KITOZER CT: 10kV Current Transformer 600/5A Class 0.5

KITOZER 10kV current transformer (CT) steps down primary current to a standardized 5A or 1A secondary current for metering, protection, and monitoring. The CT provides galvanic isolation between the high voltage primary and low voltage secondary instruments, protecting personnel and equipment from high voltage surges. This model is rated 600/5A with 0.5 accuracy for metering and 10P10 for protection, making it suitable for feeder and transformer circuits in 10kV switchgear. Accurate current measurement is the foundation of both billing and protection, so the CT directly affects revenue fairness and fault clearing selectivity.

Product Overview

The CT is a sealed cast resin insulated pole unit with primary and secondary windings encapsulated in epoxy resin. The primary winding passes through the core window or is a bar type fixed through the pole. Secondary terminals are brought out to a terminal block inside the sealed housing. Cast resin construction eliminates oil and gas, prevents moisture ingress, and withstands vibration in withdrawable switchgear trucks. A terminal cover prevents accidental contact and provides tamper evidence for revenue metering. Multiple cores can be stacked inside one housing, so the same CT serves both metering and protection without extra space. The epoxy surface is tracked with direction arrows so installers can confirm polarity at a glance.

Technical Specifications

Rated voltage 12kV, rated frequency 50/60Hz, primary current 600A, secondary current 5A, accuracy class 0.5 for metering and 10P10 for protection, rated output 15VA to 30VA, thermal rated current 1.2 times primary for continuous, short-time thermal current 20kA for 1s, dynamic rated current 50kA peak. Power frequency withstand 42kV for 1 minute, lightning impulse withstand 75kV peak. Insulation class E, ambient temperature minus 25 to plus 40 degrees Celsius. The metering core accuracy limit factor is 5, meaning the metering circuit saturates above 5 times rated current to protect downstream meters. The protection core accuracy limit factor is 10, so the protection relay sees accurate current up to 10 times rated. Compliant with IEC 61869-2 and GB 20840.

Applications

This CT is installed in KYN28A, XGN, and Ring Main Units on 10kV feeder panels, transformer incoming panels, and bus tie panels. The 0.5 winding feeds revenue or energy management meters, while the 10P winding feeds overcurrent and earth fault protection relays. It also supplies current signals for power quality analyzers and SCADA remote terminal units. Typical customers include industrial plant electrical rooms, commercial building substations, and utility distribution networks. In large plants with multiple feeders, identical CT ratios across the switchroom simplify relay settings and spare parts stocking. For revenue metering applications, the 0.5S accuracy variant is available to cover the full load range from light to full load.

Advantages

Dual core design separates metering and protection windings so that large fault currents do not saturate the metering circuit and distort billing accuracy. Cast resin insulation requires no maintenance and is immune to moisture. The sealed housing prevents dust and condensation on secondary terminals. Accurate 0.5 class supports fair energy billing and effective load management. Compact dimensions fit standard switchgear compartments. The CT has a long service life of more than 30 years when operated within ratings. Because there is no oil, there is no spill risk and no periodic oil testing, which simplifies insurance and fire safety compliance in indoor switchrooms.

Installation and Maintenance

Mount the CT on the switchgear bus or cable, observing primary and secondary polarity markings. Never open the secondary circuit while the primary is energized, as this produces dangerous overvoltage. Use shielded secondary cable with one end grounded at the relay panel. Commissioning includes ratio test, polarity test, insulation resistance test, and burden calculation to ensure the connected burden is within rated output. Inspect annually for resin cracks and terminal tightness. Calibrate metering CTs every four years according to local metering regulations. Keep secondary terminal covers sealed to prevent tampering. If a secondary circuit must be worked on, short the secondary terminals first with an insulated bar before disconnecting any relay or meter, and only then de-energize the primary.

When selecting the CT ratio, choose one that gives normal load current between 30 percent and 100 percent of the rated secondary, so the metering accuracy stays in its linear range. Oversizing the CT reduces metering accuracy at light load, while undersizing risks saturation during motor starting. The secondary cable burden must be calculated including the meter impedance, relay impedance, and cable resistance, and the total must stay below the rated output of the core. If additional instruments are added later, recheck the burden before energizing. Always label CT secondary circuits clearly and keep the terminal covers sealed to prevent accidental opening.

Ordering and Support

When ordering, specify the primary current ratio, secondary current, number and class of cores, rated burden, and the switchgear compartment the CT will fit. KITOZER supplies CTs with routine test reports, ratio and polarity certificates, and dimension drawings. Spare units can be held on site for critical feeders. Technical support covers burden calculation, protection relay coordination, and meter selection. Each CT is backed by a five year warranty, and calibration certificates are traceable to national standards for revenue metering applications.