KITOZER 10kV 630A disconnector is a medium-voltage isolating switch used to create a visible break in a 10kV circuit during maintenance. Unlike a circuit breaker, the disconnector has no fault interrupting duty and must only be operated when the circuit current is zero, typically after the upstream breaker has opened. The device provides a reliable visual isolation gap so maintenance personnel can work on cables, transformers, or switchgear sections with confidence. It is a passive but essential safety device that turns an energized bus into a visibly de-energized section.
Table of Contents
ToggleProduct Overview
The disconnector consists of three pole units mounted on a common frame, with rotating blades driven by an insulating operating rod. A motor or manual operating mechanism drives the three poles simultaneously. An integrated earthing switch closes onto the line side after the main blades open, ensuring the de-energized side is safely grounded. Mechanical interlocks between the disconnector, earthing switch, and upstream circuit breaker prevent incorrect operation sequences, such as closing the earth switch on a live line or opening the disconnector under load. The blade contacts are silver plated to maintain low contact resistance over many years of outdoor exposure.
Technical Specifications
Rated voltage 12kV, rated frequency 50/60Hz, rated normal current 630A, rated short-time withstand current 20kA for 4s, rated peak withstand current 50kA, rated power frequency withstand voltage 42kV for 1 minute across poles and to earth, lightning impulse withstand 75kV peak. Earthing switch rated short-time withstand 20kA for 2s. Operating mechanism manual or motorized with DC 110V/220V options. Insulation material epoxy resin or porcelain, ambient temperature minus 30 to plus 40 degrees Celsius, installation altitude below 1000m, pollution class 3. The contact resistance per pole is below 50 micro ohms, and the mechanical endurance is rated for 10,000 open close cycles without overhaul. Compliant with IEC 62271-102 and GB 1985.
Applications
This disconnector is installed in 10kV switchgear rooms, cable feeder panels, transformer incoming bays, and ring main units to isolate equipment for maintenance. It is commonly paired with VCB breakers in KYN28A and XGN switchgear to provide visible isolation on the cable side. Outdoor variants serve as overhead line sectionalizing points in distribution networks, and the earthing function supports safe cable testing and joint work. Industrial plants use it to isolate entire bus sections during scheduled shutdowns. In utility distribution networks, the disconnector separates a failed cable section so that the rest of the loop can remain energized through the alternate path.
Advantages
The visible open gap gives maintenance crews immediate confidence that the circuit is isolated. Combined earthing switch removes the need for separate portable earth rods and speeds up switching operations. Mechanical interlocks enforce safe operating sequences and reduce human error. Robust epoxy insulators resist tracking in damp atmospheres. Manual operation allows switching even when control power is lost, which is valuable during emergency repairs. Long mechanical life of more than 10,000 operations and no arc quenching parts mean very low lifetime cost. Because there is no interrupting duty, the disconnector has no consumable parts and no scheduled overhaul beyond visual inspection and lubrication.
Installation and Maintenance
Mount the disconnector frame plumb on the switchgear or support structure, align the three pole blades, and connect primary conductors without adding mechanical stress. Adjust blade contact pressure so the contact fingers grip evenly and the contact resistance is within the manufacturer range. Verify interlock logic: the earthing switch can only close when the disconnector is open, and the upstream breaker can only close when the earthing switch is open. Inspect annually for contact oxidation, insulator tracking, and mechanism looseness. Lubricate the drive linkages every three years. Because the disconnector does not interrupt load current, train operators to confirm zero current before each opening or closing operation. Keep a set of spare contact fingers and drive pins for emergency repairs, and replace insulators that show surface tracking or flashover marks.
Field experience shows that the most common cause of disconnector failure is poor contact pressure after many years of outdoor exposure, which leads to overheating at the blade fingers. Regular infrared thermography during peak load hours catches hot joints before they develop into faults. The silver plated contacts can be cleaned and re-greased during major overhauls, extending service life by another decade. Because the disconnector has no arc interruption duty, operators must always follow the switching sequence in the station drawing: open the upstream breaker first, rack out or open the disconnector, then close the earth switch. This sequence protects personnel and prevents damage to the contacts.
Ordering and Support
Ordering requires the rated voltage, current, number of poles, manual or motorized operation, and whether an integrated earth switch is required. KITOZER supplies the disconnector with mounting brackets, operating rod, and interlock assembly, plus a factory test report. Common spares include contact fingers, drive pins, and insulators. Technical support covers interlock logic design and switchroom layout review. The disconnector is backed by a five year warranty, and long lead items are identified in the quotation so project schedules can be planned with confidence.