The KITOZER 35kV load break switch is a medium-voltage switching device built to make and break load currents on 35kV overhead and cable distribution networks. It combines the visible isolation of a disconnector with the arc quenching ability of a small interrupter, allowing operators to switch transformers, capacitor banks, and line sections without relying on a full circuit breaker. The switch is offered in outdoor pole-mounted and substation-installed configurations, with manual or motorized spring operation. It is a cost-effective switching solution for 35kV rural distribution lines, industrial overhead feeders, and renewable energy collection stations where breaker-based protection is reserved for the most critical feeder ends.
Table of Contents
ToggleTechnical Specifications
Rated voltage 40.5kV, rated frequency 50Hz, rated normal current 1250A, rated load breaking current 1250A, rated cable charging current breaking 50A, rated capacitor bank switching current 400A, short-time withstand current 25kA for 4 seconds, peak withstand current 63kA, power frequency withstand voltage 95kV, lightning impulse withstand voltage 185kV. Arc quenching: vacuum or SF6 depending on model. Operating mechanism: manual spring or motor drive at DC 110V or 220V. Mechanical life 5,000 operations. Conforms to IEC 62271-103 and GB standards.
Applications
The KITOZER 35kV load break switch is installed on overhead pole lines to sectionalize long rural feeders, allowing a faulty section to be isolated while the rest of the line remains energized. In industrial plants it switches 35kV transformers and large capacitor banks on and off during maintenance. In solar and wind farms it acts as the line switch between the collector feeder and the substation bus, supporting routine isolation of array sections. It is also used in municipal 35kV distribution substations where a full breaker would be uneconomical for less critical feeders.
Motorized pole-mounted switches support distribution automation, allowing the control center to reconfigure the network remotely after a fault. Combined with reclosers on the upstream side, the LBS creates a layered protection scheme: the recloser handles fault interruption while the LBS handles load switching and sectionalizing. This reduces the cost of the distribution automation project while maintaining acceptable reliability for end users.
Key Advantages
The vacuum or SF6 interrupter extinguishes load-current arcs quickly and reliably, with no visible flame or external arc. The spring mechanism delivers fast, consistent opening regardless of operator speed, which is essential for reliable arc extinction. The switch provides a visible open gap when fully open, satisfying safety requirements for isolation. Outdoor models use polymer insulators and galvanized steel hardware to resist corrosion and UV degradation, and are rated for pollution and ice levels common in exposed distribution environments.
KITOZER supplies the switch in pre-assembled configurations with mounting brackets, operating rods, and interface hardware, reducing field assembly time. Optional motor drives, wireless control modules, and earth switch attachments support modern distribution automation. Compared with a full 35kV circuit breaker, the LBS reduces capital cost and simplifies maintenance, while still delivering the load-breaking function that a plain isolator cannot provide.
Installation and Maintenance
Mount the switch on a rigid pole or substation structure at the recommended height, with adequate phase-to-phase and phase-to-ground clearance. Check that insulators are intact and that moving contacts are free. Terminate overhead conductors with approved clamps and torque them to the specified value. Confirm the frame is earthed, and install the operating rod or motor drive according to the wiring diagram. Operate the switch several times manually to confirm smooth travel and correct interlock function.
Inspect the switch after storm events and at least annually: check insulator surfaces, contact condition, operating linkage tension, and motor drive power supply. Lubricate hinges and the operating shaft. Measure contact resistance and verify that the interrupter shows no gas leak or vacuum loss. Never attempt to interrupt short-circuit fault current with the load break switch; that function belongs to the upstream circuit breaker or recloser. Replace any insulator with flashover marks and keep the operating mechanism dry with the supplied heater or sunshade.
KITOZER supplies the 35kV load break switch in ratings from 630A to 1250A, with pole-mounted or substation-base mounting options. It can be ordered with manual, motorized, or wireless remote control, and with vacuum or SF6 interruption depending on the duty and environmental requirements. When ordering, specify the rated current, interruption medium, operating mode, mounting arrangement, and whether an integrated earth switch is required. KITOZER provides type test reports for load breaking, short-time withstand, and mechanical life. Spare interrupters, operating springs, and motor drive boards are available as standard spares. The switch is compatible with most pole-top mounting hardware and can be fitted with bird guards, lightning arc horns, and operating rod extensions for long-handle operation. For distribution automation projects, the wireless control module integrates with the feeder RTU and supports remote sectionalizing after faults, reducing the number of line crews dispatched for routine reconfiguration. KITOZER engineering assists with protection coordination studies to ensure the load break switch is paired with the correct upstream recloser or breaker.
Price
From $2,680/pc. Contact +86 13922289957 for 35kV load break switch quotation.