KITOZER 40 foot containerized data center is a self-contained IT room built inside a standard high cube shipping container, delivered to site ready to plug in. The 500 kW model described here houses up to 40 server racks, precision cooling, UPS, battery, switchgear, fire suppression, and security, all engineered to work in ambient temperatures from minus 20 to plus 50 degrees Celsius. It is the fastest way to add data center capacity, because the customer only needs a level pad, a utility feed, and a network connection. The container is weatherproof, seismic rated, and can be stacked or arranged in rows like a traditional hall.
Table of Contents
ToggleProduct Overview
The container is a modified 40 foot high cube unit, 12.2 meters long, 2.4 meters wide, 2.9 meters high, with reinforced floor, insulated walls, and a vapor barrier. Inside, two rows of 20 racks face each other across a cold aisle, with hot air exhausted to the rear wall where two rooftop or side-mounted precision air conditioners extract heat. Power arrives at a main switchgear, feeds a 500 kVA UPS with battery cabinet, and distributes via monitored PDUs. The container includes a self-contained fire system with clean agent suppression, VESDA smoke detection, leak detection, access control, and CCTV. A 15 inch touchscreen controller on the outside door shows power, temperature, and alarm status, and remote web access is standard.
Technical Specifications
IT load: 500 kW across 40 racks at 12.5 kW average. Container: 40 ft high cube, Corten steel, CSC certified, RAL 7035 exterior, 100 mm polyurethane insulation. Racks: 40 x 42U, 600 x 1200 mm, cold aisle contained. Cooling: 4 x 150 kW rooftop packaged air conditioners, N plus 1, EC fans, ambient range minus 20 to plus 50 C. Power: 500 kVA UPS, N plus 1, 10 minutes battery. Main switchgear: 630 A incoming, distribution to rack PDUs. Fire: clean agent suppression, VESDA, manual release. Security: biometric access control, CCTV, door contact. Monitoring: 15 inch HMI, Modbus TCP, SNMP, 4G remote. Operating ambient: minus 20 to plus 50 C. Weight: about 22,000 kg empty. Footprint: 12.2 x 2.4 m.
Applications
Containerized data centers are deployed where a permanent building is impractical or too slow: mining sites, oil and gas installations, military forward operating bases, disaster recovery sites, event-driven temporary capacity, and edge locations near 5G towers. They are also used as overflow capacity in existing data centers, as modular capacity that pays back over time, and as greenfield pods that can be added in rows. Typical customers include telecom operators, cloud service providers, system integrators serving mining and energy, and government agencies needing hardened, relocatable capacity. Because the unit is a shipping container, it can be shipped by truck, rail, or sea to almost any site.
Advantages and Features
The container delivers capacity in weeks instead of years. It requires no building permit in many jurisdictions, only a level pad and utility connection. Because it is factory integrated, every component is tested before shipment, reducing commissioning risk. The insulated shell maintains stable internal temperature even in desert or arctic climates. Rooftop air conditioners use ambient air for free cooling when outdoor temperature is low, raising energy efficiency. The container is movable: if the business moves, the whole data center goes on a truck. Security is built in, with biometric access and CCTV, which is valuable in remote sites. Finally, multiple containers can be chained in parallel to form a multi-megawatt campus, each with its own independent power and cooling.
Installation and Maintenance
On site, the customer prepares a 150 mm thick reinforced concrete pad, leveled within 5 mm. A crane places the container on the pad, and the crew connects utility power, fiber, and grounding. Commissioning takes one week: factory engineers run thermal tests, load the UPS, verify failover, and hand over documentation. Routine maintenance is quarterly: replace filters, inspect condenser coils, check battery voltages, and test door locks. Annually, load test the UPS, inspect the container seal and paint, and test fire suppression. Spare parts are kept on site in a service locker. KITOZER offers a 5 year warranty and a 24/7 remote monitoring option that dispatches service engineers automatically on alarm.
Price
From $485,000 per 40 ft 500 kW containerized data center, including racks, cooling, UPS, fire, and monitoring. Contact +86 13922289957 for factory pricing.