1. Cover / Document Information

– Document Title: Sewage Treatment Plant PLC Cabinets for Various Systems Technical Design Solution

– Prepared by: Guangzhou Lain Intelligent System Development Co., Ltd.

– Brand: KITOZER (Pioneer)

– Date: August 2026

– Version: V1.0

– Project Type: Technical design solution for Sewage Treatment Plant PLC Cabinets for Various Systems

2. Table of Contents Structure

1. Company Introduction

2. Project Overview

3. User Requirement Analysis

4. Overall Design Description

5. Detailed System Design and Product Technical Parameters

6. Project Quotation and Configuration List

7. Core Solution Advantages

8. Technical Q&A

9. Construction Schedule Plan

10. Construction Organization Plan

11. After-Sales Service System

12. Operation and Maintenance Training Plan

13. Typical Project Cases

14. SEO Optimization System and Website Backend Configuration

15. Contact Information

3. Company Introduction

3.1 Company Development Overview

Founded in 2002, Guangzhou Lain Intelligent System Development Co., Ltd. is a high-tech enterprise dedicated to the computer room construction and intelligent protection field for more than two decades, integrating R&D, production, sales, engineering implementation and after-sales service. The company focuses on innovative breakthroughs in electromagnetic shielding technology, modular computer room technology and computer room environmental monitoring technology, and has grown into a source manufacturer with core competitiveness in the domestic computer room construction field.

After more than twenty years of industry accumulation, the company has built a large-scale production and manufacturing base equipped with advanced CNC sheet metal processing equipment, automated spraying production lines and professional testing laboratories, with an annual production capacity of hundreds of sets of shielding computer rooms, integrated cabinets and micro-module products. The company’s service network covers all provinces and cities across the country, providing thousands of computer room construction and renovation services for customers in government, military, scientific research, finance and enterprise fields.

3.2 Core Business System

The company’s core business revolves around the full-lifecycle construction of computer rooms, forming four major product and service systems:

– Computer room EPC general contracting service: one-stop services from solution design, manufacturing, on-site construction to commissioning and acceptance, covering shielding computer rooms, IDC data rooms, modular computer rooms, container computer rooms and other types;

– Core equipment R&D and production: independently produces KITOZER brand series products, including shielding cabinets, shielding desks, consoles, integrated data cabinets, micro-module cold aisle cabinets, outdoor rainproof cabinets, etc., supporting non-standard customization;

– Computer room environmental monitoring system: provides full-element monitoring solutions for temperature and humidity, water leakage, access control, video, fire protection, UPS and power distribution, realizing intelligent and unattended O&M;

– Shielding and security protection products: shielding rooms, shielding doors and windows, anechoic chambers and related auxiliary materials, widely used in confidential, military and scientific research fields.

3.3 Brand and Qualification Honors

The core brand KITOZER (Pioneer) focuses on computer room equipment and shielding products, positioned as an “efficient, green, innovative and safe” solution provider. Products have passed multiple authoritative tests and comply with national and industry standards. The company holds multiple utility model patents and software copyrights, has been awarded high-tech enterprise qualification, and follows the ISO9001 quality management standard.

3.4 Core Competitive Advantages

1. Source production, controllable quality: own production base and professional processing equipment; core products independently produced with full-process quality control, providing more cost-effective solutions without intermediate links;

2. Customized design, matching needs: tailor-made solutions per site conditions, technical requirements, configuration and budget, with multiple design options provided free of charge;

3. Professional team, rich experience: a professional technical team of engineers and project managers with more than ten years of industry experience;

4. Quality after-sales, full guarantee: a 7×24 professional online service system with dedicated project follow-up from early coordination to later O&M.

4. Project Background and Objectives

4.1 Project Background

Sewage treatment plants have complex processes, many devices and strict discharge requirements; manual/relay control is hard to operate, energy-intensive and difficult to manage. This project provides complete PLC control cabinets for the plant’s core process sections — V-type filter, dosing room, dewatering room, secondary sedimentation tank and pumping station — building a full-process automation control system that stabilizes water quality, saves energy and chemicals, reduces staffing and supports smart-water management and environmental compliance.

4.2 Project Scope

Five PLC control systems: V-type filter PLC cabinet (3PLC: DI146/DO59/AI9/AO11); dosing room and distribution PLC cabinet (4PLC: DI82/DO46/AI12/AO8); dewatering room PLC cabinet (10PLC: DI64/DO64/AI16/AO8); secondary sedimentation tank PLC cabinet (1PLC: DI24/DO20/AI4); pumping station pump control system (1 main PLC cabinet + 3 field gate control boxes + upper monitoring). Plus the full industrial network, lightning/earthing, power distribution, HMI and upper monitoring platform.

4.3 Objectives

Reliable full-process automation with stable effluent; precise closed-loop dosing, pump frequency control and on-demand fans saving 15-30% energy; unattended/less-attended operation; complete data storage, reports and compliance interfaces; modular expansion for future upgrades.

4.4 Compilation Basis

Owner-provided process flow diagrams, equipment lists and site data; relevant national standards (GB 50054 low-voltage distribution, GB 7251.1 low-voltage assemblies, GB 50168 cable installation, GB 50169 earthing, GB 50057 lightning protection, GB/T 17626 EMC, HJ/T 91 water monitoring, automation engineering practices) plus company internal standards.

5. User Requirement Analysis

5.1 Overall Automation Requirements

Unified three-level architecture; per-section PLC independent control with upper-level centralized monitoring; reliable data acquisition/transmission; alarms, trends and reports; expansion capability.

5.2 V-Type Filter Requirements

Constant-water-level filtration with PID control (+-2cm); automatic backwash with three triggers (timed, head-loss, manual); multi-cell interlock (one cell backwashing at a time, sequential rotation); fan/pump start-stop sequencing and fault interlocks; valve position interlocks.

5.3 Dosing Room and Distribution Requirements

Precise automatic dosing (flow-proportional + closed-loop water-quality feedback); main/standby pump auto-switch with runtime rotation; low-level interlock protecting metering pumps from dry running; distribution monitoring; auxiliary equipment control.

5.4 Dewatering Room Requirements

Strict sequential start/stop of the dewatering train (conveyor -> dewaterer -> flocculation dosing -> sludge pump; reverse on stop) preventing clogging; H2S gas monitoring with forced ventilation and interlocks; odor control and environment gas monitoring.

5.5 Secondary Sedimentation Tank Requirements

Sludge discharge, scraper/suction bridge control and level monitoring; compact PLC configuration with full local HMI.

5.6 Pumping Station Requirements

Level-based automatic pump start/stop with hysteresis (dead zones) preventing frequent cycling; soft start/stop reducing grid impact and water hammer; gate control with limit switches and over-torque protection; field/local-remote switching; water level indication and alarming.

5.7 Upper Monitoring and Networking Requirements

Industrial fiber Ethernet ring with redundancy self-healing <=20ms; Modbus RTU field bus; SCADA with process screens, trends, alarms, reports and mobile/remote access; OPC/Modbus interface for integration.

6. Design Principles and Applicable Standards

6.1 Design Principles

Reliability first: industrial first-line components; multi-layer protection and fault tolerance; complete short-circuit/overload/phase-loss protection; dust/moisture/corrosion-resistant cabinets. Advanced + practical: mature automation and network architecture; control logic matched to actual process; simple intuitive HMI. Economy + energy saving: optimized configuration; precise closed-loop control and device scheduling cutting pump/fan/dosing energy. Expandable + open: reserved IO and slots; standard protocols; multi-brand instrument/device interfacing. Easy maintenance: modular design, self-diagnosis and fault alarms, complete data records.

6.2 Applicable Standards

GB 50054 (distribution), GB 7251.1 (assemblies), GB 50168 (cable works), GB 50169 (earthing), GB 50057 (lightning), GB/T 17626 (EMC), GB 18802.1 (SPD), GB 14048 series (low-voltage apparatus), GB 10963.1 (MCB), plus owner process requirements.

7. System Architecture and Working Principle

7.1 Three-Level Architecture

Monitoring management layer (central control room): industrial computers, SCADA software, UPS, printer — receiving all process data and device states for centralized display, storage, analysis and management; remote control commands; alarm management, trends, reports, export. Field control layer (PLC cabinets): programmable controllers with IO/communication/distribution elements — independent signal acquisition, logic, device control and interlock per section; standalone operation independent of the upper system; industrial network uplink. Field device layer: instruments (level, flow, pH, gas), actuators (pumps, fans, valves, dosing pumps, dewaterers) and field boxes.

7.2 Network Architecture

Dual-layer “industrial fiber Ethernet + field bus”: backbone — single-mode fiber between PLC cabinets and control room via industrial switches forming a 100M/gigabit Ethernet ring; ring redundancy switches links in milliseconds on fiber fault; strong EMI immunity; long distance. Field bus — RS485 Modbus RTU between PLCs and smart instruments/drives/soft starters — universal industrial protocol, broad compatibility, reduced field wiring.

7.3 Lightning and Earthing

“Graded protection, layer-by-layer discharge”: power SPD — level-1 at each cabinet incoming (In>=20kA 8/20us, Imax>=40kA, Up<=1.5kV), level-2 at secondary circuits/switch-mode power fronts; signal SPD — all outdoor analog/signal/communication lines (In>=3kA, <1ns response) protecting IO and comm modules; earthing — independent protective and working copper busbars (30x3mm T2 copper), all elements/frames/screens earthed; single cabinet ground resistance <=4 ohm to plant grid; screens single-end earthed avoiding ground loops.

7.4 Power Supply and Distribution

AC380V three-phase five-wire or AC220V supply from the site distribution; capacity for simultaneous operation; UPS for critical loops and monitoring; graded distribution (main breaker -> branch breakers -> terminal breakers) so a fault isolates only its circuit; power and control circuits separately distributed; analog and digital loops separately wired; DC24V via industrial switch-mode supplies with dual-redundant 1+1 auto-switch for critical loops; supplies with overcurrent/overvoltage/overheat protection.

7.5 EMC and Anti-Interference

Industrial-grade PLC/IO per EMC standards; shielded cables for analog signals (screen single-end earthed); power and signal cables separated with code-compliant spacing, no parallel runs; internal layout separating strong/weak current zones; surge suppressors across inductive loads (contactor/relay coils); reliable system earthing forming equipotential system.

8. Detailed Technical Design

8.1 V-Type Filter PLC Cabinet (3PLC)

800x600x2200mm floor cabinet, IP30; medium PLC (CPU with >=256KB program memory, Ethernet, 12-slot rack), 5×32 DI modules (160 points, margin), 2×32 DO relay modules, 1×16-ch 4-20mA 16-bit AI module, 1×16-ch AO module; 2-optical-8-electrical industrial fiber switch with single-mode modules; level-1 power SPD + analog signal SPDs; 63A main MCCB + branch MCBs; 2x100W DC24V supplies (1+1 redundant); 30 intermediate relays; terminal blocks; 12″ industrial touchscreen; temperature/humidity controller + fans + heater + LED light; BV/RVV/RVVP cables, trunking, labels; earthing busbar; programming/SCADA/OPC software; factory assembly, wiring, dressing and testing.

8.2 Dosing Room and Distribution PLC Cabinet (4PLC)

800x600x2200mm; medium PLC 8-slot rack; 3×32 DI, 2×32 DO relay, 1×16-ch AI, 1×8-ch AO; fiber switch; power SPD; 63A MCCB + 15 MCBs; 2x100W DC24V redundant supplies; 35 relays; 4 contactors 9A with thermal overloads for small motors; 10″ touchscreen; environment control kit; full cables and software; factory complete.

8.3 Dewatering Room PLC Cabinet (10PLC)

800x800x2200mm wide cabinet; medium PLC 10-slot rack with independent Ethernet communication module (redundant comms); 2×32 DI, 2×32 DO relay, 1×16-ch AI (incl. gas monitoring), 1×8-ch AO; fiber switch; power + 4-channel signal SPD set; 100A main MCCB + 18 MCBs; 2x200W DC24V redundant supplies; 45 relays; 8 contactors 9A/12A with thermal overloads; 12″ touchscreen; environment control kit; H2S transmitter (0-100ppm, 4-20mA + RS485, industrial); full cables incl. 2.5/4mm2 power; software incl. Modbus library.

8.4 Secondary Sedimentation Tank PLC Cabinet (1PLC)

600x600x2200mm compact cabinet; small PLC (integrated IO, 4-slot expansion rack); 1×32 DI, 1×32 DO relay, 1×8-ch AI; fiber switch kit with SPD; distribution batch (main breaker, MCBs, supply, relays, terminals); 10″ touchscreen; environment kit; cables, software and factory service.

8.5 Pumping Station PLC Control System

Main PLC power cabinet (800x600x2200mm reinforced): integrated PLC host (24DI/16DO relay output), power module, AI expansion (4-ch 4-20mA 12-bit), RS485 Modbus module, 8-port industrial switch, level-1 power SPD; 250A 3P main MCCB; 3x63A motor-circuit breakers; 3 soft starters (bypass built-in, soft start/stop); 3 main contactors; 3 thermal overloads; control-circuit breakers/supply/relays; per-pump panels (start/stop/fault, hand-auto); 2 digital water-level controllers (dual display, 8 relay outputs); 2 submersible level transmitters (4-20mA, lightning-protected); environment kit; 4/10mm2 power cables; earthing; software. 3 field gate control boxes (400x500x200mm wall-mount, IP54): 2P 16A RCD; 2 forward/reverse contactors each; thermal relays; open/close/stop buttons + run/fault lamps; local/remote selector; terminals and wiring. Upper monitoring: industrial PC (quad-core, 8GB, 1TB, 21.5″ display); SCADA 1500-point runtime (alarms, trends, reports); 1kVA online UPS 30min; system integration and commissioning; on-site supervision and 15 man-days; standardized dressing; factory + site tests.

8.6 Cabinet Body

KITOZER standard industrial cabinets: cold-rolled steel frame >=2.0mm, door >=1.5mm, back >=1.2mm; pickling/phosphating/electrostatic powder coating RAL7035 (custom colors); IP30 standard (custom IP54/65); front/rear double doors with reinforcing ribs; adjustable mounting rails; removable bottom covers for cable entry; galvanized mounting plates, earthing busbar, cable clamps, locks, gaskets; optional fans/filters/heaters/lights/thermostats; dimension tolerance <=+-1mm; per GB 7251.1 with 3C; life >=15 years.

8.7 PLC Family

Medium PLC (V-filter, dosing, dewatering): 32-bit RISC, >=0.1us/boolean, program >=256KB, data >=128KB, retentive >=32KB (>=10 years battery-free); local expansion to 12 modules / 1024 points; 1 Ethernet (TCP/IP, Modbus TCP) + 1 RS485 (Modbus RTU, free port), expandable; LAD/FBD/ST languages with online monitor, simulation, forcing; -20~+60 degC, DC24V 20.4-28.8V, <=15W; MTBF >=100,000h; CE/UL/FCC, EMC. Small PLC (sedimentation): >=0.5us boolean, program >=32KB, integrated 16DI/16DO, expand to 7 modules / 256 points; RS485 Modbus RTU; AC220V or DC24V, <=8W; MTBF >=80,000h. Integrated PLC host (pumping): compact DIN-rail; 24DI DC24V (15-30V, opto-isolated >=1500VAC, <=1ms) + 16 relay DO (AC250V/5A, 10M mechanical / 100k electrical cycles); expand 4 modules; RS485 Modbus RTU; AC220V 85-264V wide input; 0-55 degC; MTBF >=50,000h.

8.8 IO Modules

DI 32pt: DC24V sink/source selectable, threshold >=15V on / <=5V off, opto-isolated >=1500VAC, response <=0.2ms, per-channel LED, front connector, <=3W. DO 32pt relay: NO contacts, AC250V/5A DC30V/5A resistive, mechanical >=10M, electrical >=100k cycles, opto + relay isolation, <=5W. AI 16-ch: 4-20mA (0-10V jumper), 16-bit, +-0.1% F.S., drift <=50ppm/degC, >=10 samples/s, channel isolation >=1500VAC, overvoltage/overcurrent protected, software calibration, <=4W. AO 8-ch: 4-20mA (0-10V), 12-bit, +-0.2%, load <=500 ohm, short-circuit protected auto-recover, <=3.5W.

8.9 Communication and Protection Devices

Industrial fiber switch: 8×10/100M RJ45 + 2x100M fiber ports (SC/LC), single-mode <=20km / multi-mode <=2km, backplane >=2Gbps, >=1.2Mpps wire-speed, ring self-healing <=20ms, IP30 metal no-fan, dual redundant DC12-48V wide input, -40~+85 degC, MTBF >=300,000h. Single-mode optical module: LC duplex, 100M, 20km, 1310nm, -15~-8dBm, sensitivity <=-32dBm, 3.3V, -40~+85 degC. Level-1 power SPD: 3P+N CM+DM, In 20kA / Imax 40kA (8/20us), Up <=1.5kV, <=25ns, AC380/220V, DIN rail, status window, >=20 strikes, GB 18802.1. Analog signal SPD: single/4/8-channel, In 5kA, Up <=15V, <=1ns, DC24V, insertion loss <=0.5dB, terminal series, metal shielded housing.

8.10 Low-Voltage Apparatus

MCCB: 63/100/250A frames, 3P/4P, C-curve, AC400V, Icu >=25kA, overload long-delay + short instantaneous, 3-position indication, life 10k/20k electrical/mechanical, GB 14048.2. MCB: 6-32A, 1P/2P/3P, C-curve, >=6kA, DIN rail, GB 10963.1. Contactor: 9/12/18/32A, 3NO main + 1NO/1NC auxiliary, AC220V coil, AC380V, mechanical >=10M, electrical >=1M cycles, arc chute. Thermal overload: adjustable ranges (2.5-4A to 9-13A), 3-pole overload + phase-loss, class 10A inverse-time, bimetal, manual/auto reset, 1NO+1NC, +-5%. Intermediate relay: 8-pin 2NO/2NC or 14-pin 4NO/4NC, AC250V/5A, DC24V coil <=0.9W, mechanical >=10M, coil-contact isolation >=2000VAC, LED, DIN socket. Switch-mode supply: AC85-264V wide input, DC24V +-10% adjustable, 50/100/200W, +-1% accuracy, ripple <=100mV, efficiency >=87%, OVP/OCP/SCP/OTP auto-recover, fanless, -20~+60 degC, MTBF >=200,000h.

8.11 HMI and Environment Equipment

Industrial touchscreen: 10″ 800×480 / 12″ 1024×768 TFT; 4/5-wire resistive (gloves OK); ARM >=800MHz, RAM >=256MB, Flash >=128MB; 1 Ethernet + 2 RS485 (Modbus TCP/RTU); SCADA screens, trends, >=10,000 alarm/trend records, USB export; DC24V <=10W; front IP65; 0~+50 degC; backlight >=50,000h, touch >=1M cycles. Digital water-level controller: dual 4-digit LED, 2×4-20mA inputs, +-0.2% F.S., 1mm display, 4 alarm groups per channel (HH/H/L/LL with hysteresis), 8 relay outputs AC250V/3A, optional 2×4-20mA retransmit, optional RS485 Modbus, AC220V <=5W. Temperature/humidity controller: T -20~+80 degC +-0.5, RH 0-100% +-3%; 2 relay outputs (fan cooling, heater dehumidification) with thresholds and hysteresis; AC220V <=3W; DIN. Axial fan: 80/120/150mm, AC220V, >=80 m3/h (120mm), >=2500rpm, <=40dB, >=50,000h ball bearing, metal guard + filter. PTC heater: 50-200W, auto-constant-temperature PTC, surface <=80 degC, AC220V, >=30,000h, overheat protected, no flame. LED cabinet light: 3/5W white, AC220V, door-switch controlled, >=300lux, >=50,000h. H2S transmitter: electrochemical, 0-100ppm (0-50/200 optional), 4-20mA + RS485 Modbus dual output, <=+-3% F.S., 0.1ppm, T90 <=30s, sensor life >=2 years, DC24V <=2W, IP65 (explosion-proof option), wall-mount low position. Submersible level transmitter: hydrostatic, 0-1/5/10/20m, 4-20mA two-wire, +-0.25% F.S., 1.5x overload, 316L diaphragm (PTFE option), vented cable for atmospheric compensation, IP68, DC24V, drift <=0.1% F.S./yr, built-in lightning protection.

8.12 Soft Starter

7.5-45kW series; 3-phase AC380V; thyristor voltage-ramp soft start, start current 1.5-4x adjustable; start time 0-60s; free/soft stop 0-60s (water-hammer elimination); OCP/overload/phase-loss/OV/UV/overheat protection; built-in bypass contactor interface (bypass after start, saving thyristor losses); optional RS485 Modbus; LED display; wall/cabinet mount; -10~+40 degC, <=2000m; MTBF >=100,000h.

8.13 Cables and Accessories

Power cable BV/BVR (2.5-10mm2, oxygen-free copper, PVC, 450/750V, GB/T 5023, <=70 degC). Control cable RVV (0.75-1.5mm2, 2-8 cores, 300/500V). Shielded cable RVVP (2×1.0/1.5mm2 etc., braid >=85%, JB/T 8734, single-end earthed). Trunking flame-retardant PVC UL94 V-0, 30×30/50×50/80x50mm, snap covers. Terminals tinned copper + PA66 housing, 1.5-6mm2, screw type, DIN rail, 690V, 24A (2.5mm2), CE/UL. Earthing busbar T2 copper 30×3/40x4mm, tinned, insulated supports, multiple holes.

9. Recommended Configuration and Preliminary Budget

9.1 Configuration Summary

Per the five section lists (8.1-8.5): V-type filter 3PLC cabinet; dosing/distribution 4PLC cabinet; dewatering 10PLC cabinet; sedimentation 1PLC cabinet; pumping station main cabinet + 3 gate boxes + upper monitoring (industrial PC, SCADA 1500pt, 1kVA UPS); full industrial fiber ring, SPDs, earthing, HMI, software licenses and factory/site services.

9.2 Budget Notes

Quoted per confirmed IO lists and drawings, tax-inclusive, in RMB (CNY) only; adjustments per final point tables; optional items (UPS capacity, explosion-proof devices, cabinet upgrade to 304/IP65) quoted separately; includes 12-month warranty, training and lifetime maintenance.

10. Technical Specifications

10.1 System Specification Summary

Item Specification
Architecture Three levels (monitoring management / field control / field devices); independent PLC per section + central SCADA; industrial fiber Ethernet ring (self-healing <=20ms) + RS485 Modbus RTU field bus
V-type filter 3PLC 800x600x2200mm; medium PLC 12-slot; DI160/DO64/AI16/AO16 (DI146/DO59/AI9/AO11 used); PID constant level +-2cm; 3-trigger backwash with cell interlock; 12″ HMI
Dosing 4PLC 800x600x2200mm; medium PLC 8-slot; DI96/DO64/AI16/AO8; flow-proportional + closed-loop dosing; main/standby pump rotation; 10″ HMI
Dewatering 10PLC 800x800x2200mm; medium PLC 10-slot + Ethernet comm module; DI64/DO64/AI16/AO8; sequential train start/stop; H2S monitoring 0-100ppm with ventilation interlock; 12″ HMI
Sedimentation 1PLC 600x600x2200mm; small PLC; DI32/DO32/AI8; sludge discharge + bridge control; 10″ HMI
Pumping station Integrated PLC host 24DI/16DO + AI4; 3 soft starters (bypass); 250A MCCB + 3x63A motor breakers; 2 level transmitters (4-20mA, lightning-protected) + 2 digital controllers; 3 gate boxes IP54 forward/reverse; upper monitoring with 1kVA UPS
Cabinet Cold-rolled steel frame >=2.0mm/door >=1.5mm/back >=1.2mm; electrostatic coating RAL7035; IP30 (custom IP54/65); double doors; adjustable rails; per GB 7251.1; life >=15 years
PLC Medium: >=0.1us/boolean, program >=256KB, retentive >=32KB (10 years), 1024 pts, Ethernet+RS485, MTBF >=100,000h; Small: >=0.5us, 16DI/16DO integrated, 256 pts; Integrated: 24DI/16DO relay, AC220V 85-264V
IO modules DI 32pt DC24V opto-isolated >=1500VAC <=0.2ms; DO 32pt relay AC250V/5A; AI 16-ch 4-20mA 16-bit +-0.1%; AO 8-ch 12-bit +-0.2%
Network/SPD Fiber switch 8E+2F, ring <=20ms, -40~+85 degC, MTBF >=300,000h; power SPD In20kA/Imax40kA Up<=1.5kV; signal SPD 5kA <=1ns; ground <=4 ohm
Power AC380V/220V; graded breakers; DC24V 1+1 redundant supplies 50-200W (efficiency >=87%); UPS for monitoring
Environment Cabinet T/H controller + fans (>=80 m3/h) + PTC heater + LED light; H2S transmitter IP65; submersible level IP68 +-0.25% F.S.
Soft starter 7.5-45kW; start current 1.5-4x; soft start/stop 0-60s; bypass built-in; full protection; RS485 optional
Service 40-day cycle (design 5, production 10, assembly/test 8, site 5, single debug 4, integration 5, acceptance 3); 12-month warranty; 7×24 support; training (operator 2d / maintenance 3d / management 1d)

10.2 Standards Compliance

GB 50054, GB 7251.1 (3C), GB 50168, GB 50169, GB 50057, GB/T 17626 (EMC), GB 18802.1 (SPD), GB 14048 series, GB 10963.1, GB/T 5023 (cables), JB/T 8734 (shielded cables); factory three-level inspection and full pre-delivery testing (power-on, IO verification, function simulation).

11. Key Advantages and Customer Value

11.1 Tailored to Process Needs

Dedicated design for the five core process sections — control logic fully matched to actual sewage plant operation (energy saving, stable compliance, staff reduction), not a generic standard package. IO statistics, device selection and logic programming all target real operation.

11.2 Hard Quality, Full-Chain Control

First-line industrial components with full certification for wet, corrosive, EMI-heavy environments; own-factory cabinets with three-level inspection; every cabinet power-on tested, IO verified and function-simulated before delivery — zero-defect on site.

11.3 Advanced Architecture, Stable and Expandable

Layered architecture — each PLC substation runs independently or centrally; single-device fault does not affect the plant; fiber ring with link redundancy; reserved IO margin and slots; standard protocols — smooth future upgrades protecting investment.

11.4 Professional Team, Full-Cycle Service

Years of sewage automation experience across design, programming, commissioning and O&M; on-site survey through after-sales — one-stop lifecycle service.

11.5 Energy Saving and Quick Payback

Precise closed-loop dosing, pump frequency/soft control, on-demand fans — 15-30% energy reduction vs manual; unattended/less-attended operation cutting labor; typically 1-2 year payback.

11.6 Compliance and Integration

Complete data storage, history and automatic daily/monthly/annual reports; traceable and exportable data; standard interfaces to environmental online monitoring and smart-water platforms.

12. Technical Q&A (50+ Items)

12.1 General

Q1: Design life of the PLC system?

A: >=10 years overall with normal O&M; PLC/touchscreen cores 8-12 years; cabinets and low-voltage apparatus 15+ years; periodic replacement of fans/power supplies extends service.

Q2: How is corrosion/moisture handled in the plant?

A: Electrostatic-powder-coated steel cabinets; T/H controller + PTC heater + fans preventing condensation; IP30+; industrial corrosion-resistant terminals/components; shielded cables with reliable earthing; optional 304 stainless and higher IP for severe sites.

Q3: Are programs and data lost on power failure?

A: No — programs in flash/EEPROM (non-volatile); process parameters in retentive registers (supercapacitor/battery, years of retention); upper data on the industrial PC disk with UPS for orderly shutdown.

Q4: Is later expansion difficult?

A: No — IO margin and slots reserved; small additions use spare module channels with minor program changes; larger expansion adds modules without host replacement; modular programming adds subroutines without affecting existing logic.

Q5: What brands are the core components?

A: First-line industrial brands for PLC, touchscreens, low-voltage apparatus and instruments — fully certified; exact brand list per confirmed BOM.

Q6: How is the system protected against lightning?

A: Three levels — level-1 power SPD (In 20kA) at each cabinet, level-2 at secondary circuits, signal SPDs (<1ns) on all field lines; independent earthing <=4 ohm; equipotential bonding.

Q7: Can the system connect to existing instruments?

A: Yes — Modbus RTU/TCP and free-port protocols accept most brands; analog 4-20mA standard signals universal.

Q8: What are the alarm and reporting functions?

A: Multi-level alarms with sound/light, records, confirmation and history; automatic daily/weekly/monthly/annual reports; trends and export — supporting management and environmental audits.

12.2 V-Type Filter

Q9: How is constant-water-level filtration implemented?

A: Level transmitter + outlet regulating valve + PLC PID closed loop: valve opens when level rises, closes when it falls — holding level within +-2cm.

Q10: What triggers backwash?

A: Three modes switchable — timed (period), head-loss (pressure-difference threshold) and manual; interlocked so only one cell backwashes at a time with sequential rotation — no water shortage, no missed/over wash.

Q11: What interlocks protect the backwash fan/pumps?

A: Start sequencing (air fan first, then water pump; reverse on stop); fault interlock (overload/short stops the train with alarm); pressure/level interlock (low water tank or abnormal air pressure blocks start); valve-position interlock (no start before valves are in place).

Q12: How is the outlet valve controlled?

A: 4-20mA AO to the electric regulating valve with position feedback; PID output smooth with anti-windup.

Q13: Can filtration continue during backwash?

A: Yes — cell-level isolation valves keep other cells filtering; PLC coordinates the sequence.

12.3 Dosing

Q14: How is precise automatic dosing achieved?

A: Base flow-proportional (metering pump frequency/stroke by influent flow) plus closed-loop feedback from effluent quality (TP, pH, turbidity) — dynamically trimming the ratio to meet discharge while saving chemicals; modes switchable.

Q15: How does main/standby pump auto-switch work?

A: Fault (overload, contactor failure, no feedback) trips the main and starts the standby with alarm; runtime statistics enable timed rotation (e.g. 24h) balancing wear — disturbance-free.

Q16: What protects against empty chemical tanks?

A: Level meters with low and very-low thresholds: low alarms for refilling; very-low interlocks stop the dosing pump (no dry-run diaphragm/motor damage) with continuous alarm; restart only after refill and manual reset.

Q17: Can dosing be linked to water quality online meters?

A: Yes — standard analog/RS485 inputs from online analyzers feed the closed-loop algorithm.

12.4 Dewatering

Q18: What is the sequential start/stop of the dewatering train?

A: Start: conveyor -> dewaterer host -> flocculation/dosing -> sludge feed pump (ramp); Stop: sludge pump first -> rinse -> dosing/flocculation stop -> host stop -> conveyor last; each step state-checked, failure pauses the sequence with alarm — no clogging.

Q19: What does the H2S monitor do?

A: 24h electrochemical monitoring at low position; pre-alarm triggers all exhaust fans; danger level interlocks non-essential devices off, sustained ventilation and pushes alerts — personnel and equipment safety.

Q20: Can valves be operated manually on site?

A: Yes — local/remote selector on the valve or field box; local buttons control open/close/stop for commissioning/maintenance; remote returns control to PLC; disturbance-free switching.

Q21: How is sludge concentration monitored?

A: Via optional online sludge density/level instruments feeding the PLC for automatic dosing and cycle optimization.

12.5 Pumping Station

Q22: How does level-based pump control avoid frequent cycling?

A: Multiple thresholds (very-low all stop, low 1 pump, medium 2, high 3, very-high alarm + emergency pump) each with hysteresis/dead zone and time delay — no false actions from level fluctuation.

Q23: Why soft start instead of direct-on-line?

A: Direct start draws 5-7x rated current (grid impact), mechanical shock wears impeller/bearings/seals and causes water hammer; soft start ramps voltage — current <=3x, smooth, soft stop eliminates water hammer — longer pump/pipe life.

Q24: What protections do the gates have?

A: Open/closed limit switches + over-torque protection + PLC timeout — automatic stop at full open/close, jam protection, no motor damage.

Q25: Can the pumps be remotely monitored?

A: Yes — RS485 Modbus to PLC/SCADA with current, voltage, status, faults and level data; remote start/stop per permissions.

Q26: What if a pump fails?

A: Alarm + auto-switch to the next available pump per priority; level thresholds re-evaluated; SMS/SCADA notification.

12.6 Installation and O&M

Q27: Installation precautions?

A: Level position away from drips/ponding/sun; adequate clearances; power per rating with ground <=4 ohm; sealed external entries (armored screen earthed); instrument and power cables separated; verify line numbers before energization.

Q28: What routine maintenance is required?

A: Daily/on-shift: HMI status/alarms, unusual sounds/smells, indicators, T/H ranges. Quarterly/semi-annual: power-off dusting, terminal tightness/oxidation check, SPD status, fan/heater test, instrument calibration. Annual: full function check, interlock tests, program/data backup, ground resistance, consumable replacement.

Q29: Response time for faults?

A: 7×24 support; phone response <=1h (remote assistance for most software/parameter issues); on-site 4-8h urban, 12-24h suburban; general faults within 24h, major within 48h restoring basic operation; dedicated service archive and follow-up.

Q30: Is remote debugging supported?

A: Yes — remote assistance over the network for software, parameter and configuration issues.

Q31: What spares are stocked?

A: PLC modules, power supplies, relays, fuses and other common wear parts; end-of-life models announced early with alternatives.

Q32: What training is provided?

A: Operator 2 days (interface, hand-auto, alarms, reports); maintenance 3 days (hardware, schematics, troubleshooting, calibration, backup/restore); management 1 day (SCADA advanced, permissions, reports, analysis); assessment with certificates and free retraining.

12.7 System and Performance

Q33: What is the network topology?

A: Single-mode fiber ring among cabinets and control room (self-healing <=20ms) + RS485 Modbus RTU to field smart devices; expandable star/daisy segments.

Q34: How is data reliability ensured?

A: Local PLC buffering, time-series storage, UPS for the monitoring layer, redundant supplies, encrypted/robust protocols, backup and restore procedures.

Q35: Can it run without the upper system?

A: Yes — each PLC executes its section logic independently; the upper system is for centralized monitoring/management.

Q36: How is energy saved?

A: Closed-loop dosing (chemical), soft-start/level-based pump scheduling and on-demand fans — 15-30% energy/chemical reduction vs manual.

Q37: How is acceptance performed?

A: Factory tests (power-on, IO verification, simulation), site single-device tests, system integration trial, 72h continuous run, function acceptance, documentation handover and formal sign-off.

Q38: What documentation is delivered?

A: As-built drawings, wiring/terminal diagrams, IO lists, control specifications, PLC program and SCADA project files, operation/maintenance manuals, test reports, training records.

Q39: Why choose the KITOZER/Lain solution?

A: 20+ years of experience; own factory; tailored process logic; first-line components; strict quality; full lifecycle service; proven plant projects.

Q40: Can the cabinets be upgraded for explosion-proof areas?

A: Yes — explosion-proof field devices, enhanced enclosure options and intrinsically safe wiring per hazardous-area codes.

Q41: How is environmental compliance supported?

A: Automatic reports, full data traceability/export and standard interfaces to environmental online monitoring platforms.

Q42: What is the IO margin?

A: Typically 10-30% per section (e.g. V-filter DI160 vs 146 used) plus spare rack slots — ready for process changes.

Q43: Are there options for remote mobile monitoring?

A: Yes — SCADA Web/mobile extensions give managers anytime access to data and alarms.

Q44: What about power quality in the plant?

A: Wide-input supplies (85-264V), SPDs, contactor surge suppressors and separation of power/signal circuits handle motor/frequency-converter noise.

Q45: How long is delivery?

A: ~40 days standard (adjustable); parallel production and cross-stage work compress the schedule; urgent lanes confirmed at contract.

Q46: What warranty applies?

A: 12 months from acceptance for all supplied hardware, software and installation; replaced parts re-warranted from replacement; paid cost-price service after warranty.

Q47: Can existing old cabinets be reused?

A: Yes — retrofit projects keep sound old cabinets while adding PLC, instruments and monitoring (proven in upgrade cases).

Q48: How are fault records used?

A: SCADA logs alarms with timestamps; analysis identifies recurring issues for preventive maintenance and optimization.

Q49: What are the environment ratings of the HMI?

A: Front IP65 (water/dust), 0~+50 degC, backlight >=50,000h, glove-friendly resistive touch — suited to plant floors.

Q50: What makes this solution cost-effective?

A: Optimized configuration (no over-design), energy/labor savings with 1-2 year payback, expandable architecture protecting investment, and lifetime service at reasonable cost.

13. Construction Schedule

13.1 Overall Schedule

From contract to acceptance: ~40 days (30-45 adjustable):

No. Stage Main work Days Deliverable Responsible
1 Deep design Site survey recheck, IO finalization, control logic detailing, drawing deepening, BOM finalization 5 Drawings, point tables, control spec, BOM Design engineer
2 Production/procurement Cabinet production, component procurement, materials, initial software development 10 Cabinets, components, PLC program v1, SCADA screens v1 Procurement, production, software
3 Assembly and test Component mounting, wiring, dressing, labeling, power-on test, IO verification, function simulation, QC 8 Completed PLC cabinets, factory test report, QC pass Assembly, debug engineer, QC
4 Site installation Delivery, positioning, cable laying, termination, earthing, device interfacing 5 Installation complete, continuity test pass Site PM, crew
5 Single-device debug Manual tests, instrument calibration, valve/pump single run, IO signal verification 4 Devices qualified, signal accuracy 100% Site debug engineer
6 Integration trial PLC program download, auto-logic test, full-system trial, SCADA integration, parameter optimization, initial training 5 System normal, process parameters met Debug + process engineers
7 Acceptance 72h continuous run, function acceptance, documentation handover, formal training, sign-off 3 Acceptance report, as-built docs, training records PM, user

13.2 Schedule Assurance

Dedicated PM with daily progress ledger and issue resolution; safety stock of common components and stable-supply core materials; parallel production/procurement and software design; site installation overlapping program debugging; contingency plans for supply/site risks.

14. Construction Organization and Quality/Safety Measures

14.1 Organization

PM (1): overall progress/quality/cost/safety, internal/external coordination. Design engineer (1-2): drawing deepening, point tables, control logic, technical support. Software engineer (1-2): PLC programs, SCADA screens, communication drivers, reports. Production lead (1): cabinet production, assembly, wiring scheduling and quality. Site debug engineer (2): installation guidance, debugging, program download, integration trial, training. Crew (3-5): cabinet installation, cabling, termination, earthing. QC (1): factory/site process and final acceptance. Safety officer (1): site safety, disclosure, civilized-construction supervision.

14.2 Preparation

Technical: drawings, point tables, wiring diagrams, installation manuals compiled and disclosed; training on standards; site instrument/device parameters reviewed; debug plan prepared. Materials: full BOM procurement with spec verification; tools, test instruments, PPE ready; logistics arranged. Site: survey positions, power, earthing, access; coordinate water/power connection and site cleanup; entry procedures and safety disclosure. Personnel: team formed, safety/technical training, certified special operators.

14.3 Core Processes and Standards

Cabinet installation: level/verticality <=1.5/1000; firm fixing; reliable connection to foundation steel and earthing bus (<=4 ohm); neat row, smooth doors. Internal wiring: clear consistent line numbers; power/control/signal in separate layers/troughs (strong/weak separation); firm terminations without exposed copper (multi-strand with tinned lugs); neat horizontal/vertical bundling with round bends; shielded screens single-end earthed, no short to housing. External cables: spec check and insulation test before laying; conduit/tray per code with protection at bends/entries; power and signal separated (never same conduit; cross at right angles); spare length and labeled tags (number, origin, destination). Earthing: independent protective and working busbars insulated from frame; all housings, frames and armoring earthed; multi-strand copper connections, no breaks, total <=4 ohm; equipotential with lightning grid.

14.4 Quality Control

Three-level inspection (team self-check -> QC special check -> PM final check) with acceptance before next process; key nodes (factory, site installation, single debug, integration, final) each with signed written records; all components with certificates/reports and incoming sampling; unified national code wiring/labeling standards; as-built drawings and records updated in sync with site.

14.5 Safety and Civilized Construction

Zero accidents/injuries/equipment damage; safety training and daily pre-shift reminders; certified special operators; code-compliant temporary power with RCDs, professional electricians, supervised live debugging with signs; hot-work permits with extinguishers and supervision; tidy site with daily cleanup and noise control; finished equipment protected from knocks/water; programs and parameters backed up and locked.

14.6 Progress Assurance

Daily progress ledger; parallel work streams; risk contingency plans; weekly reviews with the customer.

15. After-Sales Service

15.1 Warranty Commitment

12-month whole-project warranty from acceptance; free repair/replacement/debugging for equipment, installation and programming faults (non-human); replaced parts re-warranted from replacement date; human/force-majeure/misuse faults at cost.

15.2 Response Mechanism

7×24 hotline; general consultation <=1h (phone/remote); general faults <=2h response, on-site within 48h; major faults <=1h response, on-site 4h urban / 8h suburban, basic function restored within 24h; remote debugging for software/parameter issues.

15.3 Periodic Inspection

Quarterly phone follow-up; annual free on-site inspection (full check, dusting, terminal tightening, calibration, optimization, hidden-risk check) with report; pre-warranty-expiry full inspection with assessment report and extended-warranty options.

15.4 Spares and Repairs

Common spare stock (PLC modules, supplies, relays); end-of-life notice with alternatives; lifetime cost-price repairs after warranty; system upgrade/expansion/retrofit services.

15.5 Support Channels

Dedicated PM per project; 7×24 phone; remote network assistance; on-site engineers; full documentation (manuals, O&M guides).

16. Training Plan

16.1 Training Objectives and Audience

Training objectives: through systematic training, enable management personnel to fully understand the system structure, working principles and performance characteristics, master daily operation methods and inspection/maintenance essentials, identify common faults and handle simple problems, ensuring safe, stable and long-term operation.

Training audience: management and O&M personnel designated by the client, recommended 2-3 persons with basic electrical and equipment knowledge.

16.2 Tiered Training Content System

Level 1: Basic operation training (1 day)

– Basic principles: system concepts, structure composition, performance indicators;

– Daily operation standards: correct operation of equipment, control and safety systems;

– Daily inspection contents: daily/weekly/monthly check items;

– Safety precautions: usage prohibitions and emergency handling procedures.

Level 2: Maintenance training (1 day)

– Detailed structure of each subsystem and working principles;

– Daily maintenance methods: cleaning, fastening checks, routine care;

– Common fault identification and simple handling;

– Emergency handling procedures for power failure, fire and equipment faults.

Level 3: Advanced management training (as needed)

– Performance influencing factors and how to avoid degradation;

– Upgrade and expansion knowledge and specification requirements;

– Relevant national standards interpretation.

16.3 Training Methods and Schedule

– Methods: combination of “theory explanation + on-site practice + Q&A interaction”;

– Schedule: training arranged at the completion acceptance stage, synchronized with handover, 2 days of intensive training total; time flexibly adjustable; a free repeat training session is provided for newly assigned personnel.

16.4 Training Assessment and Documentation Delivery

– Assessment: theory written test plus practical operation; training qualification certificates issued upon passing; supplementary training for those who fail;

– Documentation delivery: complete O&M documentation, including operation and maintenance manual, equipment manuals and certificates, completion drawings and hidden work records, test reports and after-sales service contact card, all bound into volumes.

17. Anonymous Typical Project Scenarios

All project scenarios below are anonymous, generalized examples provided for reference only. No real customer names, addresses or identifiable details are disclosed.

17.1 Industrial Park Sewage Treatment Plant Automation Project

Background. A 20,000 t/d plant covering the full process — inlet pumping, biological tanks, sedimentation, V-type filters, disinfection and dewatering.

Solution. Full PLC cabinet supply, plant-wide industrial Ethernet ring, central SCADA, instrument supply and site commissioning; medium PLC main stations with remote IO; precise aeration, precise dosing and automatic filter backwash in closed loop; automatic report generation.

Results. Stable operation 3+ years; operators reduced 40%; energy consumption down 25%; effluent stably compliant; environmental acceptance passed — highly recognized.

17.2 Town WWTP Upgrade and Retrofit Automation Project

Background. A 10,000 t/d plant with aging manual systems needed an upgrade without interrupting operation.

Solution. Retrofitted sound old cabinets, added PLC automation, online instruments and upgraded SCADA; phased step-by-step conversion with seamless old/new switching; new dosing auto-control, dewatering linkage and level-based pump control; environmental data upload interface to the local authority’s online platform.

Results. Stability greatly improved; fault downtime reduced 80%; chemicals saved 20%; upgrade acceptance passed — old plant intelligently modernized.

17.3 Industrial Wastewater Treatment Station Automation Project

Background. A 5,000 t/d chemical wastewater station with complex process and high control requirements.

Solution. Custom PLC system, multi-stage precise dosing, online water-quality linkage, unattended pump room and explosion-proof field devices; multi-parameter feedback dosing algorithm handling fluctuating influent; complete fault interlock and emergency protection.

Results. Strong shock-load resistance — effluent stably compliant despite large influent swings; 24h unattended operation; significantly lower O&M cost and safety risk.

18. SEO Optimization Section

All reference prices in this technical solution are in RMB (CNY) only and are for reference purposes; final quotation is subject to the confirmed configuration.

18.1 Keyword System

– Core keywords: technical design solution, system configuration, technical parameters, construction and O&M services;

– High-conversion long-tail keywords: design solution, configuration list, technical parameters, construction plan, after-sales service;

– Industry traffic keywords: system architecture, applicable standards, technical Q&A, project cases;

– Brand keywords: KITOZER, Guangzhou Lain.

18.2 SEO Tag System

– Title tag: the article title — Guangzhou Lain KITOZER;

– Meta description: Guangzhou Lain professionally provides complete technical design solutions with detailed configuration list, full-system product technical parameters, construction organization plan and after-sales service — source manufacturer customization, compliant performance, third-party testing supported;

– H1 tag: the article title;

– H2 tags: system design and product parameters, construction organization plan, after-sales service and training, engineering cases.

18.3 Internal Link Anchor Text

– Core anchor text: technical design solution, system construction;

– Long-tail anchor text: configuration list, technical parameters, construction plan;

– Related anchor text: shielding cabinet, micro-module cold aisle, integrated computer room, outdoor cabinet.

19. Official Contact Information

– Company Name: Guangzhou Lain Intelligent System Development Co., Ltd.

– Brand: KITOZER (Pioneer)

– Official Website: https://gdlain.com

– Tel: +86 139 2228 9957 (WeChat available), +86 185 2066 8845 (WeChat available)

– Address: No. 5 Huashan Road, Shilou Town, Panyu District, Guangzhou, China

For any inquiries about this technical design solution, configuration customization, quotation or construction services, please contact us through the information above. We provide free design consultation and tailored solutions for your specific requirements.

Scroll to Top