KITOZER DN50 Selector Valve For Multi-hazard Gas System

The KITOZER DN50 selector valve directs clean agent flow from a single central cylinder bank to the correct protected hazard in multi-zone gas suppression systems. By isolating inactive zones and opening only the valve serving the alarmed area, one cylinder bank can protect several rooms or enclosures sequentially, reducing capital cost and cylinder room footprint. The DN50 size is suited to medium-sized hazards with moderate pipe runs, and the valve is robust enough for 24/7 industrial service.

Product Overview

The selector valve is a piston- or diaphragm-operated normally closed valve installed in the distribution pipe network. It is held closed by pilot gas pressure and opened when the release panel energizes the corresponding solenoid pilot. The valve body is forged brass or stainless steel with flanged or threaded ends. A manual override allows operators to open the valve for testing, and a mechanical indicator shows open or closed position.

Technical Specifications

Nominal diameter is DN50 (2 inch). Working pressure is 12 megapascals for clean agent systems or 20 megapascals for inert gas systems. Pilot pressure is 1.6 to 6 megapascals. Body material is forged brass or stainless steel. End connections are threaded or flanged. Flow coefficient Kvs is approximately 40. Operating temperature is -20 to 50 degrees Celsius. Solenoid pilot is 24 volts DC. The valve is normally closed and spring-returned.

Application Scenarios

Selector valves are installed in data center gas suppression systems serving multiple server rooms, in electrical substations with several switchgear bays, in industrial facilities protecting multiple machine tools, and in commercial buildings with multiple archive or treasury rooms. The DN50 size typically handles hazards between 100 and 400 cubic meters. The valve is also used in marine systems where one cylinder room protects multiple compartments.

Advantages

Centralized cylinder banks reduce equipment duplication and simplify maintenance. Selector valves ensure agent reaches only the alarmed zone, avoiding unnecessary discharge into occupied areas. The valve is robust, with no moving seals in the main flow path when open. Manual override and position indicator simplify commissioning and troubleshooting. The design is compatible with all common clean agent types. The valve can be locally or pilot operated.

Installation and Maintenance

Install the valve in a horizontal or vertical run with the flow arrow pointing toward the hazard. Support pipework independently so valve bodies do not bear pipe load. Connect pilot tubing with suitable fittings. Commission by electrically energizing each pilot and verifying valve opening and position indication. Inspect valve position and pilot pressure quarterly. Test manual override annually. Replace seals and pilot diaphragms every 5 years. Keep valve stems lubricated per manufacturer guidance.

Engineering Notes

Interlock the release panel so only one selector valve opens at a time unless simultaneous discharge is intentionally designed. Provide a position switch on each valve to feed back open or closed status to the panel. Size the pilot tubing for fast valve opening. Keep the valve body accessible for manual override and testing. Label each valve with the zone it serves. Do not use the valve as a shutoff valve for isolation during maintenance without proper lockout.

Code and Compliance

Selector valves must be installed per the system hydraulic calculation and approved by the fire authority. Each valve must be labeled with the zone it serves. The release panel must interlock valves so only one opens at a time unless simultaneous discharge is designed. Annual testing includes manual and pilot operation checks. Replace seals and diaphragms on schedule. Keep a record of valve serial numbers and installation dates.

Detailed Application Examples

Three DN50 selector valves allow one cylinder bank to protect three switchgear rooms. The panel opens only the valve for the alarmed zone, and position switches confirm valve status. Annual testing cycles each valve through open and closed. Seals are replaced every five years.

Long-term Operational Benefits

Selector valves have no wearing seals in the main flow path, giving a long service life with only diaphragm replacement every five years. By centralizing the cylinder bank, one set of maintenance records covers several zones, reducing inspection time. The manual override allows isolated testing without releasing agent, which cuts commissioning cost and avoids unnecessary refills. Over 20 years, the valve design lowers maintenance overhead.

Why Choose KITOZER

KITOZER selector valves are engineered for 24/7 industrial service and backed by factory support. Each valve is pressure tested before shipment and tagged with a unique serial number for traceability. KITOZER supplies matching actuators, position switches, and pilot tubing as a complete package, reducing procurement risk.

Price

From $420 per DN50 selector valve with solenoid pilot. Related accessories include spare seal kits, diaphragm assemblies, solenoid coils, position switches, and manual override handles. KITOZER supplies matching flanges, gaskets, and pilot tubing. The valve The valve carries a two-year warranty. KITOZER supports valve sizing, pilot circuit design, and commissioning. Spare seals, diaphragms, and solenoid coils are held in stock. Larger sizes and stainless steel bodies are available on request. Contact +86 13922289957 for larger sizes and multi-valve packages.