KITOZER SCB14 1600kVA High Efficiency Dry Type Transformer

Product Overview

The KITOZER SCB14-1600/10 high efficiency dry type transformer is built for heavy load indoor substations serving large commercial complexes, convention centers, industrial plants, and data center main transformers. The 1600 kVA rating handles full load currents around 2300 A on the 0.4 kV side, typically feeding multiple low voltage switchboards and UPS systems. Super low loss silicon steel core and optimized winding structure bring no load loss below grade 2 energy efficiency, giving meaningful annual savings when the unit runs at 60 to 80 percent loading. The vacuum cast epoxy winding is flame retardant Class F and carries CE and IEC certification.

The SCB14 generation uses a seven step mitred core and high permeability steel, reducing no load loss by about 25 percent versus SCB11. The winding is foil cast with temperature sensors embedded at multiple points to capture the hottest spot. The enclosure is a fully welded steel frame with removable side panels, top exhaust for fan air, and a separate LV terminal chamber. For data center duty, the unit is often paralleled with an identical unit on the same bus to provide N plus one redundancy and planned maintenance without downtime.

Technical Specifications

Rated 1600 kVA, HV 10 kV plus or minus 2 times 2.5 percent, LV 0.4 kV, Dyn11, impedance 6.0 percent. No load loss 1.64 kW, load loss at 120 degrees 12.5 kW, no load current 0.5 percent. Insulation class F, temperature rise 100 K, max ambient 40 degrees C, altitude below 1000 m. Cooling AN, with AF fan kit enabling 1.3 times rated overload. Partial discharge below 10 pC. Enclosure IP20 standard, IP31 or IP32 option for dusty or splash environments. Temperature controller PT100, digital display, alarm 130 degrees, trip 150 degrees, fan control 110 degrees. Secondary terminals with laminated copper busbar rated 2500 A, HV bushing with shielded cable connection. Core and frame hot dip galvanized for corrosion protection. Routine tests include resistance ratio, no load loss, load loss, impulse withstand 75 kV, induced overpotential. CE, IEC 60076, GB/T 1094.11.

The temperature controller supports Modbus RTU and four dry contacts for remote monitoring. The AF fan kit consists of two or three axial fans mounted on the top plenum, controlled by the temperature controller. The HV side cable box has removable gland plates for 3 to 5 cables per phase. The LV busbar is tin plated and supplied with flexible braids for connection to switchgear. Earthing busbar is rated for the full short circuit current. The unit weighs about 3100 kg and is lifted by four top eyes.

Application Scenarios

This rating is the workhorse for large shopping mall main transformers, hospital central substations, industrial plant incoming substations, convention center power, and data center upstream transformers feeding 2N UPS systems. Because the unit is dry, it is installed in basement substation rooms adjacent to load. The AF fan kit suits sites with cyclic load such as stadiums or convention halls that swing between 30 percent and 120 percent over a day. IP31 enclosures are used in woodworking, textile, or food processing areas where dust and occasional water spray exist. Parallel operation of two 1600 kVA units is common for redundancy in mission critical facilities.

In large data centers, each 1600 kVA transformer feeds a 600 to 800 kVA UPS system supporting a server hall. In convention centers, it powers lighting, air conditioning, and exhibition booth feeders during events. In pharmaceutical plants, it supplies cleanroom HVAC and process equipment. The unit is also used in airport terminal distribution, metro station power, and large office building mains. For coastal sites, the enclosure is hot dip galvanized or coated with anti corrosion epoxy.

Advantages

Super low loss core cuts both no load and load losses, paying back the premium over five years in continuous duty. Low noise design under 65 dB allows installation near occupied office floors. The resin winding has unlimited shelf life when stored in dry conditions and requires no re impregnation. Front access tap changer simplifies commissioning without removing enclosure. The unit supports on load monitoring through Modbus RTU on the temperature controller, feeding energy and thermal data to DCIM or BMS. Standardized footprint and lifting fittings reduce installation crane time. Five year warranty covers winding and core defects.

Installation and Maintenance

Provide a reinforced concrete plinth, since the unit weighs over 3000 kg. Keep 1.5 m clearance front for LV busbar connection and 1.0 m sides. Use shielded HV cable rated 12 kV and terminate with cold shrink or heat shrink kits. Connect LV via busbar with flexible copper braids to absorb expansion. Before energizing, verify tap position, measure insulation with 5000 V megger, and check phase rotation. After commissioning, run a thermal imaging walk at 50 percent load, then at 100 percent load, and record hot spots. Maintenance every year: clean core surface, torque busbar, test PT100 sensors, inspect fan bearings. Every five years, perform a partial discharge test and insulation dissipation factor measurement. Keep room ventilation open; blocked filters are the leading cause of premature winding overheating.

Price

From $26,500 per piece with aluminum winding, IP20 enclosure, and digital temperature controller. Copper winding, IP31 enclosure, AF fan kit, and Modbus monitoring are optional.