KITOZER
KITOZER

KITOZER Fire Water Storage Tank: 500m3 Welded Steel Underground

Product Overview

The KITOZER 500 cubic meter welded steel fire water storage tank provides a dedicated, readily available water reserve for sprinkler, hydrant, and spray systems where municipal water supply is insufficient or unreliable. The tank is built from 6 mm Q235B steel plates welded on site, internally coated with food-grade epoxy to prevent corrosion and external reinforced with steel stiffeners to withstand earth pressure when buried. The tank includes a manhole, inlet overflow, drain, vent, and level gauge, all engineered to GB 50974 fire code. KITOZER supplies design drawings, on-site supervision, and hydrostatic testing commissioning as a complete package.

The 500 cubic meter capacity is chosen to provide at least 2 hours of independent water supply for a typical mid-size commercial building, assuming a combined sprinkler and hydrant demand of around 40 liters per second. The tank is split into two equal chambers by a welded internal wall, so one chamber can be drained, cleaned, and inspected while the other remains in service. This two-chamber design is a code requirement in most jurisdictions, because it guarantees that a maintenance event cannot remove the entire fire water reserve. KITOZER can also deliver the tank as a single chamber for projects where budget is constrained, or as three chambers for extra redundancy.

Technical Specifications

Nominal volume 500 cubic meters, usable volume 480 cubic meters, plate thickness 6 mm side wall, 8 mm bottom, material Q235B carbon steel, internal coating epoxy coal tar pitch 400 microns, external coating two-pack epoxy zinc-rich primer plus polyurethane topcoat, design temperature minus 10 to 60 degrees Celsius, inlet DN100, outlet DN150 to fire pump suction, overflow DN150, drain DN100, vent DN50 with insect screen, manhole DN600, level gauge magnetic float type, ladder and safety cage included. Hydrostatic test at 1.5 m water head for 24 hours.

The tank is typically rectangular, about 12 meters long, 8 meters wide, and 5.5 meters deep, with the top 0.5 meters below finished grade. Internal bracing uses 80 x 80 x 6 mm angle iron welded vertically to resist side wall earth pressure, and horizontal ring beams at mid-height prevent panel bulging. The internal epoxy coating is applied by brush and airless spray in three coats, totaling 400 microns dry film thickness, and holiday tested at 5000V after curing. The external coating includes a 80 micron zinc-rich primer, a 120 micron epoxy intermediate coat, and a 60 micron polyurethane topcoat, which survives 10 years in wet soil. All welded seams are full penetration and vacuum box tested for leaks before backfill.

Application Scenarios

This 500 cubic meter tank is sized for mid-size industrial parks, logistics warehouses, shopping malls, hospitals, and office complexes where the fire code requires at least 2 hours of independent water supply. Typical configurations include a rectangular underground tank under the landscape area, a covered above-ground tank on a concrete plinth, or a split tank built in two chambers so one side can be drained and cleaned while the other remains in service. KITOZER also offers bolted panel tanks in stainless steel 304 for projects preferring modular construction and shorter on-site erection time.

For data center campuses, the tank is often sized larger than the fire demand, because the same water reserve also feeds the sprinkler loop and the cooling water makeup system. For tank farms and chemical plants, the tank may be located at high elevation to provide gravity head for outdoor hose streams, eliminating the need for a pump during the first minutes of a fire. In coastal regions, KITOZER can supply the tank in stainless steel 316L to resist chloride corrosion from salt-laden groundwater. For projects in cold climates, the tank can be buried below the frost line and fitted with electric trace heating on the inlet and outlet pipes.

Key Advantages

The welded steel construction tolerates earth and traffic loads better than plastic or concrete alternatives in shallow burial applications. The internal epoxy coating keeps water clean and reduces sediment formation, extending the interval between tank cleaning cycles. The two-chamber design allows maintenance without losing the entire fire water reserve, which is a key code requirement in many jurisdictions. KITOZER provides shop-fabricated panels and on-site welding supervision, so the tank can be erected in about 30 working days regardless of site weather.

Compared with a concrete tank, the welded steel tank is thinner, lighter, and can be installed in tight urban sites where a concrete pour would require a pump truck. The steel shell is watertight by itself, so no external waterproofing membrane is needed, which eliminates a common leak source in concrete tanks. The internal epoxy coating bonds directly to the steel, so it will not delaminate the way tile or liner systems can. KITOZER provides a 10-year warranty on the steel shell and a 5-year warranty on the internal coating, with local service engineers available for inspection visits.

Installation and Maintenance Recommendations

Place the tank on a reinforced concrete slab 200 mm thick with a 100 mm sand bedding layer to level the base. Backfill symmetrically around the tank with non-cohesive gravel, compacted in 300 mm lifts, and avoid placing rocks directly against the wall. Keep the tank full at all times during service to prevent flotation during high groundwater periods. Inspect internal coating annually by sending a confined-space entry crew, and clean sediment from the bottom every three years. Test the level gauge and overflow alarm quarterly, and keep a record of water level readings in the pump room log.

Before backfill, perform a 24-hour hydrostatic test by filling the tank to normal water level and marking the water line. If the level drops more than 50 mm in 24 hours, locate and repair leaks before covering. Keep a 600 mm wide access trench along one long side of the tank, so a future excavation can expose the wall for repairs. Install a leak detection cable along the tank bottom if the tank sits under a finished floor, so any leak triggers an alarm before water reaches the slab. KITOZER recommends a 5-year internal coating inspection by a NACE Level 2 inspector, and a 10-year ultrasonic thickness survey of the side wall plates.

Price

From $28,500 per tank including plates, coating, fittings, and supervision. Contact +86 13922289957 for tank quotation and site survey.

Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com

Scroll to Top