Table of Contents
ToggleProduct Overview
The KITOZER gas fire suppression control panel is the brain of a clean-agent fire suppression system. It monitors two detection circuits (detector zone 1 and detector zone 2), cross-verify alarms from both independent detectors before initiating gas release, drives door holders, alarm bells, strobe lights, and the release solenoid, and provides an abort switch to prevent discharge during false alarms. The panel supports 2 to 8 zones, up to 50 detectors per zone, and includes a 24-hour standby battery, printer option, and RS485 or Ethernet BMS connectivity. The 2-zone model is sized for single-room protection such as a small data center or UPS room. The panel also supports BMS integration for remote alarm monitoring.
The two-stage release logic is critical for safety: the panel requires both a smoke detector and a heat detector (or two smoke detectors) to alarm within 30 seconds before it initiates a 30-second pre-discharge timer. The abort switch allows trained personnel to cancel release if the alarm is false. The panel also releases door holders to allow egress, activates bells and strobes, and triggers the solenoid at the end of the timer. KITOZER also provides operator training and as-built drawings after installation.
Technical Specifications
Zones: 2 detection zones, expandable to 8. Detectors: up to 50 per zone, 24V conventional. Release circuit: 24V DC, 1A for solenoid. Alarm outputs: bell, strobe, door holder, abort indicator. Cross-verify logic: 2 detectors in same zone within 30 seconds. Abort switch: 0 to 30 seconds delay adjustable. Pre-discharge delay: 0 to 30 seconds. Power: 220V AC 50Hz, 50W. Battery: 24V DC 7Ah sealed lead acid, 24-hour standby. Communication: RS485 Modbus, optional Ethernet. Display: LCD + LED indicators. Dimensions: 400x300x120mm wall mount. Certifications: EN 54-2, EN 54-4, GB 16806. KITOZER brand, 3 year warranty. The panel also supports BMS integration for remote monitoring.
Applications
The 2-zone gas suppression panel is used in small data center server rooms, UPS rooms, electrical switch rooms, battery rooms, control rooms, small museums, and archive vaults. It coordinates photoelectric smoke detectors and heat detectors, triggers pre-alert bells and strobes, holds doors open during delay, and releases the cylinder solenoid after the pre-discharge timer. The panel is also used as a local annunciator for larger addressable systems. KITOZER also provides operator training for the customer facilities team.
Key Advantages
First, cross-verify logic prevents false discharge. Second, abort switch saves equipment during false alarms. Third, adjustable pre-discharge delay for human egress. Fourth, 24-hour standby battery. Fifth, BMS integration. Sixth, expandable to 8 zones. Seventh, printer option for event logging. Eighth, clear LED indicators for service engineers.
Installation and Maintenance
Mount the panel on the wall near the room entrance, wire detection zones end-of-line, connect bell, strobe, door holder, abort switch, and release solenoid. Commission: walk-test detectors, simulate abort, verify release timer. Maintenance: quarterly visual inspection, annual detector test, battery load test every 2 years, and full release simulation every 5 years. KITOZER supplies batteries, fuses, and replacement panels.
Customization Options
KITOZER offers 4-zone and 8-zone expandable panels, printer modules, Ethernet BMS gateways, and redundant solenoid circuits. Custom door colors and embossed logos are available for enterprise projects.
Warranty and Global Support
KITOZER supplies batteries, fuses, and replacement panels, backed by a 3-year warranty. The company also provides long-term service contracts covering quarterly panel inspection and annual detector testing. Spare detector bases, solenoid valves, and relay modules are held in regional stock. KITOZER also offers long-term service contracts covering quarterly panel inspection, annual detector testing, and battery replacement. Spare parts are shipped from regional stock worldwide.
Price
From $680 per 2-zone gas suppression panel including battery. Contact +86 13922289957 for 4-zone or 8-zone versions.
Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com