Table of Contents
ToggleProduct Overview
KITOZER Type 2 surge protective device 40kA 385V 3+1 configuration is installed at the low-voltage main distribution cabinet of buildings, data centers, industrial plants, and commercial facilities to suppress switching surges and indirect lightning transients. The three-mode phase-to-metal varistor modules plus one neutral-to-metal spark gap combination clamp residual voltage below 1.5 kV, protecting downstream breakers, contactors, and sensitive loads. The plug-in module design allows field replacement without rewiring, and the remote contact alarm signals SPD health to the building management system. KITOZER Type 2 SPDs are certified to IEC 61643-11 and meet EN 61643-11 requirements for Class II tested equipment.
Technical Specifications
Configuration: 3 poles plus N-PE gap (3+1). Max continuous operating voltage Uc: 385V AC. Nominal discharge current In (8/20 microsecond): 20 kA per pole. Maximum discharge current Imax (8/20): 40 kA per pole. Voltage protection level Up: not more than 1.5 kV. Response time: 25 nanoseconds for varistor, 100 nanoseconds for gap. Short-circuit withstand: 50 kA rms follow current. Integrated backup fuse: 32A gG recommended. Remote signal contact: SPD fail, NO/NC 250V 0.5A. Mounting: 35mm DIN rail. Housing: UL94-V0 flame-retardant. Operating temperature: minus 40C to plus 85C. Certifications: IEC 61643-11, CE, UL 1449 optional. Brand: KITOZER. Warranty: 5 years.
Application Scenarios
This SPD is typically mounted on the main LV distribution board as the secondary stage in a coordinated protection scheme, downstream of a Type 1 service entrance SPD and upstream of branch panel SPDs. It protects server room PDUs, air conditioning compressors, elevators, LED lighting drivers, CCTV recorders, access control controllers, and production machinery. Common installations include office building main switchboards, shopping mall distribution panels, hospital electrical rooms, factory MCCs, warehouse lighting panels, and telecommunications exchange power cabinets. It is also used as the dedicated SPD for rooftop solar inverter AC outputs and wind turbine tower base power cabinets.
Advantages and Features
The 3+1 topology provides low residual voltage in normal mode while safely carrying neutral-to-earth surge current through the gap, avoiding premature failure caused by mains voltage displacement. The plug-in modules show visual red/green indicator so maintenance staff can identify degraded units without testing. The integrated failure disconnect device isolates shorted varistors to prevent fire. KITOZER SPDs are manufactured with thermally protected varistors that open safely under overvoltage stress. The remote alarm contact dry wire allows integration with BMS, fire alarm, or DCIM systems. Compared with compact Type 2 units, this 40kA model has longer service life in areas with frequent lightning activity. The DIN rail mounting allows fast retrofitting in existing cabinets.
Installation and Maintenance Recommendations
Mount the SPD as close as possible to the incoming main breaker, with lead length not exceeding 0.5m per pole to minimize inductive overshoot. Use copper conductors of at least 10mm2 for phase and neutral leads, and 16mm2 for PE. Connect the remote alarm contact to the BMS with shielded cable. Set the upstream backup breaker or gG fuse to 32A or 63A per coordination study. Inspect the visual indicator every six months; if any module shows red, replace the plug-in immediately. Test leakage current annually with a SPD analyzer. Record surge counter events if the cabinet logger is fitted. Replace the whole set after 10 years of service even if indicators remain green, because varistor drift accumulates. In high-corrosion coastal sites, clean terminals with contact cleaner yearly. KITOZER provides SPD coordination charts and commissioning checklists.
Price
From $85 per unit including remote contact. Contact +86 13922289957 for multi-pole pricing and project discount.