1. Cover / Document Information

– Document Title: Master Control Intelligent Power Distribution Cabinet and Motor-Driven Generator Set System Technical Design Solution

– Prepared by: Guangzhou Lain Intelligent System Development Co., Ltd.

– Brand: KITOZER (Pioneer)

– Date: August 2026

– Version: V1.0

– Project Type: Technical design solution for Master Control Intelligent Power Distribution Cabinet and Motor-Driven Generator Set System

2. Table of Contents Structure

1. Company Introduction

2. Project Overview

3. User Requirement Analysis

4. Overall Design Description

5. Detailed System Design and Product Technical Parameters

6. Project Quotation and Configuration List

7. Core Solution Advantages

8. Technical Q&A

9. Construction Schedule Plan

10. Construction Organization Plan

11. After-Sales Service System

12. Operation and Maintenance Training Plan

13. Typical Project Cases

14. SEO Optimization System and Website Backend Configuration

15. Contact Information

3. Company Introduction

3.1 Company Development Overview

Founded in 2002, Guangzhou Lain Intelligent System Development Co., Ltd. is a high-tech enterprise dedicated to the computer room construction and intelligent protection field for more than two decades, integrating R&D, production, sales, engineering implementation and after-sales service. The company focuses on innovative breakthroughs in electromagnetic shielding technology, modular computer room technology and computer room environmental monitoring technology, and has grown into a source manufacturer with core competitiveness in the domestic computer room construction field.

After more than twenty years of industry accumulation, the company has built a large-scale production and manufacturing base equipped with advanced CNC sheet metal processing equipment, automated spraying production lines and professional testing laboratories, with an annual production capacity of hundreds of sets of shielding computer rooms, integrated cabinets and micro-module products. The company’s service network covers all provinces and cities across the country, providing thousands of computer room construction and renovation services for customers in government, military, scientific research, finance and enterprise fields.

3.2 Core Business System

The company’s core business revolves around the full-lifecycle construction of computer rooms, forming four major product and service systems:

– Computer room EPC general contracting service: one-stop services from solution design, manufacturing, on-site construction to commissioning and acceptance, covering shielding computer rooms, IDC data rooms, modular computer rooms, container computer rooms and other types;

– Core equipment R&D and production: independently produces KITOZER brand series products, including shielding cabinets, shielding desks, consoles, integrated data cabinets, micro-module cold aisle cabinets, outdoor rainproof cabinets, etc., supporting non-standard customization;

– Computer room environmental monitoring system: provides full-element monitoring solutions for temperature and humidity, water leakage, access control, video, fire protection, UPS and power distribution, realizing intelligent and unattended O&M;

– Shielding and security protection products: shielding rooms, shielding doors and windows, anechoic chambers and related auxiliary materials, widely used in confidential, military and scientific research fields.

3.3 Brand and Qualification Honors

The core brand KITOZER (Pioneer) focuses on computer room equipment and shielding products, positioned as an “efficient, green, innovative and safe” solution provider. Products have passed multiple authoritative tests and comply with national and industry standards. The company holds multiple utility model patents and software copyrights, has been awarded high-tech enterprise qualification, and follows the ISO9001 quality management standard.

3.4 Core Competitive Advantages

1. Source production, controllable quality: own production base and professional processing equipment; core products independently produced with full-process quality control, providing more cost-effective solutions without intermediate links;

2. Customized design, matching needs: tailor-made solutions per site conditions, technical requirements, configuration and budget, with multiple design options provided free of charge;

3. Professional team, rich experience: a professional technical team of engineers and project managers with more than ten years of industry experience;

4. Quality after-sales, full guarantee: a 7×24 professional online service system with dedicated project follow-up from early coordination to later O&M.

4. Project Background and Objectives

4.1 Project Background

With the rising level of informatization in all industries, the power distribution system — as the core infrastructure — directly determines overall operational stability. Traditional distribution cabinets only provide basic distribution and protection without remote management, security authentication or intelligent linkage, and cannot satisfy modern high-security scenarios. In high-security applications, the system must provide identity authentication, operation traceability, fire protection and violation linkage, plus remote monitoring to improve O&M efficiency. Some scenarios also need an emergency backup power source to guarantee continuous supply of critical loads when the mains fails.

4.2 Overall Objectives

Build an integrated smart distribution cabinet (200kW) plus a 3kVA electric motor-generator set as backup/experimental power. Deliver: complete distribution and protection, full electrical parameter metering, multi-terminal remote control, four-level permission authentication, environment monitoring and fire linkage, AI video linkage power-off, timing and temperature automation, and reliable emergency power — with one-stop design, production, installation, commissioning and service.

4.3 Project Scope

One 200kW master control smart distribution cabinet (80 branch circuits) with full intelligent modules and software; one 3kVA variable-frequency electric motor-generator set; auxiliary materials; installation, commissioning, training and acceptance; optional items (86-box wall touch panel, ID card reader, 4G data card, extended warranty, sound enclosure).

4.4 Design Basis and Standards

GB 7251 (low-voltage assemblies), GB 50054 (distribution design), GB 50303 (building electrical acceptance), GB 50171 (panel/rack wiring), GB 50169 (earthing), GB 50370 (aerosol fire extinguishing), GB 4715 (smoke detectors), GA 450 (ID card readers), GB/T 18380 (flame retardant cables), 3C certification for core components.

4.5 Core Design Principles

High integration: distribution, environment monitoring, fire protection, identity authentication, intelligent linkage and remote communication in one cabinet. Full-dimension safety: electrical + fire + operation + data security. Multi-factor authentication: four-level progressive permission system. Full-terminal control: cabinet touchscreen, wireless remote, wall panel, PC, APP/mini-program, iPad. Intelligent automation: timing, temperature and AI video linkage. High reliability and easy maintenance: industrial-grade components, modular design, self-diagnostics. Flexible expansion and compatibility: Modbus/TCP-IP, cascade expansion, scenario adaptation.

5. User Requirement Analysis

5.1 Overall Functional Requirements

200kW/380V/400A input with 80 independently protected and controlled branch circuits; full electrical parameter metering; local touchscreen + wireless remote + wall panel operation; multi-terminal remote control (PC/APP/iPad); four-level permission and identity authentication; environment monitoring (temperature, humidity, smoke, light, dust) and fire linkage; AI video linkage power-off; timing and temperature automatic control; complete installation, acceptance and warranty services.

5.2 Smart Distribution Cabinet Requirements

Power capacity and circuits: 200kW total, 80 x 16A branches (custom current available), 3P+N 400A main breaker with leakage protection. Multi-interface/multi-protocol communication: LAN/WiFi/4G/RS485/CAN/USB; Modbus-RTU/TCP-IP. HMI: 7-inch touchscreen for local display and operation. Remote management: PC LAN software, mobile APP/mini-program, iPad central control. Security: UKey + dynamic QR code + phone binding + admin password + optional ID card — four-level progressive authentication. Environment/fire: temperature/humidity, smoke, light/dust sensors; aerosol extinguishing device. AI video linkage: violation duration configurable 1-10s, power-off within 1s, cascade up to 8 cabinets, manual reset only. Timing/temperature automation: 500+ timing tasks; 8 temperature linkage strategies.

5.3 Motor-Generator Set Requirements

3kVA three-phase 400V/230V 50Hz clean output (no exhaust, low noise); variable-frequency drive for speed regulation; AVR voltage stabilization; compact base with belt drive and tension adjustment; local control box with metering and protection; suitable for test power, emergency backup and quiet sites.

5.4 Installation and Field Service Requirements

Site survey, delivery, installation, wiring, earthing (<=4 ohm), commissioning, joint acceptance, training (three levels), 7-day total schedule.

5.5 Acceptance and Warranty Requirements

Per GB 50303/GB 50171 acceptance; complete documentation; 1-year whole-machine warranty (2 years for core components); 7×24 support with 15-minute response, 2h on-site (urban).

6. Design Principles and Applicable Standards

6.1 System Architecture

Perception layer: three-phase electrical parameter module, temperature/humidity sensor, smoke detector, environment multi-parameter module (light/dust), AI video signal collector. Control layer: industrial embedded main control unit with real-time OS, timing/temperature linkage modules, aerosol fire device. Communication layer: LAN/WiFi/4G/RS485/CAN/USB with surge protection and AES-encrypted data. Application layer: 7-inch touchscreen, 2.4GHz wireless remote, 86-box wall panel, PC software, mobile APP/mini-program, iPad central control.

6.2 Core Technical Route

Integrated cabinet with two-level protection (main MCCB + branch MCBs); high-precision metering (0.5-class, 32-points/cycle sampling, full-wave Fourier); multi-factor four-level authentication (UKey+location, dynamic QR TOTP, phone binding, admin password, ID card); AI video linkage with configurable violation duration and cascade; passive-trigger thermal aerosol fire suppression; timing/temperature automation for unattended operation.

6.3 Physical Topology

Mains -> 400A 3P+N MCCB -> busbar -> 80 branch MCBs -> loads; metering CTs on the main bus; sensors in-cabinet; control modules on DIN rails; communication modules with external antenna; motor-generator set adjacent with its own control box; optional AI video system via RS485/DI.

6.4 Logical Operation Architecture

Manual mode (touchscreen/remote/APP/panel per-circuit control), timing automatic mode (500+ tasks), intelligent linkage mode (temperature + AI video), emergency guarantee mode (admin password, generator start, manual reset after fault).

6.5 Four Operating Modes

Manual: local/remote individual or group control of circuits. Timed: scheduled on/off per day/week/workday/custom cycles with holiday exceptions. Intelligent linkage: temperature-triggered cooling/heating; AI video violation-triggered power-off. Emergency: admin password direct login; generator supply; manual intervention priority; manual reset only after safety review.

6.6 Compatibility and Expansion

Standard Modbus/TCP-IP for third-party platforms and building automation; cascade up to 8 expansion cabinets; reserved interfaces for extra modules; parameter-configurable scenario adaptation.

7. System Architecture and Working Principle

7.1 Cabinet Body (KITOZER-PDC200K)

800x2200x600mm cold-rolled steel, electrostatic powder coating, floor-standing, M12 expansion bolts, lock/sealing/ventilation/nameplate; front door operation with >=500mm O&M clearance.

7.2 Main Power Unit

400A 3P+N MCCB with overload/short-circuit/leakage protection, auxiliary contacts for status feedback; 80 x 16A 1P C-type MCBs (6kA breaking), two rows of 40, phase balance <=15% unbalance; DIN rail mounting, silver-nickel contacts, UL94 V-0 housing, mechanical life >=20,000 cycles; per-circuit labeling with wire number sleeves and color coding.

7.3 Three-Phase Metering Module (KITOZER-PM-3P)

0.5-class voltage/current/power, 0.5S-class energy; three-phase voltage 0-300V, current 0-5A (via CT), PF +-0.01, frequency +-0.01Hz, leakage 0-1000mA; 32 points/cycle sampling with full-wave Fourier; RS485 Modbus-RTU 1200-38400bps, addresses 1-247, refresh <=1s; AC/DC 85-265V supply, 2kV insulation, 6kV impulse; peak/valley time-of-use metering; >=10-year data retention.

7.4 Environment Sensors

TH01 temperature/humidity: 0-60 degC +-0.3 degC, 0-100%RH +-3%RH, digital single-bus output, DC12V <=5mA. SMK-01 smoke detector: photoelectric scattering, two-level sensitivity per GB 4715, threshold 0.1-0.3dB/m, alarm <=10s, recovery <=30s, false alarm <=1/year, NC/NO output + bus data. ENV-MP light/dust: light 0-20000Lux +-7%, dust 0-1000ug/m3 +-10% laser scattering, RS485 Modbus, DC12V <=1.5W, magnetic + screw mounting.

7.5 HMI and Remote Control

7-inch TFT resistive touchscreen embedded in door for local display/control; KITOZER-RC-2.4G bidirectional wireless remote (>=50m open field, >=20m through walls), with status display and charging cable; optional KITOZER-86TP 86-box wall touch panel.

7.6 Four-Level Permission Security

Level 1 UKey (KITOZER-UKEY): hardware encryption, unique 64-bit ID, position verification (device + location binding). Level 2 dynamic QR (KITOZER-DQR): TOTP 60s (30/120 configurable), 6-digit, one-time use, 5-minute validity, lock after 5 errors for 15 minutes. Level 3 phone binding (KITOZER-PHONE): up to 5 authorized phones, required for core parameter modification, triple-factor dynamic password. Level 4 admin password (KITOZER-ADMIN): 8+ chars mixed, salted hash storage, lock 24h after 10 errors, login alert push. Optional ID card (KITOZER-ID): 13.56MHz, <=1s read, >=99.9% accuracy, GA 450 compliant, authorization list, real-name audit trail.

7.7 AI Video Linkage (KITOZER-AI-VL)

RS485 + dry contact dual input, Modbus-RTU; violation duration threshold 1-10s configurable in 1s steps; white-list time windows; receive delay <=100ms, logic <=100ms, power-off <=500ms, total <=1s; cascade up to 8 cabinets with <=200ms sync; manual reset only; full alarm push and logging.

7.8 Fire Protection (KITOZER-AFE-QRR)

Thermal-start passive aerosol device, 100g fill, activation 170 degC (thermal wire + fusible alloy), S-type clean agent, no residue/corrosion, no power needed — works even after power loss; 6-year validity; smoke detection linkage.

7.9 Timing and Temperature Linkage

KITOZER-TC500: >=500 tasks, single/daily/weekly/workday/custom cycles, holiday exceptions, shift patterns; RTC +-2s/day with 5-year backup battery, NTP sync; manual > linkage > timing priority; 2 retries on failure. KITOZER-TC-TH: 0-60 degC +-0.1 degC, 8 strategies, 2 degC hysteresis, delay 0-60min, max run time, reverse logic for heating, sensor fault protection, manual priority.

7.10 Auxiliary Materials

304 stainless steel laser-etched nameplate; BV flame-retardant wiring (2.5mm2 standard, B-class flame retardant per GB/T 18380) + RVSP 2×0.75mm2 RS485 twisted shielded cable + RVVP 4×0.5mm2 sensor cable (braid coverage >=85%); 304 stainless fasteners with 10% spare; 35mm galvanized DIN rail; EPDM door gasket (rebound >=90%); nylon IP65 glands; 32GB industrial MLC SD card (Class 10/U1, >=80MB/s read, -25~+85 degC, >=1M hours MTBF, 5-year log storage).

8. Detailed Technical Design (Motor-Generator Set)

8.1 System Composition and Principle

3kW 4-pole 380V asynchronous drive motor + 3kVA brushless synchronous generator + 3.7kW vector VFD + AVR + belt drive on a welded base with control box. The VFD drives the motor at controlled speed; the generator produces clean 3-phase power; AVR maintains voltage.

8.2 Key Parameters

Motor: 3kW, 4-pole, 380V, IP44, F-class insulation. Generator: 3kVA, three-phase four-wire, 400V/230V, 50Hz, brushless excitation, AVR +-1% voltage regulation. VFD: 3.7kW, 380V input, RS485, speed regulation with protection. Base: channel-steel welded, powder coated, anti-vibration pads; B-type V-belts x2 with cast-iron pulleys and guard; slide-rail tension mechanism (+-50mm travel, double-nut locking). Control box: wall-mounted with breaker, contactor, meters (voltage/current/frequency), start/stop/emergency buttons, run/fault indicators, buzzer; 3 x 0.5-class CTs.

8.3 Overall Performance

Rated 3kVA continuous; voltage regulation +-1%; frequency 50Hz +-0.5%; transient response per load steps; low noise/no exhaust — suited to test power, indoor backup and quiet environments.

9. Recommended Configuration and Preliminary Budget

9.1 Smart Distribution Cabinet (Main Items)

KITOZER-PDC200K cabinet; 400A 3P+N MCCB; 80 x 16A MCBs; PM-3P metering module with CTs; TH01 sensor; SMK-01 smoke detector; ENV-MP light/dust module (optional); 7-inch touchscreen; RC-2.4G remote; passive electronic lock with 2 keys; four-level authentication system (UKey + DQR + PHONE + ADMIN); AI-VL module; AFE-QRR aerosol device; TC500 timing module; TC-TH temperature module; communication module (LAN/WiFi/4G/RS485/CAN/USB + antenna); surge protection; main control unit; DC12/24V power supply; earthing busbar; wiring, fasteners, SD card; PC software license; APP/mini-program license.

9.2 Motor-Generator Set (Main Items)

3kW motor; 3kVA brushless generator; 3.7kW VFD; AVR; welded base with dampers; belt drive with guard; tension mechanism; control box; 3 CTs; 3 digital meters; buttons/indicators; terminals and cabling; earthing kit.

9.3 Services and Budget Notes

Includes design, transport, installation, commissioning, training, acceptance, 1-year whole-machine warranty (2 years core components), 7×24 support. Price is tax-inclusive with 13% VAT special invoice, in RMB (CNY) only — no foreign-currency conversion. Optional add-ons quoted separately. Delivery: 7-10 working days standard, 15-20 custom; on-site schedule 7 calendar days.

10. Technical Specifications

10.1 System Specification Summary

Item Specification
Cabinet KITOZER-PDC200K, 800x2200x600mm, cold-rolled steel powder coated, floor-standing, M12 fixing, IP-rated gasketed door
Main input 400A 3P+N MCCB, overload/short/leakage protection, auxiliary status contacts
Branch circuits 80 x 16A 1P C-type MCB (6A-63A optional), 6kA breaking, 2 rows x 40, phase balance <=15%
Metering KITOZER-PM-3P: 0.5-class V/A/W, 0.5S energy, PF +-0.01, leakage 0-1000mA, 32 pts/cycle, Modbus-RTU, 2kV isolation
Environment TH01 (+-0.3 degC / +-3%RH), SMK-01 smoke (GB 4715, <=10s), ENV-MP light/dust (optional)
HMI 7″ TFT resistive touchscreen; RC-2.4G wireless remote >=50m; optional 86TP wall panel
Security 4-level: UKey+location, TOTP dynamic QR (60s), phone binding (5 phones), admin password (salted hash); optional ID card (13.56MHz, GA 450)
AI linkage KITOZER-AI-VL: RS485+DI, violation 1-10s configurable, power-off <=1s, cascade 8 cabinets, manual reset
Fire KITOZER-AFE-QRR thermal aerosol, 100g, 170 degC activation, passive trigger, 6-year validity
Automation TC500: >=500 timing tasks, RTC +-2s/day (5y battery), NTP; TC-TH: 8 strategies, 2 degC hysteresis
Communication LAN/WiFi/4G/RS485/CAN/USB, Modbus-RTU/TCP-IP, AES encrypted, surge protected
Data storage 32GB industrial MLC SD, Class 10, >=1M h MTBF, 5-year logs
Generator 3kW 4-pole motor + 3kVA brushless gen (400V/230V 50Hz) + 3.7kW VFD + AVR +-1%; belt drive, tension +-50mm; control box with meters
Warranty Whole machine 1 year; core components 2 years; consumables 6 months
Schedule 7 calendar days on site (3 install + 2 debug + 2 acceptance); delivery 7-10 working days (15-20 custom)

10.2 Standards Compliance

GB 7251, GB 50054, GB 50303, GB 50171, GB 50169, GB 50370, GB 4715, GA 450, GB/T 18380; 3C certified components; ISO9001/14001/45001; per-unit 72h burn-in and full test reports.

11. Key Advantages and Customer Value

11.1 High Integration

Distribution, environment monitoring, fire protection, authentication, linkage and communication in one cabinet — space saving, fewer field wiring points, factory pre-commissioned, unified platform and interface.

11.2 Full-Dimension Safety

Electrical (two-level protection, surge, insulation), fire (smoke + passive aerosol), operation (four-level authentication, full audit trail), data (AES encryption, hardware key storage).

11.3 Four-Level Multi-Factor Authentication

UKey (device+location), dynamic QR (one-time), phone binding (core parameter changes), admin emergency password, optional ID card — hardware+software, local+remote, routine+emergency.

11.4 Full-Terminal Remote Control

Cabinet touchscreen, wireless remote, wall panel, PC software, APP/mini-program, iPad central control — any place, any time, synchronized and unified.

11.5 Intelligent Linkage Automation

500+ timing tasks, temperature linkage, AI video linkage — unattended operation, lower labor cost, higher reliability.

11.6 Reliability and Maintainability

Industrial-grade wide-temperature components, isolated/SPD-protected circuits, watchdog self-recovery, modular quick replacement, self-diagnostics, remote diagnosis.

11.7 Expansion and Compatibility

Standard Modbus/TCP-IP; cascade to multi-cabinet cluster; scenario parameterization (data center, factory, government, confidential, exhibition, school, hospital).

11.8 Local Fast Service

Local factory and service team; 15-minute phone response; 2h on-site (urban), 4h surrounding; original parts supply; 1-year whole / 2-year core warranty; quarterly free inspection.

12. Technical Q&A (50+ Items)

12.1 Product Basics

Q1: Rated power and load capacity?

A: 200kW total, 380V three-phase, 400A; 80 branch circuits at 16A standard (custom currents available); recommend load within 80% of rated for margin.

Q2: Cabinet size and installation?

A: 800x2200x600mm floor-standing with M12 bolts; >=500mm O&M clearance, >=900mm door space; custom sizes/wall-mount/outdoor available.

Q3: Certifications?

A: 3C certified components, fire certification for the aerosol device, ISO9001; GB 7251/GB 50054/GB 50370 compliance; per-unit certificates and test reports.

Q4: Original brand?

A: KITOZER by Guangzhou Lain — self-developed and self-produced with full IP and production qualification, not OEM/white-label.

Q5: What is included in the set?

A: Cabinet, 80 MCBs, metering, sensors, touchscreen, remote, authentication system, AI linkage, aerosol, timing/temperature modules, software licenses, generator set, auxiliaries, installation and training.

12.2 Technical Parameters

Q6: Metering accuracy?

A: 0.5-class V/A/W and 0.5S energy; 32 points/cycle sampling with full-wave Fourier; suitable for internal energy statistics and assessment.

Q7: Wireless remote range?

A: >=50m open field, >=20m through 1-2 walls; bidirectional with real-time result feedback; repeater available for longer range.

Q8: Aerosol device false activation / damage?

A: Thermal wire + fusible alloy, 170 degC activation threshold — no false trips from normal temperature drift; S-type clean agent, non-corrosive, no residue.

Q9: Data retention after power loss?

A: All configuration, logs and alarms permanently stored; RTC keeps running >=5 years on backup battery (+-2s/day), no re-setup needed.

Q10: Communication methods?

A: LAN/WiFi/4G/RS485/CAN/USB; Modbus-RTU/TCP-IP; local functions (touch, remote, manual) work even with no network.

Q11: Surge protection?

A: Three-level communication/SPD protection on power and signal lines; insulation test 2kV; 6kV impulse withstand.

Q12: Branch circuit current options?

A: Standard 16A; 6/10/20/25/32/40/63A optional per load; each branch independently protected.

Q13: What is the smoke detector threshold?

A: Photoelectric scattering, 0.1-0.3dB/m, alarm <=10s, recovery <=30s, false alarm <=1/year, per GB 4715.

Q14: Temperature/humidity accuracy?

A: +-0.3 degC (0-60 degC), +-3%RH (20-80%RH); digital output, low drift <=0.02 degC/year.

12.3 Function and Application

Q15: How does four-level permission work — must all be enabled?

A: Progressive and configurable — password-only for daily use; UKey+password for higher security; phone scan for core parameter changes; admin password for emergencies; level set by the administrator.

Q16: Does AI video linkage require your video system?

A: No — standard RS485/Modbus and dry-contact interfaces interface with mainstream third-party AI video/content-audit systems; violation duration and circuits configurable.

Q17: Timing task capacity and cycles?

A: >=500 tasks; single/daily/weekly/workday/custom cycles; holiday exceptions; per-task circuit selection; full/partial actions.

Q18: Remote control without internet?

A: LAN for PC; WiFi for APP in local network; 4G card for external remote; all local functions still work fully offline.

Q19: Can the generator run automatically?

A: Yes — manual/automatic modes; starts on demand or as backup; speed regulated by the VFD; AVR holds voltage; stop/start via control box or remotely.

Q20: Temperature linkage scenarios?

A: High temperature starts cooling circuits, low temperature starts heating (reverse logic available); 8 strategies with names; manual/timed switching; 2 degC hysteresis prevents hunting.

Q21: Multi-cabinet cascade?

A: Up to 8 expansion cabinets via HL-M main linkage + RS485 dual channel; sync error <=200ms; single cabinet communication fault does not block others.

Q22: Who can access via APP?

A: Accounts created by the administrator with graded permissions; biometric login (fingerprint/face); abnormal-login location alerts; all operations logged.

Q23: Can existing monitoring platforms integrate?

A: Yes — standard Modbus/TCP-IP interfaces integrate with BAS, smart machine-room and third-party platforms without rebuilding.

Q24: Holiday mode?

A: Holiday lists skip scheduled tasks; shift patterns (four-shift-three, three-shift-two) supported.

12.4 Installation and Construction

Q25: Installation time and site conditions?

A: 3-5 working days for one cabinet (installation, wiring, earthing, commissioning, training, acceptance); flat solid floor, mains cable in place, earthing system, temporary power, adequate space.

Q26: Earthing requirement?

A: Cabinet protective earth to the site grid, <=4 ohm; >=16mm2 yellow-green stranded copper to the earthing busbar; dedicated earthing electrodes made if none exists.

Q27: Power outage for retrofit?

A: New projects — no outage; replacing old cabinets — short planned outage for incoming cable switch, scheduled off-peak with a detailed switchover plan.

Q28: How is the cabinet fixed?

A: M12 expansion bolts; leveling <=1.5mm/m verticality; anti-vibration pads; careful transport with hydraulic pallet truck.

Q29: Cable specifications?

A: Main incoming copper power cable sized for 400A with margin; branch BV 2.5mm2 (custom per current); RS485 RVSP 2×0.75mm2; sensor RVVP 4×0.5mm2; all color-coded and labeled.

Q30: Is weak/strong separation done?

A: Yes — power and signal in separate ducts with >=50mm spacing to reduce EMI.

12.5 O&M

Q31: Daily maintenance and inspection cycle?

A: Simple — clean dust, check door seal, review alarms; quarterly full inspection (terminal tightening, internal cleaning, earthing check, metering calibration, protection test, fire device validity); free quarterly inspection in warranty.

Q32: Consumables?

A: Door lock battery, remote battery, cooling fan, SD card — common standard parts, low cost; core components >=10 years; aerosol device replaced at 6 years.

Q33: Fault reporting and response?

A: Hotline/account manager; 15-minute response with phone/remote diagnosis; on-site within 4h (urban); general faults same day; spare-part loan scheme for long-lead parts.

Q34: Self-diagnostics?

A: Built-in fault location with hints and suggestions; remote diagnosis; watchdog auto-recovery — no freezes.

Q35: Are logs tamper-proof?

A: Yes — operation logs non-deletable and non-modifiable, audit compliant; stored on the 32GB industrial SD card (>=5 years, auto-cycle).

Q36: Data export?

A: CSV via USB/SD; Excel-readable; reports printable; automatic scheduled backup supported.

12.6 After-Sales Service

Q37: Warranty terms?

A: Whole machine 1 year from acceptance; core components (breakers, main control, metering, display) 2 years; consumables 6 months; free repair/parts/on-site/upgrades within warranty; exclusions for misuse, force majeure, unauthorized modification.

Q38: After warranty?

A: Paid extended warranty (yearly, preferential) or lifetime cost-price repair — parts at cost plus reasonable travel fee, no extra service charge.

Q39: On-site training?

A: Free three-level training at delivery: operators (2h), O&M staff (4h), administrators (6h) — theory + hands-on + assessment; manuals, videos and PPT delivered; refresher for new staff.

Q40: Quarterly inspection content?

A: Appearance/status check, cleaning, electrical parameter verification, terminal tightening, earthing check, software/firmware optimization, data analysis, report issued.

Q41: Response commitments?

A: 7×24 hotline 15-minute response; remote 30 minutes; on-site 2h urban / 4h surrounding; general fault solved within 4h on site; major within 24h.

Q42: Spare parts?

A: Dedicated spare-parts warehouse with common parts; original quality; transparent pricing; module loan/swap service.

Q43: Is the generator noisy?

A: Electric motor-generator — no exhaust and much lower noise than diesel; optional sound enclosure; suitable for indoor/quiet sites.

Q44: What documents are delivered?

A: Manuals (paper+electronic), software operation guide, maintenance handbook, fault handbook, PPT, demo video, certificates, test reports, as-built drawings, training records.

12.7 Project-Specific

Q45: What is the total schedule?

A: 7 calendar days on site (3 install + 2 commissioning + 2 acceptance); flexible per project; standard delivery 7-10 working days, custom 15-20.

Q46: Can the number of circuits be adjusted?

A: Yes — circuit count/current customized; configuration list updated and quoted separately.

Q47: Suitable for confidential sites?

A: Yes — four-level authentication, real-name ID login, location binding, tamper-proof audit logs >=5 years, AI video linkage — meets confidential management requirements.

Q48: Can it connect to existing BAS?

A: Yes — Modbus/TCP-IP with protocol handover and data mapping for seamless integration.

Q49: What about the generator set maintenance?

A: Belt check/tensioning, bearing lubrication, cleaning, control box inspection per manual; low-maintenance design; VFD and AVR protected.

Q50: Why choose KITOZER/Lain?

A: 20+ years, source factory with full R&D/production, 3C/fire certifications, four-level authentication and AI linkage patents, complete documentation, 1+2-year warranty, local fast service and lifetime support.

13. Construction Schedule

13.1 Overall Schedule (7 Calendar Days)

3 days on-site installation, 2 days commissioning, 2 days acceptance preparation and handover; adjustable per site conditions; force-majeure or non-ready site extends accordingly.

13.2 Detailed Arrangement

Day 1 — Preparation and arrival acceptance: personnel/tools/materials on site; survey recheck; technical and safety disclosure; temporary power and area guarding; open-box inspection against packing list; signed arrival acceptance; point marking; auxiliary material preparation.

Day 2 — Cabinet and generator installation: base leveling and marking; cabinet positioning, M12 fixing, verticality calibration; generator base leveling and fixing; earthing construction with copper busbar and resistance test; control box wall mounting.

Day 3 — Power wiring: main incoming cable laying, phase sequence check, terminal crimping; main breaker wiring with torque tightening; branch circuit wiring with number sleeves; generator power wiring; terminal recheck; duct covers and cable dressing.

Day 4 — Communication/sensor wiring and pre-energization check: temperature/humidity, smoke and sensor wiring; communication and linkage wiring; control circuit wiring and secondary check; full insulation resistance test with records; earthing re-test; cabinet cleaning; all breakers off; pre-energization safety check and permit.

Day 5 — Single-unit commissioning: main supply on, step-by-step energization; main control and module supply check; touchscreen startup and function verification; metering calibration vs multimeter; branch on/off tests with status feedback; sensor calibration and alarm threshold tests; full local control test.

Day 6 — System linkage and remote commissioning: timing linkage test; temperature linkage simulation; AI linkage interface test with simulated violation signal; remote pairing test; LAN commissioning with PC software; APP pairing and functions; loaded trial run with temperature observation; simulated fault tests verifying protection and alarms; full recheck.

Day 7 — Acceptance and handover: documentation binding; acceptance application and joint acceptance; on-site demo; training with hands-on practice; signed acceptance; keys, documents, accessories handover; project enters warranty.

13.3 Progress Assurance

Project manager on site throughout; daily morning/evening meetings; half-day granular plan with adjustment; parallel/cross work; materials pre-stocked and checked before shipping; dedicated material management; technical lead on site; pre-written commissioning plans and work instructions; back-office support; early coordination with the client (power, space); key acceptance nodes notified in advance for timely signatures.

14. Construction Organization and Quality/Safety Measures

14.1 Organization

Project manager (1) — overall schedule/quality/cost/safety and client interface; technical lead (1) — disclosure, guidance, debugging; team leader (1) — daily tasks and crew; QC (1) — inspections and acceptance; safety officer (1) — safety system and inspection; electricians (2) — installation and wiring, all with low-voltage operation certificates.

14.2 Construction Preparation

Drawing review and disclosure before start; special construction plans (cabinet installation, cable laying, earthing, commissioning, safety); material/equipment pre-inspection and arrival acceptance with certificates; dedicated storage with moisture/dust/theft protection; site survey (position, foundation, cable routes, power, space, interfaces); calibrated tools and instruments (multimeter, clamp meter, earth tester, insulation tester, phase meter, level, etc.) with PPE.

14.3 Main Processes and Workmanship

General flow: preparation -> cabinet installation -> earthing -> main incoming wiring -> branch wiring -> communication/sensor wiring -> pre-energization check -> single-unit commissioning -> linkage commissioning -> loaded trial -> acceptance. Foundation: flat solid floor, level deviation <=2mm/m; marking; holes per expansion bolts; careful handling; verticality <=1.5mm/m; uniform bolt tightening; anti-vibration pads; finish check of locks/hinges. Main incoming: cable sized with margin; orderly routing with correct bend radius; tinned lugs; phase colors; torque tightening with spring washers; glands; labels. Branch wiring: BV wires in ducts, neat; strong/weak separation >=50mm; consistent bends; correct strip length; max 2 wires per terminal; number sleeves on both ends; insulation covers on bare parts. Communication/sensor: shielded cables in dedicated routes; single-end shield earthing; proper joints; accurate sensor positions away from heat/EMI; continuity tests. Earthing: cabinet earth to site grid; in-cabinet copper busbar for all shells/shields; bolted tinned connections; earth resistance <=4 ohm with record. Pre-energization check: clean interior; all breakers off; terminals tight and correct; insulation >=0.5M ohm; earthing verified; environment OK; permit signed by technical lead before energizing.

14.4 Quality Control

Target: 100% first-pass acceptance, 100% material qualification, 100% wiring correctness, 100% insulation/earthing pass, 100% function compliance, complete documentation. Three-level inspection: crew self-check -> QC special check (signature; nonconformity rectified and re-inspected) -> project final inspection before client acceptance; hidden works accepted before covering. Key control points: arrival acceptance, cabinet installation, wiring workmanship, insulation testing, earthing, system commissioning. Standards: GB 50303-2015, GB 50171-2012, GB 50169-2016 plus factory standards and drawings.

14.5 Safety Management

Zero accidents target. Responsibility system (PM first responsible); pre-job safety education and disclosure; daily safety meetings; patrols; reward/penalty; PPE (helmets, insulated shoes/gloves); warnings and guard lines; supervised live work — no single-person live work; stable material stacking; fire extinguishers, no smoking, fire permits with supervision; safety belts for height work; temporary power with three-level distribution/two-level protection and RCDs; lockout-tagout for outage work — no scheduled switching; daily shutdown of temporary power. Emergency plans: electric shock (cut power, rescue, call 120, report, preserve scene), fire (cut power, extinguish, call 119, evacuate), mechanical injury (stop, bandage, hospitalize), equipment incident (power off, investigate, report); regular drills.

14.6 Civilized Construction and Environment

Neat dress and badges; tidy material stacking with labels; tool return; minimal disturbance to surrounding work; work-clean-restore; classified storage; daily garbage removal; no littering into drains/green belts; final site cleanup; noise avoided at rest hours; wet/dampened cutting to reduce dust; low-noise tools; gentle handling; vehicle speed limits; daily water spraying for dust control.

15. After-Sales Service

15.1 Warranty Commitment

Whole machine 1 year free from acceptance — free repair, parts, travel, materials for non-human, non-force-majeure faults. Core components (main/branch breakers, metering module, main control, touchscreen, communication modules) 2 years; passive lock/sensors 1 year; consumables (fuses, SD card, batteries) 6 months. Free services: fault repair, 7×24 phone consultation, quarterly on-site inspection (4 times/year with report), firmware/software upgrades, operation guidance, optimization advice. Exclusions (paid service): misuse, unauthorized disassembly/modification, water/lightning/impact/rodent damage, non-compliant maintenance, force majeure. Extended warranty available after expiry (yearly, preferential); lifetime cost-price repair without extra service fee otherwise.

15.2 Response Commitment

7×24 hotline with 15-minute response; remote handling within 30 minutes; on-site within 2h urban / 4h surrounding; general faults solved within 4h on site; major faults restored within 24h; spare-device scheme for long-lead parts.

15.3 Full-Cycle Service

Quarterly free inspection with formal report (appearance, cleaning, electrical parameters, terminal tightening, earthing, software/firmware, data analysis, guidance); firmware upgrade service (on-site or remote, verified after); 7×24 technical consultation (hotline/WeChat/email); original spare parts warehouse with module loan/swap; emergency on-site duty for important events and key periods.

15.4 Standard Service Process

Reporting (hotline/WeChat/contact) -> ticket creation -> dispatch within 15 minutes -> contact and preliminary diagnosis -> remote resolution first -> on-site visit with time notice -> diagnosis and repair plan with client consent -> repair and verification -> client confirmation and sign-off -> follow-up call within 24h -> service archive and improvement.

15.5 Supervision and Complaints

Dedicated supervision line for complaints and suggestions; reply and handling within 24h; serious handling and continuous improvement — customer satisfaction is the core.

16. Training Plan

16.1 Training Objectives and Audience

Training objectives: through systematic training, enable management personnel to fully understand the system structure, working principles and performance characteristics, master daily operation methods and inspection/maintenance essentials, identify common faults and handle simple problems, ensuring safe, stable and long-term operation.

Training audience: management and O&M personnel designated by the client, recommended 2-3 persons with basic electrical and equipment knowledge.

16.2 Tiered Training Content System

Level 1: Basic operation training (1 day)

– Basic principles: system concepts, structure composition, performance indicators;

– Daily operation standards: correct operation of equipment, control and safety systems;

– Daily inspection contents: daily/weekly/monthly check items;

– Safety precautions: usage prohibitions and emergency handling procedures.

Level 2: Maintenance training (1 day)

– Detailed structure of each subsystem and working principles;

– Daily maintenance methods: cleaning, fastening checks, routine care;

– Common fault identification and simple handling;

– Emergency handling procedures for power failure, fire and equipment faults.

Level 3: Advanced management training (as needed)

– Performance influencing factors and how to avoid degradation;

– Upgrade and expansion knowledge and specification requirements;

– Relevant national standards interpretation.

16.3 Training Methods and Schedule

– Methods: combination of “theory explanation + on-site practice + Q&A interaction”;

– Schedule: training arranged at the completion acceptance stage, synchronized with handover, 2 days of intensive training total; time flexibly adjustable; a free repeat training session is provided for newly assigned personnel.

16.4 Training Assessment and Documentation Delivery

– Assessment: theory written test plus practical operation; training qualification certificates issued upon passing; supplementary training for those who fail;

– Documentation delivery: complete O&M documentation, including operation and maintenance manual, equipment manuals and certificates, completion drawings and hidden work records, test reports and after-sales service contact card, all bound into volumes.

17. Anonymous Typical Project Scenarios

All project scenarios below are anonymous, generalized examples provided for reference only. No real customer names, addresses or identifiable details are disclosed.

17.1 Municipal Government Data Center Smart Distribution Project

Background. A municipal government data center renovation demanded high reliability and intelligent management: remote monitoring, environment linkage, multi-level permission and full operation traceability.

Solution. Multiple master smart distribution cabinets with 400A main breakers and 80 branch circuits, 0.5-class metering, temperature/humidity/smoke sensors, four-level authentication (UKey/password/ID card), PC central platform and mobile APP, standard Modbus interface to the existing environment monitoring system.

Results. Stable operation with accurate metering and timely remote control; permission levels and operation logs satisfied classified-protection assessment; one-pass acceptance. The customer praised the complete functions, stability and responsive service.

17.2 Confidential Unit Smart Distribution Control Project

Background. A classified-unit equipment room required content security, access security and operation auditing: violation-triggered power-off, real-name operations and full traceability.

Solution. Customized cabinets with passive encrypted locks and traceable unlocking records; AI video linkage module interfaced to the existing content-security system with configurable violation duration; four-level authentication plus ID card login for real-name operation; address verification binding equipment to location; 32GB local storage keeping operation/alarm records for 5+ years.

Results. Perfect match to confidentiality requirements — rapid linkage power-off, strict permission control, complete auditable records; passed confidential acceptance; customer confirmed the thorough security design and smooth technical interface.

17.3 Manufacturing Plant Distribution and Generator Project

Background. An auto-parts plant test workshop needed stable distribution for test equipment plus clean test power, in a strong-EMI industrial environment, with unattended operation.

Solution. Two smart distribution cabinets for two test areas; one 3kVA electric motor-generator set as test/backup power; energy-management software with per-circuit statistics; multiple timing tasks matching shift schedules; hardened anti-interference design with software filtering; graded training for operators and electricians.

Results. Reliable operation with no interference or freezes in the harsh environment; clear energy visibility enabling consumption optimization; quiet, exhaust-free, low-maintenance generator far better than the previous diesel unit — high value for money.

17.4 City Exhibition Hall Smart Distribution with Video Linkage Project

Background. An exhibition hall with many LED displays and interactive exhibits needed zoned power control, schedule-based switching and content-compliance power cut-off, plus simple mobile operation.

Solution. Master smart distribution cabinet with zoned circuits; AI video linkage module to the hall’s content-audit system; opening/closing timing tasks executed automatically; mobile APP and mini-program for remote view/control; simplified interface for non-professional staff; commissioning coordinated with the exhibition schedule.

Results. Much higher management efficiency — automatic daily on/off without early arrival or late departure; content-safety insurance via video linkage; remote handling when managers are away. The customer praised the intelligent, simple and efficient system.

18. SEO Optimization Section

All reference prices in this technical solution are in RMB (CNY) only and are for reference purposes; final quotation is subject to the confirmed configuration.

18.1 Keyword System

– Core keywords: technical design solution, system configuration, technical parameters, construction and O&M services;

– High-conversion long-tail keywords: design solution, configuration list, technical parameters, construction plan, after-sales service;

– Industry traffic keywords: system architecture, applicable standards, technical Q&A, project cases;

– Brand keywords: KITOZER, Guangzhou Lain.

18.2 SEO Tag System

– Title tag: the article title — Guangzhou Lain KITOZER;

– Meta description: Guangzhou Lain professionally provides complete technical design solutions with detailed configuration list, full-system product technical parameters, construction organization plan and after-sales service — source manufacturer customization, compliant performance, third-party testing supported;

– H1 tag: the article title;

– H2 tags: system design and product parameters, construction organization plan, after-sales service and training, engineering cases.

18.3 Internal Link Anchor Text

– Core anchor text: technical design solution, system construction;

– Long-tail anchor text: configuration list, technical parameters, construction plan;

– Related anchor text: shielding cabinet, micro-module cold aisle, integrated computer room, outdoor cabinet.

19. Official Contact Information

– Company Name: Guangzhou Lain Intelligent System Development Co., Ltd.

– Brand: KITOZER (Pioneer)

– Official Website: https://gdlain.com

– Tel: +86 139 2228 9957 (WeChat available), +86 185 2066 8845 (WeChat available)

– Address: No. 5 Huashan Road, Shilou Town, Panyu District, Guangzhou, China

For any inquiries about this technical design solution, configuration customization, quotation or construction services, please contact us through the information above. We provide free design consultation and tailored solutions for your specific requirements.

Shopping Cart