KITOZER Isolation Transformer: 5kVA Shielded For Medical IT

KITOZER 5 kVA shielded isolation transformer provides galvanic separation between the mains supply and sensitive medical, laboratory, or IT loads while suppressing conducted common-mode noise through an electrostatic shield between primary and secondary windings. The shield is bonded to protective earth, diverting displacement current and noise coupling across the winding capacitance. This reduces leakage current on the isolated side and helps medical IT systems comply with IEC 60601-1 isolation requirements and IT grounding concepts in wet areas.

Technical Specifications

Power rating 5 kVA, primary 230 V AC, secondary 230 V AC, frequency 50 or 60 Hz, electrostatic shield to PE, insulation class B, isolation voltage 4000 V AC, leakage current below 0.1 mA shielded, efficiency above 97 percent, no-load current below 3 percent, thermal protection included, enclosure IP20, mounting floor or wall, dimensions 320 by 260 by 280 mm, weight 45 kg, CE, UL, RoHS.

Applications

The transformer is used in medical IT systems in operating theatres and intensive care units, laboratory power supplies, audio and video production reference feeds, and sensitive test instrument isolation. It is also specified in IT installations requiring galvanic separation between building earth and equipment safety earth to eliminate ground loops and reduce conducted susceptibility.

Advantages and Features

The shielded design cuts inter-winding capacitance to below 100 pF, dramatically reducing high-frequency common-mode noise transfer. The toroidal or laminated construction offers low magnetic stray field, and the thermal switch protects against overload. Units ship pre-wired with shield ground terminal, and multiple secondary windings are available for custom applications.

Installation and Maintenance

Mount the transformer on a flat rigid surface, keep primary and secondary wiring in separate conduits, and bond the electrostatic shield to the designated PE bar with a short, thick conductor. Verify isolation resistance before energizing. Inspect terminals annually in medical installations and perform dielectric testing every two years. No routine maintenance is required for the windings themselves.

Price

From $680 per piece. Contact +86 13922289957 for medical isolation transformer pricing.

Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com