KITOZER 100 A high-current power EMI filter is designed for main distribution feeders of data centers, industrial power panels, and large UPS systems where conducted noise from upstream switching converters must be contained. The filter attenuates high-frequency noise on three-phase plus neutral feeders, protecting downstream IT loads, storage arrays, and network switches from conducted susceptibility issues. The modular chassis design allows installation in standard Rittal-style enclosures or floor-mounted switchboards, and the symmetrical Y-capacitor network minimizes neutral-to-ground noise that can interfere with sensitive measurement and grounding systems.
High-current filters of this rating are often the final EMC defense between the building low-voltage distribution and the IT load. They block noise generated by UPS rectifiers, battery inverters, and standby generator AVR systems from propagating onto the neutral conductor, where it would otherwise couple into signal reference grounds. The filter is constructed with oversized copper busbars to minimize resistive heating and voltage drop, and the nanocrystalline core array is segmented to avoid saturation from DC bias introduced by non-linear loads.
Table of Contents
ToggleTechnical Specifications
Rated voltage 400 V AC three phase plus neutral, rated current 100 A at 40 degrees Celsius, frequency 50 or 60 Hz, common-mode attenuation up to 85 dB at 10 MHz, differential-mode attenuation up to 65 dB at 100 kHz, leakage current below 5 mA, dielectric strength 2800 V AC, operating temperature minus 25 to plus 85 degrees Celsius, enclosure IP20, busbar terminals 25 mm2 and above, certified UL, CE, RoHS, dimensions approximately 360 by 180 by 120 mm, weight 6.5 kg. Optional thermal monitoring and alarm contact are available for remote monitoring in DCIM systems.
Performance Curve
The filter measures 60 dB common-mode attenuation at 100 kHz, rising to 80 dB at 1 MHz and 85 dB at 10 MHz. Differential-mode attenuation exceeds 50 dB across 100 kHz to 1 MHz and remains above 35 dB at 10 MHz. The neutral line is filtered symmetrically with the three phases, preventing neutral noise from becoming a common-mode path to ground.
Applications
The 100 A filter is installed on UPS output feeders, PDU mains, diesel generator input panels, battery energy storage system converters, and large VFD bypass cabinets. It is also used in broadcast transmitter plants, medical imaging suites, and scientific research facilities where radiated noise from power electronics must not raise the noise floor on sensitive measurement equipment.
In data centers, the filter is commonly fitted on the main breaker of each IT row distribution cabinet and on dual-cord server PDUs, ensuring that noise from one rack does not propagate through the power backbone to other racks. It is also specified in semiconductor fabs and astronomical observatories where low electromagnetic background is essential to the measurement process. Colocation providers use it as a standard building block in customer power distribution units.
Advantages and Features
KITOZER high-current filters use segmented nanocrystalline cores distributed across multiple winding sections to avoid saturation under DC bias from non-linear loads. The low-profile busbar entry reduces stray inductance, and the steel chassis provides magnetic shielding to prevent external coupling. Units are tested for full-rated current at elevated temperature and shipped with a factory test report. Custom taps, warning labels, and conformal coating are available for harsh environments. The symmetrical layout also allows back-to-back installation for bidirectional filtering where required. The filter is available with optional external current monitoring terminals that feed into the building BMS, enabling predictive maintenance of the distribution circuit.
Packaging and Lead Time
High-current filters ship in wooden crates with bolt-down brackets for safe handling. Standard models have a 3-week lead time, and expedited production is available for urgent data center cutover projects. Spare filters are recommended for critical installations to minimize downtime in the event of a component failure.
Installation and Maintenance
Mount the filter on a flat conductive panel and bond the chassis to the protective earth with short, wide straps. Keep input and output cable trays separated by at least 200 mm, and avoid looping conductors near the filter. Torque busbar lugs to the manufacturer specification, and verify the PE bond before energizing. During commissioning, measure conducted emissions with a LISN to confirm margins. Re-torque connections after the first thermal cycle, and inspect annually in mission-critical installations. Record the leakage current reading as a baseline for future trending.
Quality and Warranty
Each 100 A filter is factory-tested at rated current with thermal imaging and shipped with a calibration traceable test report. The 5-year warranty covers core degradation and component failure, and on-site commissioning support is available for large data center deployments. Long-term spare parts availability is guaranteed for 10 years from the last production date, protecting customers against obsolescence.
Compliance and Documentation
High-current filters are part of the KITOZER critical power ecosystem, and can be specified together with upstream UPS, static transfer switches, and active harmonic filters for a coordinated EMC power distribution design. The factory test report includes thermal imaging photographs at rated load, dielectric test records, and leakage current measurements. Long-term supply agreements are available for data center operators building multi-site deployments.
Price
From $680 per piece. Contact +86 13922289957 for high-current filter pricing.
Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com