Table of Contents
ToggleProduct Overview
The KITOZER YB-12/0.4-1250 European box type substation is a compact prefabricated outdoor substation combining a 1250 kVA dry type or oil transformer, 12 kV switchgear, and 0.4 kV low voltage switchboard in a single steel enclosure. It is widely used for urban distribution, shopping mall outdoor substations, construction site power, industrial park feeders, and renewable energy grid connection. European style design separates the HV room, transformer room, and LV room into three compartments with independent doors, giving safe maintenance access and clear phasing. The unit ships factory assembled, cabled, and tested, allowing plug and play installation on site.
The HV room contains a ring main unit with load break switch or vacuum circuit breaker. The transformer room contains a 1250 kVA dry type or oil immersed unit, with ventilation louvers and exhaust fan. The LV room contains a main breaker, branch breakers, and optional reactive compensation. The enclosure is a steel sandwich panel with insulation, finished in RAL7035 or decorative color. Internal lighting, heater, and temperature controller protect components in cold or humid climates. Bottom cable entry keeps connections clean and protected.
Technical Specifications
Rated transformer 1250 kVA, HV 12 kV, LV 0.4 kV, Dyn11, impedance 6.0 percent. HV side: ring main unit with 630 A load break switch, 25 kA short time, SF6 or vacuum interrupter. LV side: main breaker 1600 A, up to 12 branch breakers 630 A, plus reactive compensation cabinet 200 kVar. Enclosure steel sandwich panel with insulation, IP33, RAL paint. Transformer cooling AN or AF. Internal lighting, heater, and exhaust fan. Cable entry bottom. Dimensions approximately 3000 x 2200 x 2400 mm. Weight 6000 kg. Complies with IEC 62271, IEC 60076, GB/T 17467.
The HV ring main unit can be configured with two load break switches and one fuse switch combination for transformer protection, or with vacuum circuit breakers for cable network protection. The LV switchboard uses molded case breakers with electronic release, and the compensation cabinet uses switched capacitor banks with contactors. The enclosure heater maintains above dew point in humid conditions, and the exhaust fan prevents overheating in summer. Internal light is activated by door switch. Earthing busbar runs along the enclosure base.
Application Scenarios
European box substations serve urban residential communities, commercial plazas, hospital outdoor substations, construction sites, industrial parks, and photovoltaic or wind farm grid connection points. The three compartment layout is preferred when safety codes require separation of HV, transformer, and LV maintenance zones. For construction sites, the unit is skid mounted and relocatable. For solar farms, the LV side integrates inverter feeders and metering. The decorative enclosure can match urban landscape requirements.
In residential communities, the box substation powers several apartment buildings. In commercial plazas, it supplies lighting, HVAC, and tenant outlets. For hospitals, it provides outdoor back up supply. On construction sites, it powers cranes, elevators, and temporary lighting. In industrial parks, it feeds perimeter workshops. For solar farms, it steps up inverter output to 10 kV for grid connection. The unit is also used in sports venues, parking structures, and wastewater treatment plants.
Advantages
Factory preassembled and tested, eliminating site wiring errors. Three compartment design isolates fault zones. HV ring main unit provides reliable loop supply. LV switchboard with main, branches, and compensation reduces separate panel count. Internal heater and fan protect components in humid or cold climates. Bottom cable entry keeps connections clean and protected. Decorative paint options blend into urban environments. Five year warranty covers the complete package.
Installation and Maintenance
Place on a level concrete plinth with drainage and cable trenches. Keep 1.5 m clearance on all sides for door opening and cable bending radius. Connect HV cable to HV room terminals, LV cable to LV room busbar, and ground to the earthing bar. Commissioning includes insulation test, phase rotation, breaker operation, and protection relay test. Maintenance annually: inspect gasket, clean filters, test heater, check breakers. Every two years: HV switch SF6 gas check, transformer oil sample or dry type insulation measurement. Every five years: breaker mechanism lubrication, protection relay calibration. Keep enclosure doors locked and ventilation grilles clear.
Price
From $18,600 per piece including 1250 kVA dry transformer, RMU, LV main and 8 branches, 200 kVar compensation, and factory test report. Custom configuration, SF6 free RMU, and decorative paint are optional.
Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com