Table of Contents
ToggleProduct Overview
KITOZER 10kW downflow room-level precision air conditioner is designed for medium-size server rooms with raised-floor air distribution. Conditioned air is discharged downward into the plenum beneath the floor, where it rises through perforated tiles in front of server racks. The return air enters the unit through the front grille at room level, completing a controlled short cycle that minimizes mixing with warm room air. This architecture is the classic layout for enterprise data halls where rack densities range from 3 to 6kW per rack. The unit integrates cooling, heating, humidification, and filtration in a single floor-standing cabinet, providing year-round indoor climate stability for IT loads.
Technical Specifications
Nominal cooling capacity 10kW sensible, airflow 3,000 cubic meters per hour, plenum static pressure up to 180 Pa, scroll compressor R410A, supply voltage 380V three phase 50Hz, rated power about 3.6kW, dimensions 800 millimeters wide by 900 millimeters deep by 2,000 millimeters high, weight about 190kg, G4 plus F9 filter cascade, electrode humidifier 6 to 9kg per hour, electric reheat 3kW option, microprocessor controller with color LCD, Modbus RTU and TCP, SNMP, Bacnet IP, alarm relays, CE and ISO certified, operating indoor range 18 to 35 degrees C.
Application Scenarios
The 10kW downflow unit suits mid-size data centers hosting 15 to 25 racks, call center server rooms, university computer labs, government information rooms, and manufacturing SCADA control centers. It is commonly installed in pairs for N plus 1 redundancy in Tier-2 style rooms and can be grouped in a row along a cold aisle. The downflow plenum design works well in retrofits where existing raised floors are already in place. For locations with limited outdoor space, the unit can be matched with a remote air-cooled condenser mounted on a rooftop or external wall.
Advantages and Features
The high sensible heat ratio above 0.95 ensures efficient cooling of rack heat loads without overcooling or over-dehumidifying the space. The EC plug fan with variable speed drive automatically adjusts airflow to match plenum static pressure, saving energy as IT load varies. The controller offers remote start-stop, schedule setbacks, alarm email notifications, and trending graphs that can be exported for capacity planning. The cabinet uses double-wall insulated construction for low surface condensation risk and low radiated noise below 60 dB(A). Hot-aisle or cold-aisle containment integration is supported by adjustable discharge vanes.
Installation and Maintenance Recommendations
Verify raised-floor structural load rating before placing the unit, since a fully loaded cabinet plus condensate water can exceed 250kg. Seal plenum penetrations around cable openings to prevent hot air bypass. Balance perforated tile layout with CFD guidance if rack densities exceed 5kW. Install the outdoor condenser on a flat pad with refrigerant line lengths under 30 meters. Commission airflow measurement with a hood to confirm tile velocity distribution. Maintenance includes quarterly filter replacement, annual humidifier cartridge cleaning, biannual refrigerant leak check, and yearly electrical terminal inspection. Keep a log of compressor runtime to plan replacement before failure.
Price
From $4,280 per unit. Contact KITOZER for package pricing including outdoor condenser.