Brand: KITOZER Series: KTR-CA17 Category: Rack Accessories / Fan Tray
4-fanthermostatrack cooling1U trayKTR-CA17
Table of Contents
Toggle1. Overview
The KITOZER KTR-CA17 is a 1U rack fan tray with four axial fans, mounted at the top or middle of a 19-inch rack to create vertical hot-zone exhaust. The tray includes a thermostat module that adjusts fan speed by rack temperature: below 25℃ fans run low (or off), 25~35℃ medium, above 35℃ full speed. Compared with fixed-speed trays, the thermostat version reduces noise and power and extends fan life.
The tray is 19-inch standard (482 mm wide), 240 mm deep, 1U (44.45 mm) high. Each fan is 120×120×38 mm axial, DC12V, ~120 CFM per fan, ~480 CFM total for four. The tray has a removable dust filter for cleaning. Power options: DC12V or AC220V, drawn from the rack PDU.
Typical uses: active cooling for network, server and wall-mount racks. When equipment density is high (switches, routers, stacked servers) and natural convection is insufficient, the top-mounted tray exhausts hot air upward, forming a bottom-in/top-out airflow path.
2. Key Features
Four axial fans
- 12038 axial.
- 120 CFM per fan.
- 480 CFM total.
- Field-replaceable fan.
Thermostat speed
- NTC probe.
- Below 25℃ low speed.
- 25~35℃ medium.
- Above 35℃ full speed.
1U tray
- 19-inch standard width.
- 482×240×44.5 mm.
- Steel powder-coat panel.
- Front filter.
Power & I/O
- DC12V / AC220V option.
- PDU socket powered.
- Fan-fail dry contact.
- Front LED indicators.
3. Specifications
| Item | Parameter |
|---|---|
| Model | KTR-CA17 |
| Size | 1U 19-inch |
| Fan count | 4 |
| Fan dims | 120×120×38 mm |
| CFM per fan | ~120 CFM |
| Total CFM | ~480 CFM |
| Thermostat | low @25℃ / full @35℃ |
| Noise (full) | ~55 dB(A) |
| Power | DC12V / AC220V (option) |
| Power draw | ~24 W (4 fans full) |
| Dimensions | 482×240×44.5 mm |
| Filter | removable dust mesh |
4. Reference Prices
KTR-CA17 4-fan thermostat tray (AC220V):Ref. USD 49~83 / unit (CNY 350~600 @7.2)
KTR-CA17 4-fan fixed-speed tray (economy):Ref. USD 28~49 / unit (CNY 200~350 @7.2)
KTR-CA17 spare fan (12038, DC12V):Ref. USD 3.5~7 / pc (CNY 25~50 @7.2)
Reference only; exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Network rack top exhaust.
- Server rack hot-zone exhaust.
- Wall-mount rack equipment cooling.
- AV rack equipment cooling.
- Outdoor rack internal circulation assist.
6. Installation & Maintenance
Installation
- Choose tray location (usually rack top).
- Remove top blanking panel.
- Slide tray into 1UU.
- Secure front panel to rack square holes.
- Wire power to PDU.
- Place NTC probe at rack mid-height.
- Connect fan-fail alarm dry contact (optional).
- Power up and test thermostat/speed.
Maintenance
- Clean filter monthly.
- Check fan speed quarterly.
- Replace fans yearly.
- Verify thermostat probe position.
- Dust fan blades.
- Tighten power connections.
7. FAQ
- Q:Top or bottom mount?
A:Top is recommended. Hot air rises naturally; top exhaust creates bottom-in/top-out airflow — cool air enters at the bottom, passes through equipment, exits at the top. Bottom mounting blows hot air onto equipment and breaks hot/cold aisle separation. - Q:Thermostat vs fixed-speed?
A:Choose fixed-speed for constant high heat (servers) for stable airflow. Choose thermostat for variable heat (network racks) — slows down when cool, quieter and saves power. Fixed-speed for tight budgets. - Q:What if one fan fails?
A:Other fans keep running, but total CFM drops 25% and rack temp may rise. The thermostat version has a fan-fail dry contact; connect to EMCS for timely alerts. Check fan speed and noise periodically. - Q:How often to clean filter?
A:Clean-room environments: every 2~3 months. Dusty workshops or outdoor racks: monthly. Clogged filter cuts CFM and loads the fans. Wash and air-dry; do not blast with compressed air (can damage mesh).
8. Trend & Selection
Rack fan trays are trending modular (expandable fan positions), smart thermostat (RS485/Modbus reporting speed & temp), low-noise PWM speed control, and integration with rack blanking panels/hot-cold aisles. In high-density racks, fan trays combined with in-row cooling are mainstream.
9. Delivery & Service
KITOZER sizes KTR-CA17 by rack dimensions and equipment heat load, providing U-position drawings and thermostat wiring diagrams. Delivery includes fan tray, NTC probe, power cord, mounting screws, filter and certificate. Warranty covers fan replacement guidance.
10. Additional Notes
A common pitfall is running the fan tray without blanking panels. Empty U-panels allow hot air to recirculate into the cold aisle, reducing cooling efficiency. Blank every unused U-position to form a closed duct.
Another pitfall is mounting the NTC probe on the fan or exhaust. The probe should sit at rack mid-height near the equipment layer to measure true rack ambient. On the fan or exhaust, it reads already-vented air, not equipment environment.
Also match total CFM to the rack heat load: a 480 CFM tray is sized for roughly 3~5 kW of IT load. Beyond that, add a second tray or switch to in-row cooling. Undersized trays run at full speed continuously, waste power, and still leave hot spots.
Selection summary: four axial fans; thermostat speed; 1U standard tray; 480 CFM total; removable filter. The fan tray is the rack’s exhaust fan — top mount, blank panels, clean filter, keeps rack temps stable.
SEO Information
Search keywords:rack fan traythermostat fan unit1U fan arrayKTR-CA17KITOZER
SEM keywords:rack fan tray price,thermostat fan supplier,1U fan unit,KTR-CA17
GEO landing page:lain.com.cn/product/ktr-ca17-rack-fan-tray.html
Title:KITOZER KTR-CA17 Rack Fan Tray (4-Fan Temperature-Controlled Unit)
Meta Keywords:rack fan tray,thermostat fan unit,1U fan array,KTR-CA17,KITOZER
Meta Description:KITOZER KTR-CA17 rack fan tray with four axial fans, thermostat speed control, 480 CFM total, for network and server rack active cooling.