as “battery passivation.” It is recommended to perform a shallow discharge every 3 months (discharging about 30% of rated capacity), and a deep verification discharge every 6 to 12 months (discharging 80% of rated capacity). The discharge process must be conducted under the supervision of professional personnel, and the battery should be fully charged promptly after discharge. Before discharge, confirm that the utility power supply is stable to avoid load power interruption if utility power fails mid-discharge. Batteries stored for long periods without operation need a replenishment charge every 3 months to avoid over-discharge damage from self-discharge.

Q5: What are the specifications for equipment dust cleaning? How often should cleaning be done?

A: Dust can cause poor heat dissipation, reduced insulation, and poor contact, and is an important cause of equipment failure. Cleaning must strictly follow specifications. The cleaning cycle is determined by the ambient cleanliness level: for ordinary clean computer rooms, clean every six months; for dusty or industrial environments, clean every 3 months. Cleaning specifications: internal cleaning must be done with power off or after switching to maintenance bypass, allowing capacitors to fully discharge before operation; use anti-static brushes, industrial vacuum cleaners, and ionizing blowers for cleaning; strictly prohibit wet cloths or direct compressed air blowing; focus on cleaning heat dissipation air ducts, fans, power module heat sinks, and circuit board surfaces; after cleaning, check that no debris or loose wires remain before re-energizing. During cleaning, protect connectors and precision components, wear an anti-static wrist strap throughout, and avoid static damage to circuit boards.

Q6: Does enabling the intelligent sleep function affect power supply reliability?

A: No, it does not affect power supply reliability. Intelligent sleep puts some power modules into hot-standby sleep state during low load, while the DC bus, bypass system, and monitoring system all remain online in real time. Sleeping modules can be awakened at any time. When load suddenly increases, a running module fails, or utility power is interrupted, sleeping modules can be quickly awakened and put into operation within milliseconds, with no interruption or sag in output voltage throughout the process. Reliability is completely consistent with full-module operation. Enabling sleep only improves operating efficiency at low load and reduces energy consumption; it does not change the system’s redundant protection logic, and the N+X redundant architecture remains effective.

Q7: What are the wearing parts of the UPS? What is the replacement cycle?

A: The wearing parts of a modular UPS mainly include cooling fans, dust filter screens, electrolytic capacitors, and air switches, with different replacement cycles for different components. Cooling fans: design life is approximately 3–5 years; it is recommended to inspect every 3 years and replace promptly when abnormal noise or speed reduction occurs. Dust filter screens: consumable items, clean every 3–6 months, replace when damaged or severely blocked. Electrolytic capacitors: the main electrolytic capacitors in power modules have a life of approximately 5–8 years, shortened in high-temperature environments; it is recommended to test capacitance regularly after 6 years of use and replace when capacitance drops more than 20%. Air switches and contactors: mechanical life is approximately 10,000 operations; for frequent operation scenarios, it is recommended to test every 5 years and replace when poor contact or contact oxidation is found.

Q8: What checks are required when re-energizing equipment after long-term shutdown?

A: If equipment has been out of service for more than 1 month, a comprehensive inspection must be performed before re-energizing. Direct energization with load is strictly prohibited. Step 1 – Visual inspection: check for moisture, condensation, dust accumulation, pest/rodent traces inside the equipment, corrosion or mildew on circuit boards, and oxidation or looseness on wiring terminals. Step 2 – Insulation test: with power off, test main circuit insulation resistance to ground, which should be ≥ 2MΩ; if insulation is insufficient, drying treatment is required first. Step 3 – Battery check: measure battery total voltage and individual cell voltages; if voltage is too low, perform a separate replenishment charge first, and confirm no battery damage or reverse connection. Step 4 – No-load energization: first energize with no load for 30 minutes, observing system operation status and parameters for normality and any alarms. Step 5 – Gradual load application: after no-load operation is normal, gradually increase load, confirming that all modules operate normally and current sharing is stable, before formal commissioning.

15.6 Fault Troubleshooting Category

Q1: What causes the UPS not to respond when powered on, with the panel not lit?

A: For no response on power-up, troubleshoot in order from external to internal and from easy to difficult. First, check external power supply: whether the upstream input circuit breaker is closed, whether there is voltage at the input end, and whether utility power is normal; whether input cables have open circuits or terminals have fallen off. Second, check the unit’s own switches: whether the UPS main input circuit breaker and bypass circuit breaker are in the closed position and not tripped; whether the emergency stop (EPO) button is pressed and not reset. Third, check the auxiliary power supply: measure auxiliary power supply input and output voltage to determine whether the auxiliary power supply is damaged; whether the input-side fuse is blown. Fourth, check the monitoring module: whether the monitoring board plug connection is loose and whether the power ribbon cable has fallen off. When troubleshooting, first eliminate external power supply and operational issues, then troubleshoot internal hardware faults; if the fault cannot be located, contact the manufacturer’s technical support. Disassembling the unit without authorization is strictly prohibited to avoid expanding the fault.

Q2: What causes the UPS to frequently switch to battery mode even though utility power is normal?

A: When utility power is normal but the UPS frequently switches to battery, the core cause is substandard utility power quality or abnormal detection circuit. Common causes fall into four categories. First, large grid fluctuations: transient voltage sags, surges, or frequency drift exceed the UPS input allowable range, causing the UPS to determine grid abnormality and switch to battery. These are mostly momentary events and recover quickly. Second, poor input contact: loose input terminals, poor circuit breaker contact, or loose cable connections cause intermittent input voltage, frequently triggering battery switching. Third, overly strict input parameter settings: input voltage and frequency ranges set too narrow cause normal grid fluctuations to trigger protection; the range can be appropriately widened under manufacturer guidance. Fourth, detection circuit fault: the voltage sampling board is faulty, misjudging grid status and causing false switching; the sampling board needs inspection/repair or replacement.

Q3: What causes significantly shorter battery backup time in battery mode?

A: Insufficient backup time is a common battery-related issue, with causes concentrated in three areas: battery, charging, and load. Battery aging is the most common cause: batteries used for many years have degraded capacity and increased internal resistance, with substantially reduced actual usable capacity, appearing as full charge but fast discharge. Battery replacement is required. Insufficient charging: long-term low float charge voltage, excessive charging current, or incomplete charging after frequent short discharges leaves the battery in a chronically undercharged state; check charging parameters to ensure full charge. Increased load: actual load exceeds the design value, or significant new loads are added, increasing discharge current and naturally shortening backup time. This is a normal phenomenon; the match between load and capacity must be recalculated. Low ambient temperature: battery capacity decreases at low temperatures; at 0°C capacity is approximately 80% of rated, and at -10°C approximately 60%. Battery ambient temperature needs to be increased. Individual lagging cells: a single faulty cell in the string with excessive internal resistance causes the entire string to trigger early undervoltage protection; individual cells need to be tested and lagging cells replaced.

Q4: What causes the system to frequently alarm module over-temperature?

A: Over-temperature alarms should be investigated from four dimensions: environment, heat dissipation, load, and fault. Excessive ambient temperature is the primary cause: room air conditioning failure, temperatures exceeding 35°C, or high intake air temperature causing heat dissipation difficulties. The ambient temperature needs to be lowered. Second, blocked heat dissipation channels: severe dust accumulation on filter screens and air ducts, fan faults with reduced speed, and hot air unable to exhaust, causing heat accumulation and temperature rise. Clean dust and replace faulty fans. Third, excessive load: long-term overload operation or uneven load distribution across modules causes high heat generation in power devices and temperature rise. Reduce load or expand modules. Fourth, module fault: aging internal components or parameter drift in a module causes increased losses and abnormal heat generation, or a faulty temperature sensor causes false alarms. The faulty module requires inspection/repair or replacement.

Q5: Can the bypass mode run long-term? What are the risks?

A: Bypass mode is an emergency operation mode and is not recommended for long-term continuous operation. In bypass mode, the load is directly powered by utility power, and the UPS loses its voltage regulation, filtering, and uninterrupted power supply functions. Voltage fluctuations, harmonics, surges, and power outages in the utility power directly affect the load, equivalent to connecting the load directly to the grid, losing the UPS protection function. Risks of long-term bypass operation include: direct load power interruption when utility power fails, with no buffer time; direct harmonic and surge impact on the load, easily damaging precision equipment; and unstable voltage causing abnormal load operation and data loss. Bypass should only be used short-term during equipment maintenance or module replacement; after fault resolution, switch back to inverter mode as soon as possible. If long-term bypass is truly required, load power outage protection must be prepared and repair progress accelerated.

Q6: What causes unbalanced three-phase output voltage? How to handle it?

A: Three-phase voltage imbalance falls into two categories: normal deviation and abnormal fault. Normal conditions: severely uneven three-phase load distribution, with one phase’s load much higher than the other two; the heavily loaded phase has slightly lower voltage. Deviation within ±2% is normal; adjust load distribution to balance the three phases. Abnormal fault causes include: a power module on one phase faulting and exiting, reducing that phase’s output capability and causing low voltage; poor contact on one phase of the output circuit, with high contact resistance causing voltage sag under load; and inverter drive circuit faults causing abnormal output on one phase. Handling steps: first check three-phase load currents to confirm whether load is uneven; second, check whether all power modules are operating normally and whether any have faulted and exited; then measure voltage at output terminals and cable connection points to identify poor contact locations; if all the above are ruled out, the fault is determined to be an internal module fault, requiring inspection/replacement of the power module.

Q7: What causes garbled display or screen distortion on the monitoring screen?

A: Display anomalies are mostly monitoring module faults, divided into software and hardware causes. Software causes: abnormal firmware operation or system crash causing garbled display or lag; generally, restarting the system will restore normal operation; firmware version bugs that trigger display anomalies under specific scenarios can be resolved by upgrading to the latest firmware. Hardware causes: loose display ribbon cable or poor contact causing flickering or screen distortion; re-inserting the ribbon cable will resolve it; the display panel itself being damaged or having backlight failure requires display panel replacement; and monitoring main board failure with abnormal video memory or main control chip requires monitoring module replacement. When handling, first restart the system to rule out software issues; then check ribbon cable connections to rule out contact issues; finally determine hardware failure and contact the manufacturer for spare part replacement.

15.7 Safety Specification Category

Q1: What are the safety requirements for operating the high-voltage parts of the UPS?

A: The internal DC bus and AC input/output of the UPS are high-voltage, and operation must strictly comply with high-voltage safety specifications. First, power-off and voltage verification: anyone contacting internal live parts must disconnect all input power, battery switches, and output switches, switch to maintenance bypass (if live maintenance is required), and confirm no voltage with a voltage tester before operation. DC bus capacitors must be fully discharged to prevent electric shock from residual charge. Second, protective equipment: operators must wear insulating shoes, insulating gloves, use insulated tools, and wear an anti-static wrist strap. Single-person operation of high-voltage circuits is prohibited; two-person cooperation is required, with one operating and one supervising. Third, operation specifications: hot-plugging high-current connectors is strictly prohibited; operating high voltage with one hand is strictly prohibited to avoid forming a current path through the body; tools and metal objects must be kept away from live parts to prevent short circuits. Fourth, emergency handling: if electric shock occurs, immediately cut off power, administer first aid, and send to hospital; if short circuit arcing occurs, immediately de-energize and use a dry powder fire extinguisher. Water extinguishing is strictly prohibited.

Q2: What safety prohibitions apply to battery operation?

A: Batteries are chemical energy storage components, and improper operation can easily cause short circuits, explosions, or chemical burns. The following prohibitions must be strictly observed. Strictly prohibit positive-negative short circuits: no metal tools or objects may simultaneously contact both battery terminals. When wiring, connect the negative terminal first and the positive terminal second; when disconnecting, remove the positive terminal first and the negative terminal second. Tools should be insulated. Strictly prohibit disassembling or puncturing batteries: disassembling the battery case or puncturing plates is prohibited to avoid electrolyte leakage causing skin burns or corrosion of items. Strictly prohibit open flames nearby: batteries release trace amounts of hydrogen gas during charging, which can accumulate in confined spaces and explode in the presence of open flames. Smoking, open flames, and electrical sparks are strictly prohibited in battery rooms. Strictly prohibit overcharge and over-discharge: overcharging easily causes battery bulging, leakage, and thermal runaway; over-discharging permanently damages battery capacity. Charging protection parameters must be strictly observed. Strictly prohibit mixed use: batteries of different brands, capacities, ages, or types are prohibited from being mixed in series to avoid uneven charging, heating, and damage.

Q3: How should the UPS be handled when a fire occurs in the equipment room?

A: When a fire occurs in the equipment room, prioritize personnel safety first, then handle equipment according to procedure. Step 1: Immediately press the emergency stop (EPO) button to shut down all UPS outputs and cut off internal power; simultaneously disconnect the upstream input circuit breaker and battery switch to completely cut off equipment energy. Step 2: Call the fire department and use the room’s gas fire suppression system to extinguish the fire. Water and foam extinguishers are strictly prohibited for electrical fires. Step 3: If the fire is small and controllable, with safety assured, the equipment can be de-energized and isolated to prevent fire spread; if the fire is large, evacuate immediately. Step 4: After the fire, the equipment must be comprehensively tested by the manufacturer to confirm insulation and components are undamaged before re-energizing. Direct re-energization without testing is strictly prohibited to avoid secondary accidents.

Q4: What functions can non-professional personnel operate on the UPS?

A: To ensure equipment safety, non-professional operation and maintenance personnel may only perform basic viewing and simple operations. In-depth operations are prohibited. Allowed operations: viewing display screen operating parameters and alarm information; performing normal power-on and power-off operations (panel buttons); pressing the emergency stop button (emergency situations); recording daily inspection data. Prohibited operations: modifying system parameters or protection thresholds is prohibited; inserting/removing power modules or monitoring modules is prohibited; opening equipment covers or contacting internal circuits is prohibited; switching to maintenance bypass or performing battery discharge tests is prohibited; firmware upgrades and factory resets are prohibited. All maintenance, repair, and parameter adjustment operations must be performed by trained professionals or manufacturer engineers.

Q5: What loads can the UPS carry? Which loads cannot be connected directly?

A: The UPS is suitable for carrying precision electronic equipment with high requirements for power supply stability. Some special loads require special adaptation. Suitable loads: IT equipment such as servers, switches, and routers; industrial control equipment such as monitoring systems, DCS, and PLCs; precision electronic equipment such as medical instruments and testing equipment; and general electronic loads such as office computers and displays. Loads not recommended for direct connection: inductive loads such as motors, air compressors, and water pumps, which have large starting surge currents (5–7 times rated) and easily trigger overload protection; high-power resistive loads such as air conditioners and electric heaters, which have low power factors that substantially reduce actual load capacity; and impact loads such as printers and copiers, whose momentary high currents can easily damage the UPS. When carrying inductive or impact loads, the UPS capacity needs to be selected at 3–5 times the load, or output isolation transformers should be configured to avoid impact damage to equipment.

Chapter 16 Product Acceptance

Product acceptance is the final stage of modular UPS project delivery. It is the key process for verifying whether equipment quality, installation quality, and performance indicators meet contract and specification requirements. The acceptance work must be jointly participated in by the construction party, the installation contractor, and the equipment manufacturer. Inspections are carried out item by item strictly according to acceptance standards. After passing acceptance, acceptance documents are signed, and the equipment officially enters the warranty and operation and maintenance stage.

16.1 Acceptance Classification and Acceptance Process

16.1.1 Acceptance Classification

Modular UPS project acceptance is divided into three stages: unpacking acceptance, intermediate acceptance, and completion acceptance. Each stage progresses in sequence, and failure at the previous stage means the next stage cannot proceed.

  • Unpacking acceptance: carried out after equipment arrival; verifies whether model, quantity, appearance, and accessories meet contract requirements. See Chapter 4, Section 4.5 for details.
  • Intermediate acceptance: carried out after installation and wiring are complete but before energization and commissioning; verifies whether installation workmanship, wiring quality, grounding system, and environmental conditions meet specification requirements. It serves as the safety checkpoint before energization.
  • Completion acceptance: carried out after commissioning is complete and trial operation passes; comprehensively verifies whether equipment performance, functions, and indicators meet standards. It is the final project delivery acceptance.

16.1.2 Basic Process for Completion Acceptance

  • Acceptance preparation: the contractor organizes completion documentation, including installation records, commissioning records, test reports, and product documentation, and submits an acceptance application to the construction party; the construction party organizes the acceptance team and determines the acceptance time and participants.
  • Documentation review: the acceptance team first reviews the complete completion documentation set, verifying completeness, authenticity, and standardization. Non-compliant documentation requires supplementation and improvement within a specified deadline.
  • On-site inspection: against the acceptance standards, inspect equipment appearance, installation workmanship, operation status, and performance parameters item by item on site, conduct sampling tests of key functions, and truthfully record inspection results.
  • Issue rectification: for issues found during inspection, issue a rectification notice defining rectification requirements and deadlines; the contractor applies for re-inspection after completing rectification, until all items pass.
  • Acceptance signing: when all inspection items pass and documentation is complete and correct, the three parties jointly sign the completion acceptance report. The equipment is officially delivered and enters the warranty period.

16.2 Intermediate Acceptance Standards

Intermediate acceptance focuses on verifying installation and construction quality as the safety checkpoint before energization. Failure is not permitted to energize and commission.

16.2.1 Cabinet Installation Acceptance

  • Cabinet position and orientation conform to design drawings, arranged neatly; plan position deviation ≤ 5mm.
  • Cabinet levelness deviation ≤ 2mm/m, verticality deviation ≤ 3mm/m.
  • Cabinets are firmly fixed, expansion bolts complete and tightened, anti-vibration pads installed in place; cabinet connection to load-bearing base is reliable, without shaking or tilting.
  • Cabinet appearance is intact, free of paint peeling, deformation, or impact damage; door locks, hinges, and covers are complete and functional, opening and closing smoothly.
  • Cabinet labeling is clear, with equipment numbers, names, and warning signs complete and standardized, positioned prominently.

16.2.2 Wiring Workmanship Acceptance

  • Cable specifications and models meet design requirements, free of damage, aging, or cracks, with intact insulation.
  • Wiring phase sequence is correct with clear identification; wire number sleeves at both ends are complete, numbered to standard, legible, and not prone to falling off.
  • Terminal connections are firm, with torque meeting corresponding wire gauge specifications; copper lugs are crimped to standard, without broken strands or excessive exposed copper; multiple wires connected together are evenly stressed.
  • Cable routing is neat, horizontal and vertical, with binding orderly; strong current and weak current are separated with spacing ≥ 30cm; no crossing or tangling; cable bends have consistent radii without sharp folds.
  • Cable entry holes have intact fire-stop sealing without gaps; cables are firmly fixed with no tensile stress at terminals.

16.2.3 Grounding System Acceptance

  • Cabinets, battery cabinets, and distribution cabinets each have dedicated grounding conductors to the grounding copper bar, with no series grounding; grounding conductors are yellow-green two-color wires with cross-sections meeting specification requirements.
  • Grounding connection points are firm and reliable, treated against rust and loosening; grounding copper bar is clean and free of corrosion.
  • Grounding resistance test passes: combined grounding system resistance ≤ 1Ω, independent working grounding resistance ≤ 4Ω.
  • Grounding identification is clear with clear routing of the grounding trunk line.

16.2.4 Battery Installation Acceptance

  • Battery model, specification, and quantity meet contract requirements; appearance has no bulging, leakage, or deformation.
  • Batteries are neatly arranged with good inter-layer insulation and firm fixing; battery spacing meets ventilation and heat dissipation requirements.
  • Battery connection cables match specifications, with firm connections and torque meeting manufacturer requirements; terminals are free of oxidation and coated with conductive paste to prevent oxidation.
  • Battery polarity is correct and total voltage matches the nominal value; individual cell voltage deviation ≤ 0.05V per 12V battery.
  • Battery DC switch is installed to standard and easy to operate; battery labeling is clear with positive and negative polarity marks prominent and unambiguous.

16.3 Completion Acceptance Performance Standards

Completion acceptance core verification covers electrical performance and functional indicators, which must meet product technical parameters and contract agreement requirements.

16.3.1 Input/Output Performance Acceptance

  • Input characteristics: at rated input voltage, input power factor ≥ 0.99 (full load), input current harmonic distortion THDi ≤ 3%, meeting nameplate parameters.
  • Output voltage stability: steady-state output voltage deviation ≤ ±1%; with load changes from 0 to 100%, voltage transient deviation ≤ ±5%, recovery time ≤ 20ms.
  • Output frequency stability: in battery mode, frequency deviation ≤ ±0.1%, frequency stability meeting national standards.
  • Output waveform: output voltage total harmonic distortion THDu ≤ 3% under linear load, ≤ 5% under non-linear load, waveform being a standard sine wave.
  • Three-phase unbalance: under 100% unbalanced load, output voltage deviation ≤ ±2%, three-phase balancing capability meeting standards.

16.3.2 Transfer and Protection Performance Acceptance

  • Utility-to-battery transfer: transfer time is 0ms, load has no power interruption or restart, output voltage has no interruption.
  • Inverter-to-bypass transfer: transfer time ≤ 2ms, output voltage fluctuation during transfer ≤ ±5%, load has no abnormality.
  • Overload capability: can continuously operate for 10 minutes at 125% rated load and for 60 seconds at 150% rated load; after timeout, smoothly transfers to bypass.
  • Short-circuit protection: on output short circuit, the system instantly limits current, quickly transfers to bypass with alarm, and no component damage occurs.
  • Battery undervoltage protection: when batteries discharge to the end voltage, the system automatically alarms and shuts down in an orderly manner, protecting batteries from over-discharge.

16.3.3 Redundancy and Parallel Performance Acceptance

  • Current sharing accuracy: output current deviation among power modules ≤ ±5%, with even load distribution.
  • Redundancy verification: by manually withdrawing any one power module, system output remains normal, load has no interruption, and the remaining modules can carry the full load.
  • Hot-swap verification: online insertion/removal of power modules, system operation remains stable, output has no abnormality, and modules can smoothly join and exit.
  • Parallel system (if applicable): load distribution among cabinets is even, current deviation ≤ ±5%; single cabinet withdrawal does not affect overall power supply.

16.3.4 Monitoring and Alarm Function Acceptance

  • Display function: display parameters are complete and accurate; deviation between displayed parameters such as voltage, current, and power and measured values ≤ ±2%.
  • Alarm function: simulating various faults, audible and visual alarms work normally with accurate alarm information; alarm levels are clearly distinguished between emergency and general alarms.
  • Communication function: RS485, SNMP and other communication interfaces operate normally, can stably connect to the environment monitoring system, with accurate data transmission.
  • Historical records: alarm records, operation records, and operating data are completely stored, supporting query and export.

16.3.5 Backup Time Acceptance

  • At rated load, battery backup time meets the contract agreed value; actual discharge time is not less than 90% of the nominal value.
  • During discharge, battery voltage declines smoothly with no sudden voltage drop in individual cells.
  • At discharge termination, the system automatically protects and shuts down with no battery over-discharge.

16.4 Acceptance Documentation List

At acceptance delivery, complete technical documentation must be transferred to the construction party, including at least the following:

  • Equipment factory documentation: product certificate of conformity, factory inspection report, product manual, CCC/CE certification certificates.
  • Construction documentation: installation construction plan, electrical wiring diagram, floor plan layout, grounding test records, concealed work acceptance records.
  • Commissioning documentation: commissioning record sheets, system parameter setting tables, functional test reports, battery discharge test reports.
  • Acceptance documentation: unpacking acceptance form, intermediate acceptance records, completion acceptance report, rectification receipts (if applicable).
  • O&M documentation: operation and maintenance manual, spare parts list, warranty card, manufacturer contact information, O&M training records.
  • Other documentation: project contract, technical agreement, design change approvals, and other project files.

All documentation must be bound into volumes in duplicate, with the construction party and contractor each retaining one copy; electronic files must be transferred and archived simultaneously.

16.5 Acceptance Determination and Handover

16.5.1 Qualified Determination

  • If all acceptance items meet standards and documentation is complete, the acceptance is determined as qualified.
  • If minor defects exist that do not affect operation, acceptance may be determined as qualified after rectification within a specified deadline.
  • If major issues exist that affect safety and core performance, the acceptance is determined as unqualified, requiring comprehensive rectification and re-organization of acceptance.

16.5.2 Warranty and Handover

  • On the date the acceptance report is signed after passing, the equipment is officially handed over to the construction party and enters the warranty period.
  • The warranty period is executed according to the contract agreement, typically 12 months from equipment acceptance or 18 months from factory shipment, whichever comes first.
  • At handover, O&M training is completed simultaneously, providing practical training to the construction party’s O&M personnel on equipment operation, daily inspection, and common fault handling to ensure personnel have basic O&M capabilities.
  • After handover, the manufacturer provides ongoing technical support and conducts regular follow-up visits to ensure long-term stable equipment operation.

Chapter 17 SEO Keyword System and Optimization Tags

17.1 Search Keyword Classification

17.1.1 Core Primary Keywords

Modular UPS, modular UPS power supply, data center modular UPS, modular uninterruptible power supply

17.1.2 High-Conversion Long-Tail Keywords

Modular UPS installation wiring commissioning, modular UPS manufacturer, modular UPS price, modular UPS parameters, modular UPS working principle, modular UPS repair and maintenance, modular UPS installation manual, modular UPS commissioning method

17.1.3 Industry Traffic Keywords

Data center UPS power supply, data center UPS, online double-conversion UPS, N+X redundant UPS, three-level modular UPS, industrial-grade UPS power supply, data center uninterruptible power supply, UPS power supply installation solution

17.1.4 Brand-Specific Keywords

Lain modular UPS, Guangdong Lain UPS, Lain data center UPS, LA-M series modular UPS, Lain smart data center equipment

17.1.5 Dropdown/Related Search Keywords

Which is better: modular UPS or tower UPS, how to install modular UPS, how to wire modular UPS, common modular UPS faults, how to configure modular UPS batteries, modular UPS expansion method, modular UPS O&M guide

17.2 SEO Optimization Tag System

17.2.1 Page Core Optimization Tags

  • Page core theme: Modular UPS installation, wiring, and commissioning manual – Guangdong Lain smart data center equipment
  • Core optimization direction: covering full life cycle technical content of modular UPS, providing professional technical reference for contractors, O&M personnel, and procurement personnel, while embedding product brand and manufacturer information to achieve dual goals of technical value and search traffic.

17.2.2 Title Tag

Modular UPS installation wiring commissioning manual_Modular UPS working principle_parameters_repair and maintenance – Guangdong Lain smart data center equipment

17.2.3 Meta Keywords

Modular UPS, modular UPS installation, modular UPS wiring, modular UPS commissioning, modular UPS manual, modular UPS parameters, modular UPS working principle, modular UPS repair and maintenance, data center UPS power supply, Guangdong Lain UPS

17.2.4 Meta Description

Guangdong Lain smart data center equipment professionally provides a full-process technical manual for modular UPS installation, wiring, and commissioning, detailing modular UPS product principles, technical parameters, installation specifications, wiring methods, commissioning steps, repair and maintenance, common fault troubleshooting, and acceptance standards, covering the full LA-M series data center modular uninterruptible power supplies, providing professional technical guidance for data center engineering and O&M management.

17.2.5 H1 Tag

Modular UPS installation wiring commissioning manual

17.2.6 H2 Tags

Product introduction, product composition, product classification, product list, product working principle, product technical parameters, product functions and features, product application scenarios, product installation, product wiring, product commissioning, product precautions, product repair and maintenance, product common problems and solutions, product Q&A, product acceptance

17.2.7 Internal Link Optimization Tags (Anchor Text – Natural Placement)

  • Core anchor text: modular UPS, modular UPS power supply, data center UPS
  • Long-tail anchor text: modular UPS installation wiring commissioning, modular UPS working principle, modular UPS technical parameters, modular UPS repair and maintenance
  • Associated anchor text: data center uninterruptible power supply, three-level inverter UPS, N+X redundant UPS, battery operation and maintenance, data center environment monitoring

Copyright Notice

This document and all its contents (including but not limited to text, images, tables, technical solutions, etc.) are the copyrighted property of Guangdong Lain Intelligent System Development Co., Ltd. and are protected by the Copyright Law of the People’s Republic of China and related international copyright conventions.

Without the written authorization of the Company, no entity or individual may reproduce, redistribute, adapt, excerpt, transmit, commercially use, or otherwise use for commercial purposes all or part of this document in any form.

When authorized to reproduce or quote, the source must be indicated as “Source: Guangdong Lain Intelligent System Development Co., Ltd. official website https://gdlain.com”, and the original content must not be distorted or altered, nor used for commercial purposes.

The Company reserves the right to pursue legal liability for infringement. If the content of this document is technically updated, no separate notice will be provided. The final interpretation right belongs to Guangdong Lain Intelligent System Development Co., Ltd.

Manufacturer: Guangdong Lain Intelligent System Development Co., Ltd.

Service Hotline: +86 13538869979 (WeChat same number)

Technical Support: +86 13538869979

Company Address: Zhongrun Industrial Park, No. 5 Huashan Road, Shilou Town, Panyu District, Guangzhou

Official Website: https://gdlain.com

Shopping Cart