KITOZER
KITOZER

KITOZER KTR-SDPBNC BNC Video Surge Protector (Coax CCTV / 75 Ohm)

Brand: KITOZER Series: KTR-SDPBNC Category: Surge Protector / Signal SPD

BNC coax75 ohm5 kA dischargeinsertion loss ≤1 dBKTR-SDPBNC

1. Overview

The KITOZER KTR-SDPBNC is a surge protector for coaxial video lines (BNC). It is series-connected between the camera-end and DVR-end coaxial cable, diverting lightning-induced and switching transients to ground, protecting the DVR, encoder and camera from surge breakdown. Analog CCTV (CVBS/TVI/CVI/AHD) and HD-SDI cameras commonly use BNC; lines run from outdoor pole cameras into indoor rooms, and lightning-induced transients can reach hundreds or thousands of volts along the cable, burning video boards.

KTR-SDPBNC uses a gas-discharge tube (GDT) plus TVS diode combo: the GDT diverts large current (5 kA / 8/20 us), the TVS responds fast (1 ns) to clamp voltage. Nominal discharge In = 5 kA (8/20 us), max Imax = 10 kA, limiting voltage (protection level) ≤70 V. Characteristic impedance 75 ohm, insertion loss ≤1 dB (does not affect 1080P HD video bandwidth), frequency DC to 2 GHz. BNC male (camera end) to BNC female (DVR end), metal housing, inline on the coax, no power required.

Typical uses: outdoor pole analog/coax HD cameras; elevator traveling cables; road and plaza CCTV; substation and perimeter CCTV; industrial TV (furnace, steel mill) video protection. KTR-SDPBNC is installed at both the camera end (near the protected device) and the room DVR end, forming two-stage protection; outdoor lines must have it, otherwise DVR video boards batch-fail after the rainy season.

2. Key Features

Coax BNC

  • BNC male to female.
  • 75 ohm matched.
  • DC to 2 GHz.
  • Insertion loss ≤1 dB.

Combo circuit

  • Gas discharge tube.
  • TVS diode.
  • 5 kA nominal / 10 kA max.
  • Limiting ≤70 V.

Inline mount

  • Passive series.
  • No power.
  • Metal housing.
  • M5 ground terminal.

High-speed

  • TVI/CVI/AHD compatible.
  • HD-SDI compatible.
  • No frame loss.
  • -40 to +85 C.

3. Specifications

Item Parameter
Model KTR-SDPBNC
Connector BNC male to female
Impedance 75 ohm
Frequency DC to 2 GHz
Insertion loss ≤1 dB
Nominal discharge In 5 kA (8/20 us)
Max discharge Imax 10 kA (8/20 us)
Limiting voltage ≤70 V
Response time ≤1 ns (TVS)
Ground terminal M5 stud
Operating temp -40 to +85 C
Housing size about 70x25x25 mm

4. Reference Prices

KTR-SDPBNC single BNC: Ref. USD 3.5~6.3 / pc (CNY 25~45 at 7.2)

KTR-SDPBNC 4-channel BNC: Ref. USD 11~21 / pc (CNY 80~150 at 7.2)

KTR-SDPBNC HD-SDI version: Ref. USD 6.3~11 / pc (CNY 45~80 at 7.2)

BNC coax (SYWV-75-5, 100 m): Ref. USD 25~42 / roll (CNY 180~300 at 7.2)

M5 ground wire (yellow-green, 1 m): Ref. USD 0.7~1.4 / pc (CNY 5~10 at 7.2)

Reference only; exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Outdoor pole coax HD camera.
  • Elevator traveling cable.
  • Road and plaza CCTV.
  • Substation and perimeter.
  • Industrial TV (furnace).
  • HD-SDI studio signal.

6. Installation & Maintenance

Installation

  • Inline KTR-SDPBNC on the coax: male to camera, female to DVR (direction does not affect protection).
  • Outdoor camera end: BNC-T or inline on the camera pigtail.
  • Room DVR end: mount before the DVR BNC distributor or capture card.
  • Ground M5 with a ≥1.5 mm2 yellow-green wire to the room equipotential bar.
  • Keep the ground wire short (under 0.5 m); lead inductance raises limiting voltage.
  • Tighten BNC connectors (loose causes snow).
  • Power on and verify the video image.
  • After the storm season, check SPD degradation (megger core-to-ground insulation).

Maintenance

  • Check BNC connectors quarterly.
  • Yearly after storms, megger core-to-ground (should be >100 Mohm; near 0 means GDT failed).
  • After a strike, if a channel goes blank, replace the SPD first (it may have absorbed and failed).
  • Do not daisy-chain ground wires; ground each SPD independently.
  • Keep the metal housing away from live rack parts.

7. FAQ

  • Q:BNC vs network SPD?
    A:BNC SPD (KTR-SDPBNC) protects coax video (75 ohm, analog/TVI/CVI/AHD/HD-SDI). Network SPD protects RJ45 Ethernet (100 ohm, PoE). Media and impedance differ; they cannot be mixed (BNC cannot enter RJ45). Coax CCTV (old analog and HD-SDI) uses BNC SPD; IP cameras use RJ45 network SPD.
  • Q:One SPD or two?
    A:Outdoor lines use two-stage protection: one at the camera (outdoor pole, for direct-strike induction) and one at the room DVR (indoor, for residual overvoltage). If only one, prefer the room DVR end (DVR is expensive, camera is cheap). But without a camera-end SPD, outdoor induction enters the room; even with a room SPD, longer lead raises limiting voltage and may still damage the DVR. Critical projects use both ends.
  • Q:Does SPD affect video quality?
    A:A good BNC SPD (KTR-SDPBNC) has ≤1 dB insertion loss and DC to 2 GHz, transparent to analog CVBS (6 MHz) and HD-SDI (1.5 GHz). Cheap SPDs use large ground capacitors that short high frequency, giving a blurry or blank image. Choose by frequency (≥1 GHz) and insertion loss (≤1 dB); HD-SDI needs a high-frequency model.
  • Q:Why must the ground wire be short?
    A:Surge is a microsecond pulse; leads have inductance (about 1 uH/m). A 1 m lead at 10 kA rising at 1 kV/us gives V = 1 uH x 1000 A/us = 1000 V; plus the 70 V GDT clamp, the device sees 1070 V and is damaged. Under 0.5 m, inductance ≤0.5 uH and the drop falls to 500 V. So the SPD ground wire must be short, thick and straight, not looped.

8. Trend & Selection

Coax video is migrating to IP (IPC), reducing BNC SPD volume, but HD TVI/CVI/AHD still exist in retrofit projects. HD-SDI (broadcast) demands higher frequency (3 GHz). SPDs move from discrete TVS plus GDT to integrated semiconductor arrays (low capacitance, low clamp). Smart SPDs (remote degradation monitoring) spread in critical projects, with dry contacts to the platform.

9. Delivery & Service

KITOZER sizes KTR-SDPBNC by camera channel count and interface, providing grounding and two-stage diagrams. Delivery includes BNC SPD, M5 ground wire and certificate. Warranty covers post-strike degradation testing and replacement.

10. Additional Notes

A common pitfall is a loose SPD ground. The ground wire is screwed to a rack bolt with paint or oxidation, giving high contact resistance. During a strike, surge current cannot flow to ground and all of it hits the equipment. Ground to a dedicated equipotential copper bar, scrape the paint at the lug, and tighten with an M5 washer.

Another pitfall is omitting the SPD. Contractors shortcut and run outdoor coax straight into the DVR without SPD. One storm season, a whole row of DVR video boards fails; the repair cost is dozens of times the SPD price. Outdoor lines must have SPD; do not gamble.

Selection summary: BNC coax, 75 ohm, 5 kA, 70 V clamp, DC to 2 GHz. The BNC video SPD is standard for coax CCTV; the keys are both ends, short-thick-straight ground, tight BNC, and high-frequency model for HD-SDI.

Additional tip: elevator traveling-cable CCTV often suffers VFD interference (rolling bars on startup). This is EMI, not lightning; KTR-SDPBNC GDT and TVS have limited effect on high-frequency interference. Add a ferrite bead on the BNC line, or use an elevator-specific anti-interference camera.

Contact Us

KITOZER brand (professional data center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Scroll to Top