KITOZER SPD: 60kA Type 2+3 Combined Data Center

Product Overview

KITOZER 60kA combined Type 2+3 SPD integrates two protection stages in one enclosure, simplifying data center panel design. It handles both high-energy surge currents from the distribution network and residual fast transients from equipment switching. This combined device reduces panel space, simplifies wiring, and ensures coordination between stages. The plug-in modules and remote signaling make maintenance straightforward. It is ideal for UPS input panels, server room distribution, and critical industrial control boards where space is limited but protection must be robust.

Combining Type 2 and Type 3 in one unit is a smart solution for panels where space is tight. Instead of mounting two separate SPDs with interconnecting cables, engineers install one device that already has coordinated stages. This reduces wiring errors, saves DIN rail space, and ensures that energy sharing between stages is correct from the factory. For data center UPS input panels, the combined SPD provides both bulk energy absorption and fine clamping in a single 4 to 8 module width.

Technical Specifications

Rated voltage 230/400VAC, maximum continuous operating voltage 385VAC. Type 2 stage: In 30kA, Imax 60kA (8/20 microsecond). Type 3 stage: In 10kA, voltage protection level Up less than 1.5kV. Response time less than 25 nanoseconds. Configuration 3P+N or 4P. DIN rail or panel mount. Thermal disconnector per stage, visual indicator per stage. Remote signaling contact. CE, IEC 61643-11, RoHS. KITOZER, 5 year warranty.

The Type 2 stage uses metal oxide varistors for bulk energy absorption, while the Type 3 stage uses a fast-clamping varistor network for residual transients. Each stage has its own visual indicator and thermal disconnector, so operators can see which stage needs replacement. The remote contact reports both stage statuses. Back-up protection is recommended upstream, per manufacturer instruction. Operating temperature range is minus 40 to plus 85 degrees Celsius. The device is suitable for TT, TN-S, and TN-C-S systems. Mounting is on 35mm DIN rail.

Application Scenarios

This combined SPD is used in UPS input panels, server room distribution boards, and industrial control cabinets. It is a good fit for edge data centers, telecom huts, and broadcast rooms where a single board must provide both Type 2 and Type 3 protection. In retrofit projects, it replaces two separate SPDs, freeing panel space. It is also used in critical process panels where any surge event could cause downtime.

Typical deployments include UPS input sub-boards, server room final distribution, industrial PLC panels, and medical equipment protection. In edge data centers, the combined SPD fits in compact cabinets that cannot accommodate two separate devices. In telecom huts, it protects rectifiers and battery chargers. In broadcast rooms, it protects power amplifiers and video equipment. The device is also used in retail back offices, bank branches, and small manufacturing panels where space is limited.

Advantages and Features

The main benefit is coordinated protection in one unit. Factory coordination between stages ensures energy is shared correctly, eliminating guesswork. Two visual indicators show the health of each stage separately, so operators know which module to replace. Compact width saves panel space. Remote signaling sends both stage statuses to BMS. Plug-in modules allow replacement without disconnecting wiring. The device is suitable for both TT and TN systems.

Additional benefits include reduced installation time, lower wiring cost, and guaranteed coordination. Because the stages are factory-matched, there is no risk of mis-coordination that can reduce protection effectiveness. The plug-in module design means maintenance is fast. KITOZER provides a 5 year warranty and coordination charts for downstream SPD selection. The device is CE certified and compliant with IEC 61643-11.

Installation and Maintenance Recommendations

Mount in the distribution board with short input and earth cables. Install upstream back-up protection (gG or aR fuse) per the manufacturer instruction. Verify configuration matches the earthing system. Test remote contact and indicators. Inspect annually, and replace modules when any stage shows red. After a major surge event, replace the Type 2 stage even if indicators appear green, because energy handling capacity degrades. Keep spare modules on site.

For best performance, keep connecting cables under 0.5 meter and use wide earth conductors. Coordinate with upstream Type 1 SPDs by maintaining minimum spacing. Follow the manufacturer instruction for back-up fuse rating. Test the remote contact after installation. Replace modules after any major surge, even if indicators appear green. Keep a log of replacement dates and surge events. KITOZER recommends annual inspection and module replacement every 5 to 10 years depending on surge activity.