Table of Contents
Toggle1. Cover / Document Information
– Document Title: Cabinet Side-Mounted Integrated Air Conditioner (Computer Room Dedicated) Technical Design Solution
– Prepared by: Guangzhou Lain Intelligent System Development Co., Ltd.
– Brand: KITOZER (Pioneer)
– Date: August 2026
– Version: V1.0
– Project Type: Technical design solution for Cabinet Side-Mounted Integrated Air Conditioner (Computer Room Dedicated)
2. Table of Contents Structure
1. Company Introduction
2. Project Overview
3. User Requirement Analysis
4. Overall Design Description
5. Detailed System Design and Product Technical Parameters
6. Project Quotation and Configuration List
7. Core Solution Advantages
8. Technical Q&A
9. Construction Schedule Plan
10. Construction Organization Plan
11. After-Sales Service System
12. Operation and Maintenance Training Plan
13. Typical Project Cases
14. SEO Optimization System and Website Backend Configuration
15. Contact Information
3. Company Introduction
3.1 Company Development Overview
Founded in 2002, Guangzhou Lain Intelligent System Development Co., Ltd. is a high-tech enterprise dedicated to the computer room construction and intelligent protection field for more than two decades, integrating R&D, production, sales, engineering implementation and after-sales service. The company focuses on innovative breakthroughs in electromagnetic shielding technology, modular computer room technology and computer room environmental monitoring technology, and has grown into a source manufacturer with core competitiveness in the domestic computer room construction field.
After more than twenty years of industry accumulation, the company has built a large-scale production and manufacturing base equipped with advanced CNC sheet metal processing equipment, automated spraying production lines and professional testing laboratories, with an annual production capacity of hundreds of sets of shielding computer rooms, integrated cabinets and micro-module products. The company’s service network covers all provinces and cities across the country, providing thousands of computer room construction and renovation services for customers in government, military, scientific research, finance and enterprise fields.
3.2 Core Business System
The company’s core business revolves around the full-lifecycle construction of computer rooms, forming four major product and service systems:
– Computer room EPC general contracting service: one-stop services from solution design, manufacturing, on-site construction to commissioning and acceptance, covering shielding computer rooms, IDC data rooms, modular computer rooms, container computer rooms and other types;
– Core equipment R&D and production: independently produces KITOZER brand series products, including shielding cabinets, shielding desks, consoles, integrated data cabinets, micro-module cold aisle cabinets, outdoor rainproof cabinets, etc., supporting non-standard customization;
– Computer room environmental monitoring system: provides full-element monitoring solutions for temperature and humidity, water leakage, access control, video, fire protection, UPS and power distribution, realizing intelligent and unattended O&M;
– Shielding and security protection products: shielding rooms, shielding doors and windows, anechoic chambers and related auxiliary materials, widely used in confidential, military and scientific research fields.
3.3 Brand and Qualification Honors
The core brand KITOZER (Pioneer) focuses on computer room equipment and shielding products, positioned as an “efficient, green, innovative and safe” solution provider. Products have passed multiple authoritative tests and comply with national and industry standards. The company holds multiple utility model patents and software copyrights, has been awarded high-tech enterprise qualification, and follows the ISO9001 quality management standard.
3.4 Core Competitive Advantages
1. Source production, controllable quality: own production base and professional processing equipment; core products independently produced with full-process quality control, providing more cost-effective solutions without intermediate links;
2. Customized design, matching needs: tailor-made solutions per site conditions, technical requirements, configuration and budget, with multiple design options provided free of charge;
3. Professional team, rich experience: a professional technical team of engineers and project managers with more than ten years of industry experience;
4. Quality after-sales, full guarantee: a 7×24 professional online service system with dedicated project follow-up from early coordination to later O&M.
4. Project Background and Objectives
4.1 Project Background
With electrical automation and digital technology advancement, electronic component density in distribution cabinets, industrial control cabinets and communication cabinets continues to rise, and internal temperature control directly determines equipment stability and life. Traditional cooling methods have persistent pain points: fan cooling cannot lower internal temperature (over 35℃ ambient causes overheating failures); open fan cooling brings dust, moisture and corrosive gas inside (short circuits, corrosion); embedded/top-mounted AC occupies internal space; imprecise temperature control with hot spots; no intelligent monitoring (delayed fault discovery).
The cabinet side-mounted air conditioner (integrated) is the new-generation cabinet temperature control solution: side-mounting, closed-loop cooling and intelligent monitoring — the preferred choice for computer room, industrial and communication cabinet temperature control.
4.2 Core Objectives
– Precise control: internal temperature 20-40℃ adjustable, ±1℃ accuracy, no hot spots, extending equipment life 30%+;
– Environment protection: fully closed-loop design isolating internal/external air, IP54+, blocking dust, moisture and corrosive gas;
– Space optimization: side mounting without occupying internal space, no cabinet structure modification, adaptable to existing and new cabinets;
– Energy saving: high-efficiency system and intelligent control, 40%+ energy saving versus traditional cooling;
– Intelligent O&M: real-time temperature monitoring, fault alarms, remote data transmission, unattended operation;
– Reliability: MTBF over 60,000h, wide-temperature operation, 365-day stable operation.
4.3 Applicable Scenarios
Data center rooms (distribution, UPS, battery, server, network, column cabinets); communications (5G outdoor cabinets, control cabinets, ODF, edge sites, repeaters); industrial manufacturing (PLC, VFD, servo, robot, machine tool, production line control cabinets); power (outdoor RMUs, box substations, charging piles, PV inverters, wind control cabinets); shielded/confidential rooms; outdoor sites (highway toll, security, traffic signal, monitoring station cabinets).
5. User Requirement Analysis
5.1 Basic Functional Requirements
– Vapor-compression cooling with auto regulation per internal temperature;
– Built-in air filter for internal circulating air cleanliness;
– Side wall-mounting with standard brackets adapting to most standard cabinets;
– Display panel showing internal temperature, status and fault codes.
5.2 Performance Requirements
– Cooling capacity matched to cabinet heat load with ≥20% margin at highest ambient;
– Temperature accuracy ±1℃;
– Operating ambient -20℃~55℃; optional heating for low temperature;
– Noise ≤55dB(A) for room scenarios; EER ≥2.8.
5.3 Intelligent O&M
– Real-time monitoring of internal temperature, ambient, compressor/fan status, current;
– Multi-level alarms (high/low temperature, sensor/fan faults, compressor high/low pressure, over-current) with sound/light and signal output;
– RS485 Modbus-RTU for DCIM integration; optional 4G module for APP/cloud;
– Historical temperature and fault records with export.
5.4 Safety and Compliance
– Over-current, overload, short-circuit and leakage protection per national electrical safety standards;
– Optional power SPD for lightning areas; reliable grounding terminal;
– Environmental refrigerant (no ozone-depleting substances); RoHS materials;
– Compliant with national and industry standards.
5.5 Installation and Maintenance
– Modular design, simple installation by ordinary electricians;
– Replaceable filters and fans without special tools;
– Universal industry-standard spare parts;
– Removable side panel with modular internal layout for quick fault repair.
6. Design Principles and Applicable Standards
6.1 Design Basis
GB 50174-2017, GB 50243-2016, GB 50054-2011, GB 4208-2017, JB/T 12918-2016 (cabinet air conditioners for industrial control), YD/T 2768-2014 (outdoor cabinet temperature control), GB 4943.1-2022, enterprise standard Q/KITOZER 001-2023.
6.2 Design Principles
1. Reliability first: well-known brand core components, rigorous environmental and aging testing;
2. High efficiency and energy saving: efficient compressor/heat exchangers, intelligent control algorithms, optimized system matching;
3. Safety protection: electrical, structural and operational safety mechanisms; high-protection housing; multiple protections;
4. Intelligent and convenient: automated operation, remote management, simple interface;
5. Compatible and adaptable: standard mounting interfaces fitting most cabinets; optional modules; non-standard customization;
6. Economical: optimized design and production for high cost performance.
6.3 Working Principle
Vapor-compression cycle: compressor → condenser → capillary (throttling) → evaporator — refrigerant phase change transfers heat from the cabinet to the outside continuously.
Closed-loop air circulation: internal circulation (cabinet hot air → evaporator cooling → returned cold) and external circulation (ambient air → condenser heat rejection) are completely independent — internal air fully sealed from dust, moisture and corrosive gas.
Intelligent control: temperature sensors compare return air to setpoint — compressor starts above the upper limit, stops below the lower limit (fan continues); optional heating module activates in low temperature; modulation avoids frequent cycling for energy saving and life.
6.4 System Architecture
Six subsystems: refrigeration cycle (compressor, condenser, evaporator, capillary, filter drier, receiver); air circulation (internal centrifugal fan, external axial fan, ducts, guide covers); intelligent control (controller, sensors, display panel, communication); filtration (intake filter, outlet grille); electrical protection (breaker, fuses, overload, high/low pressure switches); mounting (brackets, bolts, sealing strips, duct adapters).
6.5 Selection Method
1. Calculate cabinet total heat load (≈ total power W);
2. Determine max ambient (55℃ outdoor, 35℃ indoor);
3. Required cooling = heat load × safety factor (1.2 indoor, 1.5 outdoor);
4. Select model with rated cooling above required with margin;
5. Verify mounting dimensions and side space.
6.6 Airflow Design
Side-mounted with bottom-inlet/top-outlet internal circulation: hot air from the upper cabinet enters the bottom return, cooled air returns from the top flowing downward over components; arc-guided ducts reduce resistance and noise; airflow optimization ensures uniform internal temperature without hot spots.
7. System Architecture and Working Principle
7.1 Series Overview (KITOZER-DG Series)
| Model | Cooling (35℃) | Power | Supply | Cabinet Volume | Typical Use |
|---|---|---|---|---|---|
| DG-300 | 300W | 110W | AC220V | ≤300L | Small distribution/PLC |
| DG-500 | 500W | 180W | AC220V | ≤500L | Medium control/comm |
| DG-1000 | 1000W | 350W | AC220V | ≤1000L | Room distribution/control |
| DG-1500 | 1500W | 520W | AC220V | ≤1500L | High-power VFD/server |
| DG-2000 | 2000W | 680W | AC220V | ≤2000L | Large cabinets |
| DG-3000 | 3000W | per spec | AC220V | ≤3000L | Extra-large cabinets |
7.2 Standard Configuration (per unit)
Side-mounted integrated AC unit (model per selection) with digital display panel, RS485 interface, G4 filter; dedicated mounting bracket; PT100 high-accuracy temperature sensor (±0.1℃); installation auxiliaries (bolts, sealant, ties, terminals).
7.3 Optional Modules
4G remote communication module (cloud/APP, 1-year data); electric heating module (200W PTC, auto low-temperature); dehumidification module (semiconductor, 0.5L/day); power SPD (Class C, 20kA); sound/light alarm.
7.4 Engineering Services
Site survey; installation and commissioning per unit; technical training; transport; tax.
7.5 Quotation Notes
Quotation per configuration list with unit prices; optional modules and services itemized; transport and tax included per contract. All reference prices in this solution are in RMB (CNY) only and are for reference purposes; a formal quotation is issued after configuration confirmation.
8. Detailed Technical Design
8.1 Refrigeration System
– High-efficiency rotary compressor with low noise and long life; high-efficiency fin-tube condenser and evaporator; capillary throttling with filter drier; refrigerant R134a/R290 per model (environmental, RoHS);
– Complete closed-loop internal/external air isolation (IP54+);
– High/low pressure protection switches, over-current protection.
8.2 Air Circulation System
– Internal centrifugal fan providing even cabinet airflow (bottom-in, top-out); external axial fan for condenser heat rejection;
– G4 washable intake filter protecting the evaporator and cabinet cleanliness;
– Arc-guided ducts reducing resistance and noise (≤55dB(A) room models).
8.3 Intelligent Control System
– Microprocessor controller with temperature sensing (PT100 ±0.1℃), digital display panel with status and fault codes;
– Auto start/stop per setpoints; optional heating module for low temperature; dehumidification module option;
– RS485 Modbus-RTU interface; optional 4G module for APP/cloud monitoring; historical data and fault records.
8.4 Protection and Safety
– Electrical: breaker, fuse, overload protection, leakage protection, grounding terminal;
– Refrigeration: high/low pressure protection, compressor thermal protection;
– Optional power SPD (Class C, 20kA);
– Compliant with GB 4943.1 safety and national standards.
8.5 Mounting and Installation
– Standard side-mounting brackets with bolts and sealing strips; bottom-inlet/top-outlet airflow orientation;
– Modular components; replaceable filters and fans; removable side panel for maintenance.
9. Recommended Configuration and Preliminary Budget
9.1 Standard Configuration (per unit, example DG-1000)
| No. | Item | Specification | Unit | Qty |
|---|---|---|---|---|
| 1 | Side-mounted cabinet AC | DG-1000 (1000W), 220V, display, RS485, G4 filter | unit | 1 |
| 2 | Dedicated mounting bracket | Cold-rolled steel sprayed, with bolts | set | 1 |
| 3 | PT100 temperature sensor | ±0.1℃ | pc | 1 |
| 4 | Installation auxiliaries | Bolts, sealant, ties, terminals | set | 1 |
9.2 Optional Modules
4G remote module (with 1-year data); electric heating 200W PTC; semiconductor dehumidifier (0.5L/day); power SPD Class C 20kA; sound/light alarm — priced per selection.
9.3 Engineering Services
Site survey; installation and commissioning per unit; technical training; transport (regional); 13% VAT — itemized per contract.
9.4 Quotation Notes
Model selection per cabinet heat load and ambient (safety factor 1.2 indoor / 1.5 outdoor); unit prices per configuration; total = equipment + options + services + tax. All reference prices in this solution are in RMB (CNY) only and are for reference purposes; a formal quotation is issued after configuration confirmation.
10. Technical Specifications
10.1 Series Specifications
| Model | Cooling (35℃) | Power | Supply | Volume | Noise | Dimensions (approx) |
|---|---|---|---|---|---|---|
| DG-300 | 300W | 110W | AC220V | ≤300L | ≤55dB | per model |
| DG-500 | 500W | 180W | AC220V | ≤500L | ≤55dB | per model |
| DG-1000 | 1000W | 350W | AC220V | ≤1000L | ≤55dB | per model |
| DG-1500 | 1500W | 520W | AC220V | ≤1500L | ≤58dB | per model |
| DG-2000 | 2000W | 680W | AC220V | ≤2000L | ≤58dB | per model |
| DG-3000 | 3000W | per spec | AC220V | ≤3000L | ≤60dB | per model |
10.2 Common Specifications
| Item | Specification |
|---|---|
| Temperature control | 20-40℃ adjustable, ±1℃ |
| Operating ambient | -20℃~55℃ |
| Protection | IP54+, closed-loop isolation |
| EER | ≥2.8 |
| MTBF | ≥60,000h |
| Filter | G4 washable |
| Communication | RS485 Modbus-RTU; optional 4G |
| Safety | Over-current/overload/short-circuit/leakage; high/low pressure protection |
| Standards | JB/T 12918, YD/T 2768, GB 4943.1 |
11. Key Advantages and Customer Value
11.1 Structural Design Advantage
Side mounting occupies no internal cabinet space, no structure modification, adaptable to existing and new cabinets of most brands — flexible installation for dense and retrofit applications.
11.2 Cooling Performance Advantage
Vapor-compression closed-loop cooling with ±1℃ accuracy and 20%+ margin — reliable internal temperature even in high ambient, eliminating hot spots and extending equipment life.
11.3 Intelligent O&M Advantage
Real-time monitoring, multi-level alarms, RS485/4G remote management and data records — unattended operation with reduced fault response time.
11.4 Safety Protection Advantage
Multi-level electrical and refrigeration protection, high-protection housing, optional SPD — safe in harsh and lightning-prone environments.
11.5 Installation and Maintenance Advantage
Modular design, simple installation by ordinary electricians, replaceable filters/fans, universal spare parts — low installation and maintenance cost.
11.6 Customization Advantage
Full series (300-3000W) plus optional modules (heating, dehumidification, 4G, SPD, alarm) and non-standard customization — matched to every scenario.
12. Technical Q&A (50+ Items)
12.1 Product Basics
Q1: What is a cabinet side-mounted air conditioner?
A: An integrated AC unit mounted on the cabinet side that cools the internal air in a closed loop via vapor-compression refrigeration, maintaining the cabinet’s internal temperature while isolating it from the outside environment.
Q2: How is it different from fan cooling?
A: Fans only circulate air without lowering temperature and bring in dust/moisture; the closed-loop AC actually cools and seals the cabinet — essential above 35℃ ambient and in dusty environments.
Q3: Why side mounting?
A: Side mounting uses no internal cabinet space and requires no structure modification — ideal for dense cabinets and retrofits where embedded/top-mounted units cannot fit.
Q4: What is the working principle?
A: Vapor-compression cycle (compressor → condenser → capillary → evaporator) transfers heat out; internal and external air loops are fully independent (closed-loop), so cabinet air stays clean.
Q5: What models are available?
A: DG-300 to DG-3000 covering 300-3000W cooling for cabinets up to 3000L — selection per heat load and ambient.
12.2 Selection and Matching
Q6: How do I select the right model?
A: Calculate cabinet heat load (≈ total power), determine max ambient (35℃ indoor / 55℃ outdoor), required cooling = load × safety factor (1.2/1.5), choose the model with cooling above required with margin.
Q7: What if the model is undersized?
A: Undersizing causes insufficient cooling in peak heat — internal temperature rises and equipment may overheat; always apply the safety factor and margin.
Q8: Can the unit handle outdoor installation?
A: Yes — IP54+ and wide-temperature operation (-20℃~55℃) suit outdoor cabinets; optional SPD for lightning areas.
Q9: What is the maximum cabinet volume?
A: Up to 3000L with the DG-3000; larger volumes can use multiple units — consult for layout.
Q10: Is heating available?
A: Yes — the optional 200W PTC heating module auto-activates in low temperature to maintain internal temperature.
Q11: What about high humidity?
A: The optional semiconductor dehumidification module (0.5L/day) controls humidity in high-moisture environments.
Q12: Can it cool server cabinets?
A: Yes — DG-1500/DG-2000 suit server cabinets; selection per server heat load.
12.3 Installation and Construction
Q13: How is the unit installed?
A: Side wall-mounting with the standard bracket: position, mark, fix with bolts, seal the interface, connect power and sensor — by ordinary electricians in about 1-2 hours.
Q14: Does installation require cabinet modification?
A: No — side mounting requires no internal changes; only the side panel mounting holes.
Q15: Where should the temperature sensor be placed?
A: At a representative internal location (typically upper area) to reflect average cabinet temperature.
Q16: What power is needed?
A: AC220V single-phase; the unit includes protection; a dedicated circuit recommended per load.
Q17: How is the air inlet/outlet oriented?
A: Bottom-inlet/top-outlet internal circulation — hot air from above enters the bottom return, cooled air returns from the top flowing down over components.
Q18: Can multiple units be installed on one cabinet?
A: Yes — for high heat loads, multiple units can be mounted (e.g., both sides) with coordinated setpoints.
Q19: What is the installation time?
A: About 1-2 hours per unit including wiring and commissioning.
Q20: Are installation services provided?
A: Yes — site survey, installation, commissioning and training services are available.
12.4 Operation and Usage
Q21: How is the temperature set?
A: Via the digital display panel buttons — set upper/lower limits within 20-40℃.
Q22: What does the display show?
A: Internal temperature, operating status and fault codes.
Q23: How does the unit save energy?
A: Intelligent start/stop per setpoints (compressor off when cooled, fan continues), efficient components and EER ≥2.8 — 40%+ energy saving versus traditional cooling.
Q24: Can it run continuously?
A: Yes — designed for 365-day continuous operation with MTBF ≥60,000h.
Q25: What is the noise level?
A: ≤55dB(A) for room models — suitable for computer room and office environments.
Q26: How is the unit controlled remotely?
A: RS485 Modbus-RTU to DCIM, or the optional 4G module for APP/cloud monitoring and settings.
Q27: What data is recorded?
A: Historical temperature data and fault records with export — for analysis and troubleshooting.
12.5 Maintenance
Q28: What daily maintenance is needed?
A: Periodic filter cleaning/replacement (G4), fan and heat exchanger inspection, condensate check (if any), sensor verification.
Q29: How are filters cleaned?
A: Remove the filter, wash or replace, reinstall — without special tools.
Q30: How often should filters be replaced?
A: Per environment dust level — typically every 3-6 months; washable types cleaned more frequently.
Q31: What spares are recommended?
A: Filters, fans, sensors, control boards and fuses — stocked for fast replacement.
Q32: How is the unit serviced?
A: The side panel is removable with modular internal layout — quick component access; refrigerant system service by qualified technicians.
Q33: What is the warranty?
A: Typically 1-2 years with free repair of non-artificial faults; lifetime cost-price maintenance after warranty.
Q34: What is the response time?
A: 7×24 support; remote within 1 hour; on-site per region; urgent faults prioritized.
12.6 Fault Troubleshooting
Q35: What if the unit does not cool?
A: Check power, setpoint vs internal temperature, filter blockage, fan operation and fault codes (high/low pressure, sensor) — per the manual; contact support if unresolved.
Q36: What do fault codes mean?
A: Display codes identify sensor fault, fan fault, high/low pressure, over-current etc. — the manual lists codes and actions.
Q37: What if the internal temperature is uneven?
A: Verify sensor placement, airflow blockage, filter condition and door sealing; reposition sensor or adjust airflow if needed.
Q38: What if condensation appears?
A: Check sealing, humidity and the dehumidification option; ensure the closed loop is intact.
Q39: What if the unit cycles frequently?
A: Check setpoint differential and sensor accuracy; excessive cycling may indicate undersizing or sensor issues.
Q40: What if communication fails?
A: Check RS485 wiring/address/baud rate, or 4G signal/data plan for the optional module.
12.7 Intelligent Functions
Q41: What alarms are available?
A: High/low temperature, sensor fault, fan fault, compressor high/low pressure and over-current — with sound/light and signal output.
Q42: Can alarms be sent remotely?
A: Yes — via RS485 to DCIM or the 4G module to APP/cloud with notifications.
Q43: Can the unit be monitored on the cloud?
A: Yes — the 4G module connects to the cloud platform for real-time monitoring and parameter settings.
Q44: Is historical data exported?
A: Yes — temperature and fault records exportable for analysis.
Q45: Can multiple units be centrally managed?
A: Yes — via RS485 bus to the DCIM, multiple units are managed centrally.
12.8 Scenario Applications
Q46: Is it suitable for 5G outdoor cabinets?
A: Yes — IP54+, wide temperature and optional SPD suit outdoor 5G site cabinets.
Q47: Can it protect PLC/VFD control cabinets?
A: Yes — precise temperature control protects sensitive electronics in dusty industrial environments.
Q48: Is it suitable for shielded/confidential rooms?
A: Yes — side mounting adapts to shielded cabinets without compromising shielding; consult for penetration sealing.
Q49: Can it be used in highway toll cabinets?
A: Yes — outdoor-rated models suit toll station and traffic signal cabinets.
Q50: How does it help extend equipment life?
A: Stable 20-40℃ (±1℃) operation reduces thermal stress, dust and corrosion — extending electronic component life 30%+.
Q51: How is the project delivered?
A: Survey → selection confirmation → production/delivery → installation → commissioning → training → acceptance; dedicated project manager.
Q52: What are the total costs?
A: Equipment + options + installation/services + transport + tax; final quotation after selection confirmation.
13. Construction Schedule
13.1 Overall Period
Standard projects complete in 10-20 working days from order: production (7-12 days), delivery (1-2), installation per unit (1-2h each), commissioning and acceptance (1-2 days); adjustable per quantity and site.
13.2 Stage Schedule
| Stage | Work | Days | Responsible |
|---|---|---|---|
| 1. Confirmation | Survey, model selection, configuration, contract | 2 | Engineer |
| 2. Production | Units, brackets, options, factory testing | 7-12 | Factory |
| 3. Delivery | Transport, incoming inspection | 1-2 | Logistics |
| 4. Installation | Mounting, wiring, sealing, commissioning | 1-2 | Engineers |
| 5. Training and acceptance | Operation training, function verification, acceptance | 1 | PM |
13.3 Schedule Assurance
Advance production planning; standard models in stock; experienced installation engineers; coordination with the client on cabinet access; spare units available.
13.4 Emergency Plan
Rush orders expedited; spare units for urgent replacement; extended-hours installation per client schedule.
14. Construction Organization and Quality/Safety Measures
14.1 Organization Structure
– Project manager: overall responsibility, client interface, progress control;
– Technical leader: selection confirmation, installation guidance, commissioning, training;
– Installation team: unit mounting and wiring;
– QC/safety officer: quality inspection, electrical safety supervision.
14.2 Pre-Installation Preparation
1. Technical: site survey (cabinet type, heat load, ambient, mounting space), selection confirmation, disclosure;
2. Materials: incoming inspection (units, brackets, sensors, accessories, certificates);
3. Site: coordinate cabinet access, power and work areas; protect existing equipment.
14.3 Installation Process
1. Position and mark bracket on the cabinet side; fix with bolts;
2. Mount the unit; seal the interface with sealing strips/tape;
3. Install the temperature sensor at the representative internal location;
4. Connect power (dedicated circuit, protection verified) and communication (RS485/4G);
5. Commission: set temperature limits, verify cooling/heating/communication functions;
6. Clean, document, acceptance.
14.4 Quality Control
– Factory testing (cooling capacity, insulation, function); incoming inspection;
– Key control points: mounting firmness, sealing integrity, sensor accuracy, setpoint verification, communication, electrical safety;
– Acceptance checklist with documentation.
14.5 Safety and Civilized Work
– Electrical safety (power-off during wiring, certified connections); PPE;
– Clean work, protection of cabinets and surroundings; compliance with site rules;
– Emergency plans for injury and equipment damage.
14.6 Protection and Acceptance
Installed units protected during other works; acceptance per checklist (cooling function, temperature control, alarms, communication) with documentation.
15. After-Sales Service
15.1 Warranty Commitment
Typically 1-2 years with free repair/replacement of non-artificial quality problems; lifetime cost-price maintenance after warranty.
15.2 Response Mechanism
7×24 hotline; remote guidance within 1 hour; on-site per region (urban 4h); urgent faults prioritized.
15.3 Daily O&M Services
Periodic inspection (filters, fans, sensors, communication), preventive maintenance and platform support.
15.4 After-Warranty Services
Paid maintenance at cost, spare parts supply, upgrade (4G, heating, dehumidification, SPD) and expansion services.
15.5 Service Supervision
Dedicated service records, customer feedback and complaint handling with documented resolution.
16. Training Plan
16.1 Audience and Objectives
O&M personnel: operate the units, set parameters, perform daily maintenance and handle common faults.
16.2 Content
Product principle and models; operation and settings; maintenance (filters, fans); fault codes and troubleshooting; communication and remote monitoring; safety.
16.3 Methods and Schedule
On-site training at installation plus documentation and videos; Q&A; repeat sessions per request.
16.4 Assessment and Materials
Practical assessment; qualified personnel certified; manuals, wiring diagrams and after-sales card delivered.
15. After-Sales Service
15.1 Warranty Commitment
The overall project warranty period is 2 years from the date of completion acceptance; core equipment has a 3-year warranty. During the warranty period, all failures and damage caused by product quality or construction process problems are repaired and parts replaced free of charge. After the warranty period, lifetime cost-price maintenance is provided, charging only parts cost and basic labor, ensuring long-term stable system operation.
15.2 After-Sales Response Mechanism
– A 7×24 after-sales hotline receives fault reports and technical consultations at any time;
– Within the urban area: respond within 2 hours, technicians on site within 4 hours;
– Suburban and surrounding areas: respond within 4 hours, personnel on site within 8 hours;
– General faults resolved on the spot; complex faults solved within 24 hours with a solution;
– Emergency faults get a green channel with priority dispatch of personnel and parts.
15.3 Periodic Inspection and Maintenance
During the warranty period, a free on-site inspection is provided every six months, with a comprehensive maintenance inspection annually. Inspection contents include equipment operating status, connection firmness, sealing and rust conditions, filtering/grounding performance and safety devices. After each inspection, a formal inspection report is issued recording equipment status and maintenance content with optimization suggestions.
15.4 Spare Parts Supply Guarantee
A local spare parts warehouse is established, stocking common wearing parts for quick replacement to shorten fault handling time. For uncommon special parts, a fast supply channel with the factory ensures availability within 48 hours. During warranty, non-artificial-damage spare parts are replaced free; after warranty, parts are charged at cost price without markup.
15.5 System Upgrade and Technical Support
– Free lifetime technical consultation services by phone or online at any time;
– If the customer later needs upgrades or expansions, preferential upgrade solutions and construction services are provided;
– Industry new technology and standard information is regularly pushed to customers.
16. Training Plan
16.1 Training Objectives and Audience
Training objectives: through systematic training, enable management personnel to fully understand the system structure, working principles and performance characteristics, master daily operation methods and inspection/maintenance essentials, identify common faults and handle simple problems, ensuring safe, stable and long-term operation.
Training audience: management and O&M personnel designated by the client, recommended 2-3 persons with basic electrical and equipment knowledge.
16.2 Tiered Training Content System
Level 1: Basic operation training (1 day)
– Basic principles: system concepts, structure composition, performance indicators;
– Daily operation standards: correct operation of equipment, control and safety systems;
– Daily inspection contents: daily/weekly/monthly check items;
– Safety precautions: usage prohibitions and emergency handling procedures.
Level 2: Maintenance training (1 day)
– Detailed structure of each subsystem and working principles;
– Daily maintenance methods: cleaning, fastening checks, routine care;
– Common fault identification and simple handling;
– Emergency handling procedures for power failure, fire and equipment faults.
Level 3: Advanced management training (as needed)
– Performance influencing factors and how to avoid degradation;
– Upgrade and expansion knowledge and specification requirements;
– Relevant national standards interpretation.
16.3 Training Methods and Schedule
– Methods: combination of “theory explanation + on-site practice + Q&A interaction”;
– Schedule: training arranged at the completion acceptance stage, synchronized with handover, 2 days of intensive training total; time flexibly adjustable; a free repeat training session is provided for newly assigned personnel.
16.4 Training Assessment and Documentation Delivery
– Assessment: theory written test plus practical operation; training qualification certificates issued upon passing; supplementary training for those who fail;
– Documentation delivery: complete O&M documentation, including operation and maintenance manual, equipment manuals and certificates, completion drawings and hidden work records, test reports and after-sales service contact card, all bound into volumes.
17. Anonymous Typical Project Scenarios
All project scenarios below are anonymous, generalized examples compiled from typical industry deployments; no real customer names, addresses or confidential information are disclosed.
17.1 Outdoor Cabinet Temperature Control for a Telecom Operator’s 5G Sites
A telecom operator deployed side-mounted cabinet AC units at outdoor 5G base station sites. The DG series units with IP54 protection and closed-loop cooling maintained stable internal temperatures through summer heat, protecting RF and transmission equipment; RS485 integration with the site DCIM enabled remote monitoring; optional SPDs protected against lightning in thunderstorm regions.
17.2 Industrial Control Cabinet Cooling in an Automobile Manufacturing Workshop
An automobile manufacturing workshop’s PLC, VFD and robot control cabinets suffered overheating and dust ingress. Side-mounted DG units with G4 filters sealed the cabinets from workshop dust while maintaining 20-40℃ internal temperatures; equipment downtime from overheating dropped significantly, and the units’ energy-efficient operation reduced cooling costs versus previous methods.
17.3 Distribution Cabinet Cooling in a Government Data Center
A government data center’s distribution and UPS cabinets required precise temperature control in a noise-sensitive environment. DG units with ≤55dB(A) noise suited the room environment; the ±1℃ temperature control and RS485 monitoring ensured stable operation; the 4G option enabled remote alarm notification for the limited O&M staff.
17.4 Cabinet Temperature Control in a Shielded Room
A confidential unit’s shielded cabinets required temperature control without compromising shielding integrity. Side-mounted units installed externally with sealed penetrations maintained internal temperatures while preserving shielding performance; the closed-loop design kept the cabinet interior clean.
17.5 Outdoor Cabinet Cooling at a Highway Toll Station
A highway toll station’s outdoor equipment cabinets required reliable cooling in harsh conditions. Outdoor-rated DG units with wide temperature range and optional SPD provided year-round temperature control; the replaceable filters simplified maintenance in dusty roadside environments.
18. SEO Optimization Section
All reference prices in this technical solution are in RMB (CNY) only and are for reference purposes; final quotation is subject to the confirmed configuration.
18.1 Keyword System
– Core keywords: technical design solution, system configuration, technical parameters, construction and O&M services;
– High-conversion long-tail keywords: design solution, configuration list, technical parameters, construction plan, after-sales service;
– Industry traffic keywords: system architecture, applicable standards, technical Q&A, project cases;
– Brand keywords: KITOZER, Guangzhou Lain.
18.2 SEO Tag System
– Title tag: the article title — Guangzhou Lain KITOZER;
– Meta description: Guangzhou Lain professionally provides complete technical design solutions with detailed configuration list, full-system product technical parameters, construction organization plan and after-sales service — source manufacturer customization, compliant performance, third-party testing supported;
– H1 tag: the article title;
– H2 tags: system design and product parameters, construction organization plan, after-sales service and training, engineering cases.
18.3 Internal Link Anchor Text
– Core anchor text: technical design solution, system construction;
– Long-tail anchor text: configuration list, technical parameters, construction plan;
– Related anchor text: shielding cabinet, micro-module cold aisle, integrated computer room, outdoor cabinet.
19. Official Contact Information
– Company Name: Guangzhou Lain Intelligent System Development Co., Ltd.
– Brand: KITOZER (Pioneer)
– Official Website: https://gdlain.com
– Tel: +86 139 2228 9957 (WeChat available), +86 185 2066 8845 (WeChat available)
– Address: No. 5 Huashan Road, Shilou Town, Panyu District, Guangzhou, China
For any inquiries about this technical design solution, configuration customization, quotation or construction services, please contact us through the information above. We provide free design consultation and tailored solutions for your specific requirements.