The KITOZER DN250 hydraulic separator, also called a low loss header or manifold, decouples primary and secondary water loops in chilled water and heating systems. It eliminates hydraulic interference between source pumps and load pumps, stabilizes differential pressure across air handling units, and provides integrated air and dirt separation. This makes it a critical component in variable volume secondary systems where multiple pumps and multiple loads operate independently.
Table of Contents
ToggleProduct Overview
KITOZER hydraulic separators are vertical cylindrical steel vessels with four side connections: primary supply and return, and secondary supply and return. An internal baffle plate slows water velocity below 0.1 m per s, allowing air bubbles to rise to the top automatic air vent and dirt particles to settle at the bottom drain. The vessel is insulated with 20 mm rubber foam and clad in aluminum for indoor installation. Pressure gauge ports and temperature wells are factory installed for monitoring.
Technical Specifications
Nominal diameter DN250, vessel diameter 400 mm. Working pressure 10 bar. Design temperature 120 C. Maximum flow 250 m3 per h. Connections: primary DN150, secondary DN150, air vent DN20, drain DN25. Flange standard PN16. Insulation thickness 20 mm. Weight 180 kg. Shell material Q235B carbon steel, internal epoxy coating. CE and PED certified, 3 year warranty.
Application Scenarios
Install the hydraulic separator between chiller primary pumps and secondary distribution pumps in commercial HVAC plants. It is also used between heat pump chillers and fan coil loops, between boilers and heating circuits, and in district heating substations. When multiple chillers or multiple boilers share a plant, the separator allows each source pump to run at its own flow rate without affecting the load side. This is essential when primary and secondary flows do not match, which is common in variable flow systems.
Advantages and Features
By decoupling loops, the separator prevents short cycling of chillers caused by variable secondary flow. Integrated air and dirt separation improves heat exchanger efficiency and protects control valves from debris. The vertical orientation saves floor space. Flanged connections simplify installation and removal for cleaning. The vessel can be supplied with stainless steel 304 or 316 construction for potable water or corrosive loops. Optional magnetic dirt separator insert captures ferrous particles extending filter service intervals.
Installation and Maintenance
Mount the vessel vertically on the plant floor with the air vent at the highest point. Ensure the primary and secondary piping orientation matches factory marking. Flush the system before commissioning. Vent air during fill. Open the bottom drain quarterly to flush settled dirt. Inspect air vent function annually. Check pressure gauge readings to confirm low pressure drop across the separator; abnormal pressure rise indicates blockage requiring service.
Price
From $860 per unit. Contact KITOZER for custom size and pressure rating.
Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com