– Document Title: Computer Room Wall Color Steel Panel (Dedicated) Technical Design Solution
– Prepared by: Guangzhou Lain Intelligent System Development Co., Ltd.
– Brand: KITOZER (Pioneer)
– Date: August 2026
– Version: V1.0
– Project Type: Technical design solution for Computer Room Wall Color Steel Panel (Dedicated)
2. Table of Contents Structure
1. Company Introduction
2. Project Overview
3. User Requirement Analysis
4. Overall Design Description
5. Detailed System Design and Product Technical Parameters
6. Project Quotation and Configuration List
7. Core Solution Advantages
8. Technical Q&A
9. Construction Schedule Plan
10. Construction Organization Plan
11. After-Sales Service System
12. Operation and Maintenance Training Plan
13. Typical Project Cases
14. SEO Optimization System and Website Backend Configuration
15. Contact Information
3. Company Introduction
3.1 Company Development Overview
Founded in 2002, Guangzhou Lain Intelligent System Development Co., Ltd. is a high-tech enterprise dedicated to the computer room construction and intelligent protection field for more than two decades, integrating R&D, production, sales, engineering implementation and after-sales service. The company focuses on innovative breakthroughs in electromagnetic shielding technology, modular computer room technology and computer room environmental monitoring technology, and has grown into a source manufacturer with core competitiveness in the domestic computer room construction field.
After more than twenty years of industry accumulation, the company has built a large-scale production and manufacturing base equipped with advanced CNC sheet metal processing equipment, automated spraying production lines and professional testing laboratories, with an annual production capacity of hundreds of sets of shielding computer rooms, integrated cabinets and micro-module products. The company’s service network covers all provinces and cities across the country, providing thousands of computer room construction and renovation services for customers in government, military, scientific research, finance and enterprise fields.
3.2 Core Business System
The company’s core business revolves around the full-lifecycle construction of computer rooms, forming four major product and service systems:
– Computer room EPC general contracting service: one-stop services from solution design, manufacturing, on-site construction to commissioning and acceptance, covering shielding computer rooms, IDC data rooms, modular computer rooms, container computer rooms and other types;
– Core equipment R&D and production: independently produces KITOZER brand series products, including shielding cabinets, shielding desks, consoles, integrated data cabinets, micro-module cold aisle cabinets, outdoor rainproof cabinets, etc., supporting non-standard customization;
– Computer room environmental monitoring system: provides full-element monitoring solutions for temperature and humidity, water leakage, access control, video, fire protection, UPS and power distribution, realizing intelligent and unattended O&M;
– Shielding and security protection products: shielding rooms, shielding doors and windows, anechoic chambers and related auxiliary materials, widely used in confidential, military and scientific research fields.
3.3 Brand and Qualification Honors
The core brand KITOZER (Pioneer) focuses on computer room equipment and shielding products, positioned as an “efficient, green, innovative and safe” solution provider. Products have passed multiple authoritative tests and comply with national and industry standards. The company holds multiple utility model patents and software copyrights, has been awarded high-tech enterprise qualification, and follows the ISO9001 quality management standard.
3.4 Core Competitive Advantages
1. Source production, controllable quality: own production base and professional processing equipment; core products independently produced with full-process quality control, providing more cost-effective solutions without intermediate links;
2. Customized design, matching needs: tailor-made solutions per site conditions, technical requirements, configuration and budget, with multiple design options provided free of charge;
3. Professional team, rich experience: a professional technical team of engineers and project managers with more than ten years of industry experience;
4. Quality after-sales, full guarantee: a 7×24 professional online service system with dedicated project follow-up from early coordination to later O&M.
4. Project Background and Objectives
4.1 Project Background and Significance
With the rapid development of the digital economy, the data center — as the core carrier of digital infrastructure — has continuously rising construction standards and reliability requirements. As a core part of room decoration engineering, the wall system not only provides space separation and aesthetics but directly affects fire safety, dust sealing, anti-static performance, sound insulation and thermal insulation — key environmental indicators ensuring stable IT equipment operation.
Ordinary civil wall materials cannot meet the room’s high-cleanliness, high-fire-safety and high-anti-static requirements: latex paint accumulates dust, is non-fire-rated and has no anti-static performance; wallpaper is flammable, edge-curling and poor at dust control — neither meets modern room codes. The dedicated room color steel panel, with its excellent combined performance, has become the standard first choice for modern room wall decoration.
This solution provides a dedicated room wall color steel panel overall solution — full-process standardized service from product selection, design and installation to after-sales O&M — helping customers build a safe, reliable, compliant and beautiful modern room space.
4.2 Applicable Scenarios
The solution adapts to all professional room scenarios: IDC data centers, cloud computing centers and computing rooms; Class A/B/C shielded rooms, electromagnetic shielding rooms and classified rooms; micro-module cold aisle rooms, integrated cabinet rooms and container rooms; enterprise core server rooms, network rooms and monitoring command centers; government, finance, medical and research laboratory rooms; outdoor prefabricated rooms and edge computing nodes. It is customizable per room grade, environmental conditions and space dimensions — from small office rooms to super-large data centers.
4.3 Overall Objectives
Safety and compliance: the wall system achieves Class A non-combustible fire performance, anti-static performance per national room anti-static codes, and meets GB 50174 and related standards — passing fire acceptance and room grade certification.
Functional performance: dust sealing, sound insulation, thermal insulation, impact resistance and washability create a stable operating environment for IT equipment with reduced dust and noise impact.
Aesthetics: flat, beautiful walls with uniform tones, straight corners and coordination with the overall decoration and cabinet colors.
O&M convenience: modular installation for easy disassembly, later retrofit and pipeline maintenance; simple daily cleaning; long service life and lower long-term O&M cost.
Custom adaptation: perfect opening adaptation for doors/windows, sockets, fire and monitoring equipment; standardized, beautiful node treatment with no sanitary dead corners and no performance degradation.
4.4 Basic Principles
Safety first: fire, anti-static and structural safety are the primary design principles — all materials and processes meet the highest safety standards.
Performance adaptation: products matched to room grade and actual environment — meeting needs without over-investment.
Standardization with customization: standard modular main structure for construction efficiency and product commonality; customized solutions for special on-site nodes and needs.
Lifecycle design: construction convenience and later O&M considered together — durability and maintainability lower total lifecycle cost.
Aesthetics and coordination: unified style with the room decoration and equipment colors; refined details.
5. User Requirement Analysis
5.1 Basic Functional Requirements
Space enclosure and separation: stable structure with code-compliant load capacity, supporting wall-mounted ancillary equipment and dividing main hall, distribution room, monitoring room and spare-part room.
Fire resistance: Class A non-combustible wall materials — no burning, dripping or toxic gas in fire, low smoke density, buying time for evacuation and equipment protection, meeting fire-compartment partition fire-resistance limits.
Dust sealing: tight joints, smooth non-dust-generating, non-dust-collecting surfaces effectively blocking external dust and lowering room cleanliness-maintenance cost.
Anti-static: stable anti-static performance with surface resistance in the static-dissipative range, reliably draining static and avoiding damage to electronic equipment.
5.2 Special Performance Requirements
Moisture and corrosion resistance: condensation from AC operation and humid/basement rooms require moisture-resistant materials — rust-resistant metal substrates, corrosion-resistant coatings, no rust, peeling, discoloration or mold over long use.
Sound insulation: server, AC and UPS noise affects staff health and must not transmit to external office areas; the wall system effectively reduces airborne sound transmission.
Thermal insulation: stable temperature/humidity rooms — the wall reduces heat transfer, AC load and condensation risk, improving energy efficiency.
Impact and abrasion resistance: equipment movement and tool knocks require sufficient impact strength and surface hardness — no deformation, scratching or damage, maintaining appearance and reducing repair cost.
5.3 Construction and O&M Requirements
Fast construction: modular installation with little wet work and short construction periods for new builds and low-business-impact retrofits.
Easy maintenance: simple cleaning, spot replacement of damaged sections without large-area demolition, low cost, no impact on room operation.
Expandability: convenient later opening for pipes, sockets and equipment; demountable and reusable panels reduce retrofit waste.
5.4 Compliance and Acceptance Requirements
Material performance, construction workmanship and acceptance standards strictly follow current national codes; complete product test reports, construction documentation and acceptance documentation satisfy fire acceptance, room grade certification and confidentiality certification.
6. Design Principles and Applicable Standards
6.1 Applicable Standards
GB 50174-2017 (data center design), GB 50222-2017 (fire protection of interior decoration), GB 50944-2013 (anti-static engineering construction and acceptance), GB 50210-2018 (decoration quality acceptance), GB 23864-2009 (fire stopping materials), GB/T 11981-2008 (light steel keels), GB/T 12754-2019 (color-coated steel sheet and strip), GB/T 50121-2005 (building sound insulation evaluation), GB 50325-2020 (indoor environment pollution control), GB 50462-2016 (electronic information system room construction and acceptance), JGJ/T 453-2019 (metal-faced sandwich panel application), GJB 3007-2021 (anti-static work area requirements).
6.2 Design Principles
Safety and reliability: Class A fire-rated, permanently anti-static certified products; load-compliant structure; standardized reliable grounding.
Advanced technology: mature modular panel technology with concealed-fixing installation at the industry frontier.
Economy: optimized design controlling cost with high cost-performance and low lifecycle cost.
Green: non-toxic environmental materials, low-pollution low-waste construction, recyclable products.
Aesthetics: clean professional style, refined details, tight joints, unified tones.
6.3 Overall Wall System Construction
The dedicated panel wall system uses a layered construction design, from inside out: building substrate → leveling treatment → light steel keel frame → insulation/sound core → dedicated panel face → sealing/trimming. Layers cooperate to provide structural support, fire resistance, sound insulation, thermal insulation, anti-static and decoration. Total thickness options: 50 mm (internal partitions, space-tight small rooms — basic fire/ESD), 75 mm (balanced performance — most Class B rooms and enterprise core rooms, the most widely used), 100 mm (strongest — Class A rooms, shielded rooms, fire-compartment partitions, high-noise room exterior walls).
6.4 Substrate Treatment Design
Thorough cleaning of floating dust, oil and debris; removal of hollow/loose old coatings; local leveling with cement mortar where deviation exceeds 5 mm/2 m; crack and hole repair; moisture-proof primer on damp areas/basement walls; line marking on floor, ceiling and walls (keel lines, panel division lines, equipment points) per drawings.
6.5 Keel Frame System Design
Hot-dip galvanized light steel keel system, corrosion-resistant and reliable: floor/ceiling U-track 75×40×0.6 mm (for 75 mm panels) fixed with expansion bolts at ≤600 mm spacing (end points ≤50 mm from ends); C-shaped vertical studs 75×50×0.6 mm at 600 mm spacing matching the panel module; U-shaped bridging 38×12×0.5 mm through the studs at ≤1200 mm vertical spacing with clips for stability; additional studs and horizontal reinforcement at door/window openings, equipment openings and heavy mounting points. Stud-to-track connections with blind rivets, verticality deviation ≤2 mm/2 m; galvanizing ≥80 g/m² with rust paint on field-cut ends.
6.6 Inner Core Functional Layer Design
High-density Class A fire rock wool core (80-120 kg/m³) as the first choice — basalt melt-spun inorganic fiber, non-combustible, with aluminum-foil facing on the inner side preventing fiber shedding and adding moisture resistance and reflective insulation. Core cut to keel spacing, fully filled with tight joints — no voids, sagging or omission; pipe penetrations cut neatly and packed with fire rock wool; concealed-work acceptance before panel installation.
6.7 Panel Face Installation Design
Concealed (hidden-fixing) installation — screws hidden in the tongue-and-groove, no exposed nail heads; tongue-and-groove joints with seal strips for dust sealing. Installation starts from a corner, benchmark panel strictly calibrated, whole panels first then cut fillers, large surfaces first then openings and corners. Accuracy: verticality ≤2 mm/2 m; flatness ≤1.5 mm/2 m; joint height difference ≤0.5 mm; joint width deviation ≤0.3 mm. Anti-static grounding: each panel connects to the keel via a dedicated conductive clip (electrical continuity); the whole keel frame connects to the room anti-static ground trunk with resistance ≤1 Ω — a continuous static-dissipative system with no dead corners.
6.8 Node Detail Treatment Design
Corners: dedicated aluminum alloy corner trims, electrostatically coated to match; rounded outside corners, tight inside corners, protected edges; neutral fire sealant in trim/panel gaps.
Top/bottom: U-shaped trims at anti-static floor and ceiling junctions — even gaps, straight sealant, seamless transition preventing dust entry.
Door/window openings: dedicated frame trims flush with panels, fire sealant filling, corner reinforcement preventing stress deformation.
Socket/switch openings: precise holes with dedicated cutters, clean edges, decorative rings, sealant; fire stopping and anti-static bridging preserving performance.
Pipe penetrations: fire-rated conduit protection, Class A fire-stop putty packing, decorative rings; power and weak-current separated per room wiring codes.
6.9 Supporting Facility Adaptation
Equipment mounting directly on reinforced keels (cabinets, monitoring, fire alarm, displays); power/weak-current/fire piping hidden in the keel cavity for aesthetics and later maintenance; all metal parts connected to the room equipotential bonding system; openings for fire detectors, manual call points and fire broadcast without degrading fire performance.
7. System Architecture and Working Principle
7.1 Product Overview
KITOZER dedicated room color steel panels are high-end metal composite wall materials developed for room environments: high-quality metal steel panel face, Class A fire-rated core, permanent anti-static coating — integrating fire resistance, anti-static, dust control, sound insulation, thermal insulation and decoration, meeting and exceeding national standards. Continuous production line one-step composite forming ensures high process accuracy and stable quality, with multi-dimensional customization (size, color, coating, thickness, core).
7.2 Substrate Technical Parameters
Galvanized steel (DX51D+Z per GB/T 2518-2019): thickness 0.4/0.5/0.6/0.8/1.0/1.2 mm (±0.02 mm); two-side zinc coating 80/120/180/275 g/m² (standard rooms 120 g/m², humid environments ≥180 g/m²); dense adherent zinc layer, no misses/tumors/scratches, no peeling at 180° bend; yield ≥230 MPa, tensile 300-450 MPa, elongation ≥26%; flatness ≤3 mm/m; neutral salt spray ≥480 h without red rust (120 g/m²).
Aluminum-zinc alloy steel (DX51D+AZ per GB/T 14978-2019): 55% Al / 43.5% Zn / 1.5% Si alloy coating, corrosion resistance 2-3× galvanized at equal weight; two-side 50/70/100/150 g/m² (standard 100 g/m²); neutral salt spray ≥1000 h without red rust; withstands 315℃ without oxidation or discoloration; yield ≥235 MPa.
7.3 Surface Coating Technical Parameters
High-weathering polyester (PE): two-coat two-bake front (primer + topcoat), one-coat one-bake back; front 20-25 μm, back 5-10 μm; adhesion class 0 (cross-cut per GB/T 9286); pencil hardness ≥2H; 10,000 wet-wipe cycles without wear or color change; resistant to neutral cleaners, alcohol and mild acids/alkalis; UV 1000 h yellowing ΔE ≤3.0; colors: matt white, ivory, light grey, silver grey (RAL/Pantone custom, same-batch ΔE ≤2.0).
PVDF fluorocarbon (≥70% PVDF resin): front 25-30 μm, back 10-15 μm; adhesion class 0; hardness ≥3H; accelerated aging ≥4000 h with gloss loss ≤10%, no powdering or cracking; outdoor color retention 15+ years; resistant to acids, alkalis, salt spray and solvents; self-cleaning dense surface; low VOC.
Permanent anti-static coating: permanent anti-static material (not temporary agents) distributed inside the coating — performance retained even with surface wear, ≥10 years; surface resistance 1.0×10⁶~1.0×10⁹ Ω (static-dissipative per GJB 3007-2021, GB 50944-2013); volume resistance 10⁶~10¹⁰ Ω; static decay 1000V→100V ≤0.1 s; triboelectric voltage ≤100V; humidity-independent; grounding ≤1 Ω.
7.4 Core Material Technical Parameters
Class A rock wool: basalt melt-spun inorganic fiber, asbestos/formaldehyde-free; density 80/100/120/150 kg/m³; Class A non-combustible (GB 8624-2012 A2), max use ≥650℃; fire-resistance limit by thickness 0.5 h (50 mm) / 1.0 h (75 mm) / 1.5 h (100 mm) up to 2.0 h; thermal conductivity ≤0.040 W/(m·K) at 25℃; weighted sound reduction 50 mm/80 kg/m³ ≥25 dB, 100 mm/120 kg/m³ ≥35 dB; shot content ≤10%; volume moisture absorption ≤0.5%, hydrophobicity ≥98%; formaldehyde not detected per GB 50325-2020; aluminum-foil facing.
High-density gypsum core (≥850 kg/m³, glass-fiber reinforced): Class A non-combustible, fire-resistance ≥1 h, crystal-water release absorbs heat; flatness ≤0.5 mm/m; sound reduction 50 mm ≥28 dB; formaldehyde-free, no radioactivity; moisture-treated.
Centrifugal glass wool (48/64/80 kg/m³, fiber ≤8 μm): Class A non-combustible, max use 450℃; sound reduction 50 mm/64 kg/m³ ≥30 dB; thermal conductivity ≤0.038 W/(m·K); hydrophobicity ≥99%; formaldehyde-free.
7.5 Finished Panel Comprehensive Parameters
Dimensions: width 950/1150 mm standard (500-1200 custom, ±2 mm); length custom per site (1000-6000 mm, ±3 mm); thickness 50/75/100 mm (30-150 custom, ±1 mm); steel 0.4-0.8 mm (±0.02 mm); tongue depth 15 mm.
Physical/mechanical: surface density ~12 kg/m² (50 mm) / 15 (75) / 18 (100); flexural load ≥1.0 kN/m² at 600 mm span, deflection ≤L/250; 1 kg steel ball from 1 m — no dent, crack or coating loss; face/core peel strength ≥0.15 N/mm; single-point hanging ≥50 N at keel positions.
Fire: Class A non-combustible (A2); smoke toxicity t0 (safe); smoke density rating ≤15; flame spread index ≤25; fire-resistance limit 0.5-2.0 h by thickness.
Anti-static: surface resistance 10⁶-10⁹ Ω; volume 10⁶-10¹⁰ Ω; decay <0.1 s; system ground ≤1 Ω; validity ≥10 years.
Sound insulation (GB/T 19889.3-2005 laboratory): 50 mm rock wool Rw ≥28 dB; 75 mm rock wool Rw ≥32 dB; 100 mm higher.
8. Detailed Technical Design
8.1 Selection Design
50 mm panels for internal partitions and space-tight small rooms; 75 mm for most Class B rooms and enterprise core rooms (mainstream); 100 mm (0.8 mm aluminum-zinc substrate, fluorocarbon anti-static coating, 120 kg/m³ core) for Class A rooms, shielded rooms, fire-compartment partitions and high-noise exterior walls; gypsum-core panels for high-flatness clean rooms; PVDF coating for outdoor/corrosive environments; shielded panels with conductive seals and trims for shielded rooms.
8.2 Layout and Keel Design
Panel module-based layout minimizing cutting waste; keel spacing 600 mm; door/window and heavy-equipment openings with additional studs and diagonal bracing; power/weak-current/fire pipes routed in the keel cavity; equipment mounting points reinforced per load.
8.3 Core and Grounding Design
Rock wool fully filled per keel spacing with aluminum-foil facing inward and foil-tape sealed joints; each panel connected to the keel by conductive clips; keel frame bonded to the room anti-static ground trunk (≤1 Ω); shielded rooms with conductive joint treatment and dedicated shielded trims and penetration treatment.
8.4 Node and Penetration Design
Standardized corner/top/bottom/door-window trims; socket/switch openings with cutters, decorative rings, fire stopping and anti-static bridging; pipe penetrations with fire conduit and Class A putty; all joints sealed with neutral fire sealant over masking tape for straight, uniform beads.
8.5 Acceptance and Testing Design
Completed-wall tests: verticality ≤2 mm/2 m; flatness ≤1.5 mm/2 m; joint height difference ≤0.5 mm; corner squareness ≤2 mm; joint width deviation ≤0.3 mm; surface resistance 10⁶-10⁹ Ω; ground resistance ≤1 Ω; third-party fire and anti-static testing optional.
9. Recommended Configuration and Preliminary Budget
9.1 Configuration Summary
Main materials:
| No. | Product | Specification | Unit |
|---|---|---|---|
| 1 | Room anti-static color steel sandwich panel | 50 mm, 0.5 mm galvanized steel, 80 kg/m³ rock wool core, polyester anti-static coating | m² |
| 2 | Room anti-static color steel sandwich panel | 75 mm, 0.6 mm galvanized steel, 100 kg/m³ rock wool core, polyester anti-static coating | m² |
| 3 | Room anti-static color steel sandwich panel | 100 mm, 0.8 mm aluminum-zinc steel, 120 kg/m³ core, fluorocarbon anti-static coating | m² |
| 4 | Gypsum-core room panel | 75 mm, 0.6 mm galvanized steel, high-density gypsum core, polyester coating | m² |
Auxiliary materials: vertical stud 75×50×0.6; floor/ceiling track 75×40×0.6; bridging 38×12×0.5; M8×80 expansion bolts; ST4.2×16 self-tapping screws; φ4×16 aluminum blind rivets; Class A rock wool 80 kg/m³ foil-faced; neutral fire sealant; aluminum corner trims (matt white); top/bottom trims; door/window trims; stainless conductive clips; Class A fire-stop putty; EPDM seal strips.
Construction services: substrate treatment, keel installation, core filling, panel installation, trim and sealant, opening treatment, grounding construction, site cleaning, acceptance support.
Other fees: material transport, floor delivery, design service (survey, scheme, drawings), third-party fire/anti-static testing (optional).
9.2 Quotation Notes
The quotation is based on standard products and normal construction conditions, including main materials, auxiliaries, labor, transport and tax — full-process service from factory testing, on-site installation and acceptance to warranty, with no hidden charges. Special customization, complex nodes, high-floor delivery and night work are quoted separately. All prices are indicative and quoted in RMB (CNY) only — no foreign-currency conversion is provided; the final quotation is calculated per actual quantities, product selection and site conditions, and is subject to a formal quotation.
10. Technical Specifications
10.1 System Performance Summary
| Item | Specification |
|---|---|
| Panel thickness | 50 / 75 / 100 mm (30-150 custom) |
| Panel width | 950 / 1150 mm standard (500-1200 custom) |
| Steel substrate | Galvanized DX51D+Z or aluminum-zinc DX51D+AZ, 0.4-1.2 mm |
| Zinc coating | 80-275 g/m² (galvanized); 50-150 g/m² (aluminum-zinc) |
| Coatings | PE / PVDF / permanent anti-static (surface 10⁶-10⁹ Ω) |
| Core materials | Rock wool (80-150 kg/m³) / gypsum / glass wool |
| Fire rating | Class A non-combustible (GB 8624 A2); limit 0.5-2.0 h |
| Smoke toxicity / density | t0 (safe) / ≤15 |
| Sound reduction | Rw ≥28 dB (50 mm) / ≥32 dB (75 mm) / up to 35 dB+ |
| Thermal conductivity | ≤0.040 W/(m·K) (rock wool); ≤0.038 (glass wool) |
| Static decay | 1000V→100V ≤0.1 s; ground ≤1 Ω; validity ≥10 years |
| Flatness / verticality | ≤1.5 mm/2 m / ≤2 mm/2 m |
| Flexural load | ≥1.0 kN/m² at 600 mm span, deflection ≤L/250 |
| Standards | GB 50174, GB 50222, GB 50944, GB/T 12754, GJB 3007 |
| Warranty | 2 years, lifetime maintenance |
10.2 Key Component Specifications
| Component | Key Parameters |
|---|---|
| 50 mm panel | 0.5 mm galvanized, 80 kg/m³ rock wool, PE anti-static, ≥0.5 h fire |
| 75 mm panel | 0.6 mm galvanized, 100 kg/m³ rock wool, PE anti-static, ≥1.0 h fire |
| 100 mm panel | 0.8 mm aluminum-zinc, 120 kg/m³ core, PVDF anti-static, ≥1.5 h fire |
| Gypsum-core panel | 75 mm, ≥850 kg/m³ core, flatness ≤0.5 mm/m, ≥1 h fire |
| Vertical stud | 75×50×0.6 mm galvanized, 600 mm spacing |
| Floor/ceiling track | 75×40×0.6 mm galvanized, bolts ≤600 mm |
| Rock wool core | 80-120 kg/m³, foil-faced, λ ≤0.040 W/(m·K), A2 |
| Anti-static coating | Surface 10⁶-10⁹ Ω, decay ≤0.1 s, ≥10 years |
| Fire sealant | Neutral silicone, Class A fire-rated |
| Conductive clip | Stainless, panel-to-keel continuity, ground ≤1 Ω |
11. Key Advantages and Customer Value
11.1 Product Performance Advantage
The panel integrates fire resistance, anti-static, dust control, sound insulation, thermal insulation and decoration in one product — Class A non-combustible, permanent anti-static (≥10 years), fire-resistance limit up to 2.0 h, sound reduction up to 35 dB+, low thermal conductivity — all indicators meeting or exceeding national standards, the first-choice Class A room wall material.
11.2 Custom Design Advantage
Multi-dimensional customization — size, color (RAL/Pantone), coating (PE/PVDF/anti-static), steel thickness and core material — plus shielded, gypsum-core and forced-clean variants; three free design options per project, perfectly matching room grade, environment and decoration style.
11.3 Construction Workmanship Advantage
Modular concealed-fixing installation with little wet work — fast construction, short periods, low business impact; standardized node treatment (corners, openings, penetrations) with fire stopping and anti-static bridging; strict accuracy control (flatness ≤1.5 mm/2 m, joint difference ≤0.5 mm); full anti-static grounding ≤1 Ω.
11.4 Full-Lifecycle Service Advantage
Full-process service from survey, design, production and installation to acceptance and training; 7×24 service with fast response; 2-year warranty; annual patrol with anti-static and ground testing; lifetime maintenance at cost; upgrade/expansion services keeping panel colors consistent.
11.5 Cost Control Advantage
Source-factory production removes intermediate links; modular installation shortens schedules and reduces labor; long-life materials lower replacement cost; easy maintenance and spot repair reduce long-term O&M cost — total lifecycle cost optimized.
12. Technical Q&A (50+ Items)
12.1 Product Knowledge
Q1: What is a room-dedicated color steel panel?
A: A high-end metal composite wall material developed for computer rooms — metal steel face, Class A fire-rated core, permanent anti-static coating — integrating fire resistance, anti-static, dust control, sound insulation, thermal insulation and decoration, meeting room codes where ordinary materials (latex paint, wallpaper) fail.
Q2: Why can’t ordinary wall materials be used in rooms?
A: Latex paint accumulates dust, is non-fire-rated and has no anti-static performance; wallpaper is flammable, curls and is poor at dust control — none meet the high-cleanliness, high-fire-safety and high-anti-static requirements of modern rooms per building codes.
Q3: What is the difference between room panels and ordinary color steel panels?
A: Room panels add permanent anti-static coating (surface resistance 10⁶-10⁹ Ω), Class A fire-rated cores with fire-resistance limits up to 2.0 h, higher flatness and joint accuracy, concealed fixing without exposed nails, and complete anti-static grounding — ordinary building panels lack these functional requirements.
Q4: What is the difference between the 50/75/100 mm thicknesses?
A: 50 mm for internal partitions and space-tight small rooms (basic fire/ESD); 75 mm balanced performance for most Class B rooms and enterprise core rooms (mainstream); 100 mm strongest — Class A rooms, shielded rooms, fire-compartment partitions and high-noise exterior walls.
Q5: What core materials are available, and how to choose?
A: Rock wool (first choice — fire + insulation + sound, best cost-performance); gypsum (higher flatness and fire for clean rooms); glass wool (best sound/thermal insulation for shielded rooms and precision laboratories). Choose per fire-resistance, sound and flatness requirements.
Q6: What is the difference between galvanized and aluminum-zinc substrates?
A: Aluminum-zinc (55% Al/43.5% Zn/1.5% Si) has 2-3× the corrosion resistance of galvanized at equal coating weight — for high-weathering, high-corrosion and high-cleanliness scenarios; galvanized is the conventional room choice at lower cost.
Q7: What does “permanent anti-static” mean?
A: The anti-static material is distributed inside the coating (not surface-sprayed temporary agents), so performance is retained even with surface wear — ≥10 years validity, humidity-independent, with surface resistance in the dissipative range and grounding ≤1 Ω.
Q8: What colors are available?
A: Standard room colors: matt white, ivory, light grey, silver grey; any RAL or Pantone color customizable, same-batch color difference ΔE ≤2.0 — coordinated with cabinets and room style.
Q9: What are the fire characteristics in a fire?
A: Class A non-combustible — no burning, melting, dripping or toxic gas; smoke toxicity t0 (safe); smoke density rating ≤15; flame spread index ≤25; fire-resistance limit up to 2.0 h by thickness — buying evacuation and equipment-protection time.
Q10: Can the panel be used in shielded rooms?
A: Yes — dedicated shielded panels with conductive joint treatment, conductive seal strips and shielded trims; penetrations treated to maintain shielding continuity; overall connected to the shielding grounding system, meeting B-class shielding requirements while providing fire and anti-static performance.
12.2 Performance Parameters
Q11: How is the anti-static performance tested?
A: Surface resistance (10⁶-10⁹ Ω dissipative range) and volume resistance with a resistance tester; static decay time (1000V→100V ≤0.1 s); triboelectric voltage (≤100V); system ground resistance (≤1 Ω) — per GJB 3007-2021 and GB 50944-2013.
Q12: How good is the sound insulation?
A: Laboratory tested per GB/T 19889.3: 50 mm rock wool Rw ≥28 dB, 75 mm ≥32 dB, 100 mm up to 35 dB+; glass wool cores even higher in mid/high frequencies — effectively isolating server/AC noise from O&M areas and external offices.
Q13: How good is the thermal insulation?
A: Core thermal conductivity ≤0.040 W/(m·K) (rock wool) / ≤0.038 (glass wool); the wall reduces heat transfer, AC load and condensation risk — supporting stable room temperature and lower energy cost.
Q14: What is the washability?
A: 10,000 wet-wipe cycles without wear or color change; stains removed easily with neutral cleaners; resistant to alcohol and mild acids/alkalis — matching high-cleanliness room maintenance.
Q15: What is the impact resistance?
A: 1 kg steel ball dropped from 1 m — no dent, crack or coating loss; yield ≥230 MPa substrates; surface hardness ≥2H (PE) / ≥3H (PVDF) — resisting daily knocks and tool contact.
Q16: What are the dimensional tolerances?
A: Width ±2 mm, length ±3 mm, thickness ±1 mm, steel ±0.02 mm; installed wall verticality ≤2 mm/2 m, flatness ≤1.5 mm/2 m, joint height difference ≤0.5 mm, joint width deviation ≤0.3 mm.
Q17: What is the fire-resistance limit by thickness?
A: 50 mm rock-wool core ≥0.5 h; 75 mm ≥1.0 h; 100 mm ≥1.5 h; thickened cores up to 2.0 h — meeting different fire-compartment partition requirements.
Q18: How is the panel grounded for anti-static?
A: Each panel connects to the keel via a stainless conductive clip (electrical continuity); the keel frame connects to the room anti-static ground trunk with resistance ≤1 Ω — a continuous dissipative system with no dead corners.
Q19: What is the panel weight?
A: Surface density about 12 kg/m² (50 mm), 15 (75 mm), 18 (100 mm) — light, low structural load, easy handling and fast installation.
Q20: What are the environmental credentials?
A: No asbestos, no formaldehyde (not detected per GB 50325-2020), no radioactivity; low VOC coatings; recyclable materials; green construction with low waste.
12.3 Selection and Adaptation
Q21: How to select the panel grade for a room?
A: Per room grade and fire requirements: Class B rooms — 75 mm rock-wool panels with PE anti-static coating; Class A rooms — 100 mm aluminum-zinc/PVDF anti-static panels; shielded rooms — shielded panels with conductive treatment; clean rooms — gypsum-core panels; outdoor/corrosive — PVDF aluminum-zinc.
Q22: Can panel colors match existing cabinets?
A: Yes — standard colors or RAL/Pantone custom with same-batch ΔE ≤2.0, coordinated with cabinets and decoration for a unified professional look.
Q23: Can the panel support wall-mounted equipment?
A: Yes — single-point hanging ≥50 N at keel positions; heavier equipment (cabinets, displays, monitoring) is pre-reinforced with additional keels per weight.
Q24: Can power/weak-current pipes be hidden?
A: Yes — the keel cavity routes power, weak-current and fire piping without exposed conduits, with separated routing and easy later access for maintenance.
Q25: Can existing rooms be retrofitted without stopping business?
A: Yes — zoned construction with dust-proof enclosures, equipment dust covers and off-peak cutting/installation (as in the government room retrofit case), keeping the room running throughout.
Q26: Can openings be added later?
A: Yes — dedicated cutters produce clean openings; decorative rings, fire stopping and anti-static bridging restore performance; panels are demountable for reconfiguration.
Q27: What is the delivery time for customized panels?
A: Standard products ship quickly from stock; customized sizes/colors typically 7-15 days after drawing confirmation, coordinated with the construction schedule.
Q28: How is on-site measurement performed?
A: Free on-site survey measures wall dimensions, openings, equipment points and pipe routes, producing the layout, keel plan and material list — three free design options provided.
Q29: What is the installation period?
A: Modular installation with little wet work — typically 30-60 m² per crew per day depending on node complexity; a 300 m² room wall system completes in about 5-10 working days.
Q30: Can the panel be reused after demolition?
A: Tongue-and-groove concealed-fixing panels are demountable and largely reusable, reducing retrofit waste and cost.
12.4 Installation and Construction
Q31: What is the construction process?
A: Survey → line marking → substrate treatment → floor/ceiling track → vertical studs → bridging → opening reinforcement → concealed-work acceptance → core filling → grounding → panel cutting → panel installation and leveling → openings → trim installation → sealant → cleaning → performance tests → acceptance.
Q32: What are the keel installation requirements?
A: Tracks bolted at ≤600 mm spacing (end points ≤50 mm from ends); studs at 600 mm with riveted connections; verticality ≤2 mm/2 m; bridging at ≤1200 mm with clips; openings reinforced with additional studs and diagonal bracing.
Q33: How is the first panel installed?
A: Start from a corner as the benchmark panel — strictly calibrate verticality and flatness, fix with concealed screws, then install subsequent panels with tongue-and-groove alignment and a rubber mallet for tight joints, checking accuracy continuously.
Q34: How are panels cut?
A: Measure precisely, cut with a cutter/electric saw, edges clean and flat; cut fillers placed at corners and less visible positions; galvanized cut ends treated with rust paint.
Q35: How are joints sealed?
A: Tongue-and-groove with EPDM seal strips; all joint/trim seams sealed with neutral fire sealant over masking tape — straight, uniform beads without bubbles or runs; masking tape removed promptly.
Q36: What are the acceptance standards?
A: Verticality ≤2 mm/2 m; flatness ≤1.5 mm/2 m; joint height difference ≤0.5 mm; corner squareness ≤2 mm; joint width deviation ≤0.3 mm; surface resistance 10⁶-10⁹ Ω; ground resistance ≤1 Ω — checked with straightedge, feeler gauge, resistance and ground testers.
Q37: What concealed works need acceptance?
A: Keel installation (spacing, verticality, reinforcement) and core filling (full, tight, foil facing inward, sealed joints) — accepted and signed before panel installation.
Q38: What safety measures apply during construction?
A: Three-level distribution with two-level protection for power; grounded tools; insulated wiring; helmets, work clothes and protective shoes; harnesses and proper scaffolding above 2 m; no smoking, extinguishers, hot-work permits with watchers; goggles for cutting.
Q39: How is the existing environment protected?
A: Finished floors, equipment, doors and windows covered; dust control during cutting; materials stacked neatly without blocking lanes; daily site cleaning — work finished, site clean.
Q40: What if a panel is damaged during installation?
A: Replace the damaged section before sealing (spare panels carried per project); minor coating scratches touched up with matching repair paint before acceptance.
12.5 Maintenance and Care
Q41: How is the wall cleaned daily?
A: Neutral cleaner with a soft cloth; no strong acids/bases, steel wool or hard brushes; stains wiped promptly; the permanent anti-static coating tolerates routine cleaning without performance loss.
Q42: What periodic checks are recommended?
A: Semi-annual visual check (cracking, loosening, rust); annual anti-static performance and ground resistance testing (10⁶-10⁹ Ω and ≤1 Ω); sealant and trim condition checks.
Q43: How are minor scratches repaired?
A: Light scratches and small paint loss with matching repair paint; larger damage replaced at the section level; trim and sealant issues re-sealed with neutral fire sealant.
Q44: What should not be done to the wall?
A: No over-heavy hanging, no sharp-object impacts, no unauthorized large openings; avoid strong corrosive cleaners; wet areas dried promptly; contact us for water ingress or heavy impact.
Q45: How long does the anti-static performance last?
A: ≥10 years under normal use — the anti-static material is distributed inside the coating, so wear does not remove it; annual testing verifies continued compliance.
Q46: Does the panel rust over time?
A: Galvanized (120 g/m²+) or aluminum-zinc substrates with 60-80 μm coatings resist corrosion; neutral salt spray ≥480 h (galvanized) / ≥1000 h (aluminum-zinc) without red rust — normal room environments last 15+ years without rusting.
Q47: What if a joint seal cracks?
A: Remove the old sealant, clean the joint, re-apply neutral fire sealant over masking tape — restoring sealing and dust control; check nearby joints for similar issues.
Q48: Can openings be made for new equipment?
A: Yes — dedicated cutters for clean edges, decorative rings, fire stopping and anti-static bridging per the standard node treatment; reinforcement per equipment weight.
Q49: What is the warranty and service commitment?
A: 2-year free warranty (product, installation and performance issues); 7×24 hotline with 30-minute initial response and 2-hour solution; urban emergency on-site within 24 hours; general issues fixed within 2 working days, complex within 5; follow-up call within 3 working days after resolution.
Q50: What services continue after warranty?
A: Lifetime maintenance at cost-only materials and labor; annual maintenance agreements (patrol, anti-static testing, cleaning); upgrade/expansion services (openings, relocation, added panels with consistent colors); long-term supply of trims, sealant, repair paint and grounding parts.
12.6 Compliance and Acceptance
Q51: What standards does the panel comply with?
A: GB 50174-2017, GB 50222-2017, GB 50944-2013, GB 50210-2018, GB/T 12754-2019, GB/T 11981-2008, GB 8624-2012, GJB 3007-2021, GB 50325-2020 and JGJ/T 453-2019.
Q52: What documentation supports fire acceptance?
A: Product type test reports (fire rating, smoke toxicity, smoke density), certificates of conformity, material certificates (steel, core, coating), anti-static test reports, construction records and concealed-work acceptance records — satisfying fire acceptance and room grade certification.
Q53: How is the fire rating verified?
A: Burning behavior per GB 8624-2012 (Class A2), fire-resistance limit per standard furnace tests by thickness, smoke toxicity t0 and smoke density ≤15 from national test reports — third-party testing available on request.
Q54: How is the anti-static system verified?
A: Completed-wall surface resistance and ground resistance tests with calibrated instruments; third-party anti-static engineering acceptance per GB 50944-2013 available — with records delivered.
Q55: Can the solution meet classified/confidential room requirements?
A: Yes — shielded panels with conductive continuity, dedicated shielded trims and penetration treatment, and integration into the shielding grounding system meet B-class shielding and confidentiality certification requirements.
Q56: What does the training cover?
A: Theory (structure, performance principles, construction, maintenance) and hands-on (cleaning, resistance/ground testing, scratch repair, terminal checks, common issue handling, emergency flow) — about 2 hours at acceptance, with manuals and follow-up support.
Q57: How is the total cost controlled?
A: Source-factory pricing, modular fast installation (short schedules, low labor), long-life corrosion-resistant materials, easy maintenance and spot repair, and upgrade-friendly design — lower total lifecycle cost than repeated redecoration.
Q58: What are the green credentials?
A: Formaldehyde-free, no asbestos/radioactivity, low VOC, recyclable steel and mineral cores, low-waste modular construction — supporting green building and data center certifications.
Q59: How is service quality supervised?
A: Follow-up calls after every service; completion visit 1 month after delivery; annual visit with free anti-static and ground testing; pre-warranty-expiry visit with extension and maintenance advice; complaint hotline with satisfaction tracking.
Q60: Why choose the KITOZER/Lain solution?
A: 20+ years of room industry experience, source factory with flexible customization, full-process quality control with third-party monitoring, three free design options, professional construction team, complete after-sales network — a one-stop room wall solution from design to lifetime maintenance.
13. Construction Schedule
13.1 Stage Division
The project is divided into: preparation, survey and design confirmation, material production and delivery, on-site installation (substrate → keels → core → panels → nodes), commissioning and testing, acceptance and handover.
13.2 Detailed Schedule (Reference, Adjustable per Scope)
| Stage | Work | Duration | Responsible |
|---|---|---|---|
| 1. Preparation | Drawing review, technical/safety disclosure, material and tool preparation, site cleanup and protection | 1-2 days | PM, technical lead |
| 2. Survey and marking | Re-measure walls, door/window positions, equipment points, pipe routes; mark keel/panel/point lines | 1 day | Engineer, foreman |
| 3. Substrate treatment | Cleaning, leveling repair, moisture-proof primer (damp areas) | 1-2 days | Crew |
| 4. Keel installation | Floor/ceiling tracks, vertical studs, bridging, opening reinforcement; concealed acceptance | 2-4 days | Crew, QC |
| 5. Core filling and grounding | Rock wool filling (foil inward, sealed joints), conductive clips, grounding bonding; concealed acceptance | 1-2 days | Crew, QC |
| 6. Panel installation | Benchmark panel, panel by panel, openings, trims, sealant | 3-8 days | Panel crew |
| 7. Testing and acceptance | Verticality/flatness/joints checks, surface/ground resistance tests, cleaning, documentation | 1-2 days | QC, engineer |
| 8. Training and handover | O&M training, manuals, acceptance report | 0.5 day | PM, engineer |
13.3 Key Node Control
Node acceptance gates: substrate quality before keels; keel verticality/reinforcement before core; core filling (full/tight/foil) before panels; panel accuracy and grounding before sealant; final performance tests before handover. Zoned parallel construction for large projects (e.g. 45 days for a 20,000 m² IDC with 8 halls); retrofit projects use zoned dust-enclosed off-peak construction.
13.4 Schedule Assurance
Advance production of customized panels; safety stock of standard panels, keels and auxiliaries; dedicated crew with experienced panel installers; daily progress tracking with same-day issue resolution; coordination on entry time, access and power windows; standby materials and substitute personnel for emergencies.
14. Construction Organization and Quality/Safety Measures
14.1 Organization Structure
Project manager: overall schedule, quality, safety, customer liaison. Technical lead: design implementation, disclosure, technical problem solving. Foreman: crew management, plan execution, workmanship and site safety. Safety officer: daily safety patrol, hazard identification, protective measures, disclosure. QC inspector: material incoming inspection, process inspection, concealed-work acceptance, records. Installation crew: certified panel installers with 3+ years of room panel experience.
14.2 Pre-Construction Preparation
Technical: study drawings, technical and safety disclosure; re-measure site (wall sizes, door/window, equipment points, pipe routes) and verify against drawings; construction/material/tooling plans; special node solutions in advance.
Materials: main and auxiliary materials per the bill of quantities; custom panels scheduled for factory production; incoming verification (certificates, test reports, appearance, size, quantity) with rejects returned; classified dry storage with moisture/fire/impact protection, panels laid flat.
Tooling: laser level, tapes, straightedge, feeler gauge, multimeter, ground resistance tester; cutter, electric saw, utility knife, punch, scissors; rotary hammer, drill, rivet gun, screwdrivers, wrenches; caulk gun, brushes, cleaning tools, PPE — all inspected before use.
Site: clear the work area, ensure space and channels; connect construction power with RCDs; protect finished floors, equipment, doors and windows; fire equipment in place, no smoking.
14.3 Core Construction Process
Survey → line marking → substrate treatment → floor/ceiling track → vertical studs → bridging → opening reinforcement → concealed acceptance → core filling → grounding → panel cutting → panel installation and leveling → openings → trims → sealant → cleaning → performance tests → acceptance.
14.4 Key Process Specifications
Line marking: wall position lines on floor/ceiling; stud division lines at 600 mm on walls; opening positions and levels marked; horizontal/vertical deviation ≤2 mm; optimized layout minimizing cutting waste.
Keel installation: tracks along lines, bolts ≤600 mm (ends ≤50 mm); studs into tracks, riveted, laser-level verticality ≤2 mm/2 m; bridging ≤1200 mm with clips; door/window and large openings reinforced with additional studs, horizontal reinforcement and diagonal bracing.
Core filling and grounding: rock wool cut to keel spacing, fully embedded with tight joints — no gaps, sagging or omission; foil facing inward, joints sealed with foil tape; conductive clip per panel position to the keel; keel frame bonded to the ground trunk with resistance ≤1 Ω.
Panel installation: benchmark panel from a corner strictly calibrated; subsequent panels tongue-and-groove aligned, rubber mallet for tight joints, uniform gaps; concealed screws in the tongue — no exposed heads; cumulative deviations corrected as installed; non-full panels measured precisely, cut edges flat, placed at less visible positions.
Openings and trims: dedicated tools for clean, burr-free openings; decorative rings; pipe penetrations packed with Class A fire-stop putty with anti-static bridging; corner/top/bottom/door-window trims fixed firmly, straight and level; all joints sealed with neutral fire sealant over masking tape — straight, uniform, bubble-free; tape removed promptly.
14.5 Quality Control
Raw materials: incoming acceptance with certificates and test reports; sampling re-check of panel thickness, zinc coating, coating thickness and core density; rejects removed; material ledger for traceability.
Process control: three-inspection system (self, mutual, special); concealed works accepted and signed by the owner/supervision before panel installation; key control points (keel verticality, panel flatness, ground resistance, fire stopping); daily quality patrol with immediate rectification.
Finished quality standards: verticality ≤2 mm/2 m; flatness ≤1.5 mm/2 m; joint height difference ≤0.5 mm; corner squareness ≤2 mm; joint width deviation ≤0.3 mm; surface resistance 10⁶-10⁹ Ω; ground resistance ≤1 Ω.
14.6 Safety and Civilized Construction
Safety objectives: zero casualties, zero fire, zero electric shock.
Measures: three-level distribution with two-level protection; grounded tools; overhead wiring, no unauthorized connections; certified electricians only; harnesses and qualified scaffolding above 2 m, no climbing keels; no smoking, extinguishers, hot-work permits with watchers, flammable materials stored separately; dedicated tool operators with guards, goggles for cutting; helmets, work clothes, protective shoes and PPE.
Civilized construction: materials stacked neatly with clear labels, no lane blocking; daily cleaning with centralized waste removal; noise control and reasonable hours; protection of finished work and facilities.
14.7 Product Protection
Panels stored flat on dry level surfaces (stack height ≤1.5 m), no heavy compression, no moisture; gentle handling during transport/installation — no scratches on coatings; no leaning or stepping on installed walls; installed walls covered during subsequent works (paint, cement, adhesive); protection around openings and sealant work; dedicated caretaker before acceptance with protection instructions delivered at handover.
15. After-Sales Service
15.1 Warranty Commitment
2-year free warranty from qualified acceptance. Scope: product quality (coating peeling/color change, substrate rust, panel deformation, core detachment); installation quality (keel loosening, panel detachment, joint cracking, trim detachment, sealant cracking); performance (anti-static non-compliance, grounding failure). Exclusions: artificial knocks/scratches/impacts; improper use, unauthorized modification, private disassembly; strong corrosive cleaners or improper cleaning; force majeure; non-supplied materials.
15.2 Response Mechanism
7×24 service: initial solution within 30 minutes of a report; clear handling plan within 2 hours; urban emergency on-site within 24 hours (remote areas per distance, fastest possible); general issues repaired within 2 working days, complex within 5 (negotiated in special cases); follow-up call within 3 working days confirming resolution and satisfaction.
15.3 Daily O&M Guidance
Delivery includes the *Room Panel O&M Manual* plus on-site training: cleaning with neutral cleaner and soft cloth (no strong acids/bases, steel wool or hard brushes); semi-annual visual checks and annual anti-static/ground testing; no over-heavy hanging, sharp impacts or unauthorized large openings; minor scratch repair with matching paint; contact us for water ingress or severe impact.
15.4 Post-Warranty Services
Lifetime maintenance at cost-only materials and labor with transparent pricing; annual maintenance agreements (patrol, anti-static testing, cleaning, hidden-risk detection); upgrade/expansion services (openings, relocation, added panels with consistent colors); long-term supply of trims, sealant, repair paint and grounding parts.
15.5 Customer Follow-Up
Completion visit 1 month after delivery; annual visit with free anti-static and ground resistance testing and overall condition checks; pre-warranty-expiry visit with extension and maintenance advice; complaint and satisfaction tracking throughout.
16. Training Plan
16.1 Objectives and Audience
Objectives: enable the owner’s O&M staff to understand panel performance, master daily maintenance, independently handle common minor issues, and keep the wall system stable long term.
Audience: the owner’s room O&M managers and cleaning staff, 2-5 persons recommended.
16.2 Training Content
Theory: panel structure and core performance; fire/anti-static/sound/thermal principles and standards; wall system construction and installation; purpose and importance of maintenance; causes and prevention of common quality issues; safety precautions and prohibitions.
Hands-on: daily cleaning demonstration and practice; surface resistance and ground resistance tester use; minor scratch and paint-loss repair; ground terminal inspection and tightening; common issue finding and handling; emergency flow drills.
16.3 Methods and Schedule
“On-site lecture + demonstration + hands-on practice + Q&A” by a senior technical engineer, about 2 hours at acceptance: theory 30 min, demonstration 30 min, practice 40 min, Q&A 20 min — adjustable per customer time.
16.4 Assessment and Documentation
Assessment by on-site questions and practical operation — trainees pass before independent maintenance. Delivered materials: product manual, O&M manual, common-issue guide and the after-sales contact card.
16. Training Plan
16.1 Training Objectives and Audience
Training objectives: through systematic training, enable management personnel to fully understand the system structure, working principles and performance characteristics, master daily operation methods and inspection/maintenance essentials, identify common faults and handle simple problems, ensuring safe, stable and long-term operation.
Training audience: management and O&M personnel designated by the client, recommended 2-3 persons with basic electrical and equipment knowledge.
16.2 Tiered Training Content System
Level 1: Basic operation training (1 day)
– Basic principles: system concepts, structure composition, performance indicators;
– Daily operation standards: correct operation of equipment, control and safety systems;
– Daily inspection contents: daily/weekly/monthly check items;
– Safety precautions: usage prohibitions and emergency handling procedures.
Level 2: Maintenance training (1 day)
– Detailed structure of each subsystem and working principles;
– Daily maintenance methods: cleaning, fastening checks, routine care;
– Common fault identification and simple handling;
– Emergency handling procedures for power failure, fire and equipment faults.
Level 3: Advanced management training (as needed)
– Performance influencing factors and how to avoid degradation;
– Upgrade and expansion knowledge and specification requirements;
– Relevant national standards interpretation.
16.3 Training Methods and Schedule
– Methods: combination of “theory explanation + on-site practice + Q&A interaction”;
– Schedule: training arranged at the completion acceptance stage, synchronized with handover, 2 days of intensive training total; time flexibly adjustable; a free repeat training session is provided for newly assigned personnel.
16.4 Training Assessment and Documentation Delivery
– Assessment: theory written test plus practical operation; training qualification certificates issued upon passing; supplementary training for those who fail;
– Documentation delivery: complete O&M documentation, including operation and maintenance manual, equipment manuals and certificates, completion drawings and hidden work records, test reports and after-sales service contact card, all bound into volumes.
17. Anonymous Typical Project Scenarios
All project scenarios below are anonymous, generalized examples provided for reference only. No real customer names, addresses or identifiable details are disclosed.
17.1 Large IDC Data Center Project
Project overview. A large cloud service provider’s data center, about 20,000 m² with 8 main halls, Class A room grade with high standards for fire resistance, anti-static, dust control and thermal insulation.
Implementation. 100 mm Class A fire-rated anti-static panels — 0.8 mm aluminum-zinc substrate, fluorocarbon anti-static coating, 120 kg/m³ rock-wool core — with 1.5-hour fire-resistance limit and stable overall anti-static performance.
Results. Total period 45 days with zoned parallel construction strictly per Class A standards; refined node treatment and reliable grounding; one-pass fire acceptance and Class A room certification; flat, beautiful walls with good sealing and uniform anti-static performance. Five years of stable operation with annual inspections showing no rust or peeling and continuously compliant anti-static performance — leading to continued cooperation on subsequent data center projects.
17.2 Shielded Room Special Construction Project
Project overview. A research institute’s electromagnetic shielding room of about 200 m², B-class shielding, requiring the wall to combine electromagnetic shielding, anti-static and Class A fire performance.
Implementation. 75 mm dedicated shielded panels — 0.8 mm galvanized substrate, polyester anti-static coating, Class A rock-wool core — with conductive seal strips and conductive trims.
Results. All panel joints conductively treated for electrical continuity; door/window openings with dedicated shielded trims; penetrations specially treated; integrated into the shielding grounding system with no shielding degradation. Third-party testing confirmed fully compliant shielding effectiveness plus fire, anti-static and sound performance; flat, beautiful walls with a short construction period — well received by the customer.
17.3 Enterprise Core Room Retrofit Project
Project overview. A large manufacturing enterprise’s headquarters core room of about 300 m², Class B grade, with main hall, distribution room and monitoring room, requiring unified professional decoration style.
Implementation. 75 mm anti-static panels — 0.6 mm galvanized substrate, polyester anti-static coating, 100 kg/m³ rock-wool core, matt white coordinated with cabinet colors; full-process service from design, production and installation to acceptance training, with optimized point layout for equipment installation.
Results. Fast construction with a tidy site; professional unified appearance with all performance indicators compliant and timely after-sales response; the enterprise subsequently selected the same solution for branch room retrofits.
18. SEO Optimization Section
All reference prices in this technical solution are in RMB (CNY) only and are for reference purposes; final quotation is subject to the confirmed configuration.
18.1 Keyword System
– Core keywords: technical design solution, system configuration, technical parameters, construction and O&M services;
– High-conversion long-tail keywords: design solution, configuration list, technical parameters, construction plan, after-sales service;
– Industry traffic keywords: system architecture, applicable standards, technical Q&A, project cases;
– Brand keywords: KITOZER, Guangzhou Lain.
18.2 SEO Tag System
– Title tag: the article title — Guangzhou Lain KITOZER;
– Meta description: Guangzhou Lain professionally provides complete technical design solutions with detailed configuration list, full-system product technical parameters, construction organization plan and after-sales service — source manufacturer customization, compliant performance, third-party testing supported;
– H1 tag: the article title;
– H2 tags: system design and product parameters, construction organization plan, after-sales service and training, engineering cases.
18.3 Internal Link Anchor Text
– Core anchor text: technical design solution, system construction;
– Long-tail anchor text: configuration list, technical parameters, construction plan;
– Related anchor text: shielding cabinet, micro-module cold aisle, integrated computer room, outdoor cabinet.
19. Official Contact Information
– Company Name: Guangzhou Lain Intelligent System Development Co., Ltd.
– Brand: KITOZER (Pioneer)
– Official Website: https://gdlain.com
– Tel: +86 139 2228 9957 (WeChat available), +86 185 2066 8845 (WeChat available)
– Address: No. 5 Huashan Road, Shilou Town, Panyu District, Guangzhou, China
For any inquiries about this technical design solution, configuration customization, quotation or construction services, please contact us through the information above. We provide free design consultation and tailored solutions for your specific requirements.