KITOZER aspirating smoke detector model ASD-1 is an air-sampling early warning fire detection unit that draws air through a network of sampling pipes and analyzes it with a laser scattering chamber. By detecting smoke at concentrations as low as 0.005 percent obscuration per meter, the unit gives very early warning before a conventional point detector would alarm, making it ideal for clean rooms, data centers, storage vaults, museums, and any environment where early fire warning prevents catastrophic loss. The detector replaces a dozen or more conventional point detectors with a single sampling pipe network covering a protected area.
Table of Contents
ToggleProduct Overview
The ASD-1 includes a laser optical chamber, suction pump, sampling pipe manifold, filter, LCD display, and relay outputs. Four programmable alert levels report to the fire alarm panel: preliminary warning, early warning, fire alert, and fire alarm. The unit continuously monitors pipe airflow and filters, and reports a fault if airflow drops due to blockage or leak. The sampling pipe network is drilled with calibrated holes to draw equal air samples from across the protected area. KITOZER provides pipe layout design and hole sizing per VdS and NFPA 72 aspirating detector guidelines.
Technical Specifications
Detection principle laser light scattering. Sensitivity range 0.005 to 20 percent obscuration per meter. Four alert levels programmable. Sampling pipe maximum length 100 meters per pipe, up to 4 pipes. Pipe material ABS or copper, 25 millimeter outer diameter. Airflow monitoring with fault threshold. Suction pump dual redundant, hot swappable. Filter replaceable, 0.2 micron. LCD display with real-time smoke concentration, airflow, and fault log. Relay outputs 4, for each alert level. RS485 Modbus, optional Ethernet. Power supply 24 volt DC, 1 ampere. Operating temperature 0 to 35 degrees Celsius. Cabinet wall mounted, steel. Certifications CCCF, ISO 9001, VdS, NFPA 72. Warranty 24 months.
Application Scenarios
This detector is specified for clean rooms in semiconductor and pharmaceutical manufacturing, data center server halls, cold storage, museum galleries and archives, library vaults, telecommunications switching rooms, electronic manufacturing workshops, and any environment where early fire warning must precede sprinkler or gas suppression activation. The sampling pipe network is mounted above the ceiling or in the raised floor, drawing air from the protected space. Facility managers select aspirating detection when conventional point detectors are too slow, too inaccessible, or would be triggered by normal dust or steam.
Advantages and Features
Very early warning gives hours of lead time before a visible fire, allowing targeted response before suppression activates. Laser sensitivity detects invisible smoke. Sampling pipe network covers large areas with one detector. Airflow monitoring reports blocked pipes, a common failure mode. Four alert levels allow graduated response. Dual redundant pump avoids single-point failure. The detector installs outside the clean room, so maintenance does not disturb the controlled environment.
Installation and Maintenance Recommendations
Mount the detector in a serviced area outside the clean room, with sampling pipes routed through sealed grommets. Drill calibrated sampling holes per the pipe design. Test airflow at commissioning and annually. Replace filter every 12 months. Clean the laser chamber every 2 years or per fault log. Verify each alert level with aerosol test at commissioning and annually. Keep spare filter, pump, and chamber on site. Log every test.
System Integration
The ASD-1 aspirating detector maps its four alert levels to the building fire alarm panel through supervised relay outputs. Preliminary and early warning levels trigger operator investigation without building-wide alarm, while fire alert and fire alarm levels activate the general alarm and release sequence. In data center applications, the early warning level typically triggers a cooling increase and a targeted walk-through before the fire alarm level releases gas or sprinklers. The detector also monitors sampling pipe airflow and filter contamination, reporting a fault if either drifts outside the calibrated band. RS485 Modbus and optional Ethernet expose real-time smoke concentration in percent obscuration per meter, airflow, and chamber contamination to the BMS, so facility engineers trend dust load and predict filter replacement. KITOZER provides the pipe layout, hole sizing, and alert level mapping as a coordinated package, so the detector integrates cleanly with the existing fire alarm panel. The detector housing mounts on a wall outside the clean room, so filter and chamber maintenance never requires entry into the controlled environment. The dual redundant suction pumps can be hot-swapped without shutting down detection, so the protected space remains supervised during servicing. The detector is certified to VdS and NFPA 72 aspirating detector guidelines, and is accepted by major insurance loss-prevention engineers for high-value environments. The sampling pipe network can be routed above suspended ceilings or through raised floors, matching the protected space layout.
Price
From 1,200 US dollars per detector head including pump, chamber, and relays. Sampling pipe and fittings quoted per layout. Contact KITOZER for pipe design and lead time.