The KITOZER 40 kW water-cooled rear door heat exchanger (RDHx) replaces the rear door of a standard server rack, absorbing hot exhaust air directly as it leaves the equipment. Water-cooled coils inside the door capture the heat before it enters the hot aisle, eliminating recirculation and allowing rack densities to rise to 30 kW or more without raising room air temperature. The RDHx contains no fans or compressors: it relies on the server rack fans to push air through the coil, making it intrinsically silent and energy neutral from a parasitic load perspective. The door opens like a standard hinged door, preserving full rear access to servers and cable management.
Technical Specifications
Rated heat rejection is 40 kW at 35 degrees Celsius entering air and 25 degree Celsius entering water. Coil is copper tube with brazed fins, rated to 1.6 MPa working pressure. Water flow is 2.0 liters per second at design delta-T of 5 degrees. Pressure drop across the coil is 25 kPa. The door matches standard 19 inch rack widths of 600 mm or 800 mm and opens like a hinged door for rear service. Weight is 95 kg. Finish is black powder coat. Connection fittings are quick-connect dry-break couplings. Optional controls include a 0 to 10 V motorized valve and temperature sensors routed to the rack management unit.
Application Scenarios
RDHx units are used in high-density AI compute racks, GPU clusters, crypto mining containers, telecommunications central offices, and retrofit projects where existing room cooling cannot be upgraded. They are also popular in edge sites with limited floor space and in laboratories running power electronics, battery cyclers, and RF test equipment that generate dense local heat. The door is particularly useful in colocation cages where tenants demand high-density compute without modifying the shared room cooling system. It is also used in retrofit projects where adding new in-row units would breach aisle width or fire separation requirements.
Advantages and Features
Capturing heat at the rack exhaust eliminates hot spots and allows the rest of the data hall to operate at higher supply temperatures, improving chiller efficiency. No fan power means zero parasitic energy. Quick-connect couplings allow door removal in seconds without draining the loop. The hinged design preserves full rear access to servers. Modbus integration allows per-rack temperature and water flow monitoring. High inlet water temperature options (up to 32 degrees Celsius) enable free cooling from dry coolers for most of the year. The door is rated to hold 100 kg of additional equipment on its exterior mounting points. The quick-connect dry-break couplings also prevent water spills when a door is removed for service, a common problem on older RDHx designs that require hoses to be drained before disconnection.
Installation and Maintenance Recommendations
A pressurized water loop with supply and return manifolds must be installed in the floor or overhead. Each RDHx connects via braided stainless steel hoses with ball valves. Water treatment is essential to prevent fouling; a 50 micron strainer should be installed at each connection. Inspect hoses annually for wear and replace every 5 years. Coil cleaning with low-pressure water occurs every 2 to 3 years, depending on dust loading. Commissioning should include a pressure test on the hose loop and a temperature balance across the rack row. A thermal imaging walk-through after commissioning confirms that no rack exhaust exceeds the design setpoint. Operators should be trained on hose connection and disconnection, valve isolation, and the procedure for removing a door for service without draining the entire loop. A remote temperature sensor can be mounted inside the rack to confirm that inlet air stays within the design window.
Energy and Environmental Performance
Because the door consumes no electricity, it adds zero parasitic load to the data hall. When paired with a dry cooler and free-cooling plate heat exchanger, the central chiller can be shut down for much of the year. The door is fully recyclable at end of life, with a steel frame and copper coil that can be separated for scrap. No refrigerants are used in the device. The high inlet water temperature also means the dry cooler can operate without mechanical compression for most of the year, dramatically reducing site-wide energy use and carbon emissions.
Configuration Options and Warranty
The door is offered in 600 mm and 800 mm rack widths, with left- or right-hand hinge. Optional extras include a motorized control valve, a rack temperature sensor, a pressure gauge set, and a stainless-steel exterior for coastal sites. The standard warranty covers the coil and frame for 2 years, with extended coverage up to 5 years available. A preventive maintenance package with annual hose inspection and strainer cleaning is available for data hall deployments.
Price
From $4,680 per door. Contact plus 86 13922289957 for RDHx manifold and hose package pricing.